La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 1
LA GESTIONEDEGLI
AMBIENTI CONFINATI
dr.a Rita Brusa
Milano 25 ottobre 2001
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 2
LIVELLI DI PROTEZIONE
ISPE Baseline® Pharmaceutical Engineering Guides Volume 1: Bulk Pharmaceutical Chemicals
LEVEL I GENERAL An area with normal housekeeping and maintenance
LEVEL II PROTECTED
An area in which steps are taken to protect exposed drug substances from contamination
LEVEL III CONTROLLED
Area for which specific environmental conditions are defined, controlled and monitored to prevent contamination of exposed drug substances
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 3
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 4
AREA ESTERNA
AREE AUSILIARIE
CLEANROOM
CLEAN ZONE
PROCESS CORE TRASPORTO MATERIALI USCITA PRODOTTI
ING
RE
SS
O P
ER
SO
NA
LE
US
CIT
A P
ER
SO
NA
LE
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 5
CLEAN ROOM
Room in which the concentration of airborne particles is controlled, and which is constructed and used in a manner to minimize the introduction, generation, and retention of particles inside the room and in which other relevants parameters, e.g. temperature, humidity, and pressure, are controlled as necessary. ISO 14644-1:1999
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 6
CLEAN ZONE
Dedicated space in which the concentation of airborne particles is controlled, and in which is constructed and used in a manner to minimize the introduction, generation, and retention of particles inside the zone, and which other relevants parameters, e.g. temperature, humidity, and pressure, are controlled as necessary. ISO 14644-1:1999
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 7
CLASSIFICATION
Level (or the process of specifying or determining the level) of airborne particulate cleanliness applicable to a cleanroom or clean zone, espressed in terms of an ISO Class N, which represents maximum allowable concentrations (in particles per cubic metre of air) for considered size of particles Classification in accordance with this International Standard is limited to the range extending from ISO Class 1 through ISO Class 9 ISO 14644-1:1999
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 8
CLASSIFICAZIONE SECONDO FEDERAL STANDARD 209E
LIMITE DI CLASSE
0.1 m 0.2 m 0.3 m 0.5 m 5 m CLASSE
Unità di volume Unità di volume Unità di volume Unità di volume Unità di volume SI Inglese m3 ft3 m3 ft3 m3 ft3 m3 ft3 m3 ft3 M1 350 9,91 75,7 2,14 30,9 0,875 10 0,283 M 1,5 1 1240 35,0 265 7,50 106 3,00 35,3 1,00 M 2 3500 99,1 757 21,4 309 8,75 100 2,83 M 2,5 10 12400 350 2650 75 1060 30,0 353 10,0 M 3 35000 991 7570 214 3090 87,5 1000 28,3 M 3,5 100 26500 750 10600 300 3530 100 M 4 75700 2140 30900 875 10000 283 M 4,5 1 000 35300 1000 247 7,0 M 5 100000 2830 618 17,5 M 5,5 10 000 353000 10000 2470 70 M 6 1000000 28300 6180 175 M 6,5 100 000 3530000 100000 24700 700 M 7 10000000 283000 61800 1750
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 9
CLASSIFICAZIONE SECONDO ISO 14644-1
Maximum concentration limits (particles/m3 of air) for particles equal to and larger than the considered size shown below (concentration limits are calculated in accordance with equation (1) in 3.2
ISO classification number (N)
0.1 m 0.2 m 0.3 m 0.5 m 1 m 5 m ISO Class 1 10 2 ISO Class 2 100 24 10 4 ISO Class 3 1 000 237 102 35 8 ISO Class 4 10 000 2 370 1 020 352 83 ISO Class 5 100 000 23 700 10 200 3 520 832 29 ISO Class 6 1 000 000 237 000 102 000 35 200 8 320 293 ISO Class 7 352 000 83 200 2 930 ISO Class 8 3 520 000 832 000 29 300 ISO Class 9 35 200 000 8 320 000 293 000 NOTE Uncertainties related to the measurement process require that concentration data with no more than three significant figures be used in determining the classification level
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 10
LIMITI DI CLASSE SECONDO GMP
a riposo in operatività
quantità massima ammissibile di particelle/m3 pari o superiore a CLASSE
0.5 m 5 m 0.5 m 5 m
A 3 500 0 3 500 0
B 3 500 0 350 000 2 000
C 350 000 2 000 3 500 000 20 000
D 3 500 000 20 000 non definita non definita
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 11
LIMITI DI CONCENTRAZIONE PARTICELLARE 0,5 m
CLASSE ISO
ISO 14644-1 FS 209E CLASSE FS 209E
1 == == == 2 4 == == 3 35 35,3 1 4 352 353 10 5 3 520 3 530 100 6 35 200 35 300 1 000 7 352 000 353 000 10 000 8 3 520 000 3 530 000 100 000 9 35 200 000 == ==
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 12
PROGETTAZIONE DI UNA CLEAN ROOM
PARAMETRI CRITICI• CLASSE DI APPARTENENZA• N° DI RICAMBI / ORA• TIPO DI FLUSSO (UNIDIREZIONALE – NON UNIDIREZIONALE)
• SEPARAZIONE LOCALI• SISTEMA INDIPENDENTE O CENTRALIZZATO• LOCALI DOTATI DI BUSSOLA• SISTEMA DI PRESSIONI DIFFERENZIALI• HR E T ADOTTATE
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 13
PRESSIONI A SANDWICH
BUSSOLA IN SOVRAPRESSIONE ARIA ESTERNA ARIA ESPULSA HEPA HEPA HEPA
CORRIDOIO PRECAMERA BOX FILTRO HEPA
+ + + +
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 14
PRESSIONI A SANDWICH
BUSSOLA IN DEPRESSIONE ARIA ESTERNA ARIA ESPULSA HEPA HEPA HEPA
CORRIDOIO PRECAMERA BOX FILTRO HEPA
+ + + + +
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 15
PRESSIONI IN CASCATA
LOCALE IN SOVRAPRESSIONE ARIA ESTERNA ARIA ESPULSA HEPA HEPA HEPA
CORRIDOIO PRECAMERA BOX FILTRO HEPA
+ + + + + +
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 16
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 17
SCHEMA DI FILTRAZIONE CONSIGLIATO
• Prefiltro per aria immessa nel condizionatore• Filtro secondario a protezione del filtro finale• Filtro terminale
PROBLEMI • Difficoltà a rientrare nella classe desiderata• Alta frequenza di cambio filtri finali con costi
inaccettabili
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 18
CLASSIFICAZIONE FILTRIsecondo EN 1822
CLASSE DEL FILTRO
EFFICIENZA
%
PENETRAZIONE
% H 10 85 15 H 11 95 5 H 12 99,5 0,5 H 13 99,95 0,05 H 14 99,995 0,005 U 15 99,9995 0,0005 U 16 99,99995 0,00005 U 17 99,999995 0,000005
HEPA High Efficiency Particulate Air H ULPA Ultra Low Penetrations Airfilters U
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 19
CLASSIFICAZIONE FILTRIsecondo EUROVENT
CLASSE DEL
FILTRO
SECONDO EUROVENT
EFFICIENZA INIZIALE
Ei %
PENETRAZIONE
P %
EFFICIENZA DI FILTRAZIONE
EU 10 95 Ei < 99.9 5 P > 0.1 AS EU 11 99.9 Ei < 99.97 0.1 P > 0.03 AS EU 12 99.97 Ei < 99.99 0.03 P > 0.01 HEPA EU 13 99.99 Ei < 99.999 0.01 P > 0.001 HEPA EU 14 99.999 Ei 0.001 P HEPA
EFFICIENZA INIZIALE (Ei %) Capacità di ritenzione % di particelle di diametro 0.3 m filtro
pulito PENETRAZIONE (P %) Penetrazione % di particelle di diametro 0.3 m filtro pulito AS Alta efficienza HEPA High Efficiency Particulate Air
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 20
SERVIZI AUSILIARI
Entrata e uscita materiali Entrata ed uscita personale
numero di persone procedure di vestizione
abiti in dotazione frequenze di cambio collocazione degli abiti
Spazi tecnici
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 21
PARAMETRI DA MONITORARE
• Umidità relativa
• Temperatura
• Pressione differenziale
Misura continua (aggiornamento costante della misura)
Misura frequente (aggiornamento ogni 60 minuti)
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 22
QUALIFICHE E TEST
STADIO DI SVILUPPO STATO “OCCUPAZIONALE” TEST
DESIGN QUALIFICATION
Concetti di base Disegni e specifiche
nessuno Non applicabile
INSTALLATION QUALIFICATION
Installazione completata Servizi collegati e
funzionanti
As Built Test di tenuta sui filtri
OPERATIONAL QUALIFICATION
Apparecchiature installate
At Rest Portata aria e ricambi Temperature ed umidità
relativa Classe di contaminazione Tempo di recupero P Carica batterica Smoke test
PERFORMANCE QUALIFICATION
(Processo in funzione) (Personale presente)
Operational Temperature ed umidità relativa
Classe di contaminazione Carica batterica P
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 23
OPERATIONAL QUALIFICATION
STADIO DI SVILUPPO
STATO “OCCUPAZIONALE” TEST
Apparecchiature installate At Rest
Portata aria e ricambi Temperature ed umidità
relativa Classe di contaminazione Tempo di recupero P Carica batterica Smoke test
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 24
RIQUALIFICA“CONDITION OF CONTINUED COMPLIANCE”
ISO 14644-1
CONTA PARTICELLARE
CLASSE INTERVALLO DI TEMPO MASSIMO ISO 5 6 MESI > ISO 5 12 MESI
TEST ADDIZIONALI
TEST INTERVALLO DI TEMPO MASSIMO VELOCITÁ DELL’ARIA 12 MESI PORTATA DELL’ARIA 12 MESI
PRESSIONE 12 MESI
TEST OPZIONALI
TEST INTERVALLO DI TEMPO MASSIMO TENUTA DEI FILTRI 24 MESI
VISUALIZZAZIONE DEL FLUSSO 24 MESI TEMPO DI RECUPERO 24 MESI
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 25
OCCUPANCY STATES
AS BUILT Condition where the installation is complete with all ser-vices connected and functioning but with no production equipment, materials, or personnel present. AT-REST Condition where the installation is complete with equip-ment installed and operanting in a manner agreed upon by the customer and supplier, but with no personnel present OPERATIONAL Condition where the installation is functioning in the speci-fied manner, with the specified number of personnel present and working in the manner agreed upon ISO 14644-1:1999
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 26
VERIFICA CLASSE DI CONTAMINAZIONE
Nel protocollo devono essere definiti:
A. il metodo secondo ISO 14644 secondo FS209E
B. lo stato di occupancy as built at rest operational
C. lo strumento D. i parametri adottati
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 27
VERIFICA CLASSE DI CONTAMINAZIONESTRUMENTAZIONE
Per determinare la concentrazione della contaminazione particellare aeroportata deve essere utilizzato un contatore ottico di particelle (O.P.C. = Optical Particle Counter) a misura della luce diffusa. Nella scelta del conta particelle si dovrà tener conto di:
sorgente luminosa campo di misura volume di campionamento efficienza di conteggio massima concentrazione di particelle
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 28
VERIFICA CLASSE DI CONTAMINAZIONE DEFINIZIONE PARAMETRI DI PROVA
• Determinazione dei punti di campionamento• Minimo volume aria da campionare• Durata delle misure• Quante volte ripetere le misure• Intervallo tra le misure• Dimensioni delle particelle• Limite di accettabilità• Limiti di allerta e azione
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 29
VERIFICA CLASSE DI CONTAMINAZIONE REPORT RISULTATI
• Identificazione e posizione della clean room• Identificazione contatore e stato di calibrazione• Rumore di fondo del contatore• Tipo di misura: classificazione o monitoraggio• Classe di contaminazione• Dimensione della(e) particella(e)• Portata d’aria della sonda• Posizione dei punti di campionamento• Dati grezzi
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 30
VERIFICA INTEGRITA’ DEI FILTRI
SCOPO: scopo del test è quello di verificare che un sistema di filtri sia installato correttamente e che non si verifichino trafilamenti.
FREQUENZA tutte le volte che si deve avviare una camera bianca in occasione della sostituzione dei filtri METODO: fotometro con areosol contatore di particelle
con certificato di calibrazione valido (< 12 mesi) I due metodi non sono comparabili Il metodo che utilizza il contatore di particelle è meno contaminante
REGISTRAZIONE DATI:
Metodo di test Identificazione strumento e data di calibrazione Classe della camera bianca e condizioni operative Posizione dei punti Dati grezzi
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 31
VERIFICA PORTATA ARIA
SCOPO: verificare l’uniformità della velocità e la portata d’aria fornita. La misura della velocità è opzionale in installazione di flussi non unidirezionali. La misura della portata viene effettuata per valutare i ricambi d’aria.
METODO: Misura a valle dei filtri terminali
Misura nei canali di mandata STRUMENTO: anemometri o a filo caldo o a ventolina
con certificato di calibrazione valido (< 12 mesi) REGISTRAZIONE DATI:
Identificazione operatore Identificazione strumento e data di calibrazione Tipo di test e condizioni Posizione dei punti Dati grezzi
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 32
VERIFICA TEMPERATURA
SCOPO: scopo del test è quello di verificare la capacità del sistema di mantenere la temperatura entro limiti definiti
METODO: Generale (1 solo punto di misura)
Globale (per aree con requisiti ristretti, almeno 3 punti di misura) STRUMENTO: Termometri Termistori
con certificato di calibrazione valido (< 12 mesi) REGISTRAZIONE DATI:
Identificazione operatore Identificazione strumento e data di calibrazione Tipo di test e condizioni Valore da mantenere Posizione dei punti Dati grezzi
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 33
VERIFICA UMIDITA’
SCOPO: scopo del test è quello di verificare la capacità del sistema di condizionamento di mantenere il livello dell’umidità entro limiti definiti, espressa come umidità relativa o punto di rugiada
METODO: almeno un punto di misura per area
La misura dovrà essere effettuata per almeno un’ora e per ciascun punto la misura dovrà essere letta e registrata almeno ogni 6 minuti
STRUMENTO: Sensore del punto di rugiada Condensatore con sottile strato dielettrico sensibile all’umidità
con certificato di calibrazione valido (< 12 mesi) REGISTRAZIONE DATI:
Identificazione operatore Identificazione strumento e data di calibrazione Tipo di test e condizioni Valore da mantenere Posizione dei punti Dati grezzi
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 34
VERIFICA PRESSIONI DIFFERENZIALI
SCOPO: scopo del test è quello di verificare la capacità del sistema di mantenere una determinata differenza di pressione tra gli ambienti
STRUMENTO: micromanometro elettronico manometro inclinato sonda per la misura della differenza di pressione
con certificato di calibrazione valido (< 12 mesi) REGISTRAZIONE DATI:
Identificazione operatore Identificazione strumento e data di calibrazione Tipo di test e condizioni Valore da mantenere Posizione dei punti Dati grezzi
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 35
RECOVERY TESTSCOPO: verificare la capacità di una camera bianca ad eliminare le particelle aerotrasportate. DEFINIZIONE Viene misurato come
cambiamento percentuale di concentrazione delle particelle tempo di recupero 100:1 (tempo richiesto per diminuire di un fattore 100 il livello di concentrazione iniziale di particelle Deve essere eseguito in condizioni “as built” o “at rest”
METODO: misurazione diretta del tempo di recupero valutazione della capacità di recupero STRUMENTI: Contatore di particelle Generatore di aerosol
con certificato di calibrazione valido (< 12 mesi) REGISTRAZIONE DATI:
Identificazione dell’operatore Identificazione strumenti e data di calibrazione Classe della camera bianca e condizioni operative Posizione dei punti Dati grezzi
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 36
SMOKE TESTVISUALIZZAZIONE DI FLUSSO
SCOPO: scopo del test è quello di verificare le caratteristiche spaziali e temporali del flusso
METODO: Iniezione di un tracciante Viene generato un fumo atossico che permette di visualizzare i flussi
dell’aria Devono essere evidenziate eventuali flussi secondari o stagnanti Il test può essere supportato da documentazione fotografica o filmata REGISTRAZIONE DATI:
Identificazione operatore Identificazione strumento e data di calibrazione Tipo di test e metodo di visualizzazione Posizione dei punti Dati e immagini grezzi
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 37
CONTROLLI MICROBIOLOGICI
• Verifica della contaminazione dell’aria immessa
• Verifica della contaminazione delle superfici
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 38
MANUTENZIONE
PROGRAMMA
• Specificare azioni da seguire quando si raggiungono o si superano i limiti dei parametri critici
• Definire gli aggiustamenti permessi• Definire i metodi per gli aggiustamenti permessi• Definire i metodi di verifica e calibrazione• Definire le caratteristiche delle parti di ricambio• Predisporre procedure di pulizia a seguito della
manutenzione• Definire le azioni, le procedure e test da eseguire dopo la
manutenzione
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 39
MANUTENZIONE
REGISTRAZIONE MANUTENZIONE
• Intervento eseguito• Data intervento• Identificazione del personale• Valori dei parametri interessati prima e dopo
l’intervento• Lista parti di ricambio utilizzate
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 40
MANUTENZIONE
CAMBIO FILTRI TERMINALI
Parametri da verificare dopo la sostituzione:
Integrità filtri
Portata
Classificazione del locale
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 41
PERSONALE• Formazione• Abbigliamento
Deve essere definito– Materiale che lo compone– Frequenza di riutilizzo– Conservazione– Sostituzione– Modalità di vestizione
• Accesso alla cleanroom – Vietato introdurre oggetti personali– Cura dell’igiene– Verifica dell’abbigliamento– Divieto d’uso di cosmetici– Divieto d’uso di gioielli:orecchini, anelli– Vietato introdurre alimenti e bevande– Utilizzo di DPI
La gestione degli ambienti confinati" ASCHIMFARMA COMMISSIONE QUALITA' E NORMATIVE DI PRODOTTO Milano 25.10.2001 42
MATERIALI
• Pulizia e decontaminazione macchinari e materiali prima dell’introduzione nella cleanroom
• Compatibilità dei materiali con la cleanroom
• Ingresso dei materiali nella cleanroom• Stoccaggio dei materiali all’interno della
cleanroom
Recommended