View
104
Download
4
Category
Preview:
Citation preview
5/20/2018 3. PUIL PP BARU 2008
1/59
INSTALASI LISTRIKBERDASARKAN PUIL 2000
OLEH
IR. H.M. MASGUNARTO BUDIMAN M.SC.
DISAMPAIKAN PADA ACARA PEMBEKALAN DALAM RANGKA
UJI KOMPETENSI TENAGA AHLI KONSTRUKSI INSTALASI KETENAGALISTRIKAN
DISELENGGARAKAN OLEH
ASOSIASI PROFESIONALIS ELEKTRIKAL-MEKANIKAL INDONESIA (APEI)
JAKARTA 18=21 APRIL 2013
5/20/2018 3. PUIL PP BARU 2008
2/59
PUIL 2000 - PERSYARATAN UNTUKINSTALASI LISTRIK
ISI BUKU PUIL (SNI 04-0225-2000):
BAGIAN 1. PENDAHULUAN
BAGIAN 2. PERSYARATAN DASAR BAGIAN 3. PROTEKSI UNTUK KESELAMATAN
BAGIAN 4. PERANCANGAN INSTALASI LISTRIK
BAGIAN 5. PERLENGKAPAN LISTRIK
BAGIAN 6. PERLENGKAPAN HUBUNG BAGI DAN
KENDALI (PHB) SERTA KOMPONENNYA
BAGIAN 7. PENGHANTAR DAN PEMASANGANNYA
BAGIAN 8. KETENTUAN UNTUK BERBAGAI RUANG
DAN INSTALASI KHUSUS
BAGIAN 9. PENGUSAHAAN INSTALASI LISTRIK
5/20/2018 3. PUIL PP BARU 2008
3/59
MAKSUD DAN TUJUAN PUIL
AGAR TERWUJUD:
PENGUSAHAAN INSTALASI LISTRIK
TERSELENGGARA DENGAN BAIK
KESELAMATAN MANUSIA DARI BAHAYA KEJUT
LISTRIK
KEAMANAN INSTALASI LISTRIK BESERTA
PERLENGKAPANNYA
KEAMANAN GEDUNG SERTA ISINYA DARI
KEBAKARAN AKIBAT LISTRIK, DAN
PERLINDUNGAN LINGKUNGAN.
5/20/2018 3. PUIL PP BARU 2008
4/59
RUANG LINGKUP PUIL
BERLAKU UNTUK SEMUA PENGUSAHAANINSTALASI LISTRIK TEGANGAN RENDAH ARUS
BOLAK-BALIK SAMPAI DENGAN 1000 V, ARUSSEARAH 1500 V DAN TEGANGAN MENENGAHSAMPAI DENGAN 35 KV DALAM BANGUNAN DANSEKITARNYA
UNTUK PERANCANGAN, PEMASANGAN,PEMERIKSAAN DAN PENGUJIAN, PELAYANAN,PEMELIHARAAN MAUPUN PENGAWASANNYA
5/20/2018 3. PUIL PP BARU 2008
5/59
PUIL TIDAK BERLAKU UNTUK
BAGIAN INSTALASI LISTRIK DENGAN TEGANGAN RENDAH YANGHANYA DIGUNAKAN UNTUK MENYALURKAN BERITA DAN ISYARAT;
BAGIAN INSTALASI LISTRIK YANG DIGUNAKAN UNTUKKEPERLUAN TELEKOMUNIKASI DAN PELAYANAN KERETA RELLISTRIK;
INSTALASI LISTRIK DALAM KAPAL LAUT, KAPAL TERBANG,KERETA REL LISTRIK, DAN KENDARAAN LAIN YANG DIGERAKKANSECARA MEKANIS;
INSTALASI LISTRIK DI BAWAH TANAH DALAM TAMBANG;
INSTALASI LISTRIK DENGAN TEGANGAN RENDAH YANG TIDAKMELEBIHI 25 V DAN DAYANYA TIDAK MELEBIHI 100 W.
5/20/2018 3. PUIL PP BARU 2008
6/59
ACUAN DAN KETENTUAN TERKAIT
ACUAN:
PERATURAN UMUM INSTALASI LISTRIK 1987 DENGAN MEMPERHATIKANSTANDAR IEC, TC 64 ELECTRICAL INSTALLATIONS OF BUILDINGS DAN
STANDAR INTERNASIONAL LAINNYA YANG BERKAITAN.KETENTUAN YANG TERKAIT YANGHARUS DIPERHATIKAN :
UNDANG-UNDANG NOMOR 1 TAHUN 1970 TENTANG KESELAMATANKERJA, BESERTA PERATURAN PELAKSANAANNYA;
UNDANG-UNDANG NOMOR 15 TAHUN 1985 TENTANGKETENAGALISTRIKAN;
UNDANG-UNDANG NOMOR 23 TAHUN 1997 TENTANG PENGELOLAANLINGKUNGAN HIDUP;
UNDANG-UNDANG NOMOR 18 TAHUN 1999 TENTANG JASAKONSTRUKSI;
PP NOMOR 10 TAHUN 1989 TENTANG PENYEDIAAN DAN PEMANFAATANTENAGA LISTRIK;
5/20/2018 3. PUIL PP BARU 2008
7/59
KETENTUAN YANG TERKAIT
(LANJUTAN)
PP NOMOR 51 TAHUN 1993 TENTANG ANALISA MENGENAI DAMPAKLINGKUNGAN;
PP NOMOR 25 TAHUN 1995 TENTANG USAHA PENUNJANG TENAGA LISTRIK;
PERMEN ESDM NOMOR 01.P/40/M.PE/1990 TENTANG INSTALASIKETENAGALISTRIKAN;
PERMEN ESDM NOMOR 02.P/0322/M.PE/1995 TENTANG STANDARDISASI,SERTIFIKASI DAN AKREDITASI DALAM LINGKUNGAN PERTAMBANGAN DANENERGI;
PERMEN ESDM NOMOR 103.K/008/M.PE/1994 TENTANG PENGAWASAN ATASPELAKSANAAN RENCANA PENGELOLAAN LINGKUNGAN DAN RENCANAPEMANTAUAN LINGKUNGAN DALAM BIDANG PERTAMBANGAN DAN ENERGI;
PERMEN ESDM NOMOR 2500.K/40/M.PE/1997 TENTANG USAHA PENUNJANGTENAGA LISTRIK BIDANG KONSULTASI, BIDANG PEMBANGUNAN DANPEMASANGAN DAN BIDANG PEMELIHARAAN PERALATANKETENAGALISTRIKAN;
PERMEN ESDM NOMOR 198.K/008/M.PE/1998 TENTANG IZIN USAHAKETENAGALISTRIKAN UNTUK KEPENTINGAN SENDIRI;
5/20/2018 3. PUIL PP BARU 2008
8/59
PERSYARATAN DASAR
ISTALASI LISTRIK
1. PROTEKSI UNTUK KESELAMATAN
2. PROTEKSI PERLENGKAPAN DAN INSTALASI
LISTRIK3. PERANCANGAN INSTALASI LISTRIK
4. PEMILIHAN PERLENGKAPAN LISTRIK
5. PEMASANGAN DAN VERIFIKASI AWAL
INSTALASI LISTRIK6. PENGUJIAN INSTALASI LISTRIK
7. PEMELIHARAAN INSTALASI LISTRIK
5/20/2018 3. PUIL PP BARU 2008
9/59
POTENSI BAHAYA LISTRIK
TEGANGAN SENTUH
ARUS HUBUNG PENDEK ARUS BEBAN LEBIH
TEGANGAN TINGGI
TEGANGAN RENDAH PANAS
5/20/2018 3. PUIL PP BARU 2008
10/59
2. Bahaya sentuh tidak langsung(3.5)
Sentuh pada BKT perlengkapan atau instalasi listrikyang menjadi bertegangan akibat kegagalan isolasi
Syarat:
Perlengkapan listrik harus dirancang dan dibuat dengan baik. Bagian aktif harus diisolasi dengan bahan yang tepat
Instalasi listrik harus dipasang dengan baik.
5/20/2018 3. PUIL PP BARU 2008
11/59
PROTEKSI SENTUH TIDAK
LANGSUNG
Sentuh tidak langsung(3.5.2.1)
a. Proteksi dengan pemutus suplai secara otomatisb. Proteksi dengan penggunaan kelas II atau
dengan isolasi ekivalen
c. Proteksi dengan lokasi tidak konduktif
d. Proteksi dengan ikatan penyama potensial lokalbebas bumi
e. Proteksi dengan separasi listrik
5/20/2018 3. PUIL PP BARU 2008
12/59
PROTEKSI UNTUK KESELAMATAN
PROTEKSI DARI SENTUH LANGSUNG
MANUSIA DAN TERNAK HARUS DIHINDARKAN/ DISELAMATKAN
DARI BAHAYA YANG BISA TIMBUL KARENA SENTUHAN DENGANBAGIAN AKTIF INSTALASI (SENTUH LANGSUNG) DENGAN SALAHSATU CARA DI BAWAH INI:
MENCEGAH MENGALIRNYA ARUS MELALUI BADAN MANUSIAATAU TERNAK;
MEMBATASI ARUS YANG DAPAT MENGALIR MELALUI BADANSAMPAI SUATU NILAI YANG LEBIH KECIL DARI ARUS KEJUT.
5/20/2018 3. PUIL PP BARU 2008
13/59
CARA PROTEKSI
RUMAH PERALATAN
IP UNTUK PERALATAN DENGAN PERINTANG
DI LUAR JANGKAUAN TANGAN
RUANG KHUSUS DAN PETUGAS KHUSUSUNTUK LLISTRIK
5/20/2018 3. PUIL PP BARU 2008
14/59
1. PROTEKSI UNTUK KESELAMATAN
(LANJUTAN)
1.3 PROTEKSI DARI EFEK TERMAL DAN DARI ARUS LEBIH
INSTALASI LISTRIK HARUS DISUSUN SEDEMIKIAN RUPA SEHINGGA TIDAKADA RISIKO TERSULUTNYA BAHAN YANG MUDAH TERBAKAR KARENATINGGINYA SUHU ATAU BUSUR API LISTRIK. DEMIKIAN PULA TIDAK AKAN
ADA RISIKO LUKA BAKAR PADA MANUSIA MAUPUN TERNAK SELAMAPERLENGKAPAN LISTRIK BEROPERASI SECARA NORMAL.
MANUSIA ATAU TERNAK HARUS DIHINDARKAN/DISELAMATKAN DARICEDERA, DAN HARTA BENDA DIAMANKAN DARI KERUSAKAN KARENA SUHUYANG BERLEBIHAN ATAU STRES ELEKTROMEKANIS KARENA ARUS LEBIHYANG SANGAT MUNGKIN TIMBUL PADA PENGHANTAR AKTIF.
PROTEKSI INI DAPAT DICAPAI DENGAN SALAH SATU CARA DI BAWAH INI:A) PEMUTUSAN SECARA OTOMATIS PADA SAAT TERJADI ARUS
LEBIH
B) PEMBATASAN ARUS LEBIH MAKSIMUM SEHINGGA NILAI DAN
LAMANYA YANG AMAN TIDAK TERLAMPAUI.
5/20/2018 3. PUIL PP BARU 2008
15/59
1. PROTEKSI UNTUK KESELAMATAN(LANJUTAN)
1.4 PROTEKSI DARI ARUS GANGGUAN DAN DARITEGANGAN LEBIH
PENGHANTAR, SELAIN PENGHANTAR AKTIF, DAN BAGIAN LAINYANG DIMAKSUDKAN UNTUK MENYALURKAN ARUS GANGGUANHARUS MAMPU MENYALURKAN ARUS TERSEBUT TANPAMENIMBULKAN SUHU YANG BERLEBIHAN.
MANUSIA ATAU TERNAK HARUS DICEGAH DARI CEDERA DAN HARTABENDA HARUS DICEGAH DARI SETIAP EFEK YANG BERBAHAYAAKIBAT ADANYA GANGGUAN ANTARA BAGIAN AKTIF SIRKIT YANG
DISUPLAI DENGAN TEGANGAN YANG BERBEDA.
MANUSIA DAN TERNAK HARUS DICEGAH DARI CEDERA DAN HARTABENDA HARUS DICEGAH DARI KERUSAKAN AKIBAT ADANYATEGANGAN YANG BERLEBIHAN YANG MUNGKIN TIMBUL AKIBATSEBAB LAIN (MISALNYA, FENOMENA ATMOSFER ATAU TEGANGANLEBIH PENYAKELARAN).
5/20/2018 3. PUIL PP BARU 2008
16/59
2. PROTEKSI PERLENGKAPAN DAN
INSTALASI LISTRIK
2.1 PERLENGKAPAN LISTRIK PADA SETIAP PERLENGKAPAN LISTRIK HARUS ADA PAPAN
NAMA YANG TIDAK MUDAH LEPAS DAN PADANYATERCANTUM DENGAN JELAS DAN DAN TIDAK MUDAHTERHAPUS:
1. NAMA PEMBUAT DAN ATAU MEREK DAGANG;
2. LOGO ATAU TANDA STANDAR SNI ATAU STANDAR LAIN
MISALNYA IEC,JIS,BS,VDEUL
3. DAYA, TEGANGAN, DAN/ATAU ARUS PENGENAL SERTADATA TEKNIS LAIN SEPERTI DISYARATKAN SNI .
PERLENGKAPAN LISTRIK HANYA BOLEH DIPASANG PADAINSTALASI JIKA MEMENUHI KETENTUAN DALAM PUIL 2000DAN/ATAU STANDAR YANG BERLAKU.
SETIAP PERLENGKAPAN LISTRIK TIDAK BOLEH DIBEBANI
MELEBIHI KEMAMPUANNYA.
5/20/2018 3. PUIL PP BARU 2008
17/59
2. PROTEKSI PERLENGKAPAN DAN
INSTALASI LISTRIK (LANJUTAN)
2.2 INSTALASI LISTRIK
INSTALASI YANG BARU DIPASANG ATAU MENGALAMI
PERUBAHAN HARUS DIPERIKSA DAN DIUJI DULU SESUAIDENGAN KETENTUAN MENGENAI :
1. RESISTANS ISOLASI (3.20);
2. PENGUJIAN SISTEM PROTEKSI (3.21);
3. PEMERIKSAAN DAN PENGUJIAN INSTALASI LISTRIK (9.5.6).
INSTALASI LISTRIK YANG SUDAH MEMENUHI SEMUAKETENTUAN TERSEBUT DAPAT DIOPERASIKAN SETELAHMENDAPAT IZIN ATAU PENGESAHAN DARI INSTANSI YANGBERWENANG (KONSUIL DAN LEMBAGA INSPEKSI) DENGANSYARAT TIDAK BOLEH DIBEBANI MELEBIHI KEMAMPUANNYA.
5/20/2018 3. PUIL PP BARU 2008
18/59
1. Sistem TT atau Pembumian Pengaman (PP)
Tujuan pembumian :
Bila terjadi arus bocor atau hubung singkat, arusakan tersalur ke bumi yang akan menyebabkan
meningkatnya arus sehingga pengaman akan
terputus secara otomatik
Fasa tunggal 2 kawat AktifNol/Netral
5/20/2018 3. PUIL PP BARU 2008
19/59
2. Sistem IT atau Hantaran pengaman (HP)Tujuan pembumian :
Bila terjadi arus bacor atau hubung singkat, arus
akan tersalur ke bumi melalui penghantarpengaman sehingga arus meningkat dan
pengaman akan terputus secara otomatik
Fasa tunggal 3 kawat Penghantar AktifPenghantar Nol/Netral
Hantaran pengaman
5/20/2018 3. PUIL PP BARU 2008
20/59
3. Sistem TN atau
Pembumian Netral Pengaman (PNP)
Nol &Ground
dihubungkan
Fasa tunggal 3 kawat
5/20/2018 3. PUIL PP BARU 2008
21/59
SISTIM PROTEKSI
Pembumian
Ikatan penyama potensial
Arester
L1
L2
L3
N
PEN
GPAS
Pengaman lebur
L1 L2 L3PEN
Penempatan arester untuk sistem TT
5/20/2018 3. PUIL PP BARU 2008
22/59
SISTIM PROTEKSI
Proteksi dengan separasi listrik
Adalah suatu tindakan proteksi dengan memisahkan sirkit
perlengkapan listrik dari jaringan sumber denganmenggunakan transformator pemisah atau motor generator
(3.11)
Sistim ini hanya akan efektif selama dalam sirkit sekunder
tidak terjadi gangguan bumi.
Sirkit sekunder adalah sirkit sekunder dari transformatorpemisah atau sirkit generator dari motor generator.
Tegangan jaringan yang diizinkan max. 500 volt.
5/20/2018 3. PUIL PP BARU 2008
23/59
Rekom : a. V x l kwt 100.000b. L kwt 500 m
Transformator pemisah dengan pendek ke bumi pada sirkit
sekunder dan hubung pendek ke BKT perlengkapan listrik
5/20/2018 3. PUIL PP BARU 2008
24/59
PROTEKSI BAHAYA LISTRIK
1. Bahaya sentuh langsung
Sentuh langsung pada bagian aktif perlengkapan atauinstalasi listrik(3.4)
Cara Mengatasia. Proteksi dengan isolasi bagian aktif(3.4.1)
b. Proteksi dengan penghalang atau selungkup(3.4.2)
c. Proteksi dengan rintangan(3.4.3)
d. Proteksi dengan penempatan diluar jangkauan(3.4.4)
e. Proteksi tambahan dengan gawai pengaman arus sisa(3.4.5)
5/20/2018 3. PUIL PP BARU 2008
25/59
3. PERANCANGAN INSTALASI LISTRIK
HAL-HAL YANG PERLU DIPERHATIKAN:
FAKTOR YANG HARUS DIPERHATIKAN UNTUK MENJAMINKESELAMATAN MANUSIA DAN KESELAMATAN HARTA BENDA SERTA
BERFUNGSINYA INSTALASI LISTRIK DENGAN BAIK KARAKTERISTIK SUPLAI
MACAM KEBUTUHAN AKAN LISTRIK
SUPLAI DARURAT
KONDISI LINGKUNGAN
LUAS PENAMPANG PENGHANTAR
JENIS PENGAWATAN DAN CARA PEMASANGAN GAWAI PROTEKSI
KENDALI DARURAT
GAWAI PEMISAH
PENCEGAHAN PENGARUH TIMBAL BALIK
KETERJANGKAUAN PERLENGKAPAN LISTRIK
RUANG KERJA DI SEKITAR`PERLENGKAPAN LISTRIK
5/20/2018 3. PUIL PP BARU 2008
26/59
PENGHANTAR,PEMASANGAN
DAN PEMBEBANANNYA
FUNGSI
JENIS DAN PENGGUNAAN KONSTRUKSI DAN BAHAN
PERSYARATAN
KETENTUAN WARNA PENYAMBUNGAN DAN PEMASANGAN
PEMBEBANAN
5/20/2018 3. PUIL PP BARU 2008
27/59
SIRKIT MOTOR
Sirkit penghantar motor.
2.1.1. KHA sirkit motor tunggal minimal 125 %
arus pengenal beban penuh motor.
KHA = 125 % x In
2.1.2. Sirkit penghantar motor yang mensuplai 2
motor atau lebih, minimal jumlah arus beban
penuh semua motor + 25 % arus beban penuhmotor terbesar ( arus beban tertinggi).
KHA = I n + 25 % x I n terbesar.
2.1.3. Untuk motor dengan daur kerja intermitten,
pembebanan singkat, tidak bekerja bersama-
sama, KHA penghantar sirkit dapat minimal
5/20/2018 3. PUIL PP BARU 2008
28/59
PROTEKSI BEBAN LEBIH
Proteksi beban lebih sirkit motor.
2.2.1
Jika gawai proteksi bukan pengaman lebur
(misalnya relai, Bimetal) dipasang pada :
Satu fasa : pada penghantar fasa.
Tiga fasa : cukup pada penghantar fasa 1
dan 2, atau 2 dan 3, atau 1 dan 3.
2.2.5. Proteksi beban lebih harus dilengkapi
dengan proteksi arus hubung pendek.
5/20/2018 3. PUIL PP BARU 2008
29/59
SETELAN GAWAI PENGAMAN MOTOR
Setelan beberapa motor tidak boleh melebihi nilai terbesar
berdasarkan tabel 5.5.2 untuk masing- masing motor
ditambahjum lah arus beban penuh motor lain dalamsirk i t tersebut.
Setelan gawai = setelan gawai proteksi terbesar + In motor
lain.
x
x
x
M1
M2
M3
IN3
IN2
IN1
IG2 = IG3 + IN1 + In2
IG3
IG2x
5/20/2018 3. PUIL PP BARU 2008
30/59
Arus gawai proteksi hubung singkat sirkitcabang yang mensuplai beberapa motor :
Arus gawai proteksi menurut tabel 5.5.2 + Jumlah
arus beban penuh semua motor yang di pasok
sirkit cabang tersebut.
x
Sirkit cabang
x
M MM
BA C
Gawai proteksi 218 A
85A + 52,5A +67,5A = 181A
125% x 54A
67,5A
125% x 42A
52,5A
125% x 68A
85A
Sirkit
Akhir
motor
102A108A
Motor sinkron
dengan autotrafoIN : 54A
Motor cincin
IN : 68A
Motort sangkar
IN : 42A
KHA Penghantar
Sirkit A
125% x 42A = 52,5 A
Sirkit B
125% x 54,5A
Sirkit C125% x 68 = 85A
Kuat hantar arus sirkit cabang
125% x Iu motor terbesar + In
masing-masing motor lain
= 125 % x 68A+42A+54 = 181A
5/20/2018 3. PUIL PP BARU 2008
31/59
x x
M MM
Gawai proteksi
= 108A + 42A + 68A= 218 A
1,25 x 68
= 85A
1,25 x 54
= 67,5A
1,25 x 42
= 52,5A
2,5 x 54A
=108A
Motor sinkron
dengan autotrafo
IN : 54A
Motor cincin
IN : 68A
Motort sangkar
IN : 42A
KHA
x 1,5 x 68 =102A Gawa Proteksi2,5 x 42
=105A
x
KHA =
85A+42+54
=181A
x
M
Motor cincin
68A
KHA =
1,25 x 68 = 85A
Sirkit Cabang
Sirkit Akhir
Sirkit UtamaxGawai proteksi
218A+68A=286A
KHA = 181+68=249A
1,5 x 68 = 102A
5/20/2018 3. PUIL PP BARU 2008
32/59
PERLENGKAPAN HUBUNG BAGI
FUNGSI
JENIS SIRKIT MASUK DAN KELUAR
KOMPONEN
RUANG PELAYANAN PENANDAAN
5/20/2018 3. PUIL PP BARU 2008
33/59
3. PERANCANGAN INSTALASI LISTRIK
KONDISI LINGKUNGANDALAM MENETAPKAN KONDISI LINGKUNGAN PENGGUNAANPERLENGKAPAN INSTALASI, PERLU DIPERHITUNGKAN BEBERAPA FAKTORDAN PARAMETER LINGKUNGAN TERKAIT, DAN DIPILIH TINGKAT
KEPARAHAN AKIBAT PARAMETER LINGKUNGAN TERSEBUT. FAKTOR DANPARAMETER LINGKUNGAN TERSEBUT, ANTARA LAIN :
KONDISI IKLIM: DINGIN/PANAS, KELEMBABAN, TEKANAN, GERAKAN MEDIASEKELILING PENGUAPAN, RADIASI DAN AIR SELAIN DARI HUJAN.
KONDISI BIOLOGIS: FLORA DAN FAUNA SEPERTI JAMUR DAN RAYAP.
BAHAN KIMIA AKTIF: GARAM, SULFUR DIOKSIDA, HIDROGEN SULFIT,NITROGEN OKSIDA, OZON, AMONIA, KLOR, HIDROGEN KLORIDA, HIDROGENFLOR DAN HIDROKARBON ORGANIK.
BAHAN MEKANIS AKTIF: PASIR, DEBU, DEBU MELAYANG, SEDIMEN DEBU,LUMPUR DAN JELAGA.
CAIRAN PENGOTOR: BERBAGAI MINYAK, CAIRAN PENDINGIN, GEMUK,BAHAN BAKAR DAN AIR BATERAI.
KONDISI MEKANIS: GETARAN, JATUH BEBAS, BENTURAN, GERAKANBERPUTAR, DEVIASI SUDUT, PERCEPATAN, BEBAN STATIS DAN ROBOH.
GANGGUAN LISTRIK DAN ELEKTROMAGNET: MEDAN MAGNET, MEDAN
LISTRIK, HARMONIK, TEGANGAN SINYAL, VARIASI TEGANGAN DANFREKUENSI, DAN TEGANGAN INDUKSI DAN TRANSIEN.
5/20/2018 3. PUIL PP BARU 2008
34/59
3. PEMASANGAN INSTALASI LISTRIK
JENIS PENGAWATAN DAN CARA PEMASANGAN
PEMILIHAN JENIS PENGAWATAN DAN CARA PEMASANGANBERGANTUNG PADA:
SIFAT LOKASI; SIFAT DINDING ATAU BAGIAN LAIN DARI BANGUNAN YANG
MENYANGGA PENGAWATAN;
DAPAT TERJANGKAUNYA PENGAWATAN OLEH MANUSIA ATAUTERNAK;
TEGANGAN A.L. MENENYUKAN DIMENSI (CLEARANCE);
STRES ELEKTROMEKANIS YANG MUNGKIN TERJADI KARENAHUBUNG-PENDEK;
STRES LAIN YANG MUNGKIN DIALAMI OLEH PENGAWATAN ITUSELAMA PEMASANGAN INSTALASI LISTRIK ATAU WAKTUPENGOPERASIAN.
5/20/2018 3. PUIL PP BARU 2008
35/59
3. GAWAI PROTEKSI
KARAKTERISTIK GAWAI PROTEKSI HARUS
DITENTUKAN BERDASARKAN FUNGSINYA,YAITU PROTEKSI DARI EFEK:
ARUS LEBIH (BEBAN LEBIH, HUBUNG PENDEK);
ARUS GANGGUAN BUMI;
TEGANGAN LEBIH; TEGANGAN KURANG ATAU TAK BERTEGANGAN
.
5/20/2018 3. PUIL PP BARU 2008
36/59
PERALATAN PENYAMBUNG
PEMUTUS
PEMISAH (DS)
UNTUK MENGAMANKAN MANUSIASAKLAR BEBAN
UNTUK PENGENDALIAN
PEMUTUS SIRKIT
UNTUK MENGAMANKAN
INSTALASI/PERALATAN
5/20/2018 3. PUIL PP BARU 2008
37/59
4. PEMILIHAN
PERLENGKAPAN LISTRIK
1. UMUM
SETIAP BAGIAN PERLENGKAPAN LISTRIK YANG DIGUNAKAN DALAMINSTALASI LISTRIK HARUS MEMENUHI PUIL 2000 DAN/ATAU STANDAR
YANG BERLAKU.
- BAIK, TIDAK CACAT DAN BERFUNGSI DENGAN BAIK
- BAIK, SESUAI DENGAN STANDAR YANG DITETAPKAN (ADA TANDA
STANDAR)
- HARUS DIPILIH SESUAI DENGAN PEMBEBANANNYA
2. KARAKTERISTIK
SETIAP BAGIAN PERLENGKAPAN LISTRIK YANG DIPILIH HARUS
MEMPUNYAI KARAKTERISTIK YANG SESUAI DENGAN NILAI DANKONDISI YANG MENDASARI PERANCANGAN INSTALASI LISTRIK DANKHUSUSNYA HARUS MEMENUHI PERSYARATAN DALAM BUTIRBERIKUTNYA.
- TEGANGAN
- ARUS
- FREKUENSI
- DAYA
5/20/2018 3. PUIL PP BARU 2008
38/59
4. PEMILIHAN
PERLENGKAPAN LISTRIK
3. KONDISI INSTALASI DAN PENCEGAHAN PENGARUH YANG
MERUSAK
DALAM MEMILIH PERLENGKAPAN INSTALASI LISTRIK, TERMASUK JUGAMENENTUKAN JENIS, UKURAN, TEGANGAN DAN KEMAMPUANNYA, HARUSDIPERHATIKAN HAL BERIKUT :
KESESUAIAN DENGAN MAKSUD PEMASANGAN DAN PENGGUNAANNYA;
KEKUATAN DAN KEAWETANNYA, TERMASUK BAGIAN YANG DIMAKSUDKANUNTUK MELINDUNGI PERLENGKAPAN LAIN;
KEADAAN DAN RESISTANS ISOLASINYA;
PENGARUH SUHU, BAIK PADA KEADAAN NORMAL MAUPUN TIDAK NORMAL;
PENGARUH API;
PENGARUH KELEMBABAN
5/20/2018 3. PUIL PP BARU 2008
39/59
4. PEMILIHAN
PERLENGKAPAN LISTRIK
4. PENCEGAHAN DARI EFEK YANG MERUSAK
SEMUA PERLENGKAPAN LISTRIK HARUS DIPILIH SEHINGGATIDAK MEMPENGARUHI DAN TIDAK MENYEBABKAN EFEKMERUSAK PADA PERLENGKAPAN LAIN ATAU MENGGANGGUSUPLAI SELAMA PELAYANAN NORMAL, TERMASUK OPERASIPENYAKELARAN.
DALAM KONTEKS INI, FAKTOR-FAKTOR YANG MUNGKINBERPENGARUH, TERMASUK ANTARA LAIN :
A) FAKTOR DAYA;B) ARUS KEJUT AWAL (INRUSH CURRENT);
C) BEBAN TAK SEIMBANG;
D) HARMONIK.
5/20/2018 3. PUIL PP BARU 2008
40/59
4. PEMILIHAN
PERLENGKAPAN LISTRIK
5. GAWAI PROTEKSI
PEMUTUS SIRKIT HARUS MEMPUNYAI
KAPASITAS PEMUTUS SEKURANG-KURANGNYASAMA DENGAN HASIL PERKALIAN TEGANGANNOMINAL DAN ARUS PUTUS.
GAWAI PROTEKSI ARUS-LEBIH DANKARAKTERISTIK SIRKIT YANG DIAMANKAN,HARUS DIPILIH DAN DIKOORDINASIKANSEHINGGA KERUSAKAN KOMPONEN LISTRIKSIRKIT DAPAT DICEGAH ATAU DIKURANGI.
5/20/2018 3. PUIL PP BARU 2008
41/59
5. PEMASANGAN DAN VERIFIKASI
AWAL INSTALASI LISTRIK
1 UMUM
INSTALASI LISTRIK HARUS DIPASANG SEHINGGA MENGHASILKAN KERJA YANGBAIK, DIKERJAKAN OLEH PERSONEL YANG BERKUALITAS SESUAI DENGAN
BIDANGNYA, DAN MENGGUNAKAN BAHAN YANG TEPAT. PENGAWATAN HARUS DILAKUKAN SEHINGGA BEBAS DARI HUBUNG PENDEK
DAN HUBUNG BUMI.
PERLENGKAPAN LISTRIK YANG DIPASANG HARUS BERMUTU LAIK PASANGDAN/ATAU MEMENUHI PERSYARATAN STANDAR (LIHAT 2.2.1.2).
KARAKTERISTIK TERTENTU DARI PERLENGKAPAN LISTRIK SEPERTI TERSEBUTDALAM 2.4.2, TIDAK BOLEH MEMBURUK DALAM PROSES PEMASANGANNYA.
PERLENGKAPAN LISTRIK HARUS DIRAWAT DENGAN BAIK UNTUK MENCEGAHKEMUNGKINAN MENURUNNYA MUTU PERLENGKAPAN LISTRIK AKIBAT PROSESTERTENTU DALAM MASA PENYIMPANAN, PERSIAPAN, PELAKSANAANPEKERJAAN DAN MASA PENGGUNAAN.
5/20/2018 3. PUIL PP BARU 2008
42/59
5. PEMASANGAN DAN VERIFIKASI
AWAL INSTALASI LISTRIK (LANJUTAN)
2. PENANDAAN DAN POLARITAS
SETIAP SIRKIT SUPLAI, REL ATAU SIRKIT CABANG PADA TITIKSUMBERNYA HARUS DITANDAI DENGAN JELAS MAKSUDPENGGUNAANNYA DENGAN TANDA YANG CUKUP AWET TERHADAPPENGARUH CUACA SEKITARNYA. PENANDAAN YANG DEMIKIAN ITUDIPERLUKAN PULA BAGI SETIAP SARANA PEMUTUS UNTUK MOTORDAN PERANTI LISTRIK. PENANDAAN TIDAK DIPERLUKAN APABILAMAKSUD PENGGUNAANNYA SUDAH JELAS DARI PENEMPATANNYA.
PENGHANTAR PROTEKSI DAN PENGHANTAR NETRAL HARUS BISADIIDENTIFIKASI, PALING TIDAK PADA TERMINALNYA, DENGAN WARNAATAU CARA LAIN. PENGHANTAR-PENGHANTAR BERBENTUK KAWATATAU KABEL YANG FLEKSIBEL, HARUS BISA DIIDENTIFIKASI DENGANWARNA ATAU CARA LAIN SEPANJANG PENGHANTARNYA.
5/20/2018 3. PUIL PP BARU 2008
43/59
5. PEMASANGAN DAN VERIFIKASI
AWAL INSTALASI LISTRIK (LANJUTAN)
SAKELAR HARUS DIPASANG SEHINGGA :
A) BAGIAN YANG DAPAT BERGERAK, TIDAK BERTEGANGAN PADA WAKTU
SAKELAR DALAM KEADAAN TERBUKA ATAU TIDAK MENGHUBUNG;
B) KEDUDUKAN KONTAK SEMUA TUAS SAKELAR DAN TOMBOL SAKELARDALAM SATU INSTALASI HARUS SERAGAM; MISALNYA AKAN
MENGHUBUNG JIKA TUASNYA DIDORONG KE ATAS ATAU TOMBOLNYA
DITEKAN.
FITING LAMPU JENIS EDISON HARUS DIPASANG DENGAN CARAMENGHUBUNGKAN KONTAK DASARNYA PADA PENGHANTAR FASE, DANKONTAK LUARNYA PADA PENGHANTAR NETRAL (LIHAT JUGA BAB 5).
PENGAMAN LEBUR JENIS D (DIASED) HARUS DIPASANG DENGAN KONTAKLUARNYA MENGHUBUNG PADA PENGHANTAR YANG MENUJU KE BEBAN.
KOTAK-KONTAK FASE TUNGGAL, BAIK YANG BERKUTUB DUA MAUPUNTIGA HARUS DIPASANG SEHINGGA KUTUB NETRALNYA ADA DI SEBELAHKANAN ATAU DI SEBELAH BAWAH KUTUB TEGANGAN.
5/20/2018 3. PUIL PP BARU 2008
44/59
5. PEMASANGAN DAN VERIFIKASI
AWAL INSTALASI LISTRIK (LANJUTAN)
3. PEMASANGAN DAN PENEMPATAN PERLENGKAPAN LISTRIK
JIKA TIDAK ADA KETENTUAN LAIN, PERLENGKAPAN LISTRIKTIDAK BOLEH DITEMPATKAN DI :
DAERAH LEMBAB ATAU BASAH; RUANG YANG MENGANDUNG GAS, UAP, DEBU, CAIRAN, ATAU
ZAT LAIN YANG DAPAT MERUSAKKAN PERLENGKAPAN LISTRIK;
RUANG YANG SUHUNYA MELAMPAUI BATAS NORMAL (LIHATBAB 8).
SELAMA MASA PEMBANGUNAN, PERLENGKAPAN LISTRIK YANGHANYA BOLEH DIPASANG DI RUANG KERING HARUS
DILINDUNGI TERHADAP CUACA UNTUK MENCEGAHPERLENGKAPAN TERSEBUT MENGALAMI KERUSAKAN YANGPERMANEN (LIHAT BAB 8).
PERLENGKAPAN LISTRIK HARUS DIPASANG DENGAN RAPI DANDENGAN CARA YANG BAIK DAN TEPAT.
5/20/2018 3. PUIL PP BARU 2008
45/59
5. PEMASANGAN DAN VERIFIKASI
AWAL INSTALASI LISTRIK (LANJUTAN)
4. SAMBUNGAN LISTRIK
SEMUA SAMBUNGAN LISTRIK HARUS BAIK DAN BEBAS DARI GAYATARIK.
SAMBUNGAN ANTAR PENGHANTAR DAN ANTARA PENGHANTAR DAN
PERLENGKAPAN LISTRIK YANG LAIN HARUS DIBUAT SEDEMIKIANSEHINGGA TERJAMIN KONTAK YANG AMAN DAN ANDAL.
GAWAI PENYAMBUNG SEPERTI TERMINAL TEKAN, PENYAMBUNGPUNTIR TEKAN, ATAU PENYAMBUNG DENGAN SOLDER HARUS SESUAIDENGAN BAHAN PENGHANTAR YANG DISAMBUNGNYA DAN HARUSDIPASANG DENGAN BAIK (LIHAT JUGA 2.5.4.4).
DUA PENGHANTAR LOGAM YANG TIDAK SEJENIS (SEPERTI TEMBAGADAN ALUMINIUM ATAU TEMBAGA BERLAPIS ALUMINIUM) TIDAKBOLEH DISATUKAN DALAM TERMINAL ATAU PENYAMBUNG PUNTIRKECUALI JIKA ALAT PENYAMBUNG ITU COCOK UNTUK MAKSUD DANKEADAAN PENGGUNAANNYA.
5/20/2018 3. PUIL PP BARU 2008
46/59
5. PEMASANGAN DAN VERIFIKASI
AWAL INSTALASI LISTRIK (LANJUTAN)
Sambungan penghantar pada terminal harus terjaminkebaikannya dan tidak merusakkan penghantar. Menyambungkabel fleksibel harus menggunakan sambung tekan (termasuk
jenis sekrup), sambung solder atau sambung puntir. Sepatukabel harus disambungkan dengan mur baut secara baik.
Sambung puntir harus dilaksanakan dengan:
a) menggunakan penyambung puntir; atau
b) cara dilas atau disolder. Sebelum dilas atau disolder,sambungan itu harus dipuntir dahulu agar diperoleh
sambungan yang baik secara mekanis dan listrik. Bahan yang digunakan seperti solder, fluks, dan pasta harus
terbuat dari jenis yang tidak berakibat buruk terhadap instalasidan perlengkapan listrik.
5/20/2018 3. PUIL PP BARU 2008
47/59
5. PEMASANGAN DAN VERIFIKASI
AWAL INSTALASI LISTRIK (LANJUTAN)
5. Pemeriksaan dan pengujian (verifikasi)
Instalasi listrik harus diuji dan diperiksa sebelum dioperasikan dan/atausetelah mengalami perubahan penting untuk membuktikan bahwa
pekerjaan pemasangan telah dilaksanakan sebagaimana semestinyasesuai dengan PUIL 2000 dan/atau standar lain yang berlaku.
Instalasi dalam pabrik atau bengkel, instalasi dengan 100 titik beban ataulebih, dan instalasi dengan daya lebih dari 5 kW, sebaiknya keadaanresistans isolasinya diperiksa secara berkala, dan jika resistans isolasinyatidak memenuhi ketentuan atau terlihat adanya gejala penurunan instalasiitu harus diperbaiki.
Pengukuran resistans isolasi harus dilakukan dengan gawai khusus yangbaik dan telah ditera.
Resistans isolasi harus diuji dengan cara seperti dijelaskan dalam 3.20.
Pada sistem IT harus ada sekurang-kurangnya satu gawai yang dipasangpermanen untuk memantau keadaan isolasi instalasi (gawai monitor isolasi,lihat 3.14.2.2).
5/20/2018 3. PUIL PP BARU 2008
48/59
5. PEMASANGAN DAN VERIFIKASI
AWAL INSTALASI LISTRIK (LANJUTAN)
6 PEMELIHARAAN
PEMELIHARAAN INSTALASI LISTRIK MELIPUTI PROGRAMPEMERIKSAAN, PERAWATAN, PERBAIKAN, DAN PENGUJIAN
ULANG BERDASARKAN PETUNJUK PEMELIHARAAN YANGTELAH DITENTUKAN.
PEMELIHARAAN TERSEBUT DIMAKSUDKAN AGAR INSTALASISELALU BAIK DAN BERSIH SERTA PENGGUNAAN DANPERBAIKANNYA DENGAN MUDAH DAN AMAN SEHINGGA
INSTALASI BERFUNGSI DENGAN BAIK SESUAI DENGAN YANGDIHARAPKAN.
KETENTUAN DASAR
UNTUK MEMELIHARA DAN MEMPEROLEH INSTALASI SEPERTITERSEBUT PADA 2.6.1.2 HARUS DIIKUTI PETUNJUKPEMELIHARAAN SEPERTI TERTUANG DALAM BAB 9, 9.12.
5/20/2018 3. PUIL PP BARU 2008
49/59
6. PEMERIKSAAN DAN PENGUJIAN
(VERIFIKASI)
Instalasi listrik harus diuji dan diperiksa sebelumdioperasikan dan/atau setelah mengalami perubahanpenting untuk membuktikan bahwa pekerjaan pemasangan
telah dilaksanakan sebagaimana semestinya sesuaidengan PUIL 2000 dan/atau standar lain yang berlaku.
Instalasi dalam pabrik atau bengkel, instalasi dengan 100titik beban atau lebih, dan instalasi dengan daya lebih dari5 kW, sebaiknya keadaan resistans isolasinya diperiksasecara berkala, dan jika resistans isolasinya tidakmemenuhi ketentuan atau terlihat adanya gejala penurunaninstalasi itu harus diperbaiki.
Pengukuran resistans isolasi harus dilakukan dengangawai khusus yang baik dan telah ditera.
Resistans isolasi harus diuji dengan cara sepertidijelaskan dalam 3.20.
Pada sistem IT harus ada sekurang-kurangnya satu gawaiyang dipasang permanen untuk memantau keadaan isolasi
5/20/2018 3. PUIL PP BARU 2008
50/59
TUJUANMEMASTIKAN INSTALASI YANG TELAH DIPASANG TELAHMEMENUHI KONTRAK DAN PERATURAN PERUNDANGANYANG BERLAKU (PUIL 2000)
PELAKSANALEMBAGA INSPEKSI KONSUIL DAN LEMBAGA LAIN YANGDITUNJUK OLEH BADAN YANG BERWENANG
MATA UJI A.L.:
PERALATAN DAN PENANDAANTANDA DAN POLARITASTAHANAN ISOLASITEGANGANKONTINUITAS SIRKITSISTEM PROTEKSI
5/20/2018 3. PUIL PP BARU 2008
51/59
PENGUJIAN INSTALASI LISTRIK
INSTALASI LISTRIK YANG TELAH SELESAI DIPASANG,ATAU YANG MENGALAMI PERUBAHAN, HARUS
DIPERIKSA DAN DIUJI DAHULU SEBELUM DIALIRI LISTRIKSESUAI DENGAN KETENTUAN YANG DITETAPKAN DALAM
PUIL 2000.
AGAR INSTALASI LISTRIK DAPAT DIGUNAKAN DENGAN
BAIK, INSTALASI PERLU DIULANG UJISECARA BERKALA
5/20/2018 3. PUIL PP BARU 2008
52/59
PENGUJIAN INSTALASI LISTRIK
PENGGUNA INSTALASI HARUS MEMPUNYAI DOKUMEN
BERIKUT:
DIAGRAM UMUM ATAU DIAGRAM LISTRIK SEDERHANA GAMBAR INSTALASI LISTRIK SESUAI KETENTUAN
PETUNJUK PENGGUNAAN DAN PEMELIHARAAN
BERITA ACARA PENGUJIAN MENGENAI HASIL HASIL
SEMUA PENGUJIAA
5/20/2018 3. PUIL PP BARU 2008
53/59
PENGUJIAN INSTALASI LISTRIK
TUJUAN
MEMASTIKAN INSTALASI YANG TELAH DIPASANG TELAH
MEMENUHI KONTRAK DAN PERATURAN PERUNDANGANYANG BERLAKU (PUIL 2000)
PELAKSANA
LEMBAGA INSPEKSI KONSUIL DAN LEMBAGA LAIN YANG
DITUNJUK OLEH BADAN YANG BERWENANG
(DIAKREDITASI)
.
5/20/2018 3. PUIL PP BARU 2008
54/59
PENGUJIAN INSTALASI LISTRIK
KETENTUAN:
1. PERSONIL PELAKSANA PENGUJIAN HARUS KOMPETEN
DALAM BIDANG PENGUJIAN DAN MEMILIKI SERTIFIKATYANG MASIH BERLAKU
2. METODE PENGUJIAN HARUS SESUAI STANDAR YANG
TELAH DITETAPKAN(TELAH DIKALIBRASI
3. ALAT ATAU PERLENGKAPAN UJI HARUS SESUAI
KETENTUAN
5/20/2018 3. PUIL PP BARU 2008
55/59
PENGUJIAN INSTALASI LISTRIK
PEMERIKSAAN DAN PENGUJIAN SBB.:
1. BERBAGAI MACAM TANDA PENGENAL DAN PAPAN
PERINGATAN2. PERLENGKAPAN LISTRIK YANG DIPASANG
3. CARA MEMASANG PERLENGKAPAN LISTRIK
4. POLARITAS
5. PEMBUMIAN
6. RESISTAN ISOLASI
7. KESINAMBUNGAN SIRKIT
8. FUNGSI PROTEKSI SISTEM INSTALASI
5/20/2018 3. PUIL PP BARU 2008
56/59
7. PEMELIHARAAN INSTALASI
Pemeliharaan instalasi listrik meliputi programpemeriksaan, perawatan, perbaikan, dan
pengujian ulang berdasarkan petunjukpemeliharaan yang telah ditentukan.
Pemeliharaan tersebut dimaksudkan agarinstalasi selalu baik dan bersih sertapenggunaan dan perbaikannya dengan mudah
dan aman sehingga instalasi berfungsi denganbaik sesuai dengan yang diharapkan.
Untuk memelihara dan memperoleh instalasiyang layak operasi harus diikuti petunjukpemeliharaan seperti tertuang dalam BAB 9, 9.12.
5/20/2018 3. PUIL PP BARU 2008
57/59
7. PEMELIHARAAN INSTALASI
PEMELIHARAAN INSTALASI LISTRIK MELIPUTI
PROGRAM PEMERIKSAAN, PERAWATAN,
PERBAIKAN DAN UJI ULANG BERDASARKANPETUNJUK PEMELIHARAAN YANG SUDAH
DITENTUKAN, AGAR KEADAAN INSTALASI
SELALU BAIK DAN BERSIH, PENGGUNAANNYA
AMAN DAN GANGGUAN SERTA KERUSAKANMUDAH DIKETAHUI, DICEGAH ATAU
DIPERKECIL. TUJUANNYA AGAR INSTALASI
LISTRIK BERFUNGSI DENGAN BAIK..
5/20/2018 3. PUIL PP BARU 2008
58/59
PEMELIHARAAN INSTALASI
KETENTUAN PEMELIHARAAN A.L.:SELURUH INSTALASI LISTRIK TERMASUK PENGAMAN,
PELINDUNG DAN LENGKAPANNYA SERTA BANGUNANINSTALASINYA HARUS TERPELIHARA DENGAN BAIK
KARENA INSTALASI MENGALAMI KEAUSAN, PENUAAN DAN
KERUSAKAN, SECARA BERKALA HARUS DIPRIKSA DAN
DIPERBAIKI DAN KOMPONEN YANG RUSAK
MINYAK ISOLASI CB ATAU TRAFO HARUS DIJAGA AGARKEMAMPUAN ISOLASINYA TIDAK KURANG DARI
PERSYARATAN YANG TELAH DITETAPKAN.
KONTAK CB, RELE SECARA BERKALA HRUS DIPERIKSA