Proper Use of Fabricated Fittings&

Fusion Methods for Transition Connections

John MurphyBlair Supply 

Agenda

Butt Fusion vs. Electrofusion

Proper Use of Fittings

Types Of Transition Fittings

Restraining Fittings & Pipe Movement

Hands on Fusion Demo

HDPE MARKET - WATERHDPE MARKET - WATER

EUROPE 70 – 75% HDPE MARKET PENETRATION

RUSSIA  90% HDPE MARKET PENETRATION

U.S.3% HDPE MARKET PENETRATIONGROWING STEADILY

ELECTROFUSION vs. BUTT FUSION

ELECTROFUSION vs. BUTT FUSION

EUROPEAN MARKET85% ELECTROFUSION FITTINGS15% BUTT FUSION FITTINGSUP TO 18” IN MOLDED BUTT FITTINGSUP TO 12” IN EF TEES, ELBOWS, CAPS

US MARKET15% ELECTROFUSION85% BUTT FUSIONUP TO 12” IN MOLDED BUTT FITTINGSSTILL DEVELOPING EF TEES, ELBOWS, CAPS(LIMITED SIZES CURRENTLY OFFERED)

What is Butt Fusion? The Joining of two ends of HDPE pipe or fittings

Pipe Ends are Heated to 395 – 420 degrees

Pipe Ends are joined together to mold into one and 

allowed to cool

Beads are same inside and outside of pipe

Butt Fusion Procedures

•Pipe Cutting, Square Ends•Proper Alignment Into Machine 

•Fusion Temperature 

•Fusion Pressure

•Cooling Time 

Butt Fusion MachineCF14 , 1” – 4” Size

City of Courtland WWTP Up‐GradesCF‐28 Machine 2”IPS – 8” DIPS

Village of Sodus, Water  Intake ExtensionCF620 Machine 6” IPS‐ 20DIPS 

Village of Sodus, Water  Intake Extension 

MJ Adapters IPS & DIPS With & W/O StiffenersAccessory Kits C110 HD Gland, Gaskets, & Long Tee Botls

NPT Threads Up to 4” Male & Female  Carbon & Stainless

Transition Fittings 

Butt Fuse Fittings

What is Electrofusion ?? This technique involves preparing the outside surface of a pipe end, and inserting the Electrofusion fittings onto the pipe.  The inside of the fitting has a copper coil that will heat to specific temperature when connected to  EF processor . The melts from the two components flow together and fuse as the joint cools 

Couplers 1/2” - 48” IPS 4” – 30” DIPS SDR 6 to SDR 32.5 Available

Specialty Fittings 90’s, 45’s & Tees Reducers & Flex Restraints

Branch Saddles 2” x 2” – 48” x 36” SDR 9 to SDR 32.5 Fusions Available NEW: Saddles with Electrofusion Outlets

IntegriFuse EF Fittings

IntegriFuse Electrofusion Fittings

Cutting Pipe Ends

Cut pipe at right angles 

Marking the Fusion Zone

Measure the fusion zone

Scraping the fusion zone This operation ensures removal of oxide layer, which will increase melt flow 

during the fusion process. It is critical that the oxide layer be removed completely; otherwise it may cause cold welding resulting in leakage. 

Mechanical Scraper                                     Manual Scraper            

Deburring/Beveling Ends

Debur or Bevel pipe ends              

Cleaning the Fusion Zone

Insert the Pipe into the Coupler

An assembly, which is stressed, may result in defective joint.  Ensure that both pipes are inserted into the fitting and the two ends are meeting 

each other in the center of the coupler (the cold zone). The maximum allowable gap between the two pipes is to be less than > ½”. If there are stops, push all the way to the stops.

Mis-Alignment- Unacceptable FusionPossible Causes: Inadequate Clamping or

Restraint during fusion.

Mis-Stab- Unacceptable FusionPossible Causes: Failure to mark and monitor

stab depth.

Short Stab- Unacceptable FusionPossible Causes: Failure to mark and monitor

stab depth.

Exposed Wire- Unacceptable FusionPossible Causes: Pipe Ovality, Flat Spots,

Undersized Pipe, Binding

Melt Out- Unacceptable FusionPossible Causes: Pipe Ovality, Flat Spots,

Undersized Pipe, Binding

Good Fusion- Acceptable.

Cool Time

The Cooling time is a critical step in determining the successful fusion of the EF Coupler to the pipe.

The Cooling Time is indicated by “Cool” on the coupler and is the amount of time required prior to examination, movement, and pressurization of the coupler.

After the Cooling time is finished, you are required to perform a flashlight test, in which the installer views the coupler/pipe interface to check for remaining gaps or wires that can be seen.

Utilize a metal hose clamp or plastic electrical tie to check the coupler/pipe interface to make sure that the tie or claps stops at the first wire.

The EF Fitting can be fused a maximum of 3 times if necessary, after the cooling time. 

FLEX RESTRAINT ELECTROFUSION Designed for use on HDPE pipe 6" IPS/DIPS - 63" IPS Used to Create Thrust Restraints To minimize Pipe Expansion & Contraction

Water Park – Discovery Cove (Disney)

Village of Macedon WWTP Improvements 2013

Fusion Demo & QuestionsResources   

Blair Supply , www.blairsupplyusa.com 

Integrity Fusion Products, www.integrityfusion.com 

Recommended