Upload
carlos-lehman
View
214
Download
0
Embed Size (px)
Citation preview
7/29/2019 15-RAUGEO
1/24
Construction
AutomotiveIndustry
PEXa GROUND LOOP HEAT EXCHANGE SYSTEM
RAUGEOTM
7/29/2019 15-RAUGEO
2/24
REHAU 10.09.08- Page 2
- Geothermal overview
- Terminology
- Benefits
- HDPE piping systems
- RAUGEO system components
- PEXa ground loop pipe
- Fittings
- Manifolds- System sizing typical outputs
- Reference projects
- Regulations
RAUGEO SYSTEM
OUTLINE
7/29/2019 15-RAUGEO
3/24
REHAU 10.09.08- Page 3
Ground source heat pumps are
- self-contained, electrically-powered systems that take advantage of the Earths
relatively constant, moderate ground temperature to provide heating, cooling, and
domestic hot water more effic iently and less expensively than would be possible
though other conventional heating and cooling technologies. IGSHPA*
*International Ground Source Heat Pump Association (IGSHPA)
www.igshpa.org
GEOTHERMAL OVERVIEW
INTRODUCTION
7/29/2019 15-RAUGEO
4/24
REHAU 10.09.08- Page 4
GEOTHERMAL INTRODUCTION
Definitions:
- Geo (Earth) thermal (heat)
- Ground sourcea.k.a. geothermal
- Geoexchangeis also used
Units:
- BTU (British Thermal Unit)
- Heat energy required to raise 1 poundof water 1Fahrenheit
- Ton
- 1 Ton = 12,000 BTU/hr
- 1 Ton = 3.51 kW
kW (kiloWatt)- 1 kW = 3,413 BTU
TERMINOLOGY
7/29/2019 15-RAUGEO
5/24
REHAU 10.09.08- Page 5
GEOTHERMAL INTRODUCTION
Ground source heat pump system types:
- Direct exchange
- A direct exchange (DX) geothermal heat pump system is a geothermal heat pump system in
which the refrigerant circulates through copper tubing placed in the ground. The refrigerant
exchanges heat directly with the soil through the walls of the copper tubing. This eliminates the
plastic water pipe and water pump to circulate water found in a water-source geothermal heat
pump.
- Open loop
- Also known as pump and dump- Closed loop
- Vertical wells
- Horizontal trenches
- Pond loops
- Thermal piles (storage)
TYPES
7/29/2019 15-RAUGEO
6/24
REHAU 10.09.08- Page 6
GEOTHERMAL INTRODUCTION
Ground source heat pump systems:
- Closed loop
- Vertical wells
- Horizontal trenches
TYPES
Closed-loop ground source heat
pump system elements:
- Ground connection- Ground loop a.k.a. the Ground
heat exchanger a.k.a. GHEX
- Grout
- Antifreeze/water (fluid)
- Heat pump and controls- Pumping systems
- Indoor distribution
7/29/2019 15-RAUGEO
7/24
REHAU 10.09.08- Page 7
GEOTHERMAL INTRODUCTION
From where does the energy come?
- The Earth's core?
- Radioactive decay
- This heat energy is very deep, more than 1
km
TAPPING THE EARTHS STORED ENERGY
- The sun
-Insolationimpacts the outer crust
- Vast majority of thermal energy in the top
500 feet of the Earth is from the Sun
7/29/2019 15-RAUGEO
8/24
REHAU 10.09.08- Page 8
Energy source:
- Heat is continually supplied to the
ground in the form of solar energy
- Approximately 50% of the Suns
energy is absorbed by the Earth
- At a depth of approximately 15
feet the ground temperature
remains fairly constant (per
location), with a mean annual
Earth temperature of42-77F
(depending on latitude)
TAPPING THE EARTHS STORED ENERGY
GEOTHERMAL INTRODUCTION
7/29/2019 15-RAUGEO
9/24
REHAU 10.09.08- Page 9
Heat pump in winter
Heat pump in summer
Principles:
- A geothermal system does not directly burn
fossil fuel
- Electricity is used for circulator pumps
and compressor
- A geothermal system can be used to heat or
cool a space
- When heating, a geothermal system collects
and concentrates heat from the ground and
delivers it to the building
- When cooling, a geothermal system collects
and concentrates heat from the building and
delivers it to the ground- The ground acts l ike a heat battery
- The piping ground loop is like the
battery cables
GROUND SOURCE HEAT PUMP
HOW DOES IT WORK?
GEOTHERMAL INTRODUCTION
7/29/2019 15-RAUGEO
10/24
REHAU 10.09.08- Page 10
CONFIGURATIONS: CLOSED LOOP
Vertical Wells Horizontal Trenches
GEOTHERMAL INTRODUCTION
7/29/2019 15-RAUGEO
11/24
REHAU 10.09.08- Page 12
COPEnergy Source
4.0
0.93
0.85
0.88
1.00
Geothermal heat pump
Natural Gas
(condensing boiler)
Fuel Oil (boiler)
Propane (boiler)
Electrical Resistance
COP = Total energy delivered
Energy purchased
ENERGY SAVINGS
COP = COEFFICIENT OF PERFORMANCE
GEOTHERMAL INTRODUCTION
Example:
- A geothermal system which
delivers 4 kW of heat for every 1kW of energy purchased (for
circulators and the compressor)
has a Coefficient of Performance
of4.0/1.0 = 4.0
- Some systems deliver COP
even greater than 5.0
COP is analogous to Efficiency
7/29/2019 15-RAUGEO
12/24
REHAU 10.09.08- Page 16
1
BASIC COMPONENTS OF WATER-TO-WATER AND WATER-TO-AIR GEOTHERMAL SYSTEMS
2
3
GEOTHERMAL SYSTEM COMPONENTS
Ground Loop (vertical)Heat Pump
Radiant Heat Distribution
Forced Air Distribution
1
2
3
4
4
7/29/2019 15-RAUGEO
13/24
REHAU 10.09.08- Page 17
GROUND LOOP PIPES
POLYETHYLENE PIPES WITH FUSED U-BEND
SYSTEM COMPONENTS
Fusion-welded HDPE single U-bend:
- High Density PolyEthylene
- 3/4, 1, 1 1/4pipes
- CTS or IPS dimensions
- Fused joints, in field or factory
- Two pipes in a bore hole (one loop)
- Field joints may be butt-fused (pipe-to-
pipe) or socket-fused (pipe-to-fitting)
Socket fusion HDPE connection
7/29/2019 15-RAUGEO
14/24
REHAU 10.09.08- Page 18
GROUND LOOP PIPES
POLYETHYLENE PIPES WITH FUSED U-BEND
SYSTEM COMPONENTS
Fusion-welded HDPE single U-bend:
- J oints may be butt-fused (fitting-to-fitting)
or socket-fused (pipes-to-fittings)
Butt and socket fusion HDPE U-bend connection
7/29/2019 15-RAUGEO
15/24
REHAU 10.09.08- Page 20
How to join these pipes?
- Pipes must be connected in
some sort of header
- Fusion becomes more of a
challenge in wet, cold
conditions
- Typical trench conditions
following rain or reaching
the water table
SYSTEM COMPONENTSHDPE BUTT FUSION TECHNOLOGY
7/29/2019 15-RAUGEO
16/24
REHAU 10.09.08- Page 21
Reverse return piping arrangement:
- Field assembled manifolds of fused HDPE tees and pipes
- Headers need to step-up and step-down to forcethe fluid flow to be equal to all wells
- Larger diameter header pipes are costly and require extra fusion equipment
- Each piped U-bend must be within 5% length of one-another to avoid short circuits
- Pressure drop can become an issue
- Purging is a challenge, requiring high velocity through purge carts, lots of water and time
SYSTEM COMPONENTSTRADITIONAL HDPE MANIFOLDS
Example of step-up, step-down reverse return header with a four-well vertical system
Heat
Pump
Flow
Center
7/29/2019 15-RAUGEO
17/24
REHAU 10.09.08- Page 22
HDPE Close Manifold :
- Field assembled manifolds of fused
HDPE tees
- Reducing tees need to step-upor
step-down
- Each piped U-bend must be within
5% length of each other to avoid
short circuits
- Purging is a challenge, requiring high
velocity through purge carts, lots of
water and time
SYSTEM COMPONENTSTRADITIONAL HDPE MANIFOLDS
7/29/2019 15-RAUGEO
18/24
REHAU 10.09.08- Page 23
RAUPEX cross-linked polyethylene
- Radiant heating/cooling in the building
PRO-BALANCE manifold
- Connection to ground source pipes
- Increased control of flow
- Ease of installation
- Ease of operation
RAUGEO pipe in wells or ground loop
- System security
- Ease of installation
- Savings
EVERLOC fit tings
- Easy to install, secure
1
2
2
1
3
3
RAUGEO GROUND SOURCE HEAT EXCHANGE SYSTEMBASIC SYSTEM COMPONENTS OF REHAU SYSTEM
3
RAUGEO Double U-bend assembly
4
4
7/29/2019 15-RAUGEO
19/24
REHAU 10.09.08- Page 30
PEXa PIPE CAPABILITIESENVIRONMENTAL STRESS CRACK RESISTANCE
RESISTANCE TO IMPACT, SLOW CRACK GROWTH, ROCK IMPINGEMENT, SCRATCHES
PEXa pipe in rocky native soil
PEXa has high impact resistance:
- More flexible than other piping materials
- Will not crush, kink or collapse when proper
backfill techniques are used
- Superior notch resistance
- Will not dent or crush from typical impacts
- Native backfill is usually allowed, no sand
Note: Clay is not recommended backfill due to shrinkage
7/29/2019 15-RAUGEO
20/24
REHAU 10.09.08- Page 33
RAUGEO GROUND LOOP PIPES
Pipe dimensions:
- 3/4, 1 and 1 1/4 Inch Copper Tube Size
- PEXa, grey UV Shield
- Inside Diameter: 0.681 Inch
- Outside Diameter: 0.875 Inch
- Boxed in coil lengths 300 - 800 ft
depending on size
- Used for field systems
HORIZONTAL APPLICATIONS: RAUGEO COLLECT
7/29/2019 15-RAUGEO
21/24
REHAU 10.09.08- Page 36
RAUGEO GROUND LOOP PIPES
U-bend packaging:
- Delivered on pallets as individual coils
VERTICAL APPLICATIONS:
SINGLE AND DOUBLE U-BENDS, CONTINUOUS U-BENDS WITHOUT JOINTS
7/29/2019 15-RAUGEO
22/24
REHAU 10.09.08- Page 50
- Commonly used in residential applications
- Sometimes used in commercial applications where space allows
- Approximately 300 - 400 ft. of trench (600 - 800 ft. of pipe) per ton of energy required
- Variations in trench layout are acceptable
SYSTEM SIZINGCONFIGURATIONS: HORIZONTAL FIELD
7/29/2019 15-RAUGEO
23/24
REHAU 10.09.08- Page 51
SYSTEM SIZINGCONFIGURATIONS: VERTICAL BOREHOLES
- Commonly used in commercial applications or
wherever where space is limited
- Approximately 200 ft. of borehole per ton of energy
required. This varies across the country with
different soil types, water tables, etc.
- Typical sizing is 1.5 tons per 300 feet well depth
7/29/2019 15-RAUGEO
24/24
REHAU 10.09.08- Page 53
RAUGEO GROUND LOOP HEAT EXCHANGE SYSTEMREFERENCE PROJECTS