Dynamic VAR’s [D-VAR]
What are D-VAR Devices?
• Dynamic VARs… Fully integrated modular STATCOM
with proprietary 3X overload
• Instantaneously injects precise amounts of reactive
power into a network
• Can be seamlessly integrated with static shunt devices
as part of a larger solution
Ref. American Superconductors
7/27/2019 0R-D-VAR
http://slidepdf.com/reader/full/0r-d-var 2/9
Transmission Problems That D-VAR Can Solve:
•Voltage Stability / Voltage Collapse -
•Uncontrolled rapid decline in system voltage
• Steady State Voltage Regulation -• Wind farms, radial lines, etc...
• Import/ Transfer Capability Restrictions -
• Limited ability to reliably import, export, or transfer power
• Mitigate voltage flicker/ power quality -
• Wind farms, industrial facilities
Ref. American Superconductors
7/27/2019 0R-D-VAR
http://slidepdf.com/reader/full/0r-d-var 3/9
Single Phase DC/AC Inverter
• Devices 1A, 1B, 2A and 2B are IGBT’s
acting as fast switches
• Capacitors hold DC charge• Lf and Cf are AC smoothing filter
components
Lf
Cf
1A
1B
2A
2B
AC DC
+
-
Ref. American Superconductors
7/27/2019 0R-D-VAR
http://slidepdf.com/reader/full/0r-d-var 4/9
Each D-VAR system hascontinuous reactive power…
with temporary over load
capabi l i ty up to 3 t imes i ts
cont inuous rat ing . Each
phase is individually controlled.
Proprietary Power ElectronicsTechnology
Ref.
American Superconductors
D-VAR Unit
7/27/2019 0R-D-VAR
http://slidepdf.com/reader/full/0r-d-var 5/9
Southold
Tiana
Southampton
Bridgehampton
Riverhead
Buell
Generating
Hero
Orient Point
Tuthill
Mattituck
Peconic
East Hampton Amagansett
Installation Site Double Circuit 69kV fault
Areas of Voltage Collapse Concerns
East End of Long Island
Ref. American Superconductors
7/27/2019 0R-D-VAR
http://slidepdf.com/reader/full/0r-d-var 6/9
To East Hampton Diesels
8 MVA
D-VAR Inputs to DVAR
for Voltage Control
VT
480-13800 V
Padmount
Transformers
69 kV
13.8 kVLoad
Load
VT
13.8 kV
To BuellTo Bridgehampton
Easthampton
Proposed Solution for the East End Voltage Issues
8 MVA D-VAR Installed at Bridgehampton
Ref. American Superconductors
7/27/2019 0R-D-VAR
http://slidepdf.com/reader/full/0r-d-var 7/9
Stony Hill
Plumtree
Rocky
River
West
BrookfieldBates
Rock
Shepaug
Carmel
Hill
Long
Mountain
Frost
Bridge
G
G
G
345 kV
115 kV
Hydro Generator
Substation
Trans. Capacitor
Distrib. Capacitor
D-VAR TM
Northeast Utilities Danbury Area
D-VAR solution by American Superconductors
7/27/2019 0R-D-VAR
http://slidepdf.com/reader/full/0r-d-var 8/9
SW Connecticut Imports
P e r U n i t V o l t a g
e s
Problem
Solution
Northeast Utilities Danbury Area
Comparison of Load-flow Results
Ref. American Superconductors
7/27/2019 0R-D-VAR
http://slidepdf.com/reader/full/0r-d-var 9/9
D-VAR™ Solution’s Dynamic Voltage Support
Provides a total of -48 MVAR/+84 MVAR
28 MW
26 MW
600V
600V 115 kV34.5 kV
T1
60/90 MVAwith LTC
28 units
26 units
97%
Lagging PF
97%
Lagging PF
26 MW
600V
26 units
34.5 kV UDG
collector
system
97%
Lagging PF
Utility
Interconnection
Point
8/24 MVAR
D-VAR
VTs
8/24 MVARD-VAR
Dynamic Capaci tor Banks
2 x 18 MVAR = 36 MVAR
D-VARs .
Dynamic 2 x 8 x 3 = 48 MVAR
1200 Amp
Breaker
4x2500 KVA
34500-480V
padmounttransformers
Joslyn
VBM
Switch
Joslyn
VBU
Switch
The dynamic MVARs are sized to
prevent the wind farm from
tripping off-line for the faults that
the utility specified.
9 X 3.6 MVAR
Caprock Wind Farm, New Mexico; D-VAR built by American Superconductors