Upload
vankurd
View
215
Download
0
Embed Size (px)
Citation preview
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 146
Advanc ed Bus Transfer and Load Shedding Appl ic at ions
w i t h IEC61850
Tony Zhao Lubomir Sevov Craig WesterPowell Electrical Systems Inc GE Digital Energy Multilin
Texas AampM 64th Relay ConferenceApril 13 2011 College Station Texas USA
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 246
2
IEC61850
What is GOOSE IEC61850 Substation Communication Standard one technology one standard one world for substation
communications Ethernet network based communications between IEC61850 compatible devices
No serial (RS232 RS485 RS422 etc) communication no RTU Every manufacturer follows the same rules universal self-descriptive tag addressing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 346
3
IEC61850
Why do w e use GOOSE Replace the conventional hard wiring connections between IEDs Reducing wiring complexity Lower installation cost Cost saving by eliminating hard wiring and sometimes even eliminating hardwire components
Communications between IEDs are through Ethernet switches alwaysuse Ethernet TCPIP not serial RTU VLAN and priority need to besetup in the Ethernet switches
HMI Computer
Substation Controller(s) toEMSDCS or SCADAsystem (if needed)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 446
4
IEC61850
GOOSE How fas t
The time needed for trippingopening 52 breaker
with different technologies
Hardwire control relay output
about 12ms
Legacy device communications
about 500ms
GOOSE with IEC61850 capable relays
LAN response time 2-4ms
Relay 1 response time 2 msRelay 2 response time 2 ms
Add input recognition time 0-2ms
Add output operation time 2-4ms
Total 8-14ms
ExampleTripOpen a CB connected to Relay 2from Relay 1 through GOOSE messaging
Station LAN
IEC61850 CapableRelay 1
IEC61850 CapableRelay 2
GOOSE MessageTripOpen command
52Breaker
Output
Ethernet Switch
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 546
5
GOOSE m essaging
Indust r ia l app l ic a t ions Bus transfer between incoming sources Trip zone interlocking Under frequencyUnder voltage load shedding Load management in case of source capacity changes Arc flash signal initiate to a fast trip of incoming power source Publish a trip message to all feeder breakers Relay setting group change Breaker reclose initiation Transfer tripping Breaker failure initiate (BFI) to other breakers Fast bus trip scheme helliphellip
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 646
6
GOOSE m essaging
Bus t ransfer in a double-ended sub
52M1 52M2
SOURCE 1 SOURCE 2
Tx 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
NC NC
NOFEEDERS
on Bus 2
FEEDERSon Bus 1
Note
1 10-Switch is hardwired or wired to Relay 3 4 and 5 input2 Load shed if needed is hardwired
3 Popular relay based scheme transfer scheme for Relay 3 4 and 5
By SEL 3xSEL-351s Relay communications are through mirror bitBy GE 3xSR750 no relay communication everything is hardwired
4 If not using relays for MTM transfer a PLC is needed to be
programmed do the MTM transfer logic5 For HRG system need hard wire to block transfer or block closing if
GF on both sides
DOUBLE-ENDED MTM SUBSTATION
PROTECTION CONTROL AND METERING
CURRENTLY TYPICAL ARRANGEMENT
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 746
7
GOOSE m essagingBus t ransfer in a double-ended sub
New approach
Use 2 relays to do it all
52M1 52M2
3PH
D or Y
SOURCE 1 SOURCE 2
Tx1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 846
8
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 1 Di rec t f iber c onnec t ion
----Pros
bullSimple
bullNo need for network switchcost saving
bullEasy to add other
relaysIEDs through fiberexpansion for GOOSE toother relaysIEDs from thesame manufacturer
----Cons
bullLess Flexibility
bullFiber ports may take the
place where other modulecan not be added resultingin less IOs
bullDifficult to add other relaysthrough fiber expansion forGOOSE to other relaysIEDsfrom other manufacturers
Link Fiber Direct Connection Example
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 946
9
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 2 Add Et hernet sw i t c hes
52M1 52M2
PORT 2
SOURCE 1 SOURCE 2
Tx 1 Tx 2
L I NE 1
BUS 1 BUS 2
L I NE 2
52T
NC NC
NOFEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1046
10
GOOSE c om m unic at ion-assis t edBus t ransfer in a double-ended subRequirem ent s for t he Relays CT input
bull Three groups of three-phase CT inputs for 87T 5051 (50G51G) for incomers 5051 (50G51G) for tieprotection
bull One group of single-phase CT inputs for 51G at transformer Y secondary for transformer neutralprotection if it is not HRG system
PT inputbull 1 group of three-phase PT on the linebull 1 group of single-phase PT on the bus
bull Main breaker closing 25 is done by line PT and bus PT sync check and voltage permissivebull Bus 1 PT in Relay 1 and Bus 2 PT in Relay 2 are used for tie breaker manual closing (with 10-Switch
function) 25 sync check
Enough available terminals to handle needed digital inputs and digital outputsbull DIs must be hard wired in 52A TOC HRG GF transformer trip signals etcbull DIs may be hard wired in or may be from GOOSE PB or VI (or RB) AutoManual selection 94T 10-
Switch CSC CSO etcbull DOs Close and opentrip commands for each breaker It is better to have trip circuit monitoring
capability also
Protection elementsbull Used for protection 87T 5051 for lines 5051 for bus 51G for TX Y secondary 27 59bull Used for control 27 line to initiate transfer NOT27 line for source healthy (the other line) 25
Comprehensive logic capability Communication capability for substation automation and integration particularly GOOSE
capability to get DI and AI data values from the remote relay Other features nice to have Event waveform force contact input virtual input (remote bit)
and force contact output for easy testing propose
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1146
11
IEC61850GOOSE Double-Ended Sub
Use two relays to do everything
bull Meteringbull Protection
bull Control
bull Other
bull These relays are super relays
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1246
12
GOOSE Double-Ended SubMeter ing and prot ec t ion
Meteringbull Incoming linebull Voltage magnitude and angle each phasebull Current magnitude and angle each phasebull Frequency
bull Powerbull Power Active Power Pbull Reactive Power Qbull Apparent Power S
bull Power factor
Protectionbull 87T main protection element
bull 5051 (50G51G) for transformer primarybull 5051 (50G51G) for transformer secondarybull 51G for transformer Y sec neutral protectionbull 27 line and bus (also for control purpose)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1346
13
GOOSE Double-Ended SubCont ro l
Manual breaker operations Auto transfer operations
Auto retransfer operations (if needed) 25 function for breaker closing supervision LTC controls if needed Maintenance switch (change settings disable auto
transfer function etc) Arc flash sensor to incoming source breaker Other controls (load shed load management etc)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1446
14
GOOSE Double-Ended SubDig i t a l ou tput a r rangem ent
Relay 1 output to both 52M1 and 52T breaker control circuits Relay 2 output to 52M2 breaker control circuit only Logic for controlling 52M1 and 52T breakers is programmed in Relay
1 but control commands can go there from Relay 2 to Relay 1 through
GOOSE Logic for controlling 52M2 is programmed in Relay 2 butcontrol command can go from Relay 1 to Relay 2 through GOOSE Relay 1 can control 52M2 through GOOSE For example using front
pushbuttons located at Relay 1 to close or open 52M2 breaker Relay 2 can control 52M1 and 52T through GOOSE For example
using front pushbuttons located at Relay 2 to close or open 52M1breaker or 52T breaker
By careful selection of relay part numbers and program the relay logictrip circuit monitoring function for the output contacts used for breakertripopen purpose can be obtained in these relays No need forseparate trip coil monitoring devices
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1546
15
GOOSE Double-Ended SubDig i t a l input s needed for Relay 1
52A and TOC for 52M1 52A and TOC for 52T HRG GF from Transformer 1 (if using HRG system)
94T1 upstream schemebreaker trip (94T1 may come fromGOOSE instead) Transformer 1 common trip or individual trip signal 63X 26HH
71LL etc Bell alarm for 52M1 and 52T (for LVCB applications if needed) Local control switch CO commands for 52M1 and 52T Physical 10-Switch used to select 52M1 or 52T as the breaker
to trip [instead they may come from VIs (or RBs) or local PBs] Optional Remote closeopen commands for 52M1 and 52T
from remote (SCADA DCS HMI etc) through communicationpath
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 246
2
IEC61850
What is GOOSE IEC61850 Substation Communication Standard one technology one standard one world for substation
communications Ethernet network based communications between IEC61850 compatible devices
No serial (RS232 RS485 RS422 etc) communication no RTU Every manufacturer follows the same rules universal self-descriptive tag addressing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 346
3
IEC61850
Why do w e use GOOSE Replace the conventional hard wiring connections between IEDs Reducing wiring complexity Lower installation cost Cost saving by eliminating hard wiring and sometimes even eliminating hardwire components
Communications between IEDs are through Ethernet switches alwaysuse Ethernet TCPIP not serial RTU VLAN and priority need to besetup in the Ethernet switches
HMI Computer
Substation Controller(s) toEMSDCS or SCADAsystem (if needed)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 446
4
IEC61850
GOOSE How fas t
The time needed for trippingopening 52 breaker
with different technologies
Hardwire control relay output
about 12ms
Legacy device communications
about 500ms
GOOSE with IEC61850 capable relays
LAN response time 2-4ms
Relay 1 response time 2 msRelay 2 response time 2 ms
Add input recognition time 0-2ms
Add output operation time 2-4ms
Total 8-14ms
ExampleTripOpen a CB connected to Relay 2from Relay 1 through GOOSE messaging
Station LAN
IEC61850 CapableRelay 1
IEC61850 CapableRelay 2
GOOSE MessageTripOpen command
52Breaker
Output
Ethernet Switch
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 546
5
GOOSE m essaging
Indust r ia l app l ic a t ions Bus transfer between incoming sources Trip zone interlocking Under frequencyUnder voltage load shedding Load management in case of source capacity changes Arc flash signal initiate to a fast trip of incoming power source Publish a trip message to all feeder breakers Relay setting group change Breaker reclose initiation Transfer tripping Breaker failure initiate (BFI) to other breakers Fast bus trip scheme helliphellip
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 646
6
GOOSE m essaging
Bus t ransfer in a double-ended sub
52M1 52M2
SOURCE 1 SOURCE 2
Tx 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
NC NC
NOFEEDERS
on Bus 2
FEEDERSon Bus 1
Note
1 10-Switch is hardwired or wired to Relay 3 4 and 5 input2 Load shed if needed is hardwired
3 Popular relay based scheme transfer scheme for Relay 3 4 and 5
By SEL 3xSEL-351s Relay communications are through mirror bitBy GE 3xSR750 no relay communication everything is hardwired
4 If not using relays for MTM transfer a PLC is needed to be
programmed do the MTM transfer logic5 For HRG system need hard wire to block transfer or block closing if
GF on both sides
DOUBLE-ENDED MTM SUBSTATION
PROTECTION CONTROL AND METERING
CURRENTLY TYPICAL ARRANGEMENT
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 746
7
GOOSE m essagingBus t ransfer in a double-ended sub
New approach
Use 2 relays to do it all
52M1 52M2
3PH
D or Y
SOURCE 1 SOURCE 2
Tx1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 846
8
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 1 Di rec t f iber c onnec t ion
----Pros
bullSimple
bullNo need for network switchcost saving
bullEasy to add other
relaysIEDs through fiberexpansion for GOOSE toother relaysIEDs from thesame manufacturer
----Cons
bullLess Flexibility
bullFiber ports may take the
place where other modulecan not be added resultingin less IOs
bullDifficult to add other relaysthrough fiber expansion forGOOSE to other relaysIEDsfrom other manufacturers
Link Fiber Direct Connection Example
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 946
9
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 2 Add Et hernet sw i t c hes
52M1 52M2
PORT 2
SOURCE 1 SOURCE 2
Tx 1 Tx 2
L I NE 1
BUS 1 BUS 2
L I NE 2
52T
NC NC
NOFEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1046
10
GOOSE c om m unic at ion-assis t edBus t ransfer in a double-ended subRequirem ent s for t he Relays CT input
bull Three groups of three-phase CT inputs for 87T 5051 (50G51G) for incomers 5051 (50G51G) for tieprotection
bull One group of single-phase CT inputs for 51G at transformer Y secondary for transformer neutralprotection if it is not HRG system
PT inputbull 1 group of three-phase PT on the linebull 1 group of single-phase PT on the bus
bull Main breaker closing 25 is done by line PT and bus PT sync check and voltage permissivebull Bus 1 PT in Relay 1 and Bus 2 PT in Relay 2 are used for tie breaker manual closing (with 10-Switch
function) 25 sync check
Enough available terminals to handle needed digital inputs and digital outputsbull DIs must be hard wired in 52A TOC HRG GF transformer trip signals etcbull DIs may be hard wired in or may be from GOOSE PB or VI (or RB) AutoManual selection 94T 10-
Switch CSC CSO etcbull DOs Close and opentrip commands for each breaker It is better to have trip circuit monitoring
capability also
Protection elementsbull Used for protection 87T 5051 for lines 5051 for bus 51G for TX Y secondary 27 59bull Used for control 27 line to initiate transfer NOT27 line for source healthy (the other line) 25
Comprehensive logic capability Communication capability for substation automation and integration particularly GOOSE
capability to get DI and AI data values from the remote relay Other features nice to have Event waveform force contact input virtual input (remote bit)
and force contact output for easy testing propose
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1146
11
IEC61850GOOSE Double-Ended Sub
Use two relays to do everything
bull Meteringbull Protection
bull Control
bull Other
bull These relays are super relays
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1246
12
GOOSE Double-Ended SubMeter ing and prot ec t ion
Meteringbull Incoming linebull Voltage magnitude and angle each phasebull Current magnitude and angle each phasebull Frequency
bull Powerbull Power Active Power Pbull Reactive Power Qbull Apparent Power S
bull Power factor
Protectionbull 87T main protection element
bull 5051 (50G51G) for transformer primarybull 5051 (50G51G) for transformer secondarybull 51G for transformer Y sec neutral protectionbull 27 line and bus (also for control purpose)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1346
13
GOOSE Double-Ended SubCont ro l
Manual breaker operations Auto transfer operations
Auto retransfer operations (if needed) 25 function for breaker closing supervision LTC controls if needed Maintenance switch (change settings disable auto
transfer function etc) Arc flash sensor to incoming source breaker Other controls (load shed load management etc)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1446
14
GOOSE Double-Ended SubDig i t a l ou tput a r rangem ent
Relay 1 output to both 52M1 and 52T breaker control circuits Relay 2 output to 52M2 breaker control circuit only Logic for controlling 52M1 and 52T breakers is programmed in Relay
1 but control commands can go there from Relay 2 to Relay 1 through
GOOSE Logic for controlling 52M2 is programmed in Relay 2 butcontrol command can go from Relay 1 to Relay 2 through GOOSE Relay 1 can control 52M2 through GOOSE For example using front
pushbuttons located at Relay 1 to close or open 52M2 breaker Relay 2 can control 52M1 and 52T through GOOSE For example
using front pushbuttons located at Relay 2 to close or open 52M1breaker or 52T breaker
By careful selection of relay part numbers and program the relay logictrip circuit monitoring function for the output contacts used for breakertripopen purpose can be obtained in these relays No need forseparate trip coil monitoring devices
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1546
15
GOOSE Double-Ended SubDig i t a l input s needed for Relay 1
52A and TOC for 52M1 52A and TOC for 52T HRG GF from Transformer 1 (if using HRG system)
94T1 upstream schemebreaker trip (94T1 may come fromGOOSE instead) Transformer 1 common trip or individual trip signal 63X 26HH
71LL etc Bell alarm for 52M1 and 52T (for LVCB applications if needed) Local control switch CO commands for 52M1 and 52T Physical 10-Switch used to select 52M1 or 52T as the breaker
to trip [instead they may come from VIs (or RBs) or local PBs] Optional Remote closeopen commands for 52M1 and 52T
from remote (SCADA DCS HMI etc) through communicationpath
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 346
3
IEC61850
Why do w e use GOOSE Replace the conventional hard wiring connections between IEDs Reducing wiring complexity Lower installation cost Cost saving by eliminating hard wiring and sometimes even eliminating hardwire components
Communications between IEDs are through Ethernet switches alwaysuse Ethernet TCPIP not serial RTU VLAN and priority need to besetup in the Ethernet switches
HMI Computer
Substation Controller(s) toEMSDCS or SCADAsystem (if needed)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 446
4
IEC61850
GOOSE How fas t
The time needed for trippingopening 52 breaker
with different technologies
Hardwire control relay output
about 12ms
Legacy device communications
about 500ms
GOOSE with IEC61850 capable relays
LAN response time 2-4ms
Relay 1 response time 2 msRelay 2 response time 2 ms
Add input recognition time 0-2ms
Add output operation time 2-4ms
Total 8-14ms
ExampleTripOpen a CB connected to Relay 2from Relay 1 through GOOSE messaging
Station LAN
IEC61850 CapableRelay 1
IEC61850 CapableRelay 2
GOOSE MessageTripOpen command
52Breaker
Output
Ethernet Switch
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 546
5
GOOSE m essaging
Indust r ia l app l ic a t ions Bus transfer between incoming sources Trip zone interlocking Under frequencyUnder voltage load shedding Load management in case of source capacity changes Arc flash signal initiate to a fast trip of incoming power source Publish a trip message to all feeder breakers Relay setting group change Breaker reclose initiation Transfer tripping Breaker failure initiate (BFI) to other breakers Fast bus trip scheme helliphellip
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 646
6
GOOSE m essaging
Bus t ransfer in a double-ended sub
52M1 52M2
SOURCE 1 SOURCE 2
Tx 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
NC NC
NOFEEDERS
on Bus 2
FEEDERSon Bus 1
Note
1 10-Switch is hardwired or wired to Relay 3 4 and 5 input2 Load shed if needed is hardwired
3 Popular relay based scheme transfer scheme for Relay 3 4 and 5
By SEL 3xSEL-351s Relay communications are through mirror bitBy GE 3xSR750 no relay communication everything is hardwired
4 If not using relays for MTM transfer a PLC is needed to be
programmed do the MTM transfer logic5 For HRG system need hard wire to block transfer or block closing if
GF on both sides
DOUBLE-ENDED MTM SUBSTATION
PROTECTION CONTROL AND METERING
CURRENTLY TYPICAL ARRANGEMENT
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 746
7
GOOSE m essagingBus t ransfer in a double-ended sub
New approach
Use 2 relays to do it all
52M1 52M2
3PH
D or Y
SOURCE 1 SOURCE 2
Tx1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 846
8
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 1 Di rec t f iber c onnec t ion
----Pros
bullSimple
bullNo need for network switchcost saving
bullEasy to add other
relaysIEDs through fiberexpansion for GOOSE toother relaysIEDs from thesame manufacturer
----Cons
bullLess Flexibility
bullFiber ports may take the
place where other modulecan not be added resultingin less IOs
bullDifficult to add other relaysthrough fiber expansion forGOOSE to other relaysIEDsfrom other manufacturers
Link Fiber Direct Connection Example
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 946
9
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 2 Add Et hernet sw i t c hes
52M1 52M2
PORT 2
SOURCE 1 SOURCE 2
Tx 1 Tx 2
L I NE 1
BUS 1 BUS 2
L I NE 2
52T
NC NC
NOFEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1046
10
GOOSE c om m unic at ion-assis t edBus t ransfer in a double-ended subRequirem ent s for t he Relays CT input
bull Three groups of three-phase CT inputs for 87T 5051 (50G51G) for incomers 5051 (50G51G) for tieprotection
bull One group of single-phase CT inputs for 51G at transformer Y secondary for transformer neutralprotection if it is not HRG system
PT inputbull 1 group of three-phase PT on the linebull 1 group of single-phase PT on the bus
bull Main breaker closing 25 is done by line PT and bus PT sync check and voltage permissivebull Bus 1 PT in Relay 1 and Bus 2 PT in Relay 2 are used for tie breaker manual closing (with 10-Switch
function) 25 sync check
Enough available terminals to handle needed digital inputs and digital outputsbull DIs must be hard wired in 52A TOC HRG GF transformer trip signals etcbull DIs may be hard wired in or may be from GOOSE PB or VI (or RB) AutoManual selection 94T 10-
Switch CSC CSO etcbull DOs Close and opentrip commands for each breaker It is better to have trip circuit monitoring
capability also
Protection elementsbull Used for protection 87T 5051 for lines 5051 for bus 51G for TX Y secondary 27 59bull Used for control 27 line to initiate transfer NOT27 line for source healthy (the other line) 25
Comprehensive logic capability Communication capability for substation automation and integration particularly GOOSE
capability to get DI and AI data values from the remote relay Other features nice to have Event waveform force contact input virtual input (remote bit)
and force contact output for easy testing propose
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1146
11
IEC61850GOOSE Double-Ended Sub
Use two relays to do everything
bull Meteringbull Protection
bull Control
bull Other
bull These relays are super relays
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1246
12
GOOSE Double-Ended SubMeter ing and prot ec t ion
Meteringbull Incoming linebull Voltage magnitude and angle each phasebull Current magnitude and angle each phasebull Frequency
bull Powerbull Power Active Power Pbull Reactive Power Qbull Apparent Power S
bull Power factor
Protectionbull 87T main protection element
bull 5051 (50G51G) for transformer primarybull 5051 (50G51G) for transformer secondarybull 51G for transformer Y sec neutral protectionbull 27 line and bus (also for control purpose)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1346
13
GOOSE Double-Ended SubCont ro l
Manual breaker operations Auto transfer operations
Auto retransfer operations (if needed) 25 function for breaker closing supervision LTC controls if needed Maintenance switch (change settings disable auto
transfer function etc) Arc flash sensor to incoming source breaker Other controls (load shed load management etc)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1446
14
GOOSE Double-Ended SubDig i t a l ou tput a r rangem ent
Relay 1 output to both 52M1 and 52T breaker control circuits Relay 2 output to 52M2 breaker control circuit only Logic for controlling 52M1 and 52T breakers is programmed in Relay
1 but control commands can go there from Relay 2 to Relay 1 through
GOOSE Logic for controlling 52M2 is programmed in Relay 2 butcontrol command can go from Relay 1 to Relay 2 through GOOSE Relay 1 can control 52M2 through GOOSE For example using front
pushbuttons located at Relay 1 to close or open 52M2 breaker Relay 2 can control 52M1 and 52T through GOOSE For example
using front pushbuttons located at Relay 2 to close or open 52M1breaker or 52T breaker
By careful selection of relay part numbers and program the relay logictrip circuit monitoring function for the output contacts used for breakertripopen purpose can be obtained in these relays No need forseparate trip coil monitoring devices
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1546
15
GOOSE Double-Ended SubDig i t a l input s needed for Relay 1
52A and TOC for 52M1 52A and TOC for 52T HRG GF from Transformer 1 (if using HRG system)
94T1 upstream schemebreaker trip (94T1 may come fromGOOSE instead) Transformer 1 common trip or individual trip signal 63X 26HH
71LL etc Bell alarm for 52M1 and 52T (for LVCB applications if needed) Local control switch CO commands for 52M1 and 52T Physical 10-Switch used to select 52M1 or 52T as the breaker
to trip [instead they may come from VIs (or RBs) or local PBs] Optional Remote closeopen commands for 52M1 and 52T
from remote (SCADA DCS HMI etc) through communicationpath
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 446
4
IEC61850
GOOSE How fas t
The time needed for trippingopening 52 breaker
with different technologies
Hardwire control relay output
about 12ms
Legacy device communications
about 500ms
GOOSE with IEC61850 capable relays
LAN response time 2-4ms
Relay 1 response time 2 msRelay 2 response time 2 ms
Add input recognition time 0-2ms
Add output operation time 2-4ms
Total 8-14ms
ExampleTripOpen a CB connected to Relay 2from Relay 1 through GOOSE messaging
Station LAN
IEC61850 CapableRelay 1
IEC61850 CapableRelay 2
GOOSE MessageTripOpen command
52Breaker
Output
Ethernet Switch
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 546
5
GOOSE m essaging
Indust r ia l app l ic a t ions Bus transfer between incoming sources Trip zone interlocking Under frequencyUnder voltage load shedding Load management in case of source capacity changes Arc flash signal initiate to a fast trip of incoming power source Publish a trip message to all feeder breakers Relay setting group change Breaker reclose initiation Transfer tripping Breaker failure initiate (BFI) to other breakers Fast bus trip scheme helliphellip
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 646
6
GOOSE m essaging
Bus t ransfer in a double-ended sub
52M1 52M2
SOURCE 1 SOURCE 2
Tx 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
NC NC
NOFEEDERS
on Bus 2
FEEDERSon Bus 1
Note
1 10-Switch is hardwired or wired to Relay 3 4 and 5 input2 Load shed if needed is hardwired
3 Popular relay based scheme transfer scheme for Relay 3 4 and 5
By SEL 3xSEL-351s Relay communications are through mirror bitBy GE 3xSR750 no relay communication everything is hardwired
4 If not using relays for MTM transfer a PLC is needed to be
programmed do the MTM transfer logic5 For HRG system need hard wire to block transfer or block closing if
GF on both sides
DOUBLE-ENDED MTM SUBSTATION
PROTECTION CONTROL AND METERING
CURRENTLY TYPICAL ARRANGEMENT
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 746
7
GOOSE m essagingBus t ransfer in a double-ended sub
New approach
Use 2 relays to do it all
52M1 52M2
3PH
D or Y
SOURCE 1 SOURCE 2
Tx1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 846
8
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 1 Di rec t f iber c onnec t ion
----Pros
bullSimple
bullNo need for network switchcost saving
bullEasy to add other
relaysIEDs through fiberexpansion for GOOSE toother relaysIEDs from thesame manufacturer
----Cons
bullLess Flexibility
bullFiber ports may take the
place where other modulecan not be added resultingin less IOs
bullDifficult to add other relaysthrough fiber expansion forGOOSE to other relaysIEDsfrom other manufacturers
Link Fiber Direct Connection Example
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 946
9
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 2 Add Et hernet sw i t c hes
52M1 52M2
PORT 2
SOURCE 1 SOURCE 2
Tx 1 Tx 2
L I NE 1
BUS 1 BUS 2
L I NE 2
52T
NC NC
NOFEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1046
10
GOOSE c om m unic at ion-assis t edBus t ransfer in a double-ended subRequirem ent s for t he Relays CT input
bull Three groups of three-phase CT inputs for 87T 5051 (50G51G) for incomers 5051 (50G51G) for tieprotection
bull One group of single-phase CT inputs for 51G at transformer Y secondary for transformer neutralprotection if it is not HRG system
PT inputbull 1 group of three-phase PT on the linebull 1 group of single-phase PT on the bus
bull Main breaker closing 25 is done by line PT and bus PT sync check and voltage permissivebull Bus 1 PT in Relay 1 and Bus 2 PT in Relay 2 are used for tie breaker manual closing (with 10-Switch
function) 25 sync check
Enough available terminals to handle needed digital inputs and digital outputsbull DIs must be hard wired in 52A TOC HRG GF transformer trip signals etcbull DIs may be hard wired in or may be from GOOSE PB or VI (or RB) AutoManual selection 94T 10-
Switch CSC CSO etcbull DOs Close and opentrip commands for each breaker It is better to have trip circuit monitoring
capability also
Protection elementsbull Used for protection 87T 5051 for lines 5051 for bus 51G for TX Y secondary 27 59bull Used for control 27 line to initiate transfer NOT27 line for source healthy (the other line) 25
Comprehensive logic capability Communication capability for substation automation and integration particularly GOOSE
capability to get DI and AI data values from the remote relay Other features nice to have Event waveform force contact input virtual input (remote bit)
and force contact output for easy testing propose
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1146
11
IEC61850GOOSE Double-Ended Sub
Use two relays to do everything
bull Meteringbull Protection
bull Control
bull Other
bull These relays are super relays
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1246
12
GOOSE Double-Ended SubMeter ing and prot ec t ion
Meteringbull Incoming linebull Voltage magnitude and angle each phasebull Current magnitude and angle each phasebull Frequency
bull Powerbull Power Active Power Pbull Reactive Power Qbull Apparent Power S
bull Power factor
Protectionbull 87T main protection element
bull 5051 (50G51G) for transformer primarybull 5051 (50G51G) for transformer secondarybull 51G for transformer Y sec neutral protectionbull 27 line and bus (also for control purpose)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1346
13
GOOSE Double-Ended SubCont ro l
Manual breaker operations Auto transfer operations
Auto retransfer operations (if needed) 25 function for breaker closing supervision LTC controls if needed Maintenance switch (change settings disable auto
transfer function etc) Arc flash sensor to incoming source breaker Other controls (load shed load management etc)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1446
14
GOOSE Double-Ended SubDig i t a l ou tput a r rangem ent
Relay 1 output to both 52M1 and 52T breaker control circuits Relay 2 output to 52M2 breaker control circuit only Logic for controlling 52M1 and 52T breakers is programmed in Relay
1 but control commands can go there from Relay 2 to Relay 1 through
GOOSE Logic for controlling 52M2 is programmed in Relay 2 butcontrol command can go from Relay 1 to Relay 2 through GOOSE Relay 1 can control 52M2 through GOOSE For example using front
pushbuttons located at Relay 1 to close or open 52M2 breaker Relay 2 can control 52M1 and 52T through GOOSE For example
using front pushbuttons located at Relay 2 to close or open 52M1breaker or 52T breaker
By careful selection of relay part numbers and program the relay logictrip circuit monitoring function for the output contacts used for breakertripopen purpose can be obtained in these relays No need forseparate trip coil monitoring devices
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1546
15
GOOSE Double-Ended SubDig i t a l input s needed for Relay 1
52A and TOC for 52M1 52A and TOC for 52T HRG GF from Transformer 1 (if using HRG system)
94T1 upstream schemebreaker trip (94T1 may come fromGOOSE instead) Transformer 1 common trip or individual trip signal 63X 26HH
71LL etc Bell alarm for 52M1 and 52T (for LVCB applications if needed) Local control switch CO commands for 52M1 and 52T Physical 10-Switch used to select 52M1 or 52T as the breaker
to trip [instead they may come from VIs (or RBs) or local PBs] Optional Remote closeopen commands for 52M1 and 52T
from remote (SCADA DCS HMI etc) through communicationpath
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 546
5
GOOSE m essaging
Indust r ia l app l ic a t ions Bus transfer between incoming sources Trip zone interlocking Under frequencyUnder voltage load shedding Load management in case of source capacity changes Arc flash signal initiate to a fast trip of incoming power source Publish a trip message to all feeder breakers Relay setting group change Breaker reclose initiation Transfer tripping Breaker failure initiate (BFI) to other breakers Fast bus trip scheme helliphellip
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 646
6
GOOSE m essaging
Bus t ransfer in a double-ended sub
52M1 52M2
SOURCE 1 SOURCE 2
Tx 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
NC NC
NOFEEDERS
on Bus 2
FEEDERSon Bus 1
Note
1 10-Switch is hardwired or wired to Relay 3 4 and 5 input2 Load shed if needed is hardwired
3 Popular relay based scheme transfer scheme for Relay 3 4 and 5
By SEL 3xSEL-351s Relay communications are through mirror bitBy GE 3xSR750 no relay communication everything is hardwired
4 If not using relays for MTM transfer a PLC is needed to be
programmed do the MTM transfer logic5 For HRG system need hard wire to block transfer or block closing if
GF on both sides
DOUBLE-ENDED MTM SUBSTATION
PROTECTION CONTROL AND METERING
CURRENTLY TYPICAL ARRANGEMENT
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 746
7
GOOSE m essagingBus t ransfer in a double-ended sub
New approach
Use 2 relays to do it all
52M1 52M2
3PH
D or Y
SOURCE 1 SOURCE 2
Tx1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 846
8
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 1 Di rec t f iber c onnec t ion
----Pros
bullSimple
bullNo need for network switchcost saving
bullEasy to add other
relaysIEDs through fiberexpansion for GOOSE toother relaysIEDs from thesame manufacturer
----Cons
bullLess Flexibility
bullFiber ports may take the
place where other modulecan not be added resultingin less IOs
bullDifficult to add other relaysthrough fiber expansion forGOOSE to other relaysIEDsfrom other manufacturers
Link Fiber Direct Connection Example
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 946
9
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 2 Add Et hernet sw i t c hes
52M1 52M2
PORT 2
SOURCE 1 SOURCE 2
Tx 1 Tx 2
L I NE 1
BUS 1 BUS 2
L I NE 2
52T
NC NC
NOFEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1046
10
GOOSE c om m unic at ion-assis t edBus t ransfer in a double-ended subRequirem ent s for t he Relays CT input
bull Three groups of three-phase CT inputs for 87T 5051 (50G51G) for incomers 5051 (50G51G) for tieprotection
bull One group of single-phase CT inputs for 51G at transformer Y secondary for transformer neutralprotection if it is not HRG system
PT inputbull 1 group of three-phase PT on the linebull 1 group of single-phase PT on the bus
bull Main breaker closing 25 is done by line PT and bus PT sync check and voltage permissivebull Bus 1 PT in Relay 1 and Bus 2 PT in Relay 2 are used for tie breaker manual closing (with 10-Switch
function) 25 sync check
Enough available terminals to handle needed digital inputs and digital outputsbull DIs must be hard wired in 52A TOC HRG GF transformer trip signals etcbull DIs may be hard wired in or may be from GOOSE PB or VI (or RB) AutoManual selection 94T 10-
Switch CSC CSO etcbull DOs Close and opentrip commands for each breaker It is better to have trip circuit monitoring
capability also
Protection elementsbull Used for protection 87T 5051 for lines 5051 for bus 51G for TX Y secondary 27 59bull Used for control 27 line to initiate transfer NOT27 line for source healthy (the other line) 25
Comprehensive logic capability Communication capability for substation automation and integration particularly GOOSE
capability to get DI and AI data values from the remote relay Other features nice to have Event waveform force contact input virtual input (remote bit)
and force contact output for easy testing propose
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1146
11
IEC61850GOOSE Double-Ended Sub
Use two relays to do everything
bull Meteringbull Protection
bull Control
bull Other
bull These relays are super relays
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1246
12
GOOSE Double-Ended SubMeter ing and prot ec t ion
Meteringbull Incoming linebull Voltage magnitude and angle each phasebull Current magnitude and angle each phasebull Frequency
bull Powerbull Power Active Power Pbull Reactive Power Qbull Apparent Power S
bull Power factor
Protectionbull 87T main protection element
bull 5051 (50G51G) for transformer primarybull 5051 (50G51G) for transformer secondarybull 51G for transformer Y sec neutral protectionbull 27 line and bus (also for control purpose)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1346
13
GOOSE Double-Ended SubCont ro l
Manual breaker operations Auto transfer operations
Auto retransfer operations (if needed) 25 function for breaker closing supervision LTC controls if needed Maintenance switch (change settings disable auto
transfer function etc) Arc flash sensor to incoming source breaker Other controls (load shed load management etc)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1446
14
GOOSE Double-Ended SubDig i t a l ou tput a r rangem ent
Relay 1 output to both 52M1 and 52T breaker control circuits Relay 2 output to 52M2 breaker control circuit only Logic for controlling 52M1 and 52T breakers is programmed in Relay
1 but control commands can go there from Relay 2 to Relay 1 through
GOOSE Logic for controlling 52M2 is programmed in Relay 2 butcontrol command can go from Relay 1 to Relay 2 through GOOSE Relay 1 can control 52M2 through GOOSE For example using front
pushbuttons located at Relay 1 to close or open 52M2 breaker Relay 2 can control 52M1 and 52T through GOOSE For example
using front pushbuttons located at Relay 2 to close or open 52M1breaker or 52T breaker
By careful selection of relay part numbers and program the relay logictrip circuit monitoring function for the output contacts used for breakertripopen purpose can be obtained in these relays No need forseparate trip coil monitoring devices
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1546
15
GOOSE Double-Ended SubDig i t a l input s needed for Relay 1
52A and TOC for 52M1 52A and TOC for 52T HRG GF from Transformer 1 (if using HRG system)
94T1 upstream schemebreaker trip (94T1 may come fromGOOSE instead) Transformer 1 common trip or individual trip signal 63X 26HH
71LL etc Bell alarm for 52M1 and 52T (for LVCB applications if needed) Local control switch CO commands for 52M1 and 52T Physical 10-Switch used to select 52M1 or 52T as the breaker
to trip [instead they may come from VIs (or RBs) or local PBs] Optional Remote closeopen commands for 52M1 and 52T
from remote (SCADA DCS HMI etc) through communicationpath
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 646
6
GOOSE m essaging
Bus t ransfer in a double-ended sub
52M1 52M2
SOURCE 1 SOURCE 2
Tx 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
NC NC
NOFEEDERS
on Bus 2
FEEDERSon Bus 1
Note
1 10-Switch is hardwired or wired to Relay 3 4 and 5 input2 Load shed if needed is hardwired
3 Popular relay based scheme transfer scheme for Relay 3 4 and 5
By SEL 3xSEL-351s Relay communications are through mirror bitBy GE 3xSR750 no relay communication everything is hardwired
4 If not using relays for MTM transfer a PLC is needed to be
programmed do the MTM transfer logic5 For HRG system need hard wire to block transfer or block closing if
GF on both sides
DOUBLE-ENDED MTM SUBSTATION
PROTECTION CONTROL AND METERING
CURRENTLY TYPICAL ARRANGEMENT
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 746
7
GOOSE m essagingBus t ransfer in a double-ended sub
New approach
Use 2 relays to do it all
52M1 52M2
3PH
D or Y
SOURCE 1 SOURCE 2
Tx1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 846
8
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 1 Di rec t f iber c onnec t ion
----Pros
bullSimple
bullNo need for network switchcost saving
bullEasy to add other
relaysIEDs through fiberexpansion for GOOSE toother relaysIEDs from thesame manufacturer
----Cons
bullLess Flexibility
bullFiber ports may take the
place where other modulecan not be added resultingin less IOs
bullDifficult to add other relaysthrough fiber expansion forGOOSE to other relaysIEDsfrom other manufacturers
Link Fiber Direct Connection Example
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 946
9
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 2 Add Et hernet sw i t c hes
52M1 52M2
PORT 2
SOURCE 1 SOURCE 2
Tx 1 Tx 2
L I NE 1
BUS 1 BUS 2
L I NE 2
52T
NC NC
NOFEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1046
10
GOOSE c om m unic at ion-assis t edBus t ransfer in a double-ended subRequirem ent s for t he Relays CT input
bull Three groups of three-phase CT inputs for 87T 5051 (50G51G) for incomers 5051 (50G51G) for tieprotection
bull One group of single-phase CT inputs for 51G at transformer Y secondary for transformer neutralprotection if it is not HRG system
PT inputbull 1 group of three-phase PT on the linebull 1 group of single-phase PT on the bus
bull Main breaker closing 25 is done by line PT and bus PT sync check and voltage permissivebull Bus 1 PT in Relay 1 and Bus 2 PT in Relay 2 are used for tie breaker manual closing (with 10-Switch
function) 25 sync check
Enough available terminals to handle needed digital inputs and digital outputsbull DIs must be hard wired in 52A TOC HRG GF transformer trip signals etcbull DIs may be hard wired in or may be from GOOSE PB or VI (or RB) AutoManual selection 94T 10-
Switch CSC CSO etcbull DOs Close and opentrip commands for each breaker It is better to have trip circuit monitoring
capability also
Protection elementsbull Used for protection 87T 5051 for lines 5051 for bus 51G for TX Y secondary 27 59bull Used for control 27 line to initiate transfer NOT27 line for source healthy (the other line) 25
Comprehensive logic capability Communication capability for substation automation and integration particularly GOOSE
capability to get DI and AI data values from the remote relay Other features nice to have Event waveform force contact input virtual input (remote bit)
and force contact output for easy testing propose
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1146
11
IEC61850GOOSE Double-Ended Sub
Use two relays to do everything
bull Meteringbull Protection
bull Control
bull Other
bull These relays are super relays
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1246
12
GOOSE Double-Ended SubMeter ing and prot ec t ion
Meteringbull Incoming linebull Voltage magnitude and angle each phasebull Current magnitude and angle each phasebull Frequency
bull Powerbull Power Active Power Pbull Reactive Power Qbull Apparent Power S
bull Power factor
Protectionbull 87T main protection element
bull 5051 (50G51G) for transformer primarybull 5051 (50G51G) for transformer secondarybull 51G for transformer Y sec neutral protectionbull 27 line and bus (also for control purpose)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1346
13
GOOSE Double-Ended SubCont ro l
Manual breaker operations Auto transfer operations
Auto retransfer operations (if needed) 25 function for breaker closing supervision LTC controls if needed Maintenance switch (change settings disable auto
transfer function etc) Arc flash sensor to incoming source breaker Other controls (load shed load management etc)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1446
14
GOOSE Double-Ended SubDig i t a l ou tput a r rangem ent
Relay 1 output to both 52M1 and 52T breaker control circuits Relay 2 output to 52M2 breaker control circuit only Logic for controlling 52M1 and 52T breakers is programmed in Relay
1 but control commands can go there from Relay 2 to Relay 1 through
GOOSE Logic for controlling 52M2 is programmed in Relay 2 butcontrol command can go from Relay 1 to Relay 2 through GOOSE Relay 1 can control 52M2 through GOOSE For example using front
pushbuttons located at Relay 1 to close or open 52M2 breaker Relay 2 can control 52M1 and 52T through GOOSE For example
using front pushbuttons located at Relay 2 to close or open 52M1breaker or 52T breaker
By careful selection of relay part numbers and program the relay logictrip circuit monitoring function for the output contacts used for breakertripopen purpose can be obtained in these relays No need forseparate trip coil monitoring devices
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1546
15
GOOSE Double-Ended SubDig i t a l input s needed for Relay 1
52A and TOC for 52M1 52A and TOC for 52T HRG GF from Transformer 1 (if using HRG system)
94T1 upstream schemebreaker trip (94T1 may come fromGOOSE instead) Transformer 1 common trip or individual trip signal 63X 26HH
71LL etc Bell alarm for 52M1 and 52T (for LVCB applications if needed) Local control switch CO commands for 52M1 and 52T Physical 10-Switch used to select 52M1 or 52T as the breaker
to trip [instead they may come from VIs (or RBs) or local PBs] Optional Remote closeopen commands for 52M1 and 52T
from remote (SCADA DCS HMI etc) through communicationpath
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 746
7
GOOSE m essagingBus t ransfer in a double-ended sub
New approach
Use 2 relays to do it all
52M1 52M2
3PH
D or Y
SOURCE 1 SOURCE 2
Tx1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 846
8
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 1 Di rec t f iber c onnec t ion
----Pros
bullSimple
bullNo need for network switchcost saving
bullEasy to add other
relaysIEDs through fiberexpansion for GOOSE toother relaysIEDs from thesame manufacturer
----Cons
bullLess Flexibility
bullFiber ports may take the
place where other modulecan not be added resultingin less IOs
bullDifficult to add other relaysthrough fiber expansion forGOOSE to other relaysIEDsfrom other manufacturers
Link Fiber Direct Connection Example
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 946
9
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 2 Add Et hernet sw i t c hes
52M1 52M2
PORT 2
SOURCE 1 SOURCE 2
Tx 1 Tx 2
L I NE 1
BUS 1 BUS 2
L I NE 2
52T
NC NC
NOFEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1046
10
GOOSE c om m unic at ion-assis t edBus t ransfer in a double-ended subRequirem ent s for t he Relays CT input
bull Three groups of three-phase CT inputs for 87T 5051 (50G51G) for incomers 5051 (50G51G) for tieprotection
bull One group of single-phase CT inputs for 51G at transformer Y secondary for transformer neutralprotection if it is not HRG system
PT inputbull 1 group of three-phase PT on the linebull 1 group of single-phase PT on the bus
bull Main breaker closing 25 is done by line PT and bus PT sync check and voltage permissivebull Bus 1 PT in Relay 1 and Bus 2 PT in Relay 2 are used for tie breaker manual closing (with 10-Switch
function) 25 sync check
Enough available terminals to handle needed digital inputs and digital outputsbull DIs must be hard wired in 52A TOC HRG GF transformer trip signals etcbull DIs may be hard wired in or may be from GOOSE PB or VI (or RB) AutoManual selection 94T 10-
Switch CSC CSO etcbull DOs Close and opentrip commands for each breaker It is better to have trip circuit monitoring
capability also
Protection elementsbull Used for protection 87T 5051 for lines 5051 for bus 51G for TX Y secondary 27 59bull Used for control 27 line to initiate transfer NOT27 line for source healthy (the other line) 25
Comprehensive logic capability Communication capability for substation automation and integration particularly GOOSE
capability to get DI and AI data values from the remote relay Other features nice to have Event waveform force contact input virtual input (remote bit)
and force contact output for easy testing propose
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1146
11
IEC61850GOOSE Double-Ended Sub
Use two relays to do everything
bull Meteringbull Protection
bull Control
bull Other
bull These relays are super relays
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1246
12
GOOSE Double-Ended SubMeter ing and prot ec t ion
Meteringbull Incoming linebull Voltage magnitude and angle each phasebull Current magnitude and angle each phasebull Frequency
bull Powerbull Power Active Power Pbull Reactive Power Qbull Apparent Power S
bull Power factor
Protectionbull 87T main protection element
bull 5051 (50G51G) for transformer primarybull 5051 (50G51G) for transformer secondarybull 51G for transformer Y sec neutral protectionbull 27 line and bus (also for control purpose)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1346
13
GOOSE Double-Ended SubCont ro l
Manual breaker operations Auto transfer operations
Auto retransfer operations (if needed) 25 function for breaker closing supervision LTC controls if needed Maintenance switch (change settings disable auto
transfer function etc) Arc flash sensor to incoming source breaker Other controls (load shed load management etc)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1446
14
GOOSE Double-Ended SubDig i t a l ou tput a r rangem ent
Relay 1 output to both 52M1 and 52T breaker control circuits Relay 2 output to 52M2 breaker control circuit only Logic for controlling 52M1 and 52T breakers is programmed in Relay
1 but control commands can go there from Relay 2 to Relay 1 through
GOOSE Logic for controlling 52M2 is programmed in Relay 2 butcontrol command can go from Relay 1 to Relay 2 through GOOSE Relay 1 can control 52M2 through GOOSE For example using front
pushbuttons located at Relay 1 to close or open 52M2 breaker Relay 2 can control 52M1 and 52T through GOOSE For example
using front pushbuttons located at Relay 2 to close or open 52M1breaker or 52T breaker
By careful selection of relay part numbers and program the relay logictrip circuit monitoring function for the output contacts used for breakertripopen purpose can be obtained in these relays No need forseparate trip coil monitoring devices
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1546
15
GOOSE Double-Ended SubDig i t a l input s needed for Relay 1
52A and TOC for 52M1 52A and TOC for 52T HRG GF from Transformer 1 (if using HRG system)
94T1 upstream schemebreaker trip (94T1 may come fromGOOSE instead) Transformer 1 common trip or individual trip signal 63X 26HH
71LL etc Bell alarm for 52M1 and 52T (for LVCB applications if needed) Local control switch CO commands for 52M1 and 52T Physical 10-Switch used to select 52M1 or 52T as the breaker
to trip [instead they may come from VIs (or RBs) or local PBs] Optional Remote closeopen commands for 52M1 and 52T
from remote (SCADA DCS HMI etc) through communicationpath
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 846
8
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 1 Di rec t f iber c onnec t ion
----Pros
bullSimple
bullNo need for network switchcost saving
bullEasy to add other
relaysIEDs through fiberexpansion for GOOSE toother relaysIEDs from thesame manufacturer
----Cons
bullLess Flexibility
bullFiber ports may take the
place where other modulecan not be added resultingin less IOs
bullDifficult to add other relaysthrough fiber expansion forGOOSE to other relaysIEDsfrom other manufacturers
Link Fiber Direct Connection Example
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 946
9
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 2 Add Et hernet sw i t c hes
52M1 52M2
PORT 2
SOURCE 1 SOURCE 2
Tx 1 Tx 2
L I NE 1
BUS 1 BUS 2
L I NE 2
52T
NC NC
NOFEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1046
10
GOOSE c om m unic at ion-assis t edBus t ransfer in a double-ended subRequirem ent s for t he Relays CT input
bull Three groups of three-phase CT inputs for 87T 5051 (50G51G) for incomers 5051 (50G51G) for tieprotection
bull One group of single-phase CT inputs for 51G at transformer Y secondary for transformer neutralprotection if it is not HRG system
PT inputbull 1 group of three-phase PT on the linebull 1 group of single-phase PT on the bus
bull Main breaker closing 25 is done by line PT and bus PT sync check and voltage permissivebull Bus 1 PT in Relay 1 and Bus 2 PT in Relay 2 are used for tie breaker manual closing (with 10-Switch
function) 25 sync check
Enough available terminals to handle needed digital inputs and digital outputsbull DIs must be hard wired in 52A TOC HRG GF transformer trip signals etcbull DIs may be hard wired in or may be from GOOSE PB or VI (or RB) AutoManual selection 94T 10-
Switch CSC CSO etcbull DOs Close and opentrip commands for each breaker It is better to have trip circuit monitoring
capability also
Protection elementsbull Used for protection 87T 5051 for lines 5051 for bus 51G for TX Y secondary 27 59bull Used for control 27 line to initiate transfer NOT27 line for source healthy (the other line) 25
Comprehensive logic capability Communication capability for substation automation and integration particularly GOOSE
capability to get DI and AI data values from the remote relay Other features nice to have Event waveform force contact input virtual input (remote bit)
and force contact output for easy testing propose
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1146
11
IEC61850GOOSE Double-Ended Sub
Use two relays to do everything
bull Meteringbull Protection
bull Control
bull Other
bull These relays are super relays
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1246
12
GOOSE Double-Ended SubMeter ing and prot ec t ion
Meteringbull Incoming linebull Voltage magnitude and angle each phasebull Current magnitude and angle each phasebull Frequency
bull Powerbull Power Active Power Pbull Reactive Power Qbull Apparent Power S
bull Power factor
Protectionbull 87T main protection element
bull 5051 (50G51G) for transformer primarybull 5051 (50G51G) for transformer secondarybull 51G for transformer Y sec neutral protectionbull 27 line and bus (also for control purpose)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1346
13
GOOSE Double-Ended SubCont ro l
Manual breaker operations Auto transfer operations
Auto retransfer operations (if needed) 25 function for breaker closing supervision LTC controls if needed Maintenance switch (change settings disable auto
transfer function etc) Arc flash sensor to incoming source breaker Other controls (load shed load management etc)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1446
14
GOOSE Double-Ended SubDig i t a l ou tput a r rangem ent
Relay 1 output to both 52M1 and 52T breaker control circuits Relay 2 output to 52M2 breaker control circuit only Logic for controlling 52M1 and 52T breakers is programmed in Relay
1 but control commands can go there from Relay 2 to Relay 1 through
GOOSE Logic for controlling 52M2 is programmed in Relay 2 butcontrol command can go from Relay 1 to Relay 2 through GOOSE Relay 1 can control 52M2 through GOOSE For example using front
pushbuttons located at Relay 1 to close or open 52M2 breaker Relay 2 can control 52M1 and 52T through GOOSE For example
using front pushbuttons located at Relay 2 to close or open 52M1breaker or 52T breaker
By careful selection of relay part numbers and program the relay logictrip circuit monitoring function for the output contacts used for breakertripopen purpose can be obtained in these relays No need forseparate trip coil monitoring devices
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1546
15
GOOSE Double-Ended SubDig i t a l input s needed for Relay 1
52A and TOC for 52M1 52A and TOC for 52T HRG GF from Transformer 1 (if using HRG system)
94T1 upstream schemebreaker trip (94T1 may come fromGOOSE instead) Transformer 1 common trip or individual trip signal 63X 26HH
71LL etc Bell alarm for 52M1 and 52T (for LVCB applications if needed) Local control switch CO commands for 52M1 and 52T Physical 10-Switch used to select 52M1 or 52T as the breaker
to trip [instead they may come from VIs (or RBs) or local PBs] Optional Remote closeopen commands for 52M1 and 52T
from remote (SCADA DCS HMI etc) through communicationpath
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 946
9
Bus t ransfer in a double-ended subComm unic a t ions set upMethod 2 Add Et hernet sw i t c hes
52M1 52M2
PORT 2
SOURCE 1 SOURCE 2
Tx 1 Tx 2
L I NE 1
BUS 1 BUS 2
L I NE 2
52T
NC NC
NOFEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1046
10
GOOSE c om m unic at ion-assis t edBus t ransfer in a double-ended subRequirem ent s for t he Relays CT input
bull Three groups of three-phase CT inputs for 87T 5051 (50G51G) for incomers 5051 (50G51G) for tieprotection
bull One group of single-phase CT inputs for 51G at transformer Y secondary for transformer neutralprotection if it is not HRG system
PT inputbull 1 group of three-phase PT on the linebull 1 group of single-phase PT on the bus
bull Main breaker closing 25 is done by line PT and bus PT sync check and voltage permissivebull Bus 1 PT in Relay 1 and Bus 2 PT in Relay 2 are used for tie breaker manual closing (with 10-Switch
function) 25 sync check
Enough available terminals to handle needed digital inputs and digital outputsbull DIs must be hard wired in 52A TOC HRG GF transformer trip signals etcbull DIs may be hard wired in or may be from GOOSE PB or VI (or RB) AutoManual selection 94T 10-
Switch CSC CSO etcbull DOs Close and opentrip commands for each breaker It is better to have trip circuit monitoring
capability also
Protection elementsbull Used for protection 87T 5051 for lines 5051 for bus 51G for TX Y secondary 27 59bull Used for control 27 line to initiate transfer NOT27 line for source healthy (the other line) 25
Comprehensive logic capability Communication capability for substation automation and integration particularly GOOSE
capability to get DI and AI data values from the remote relay Other features nice to have Event waveform force contact input virtual input (remote bit)
and force contact output for easy testing propose
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1146
11
IEC61850GOOSE Double-Ended Sub
Use two relays to do everything
bull Meteringbull Protection
bull Control
bull Other
bull These relays are super relays
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1246
12
GOOSE Double-Ended SubMeter ing and prot ec t ion
Meteringbull Incoming linebull Voltage magnitude and angle each phasebull Current magnitude and angle each phasebull Frequency
bull Powerbull Power Active Power Pbull Reactive Power Qbull Apparent Power S
bull Power factor
Protectionbull 87T main protection element
bull 5051 (50G51G) for transformer primarybull 5051 (50G51G) for transformer secondarybull 51G for transformer Y sec neutral protectionbull 27 line and bus (also for control purpose)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1346
13
GOOSE Double-Ended SubCont ro l
Manual breaker operations Auto transfer operations
Auto retransfer operations (if needed) 25 function for breaker closing supervision LTC controls if needed Maintenance switch (change settings disable auto
transfer function etc) Arc flash sensor to incoming source breaker Other controls (load shed load management etc)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1446
14
GOOSE Double-Ended SubDig i t a l ou tput a r rangem ent
Relay 1 output to both 52M1 and 52T breaker control circuits Relay 2 output to 52M2 breaker control circuit only Logic for controlling 52M1 and 52T breakers is programmed in Relay
1 but control commands can go there from Relay 2 to Relay 1 through
GOOSE Logic for controlling 52M2 is programmed in Relay 2 butcontrol command can go from Relay 1 to Relay 2 through GOOSE Relay 1 can control 52M2 through GOOSE For example using front
pushbuttons located at Relay 1 to close or open 52M2 breaker Relay 2 can control 52M1 and 52T through GOOSE For example
using front pushbuttons located at Relay 2 to close or open 52M1breaker or 52T breaker
By careful selection of relay part numbers and program the relay logictrip circuit monitoring function for the output contacts used for breakertripopen purpose can be obtained in these relays No need forseparate trip coil monitoring devices
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1546
15
GOOSE Double-Ended SubDig i t a l input s needed for Relay 1
52A and TOC for 52M1 52A and TOC for 52T HRG GF from Transformer 1 (if using HRG system)
94T1 upstream schemebreaker trip (94T1 may come fromGOOSE instead) Transformer 1 common trip or individual trip signal 63X 26HH
71LL etc Bell alarm for 52M1 and 52T (for LVCB applications if needed) Local control switch CO commands for 52M1 and 52T Physical 10-Switch used to select 52M1 or 52T as the breaker
to trip [instead they may come from VIs (or RBs) or local PBs] Optional Remote closeopen commands for 52M1 and 52T
from remote (SCADA DCS HMI etc) through communicationpath
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1046
10
GOOSE c om m unic at ion-assis t edBus t ransfer in a double-ended subRequirem ent s for t he Relays CT input
bull Three groups of three-phase CT inputs for 87T 5051 (50G51G) for incomers 5051 (50G51G) for tieprotection
bull One group of single-phase CT inputs for 51G at transformer Y secondary for transformer neutralprotection if it is not HRG system
PT inputbull 1 group of three-phase PT on the linebull 1 group of single-phase PT on the bus
bull Main breaker closing 25 is done by line PT and bus PT sync check and voltage permissivebull Bus 1 PT in Relay 1 and Bus 2 PT in Relay 2 are used for tie breaker manual closing (with 10-Switch
function) 25 sync check
Enough available terminals to handle needed digital inputs and digital outputsbull DIs must be hard wired in 52A TOC HRG GF transformer trip signals etcbull DIs may be hard wired in or may be from GOOSE PB or VI (or RB) AutoManual selection 94T 10-
Switch CSC CSO etcbull DOs Close and opentrip commands for each breaker It is better to have trip circuit monitoring
capability also
Protection elementsbull Used for protection 87T 5051 for lines 5051 for bus 51G for TX Y secondary 27 59bull Used for control 27 line to initiate transfer NOT27 line for source healthy (the other line) 25
Comprehensive logic capability Communication capability for substation automation and integration particularly GOOSE
capability to get DI and AI data values from the remote relay Other features nice to have Event waveform force contact input virtual input (remote bit)
and force contact output for easy testing propose
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1146
11
IEC61850GOOSE Double-Ended Sub
Use two relays to do everything
bull Meteringbull Protection
bull Control
bull Other
bull These relays are super relays
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1246
12
GOOSE Double-Ended SubMeter ing and prot ec t ion
Meteringbull Incoming linebull Voltage magnitude and angle each phasebull Current magnitude and angle each phasebull Frequency
bull Powerbull Power Active Power Pbull Reactive Power Qbull Apparent Power S
bull Power factor
Protectionbull 87T main protection element
bull 5051 (50G51G) for transformer primarybull 5051 (50G51G) for transformer secondarybull 51G for transformer Y sec neutral protectionbull 27 line and bus (also for control purpose)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1346
13
GOOSE Double-Ended SubCont ro l
Manual breaker operations Auto transfer operations
Auto retransfer operations (if needed) 25 function for breaker closing supervision LTC controls if needed Maintenance switch (change settings disable auto
transfer function etc) Arc flash sensor to incoming source breaker Other controls (load shed load management etc)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1446
14
GOOSE Double-Ended SubDig i t a l ou tput a r rangem ent
Relay 1 output to both 52M1 and 52T breaker control circuits Relay 2 output to 52M2 breaker control circuit only Logic for controlling 52M1 and 52T breakers is programmed in Relay
1 but control commands can go there from Relay 2 to Relay 1 through
GOOSE Logic for controlling 52M2 is programmed in Relay 2 butcontrol command can go from Relay 1 to Relay 2 through GOOSE Relay 1 can control 52M2 through GOOSE For example using front
pushbuttons located at Relay 1 to close or open 52M2 breaker Relay 2 can control 52M1 and 52T through GOOSE For example
using front pushbuttons located at Relay 2 to close or open 52M1breaker or 52T breaker
By careful selection of relay part numbers and program the relay logictrip circuit monitoring function for the output contacts used for breakertripopen purpose can be obtained in these relays No need forseparate trip coil monitoring devices
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1546
15
GOOSE Double-Ended SubDig i t a l input s needed for Relay 1
52A and TOC for 52M1 52A and TOC for 52T HRG GF from Transformer 1 (if using HRG system)
94T1 upstream schemebreaker trip (94T1 may come fromGOOSE instead) Transformer 1 common trip or individual trip signal 63X 26HH
71LL etc Bell alarm for 52M1 and 52T (for LVCB applications if needed) Local control switch CO commands for 52M1 and 52T Physical 10-Switch used to select 52M1 or 52T as the breaker
to trip [instead they may come from VIs (or RBs) or local PBs] Optional Remote closeopen commands for 52M1 and 52T
from remote (SCADA DCS HMI etc) through communicationpath
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1146
11
IEC61850GOOSE Double-Ended Sub
Use two relays to do everything
bull Meteringbull Protection
bull Control
bull Other
bull These relays are super relays
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1246
12
GOOSE Double-Ended SubMeter ing and prot ec t ion
Meteringbull Incoming linebull Voltage magnitude and angle each phasebull Current magnitude and angle each phasebull Frequency
bull Powerbull Power Active Power Pbull Reactive Power Qbull Apparent Power S
bull Power factor
Protectionbull 87T main protection element
bull 5051 (50G51G) for transformer primarybull 5051 (50G51G) for transformer secondarybull 51G for transformer Y sec neutral protectionbull 27 line and bus (also for control purpose)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1346
13
GOOSE Double-Ended SubCont ro l
Manual breaker operations Auto transfer operations
Auto retransfer operations (if needed) 25 function for breaker closing supervision LTC controls if needed Maintenance switch (change settings disable auto
transfer function etc) Arc flash sensor to incoming source breaker Other controls (load shed load management etc)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1446
14
GOOSE Double-Ended SubDig i t a l ou tput a r rangem ent
Relay 1 output to both 52M1 and 52T breaker control circuits Relay 2 output to 52M2 breaker control circuit only Logic for controlling 52M1 and 52T breakers is programmed in Relay
1 but control commands can go there from Relay 2 to Relay 1 through
GOOSE Logic for controlling 52M2 is programmed in Relay 2 butcontrol command can go from Relay 1 to Relay 2 through GOOSE Relay 1 can control 52M2 through GOOSE For example using front
pushbuttons located at Relay 1 to close or open 52M2 breaker Relay 2 can control 52M1 and 52T through GOOSE For example
using front pushbuttons located at Relay 2 to close or open 52M1breaker or 52T breaker
By careful selection of relay part numbers and program the relay logictrip circuit monitoring function for the output contacts used for breakertripopen purpose can be obtained in these relays No need forseparate trip coil monitoring devices
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1546
15
GOOSE Double-Ended SubDig i t a l input s needed for Relay 1
52A and TOC for 52M1 52A and TOC for 52T HRG GF from Transformer 1 (if using HRG system)
94T1 upstream schemebreaker trip (94T1 may come fromGOOSE instead) Transformer 1 common trip or individual trip signal 63X 26HH
71LL etc Bell alarm for 52M1 and 52T (for LVCB applications if needed) Local control switch CO commands for 52M1 and 52T Physical 10-Switch used to select 52M1 or 52T as the breaker
to trip [instead they may come from VIs (or RBs) or local PBs] Optional Remote closeopen commands for 52M1 and 52T
from remote (SCADA DCS HMI etc) through communicationpath
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1246
12
GOOSE Double-Ended SubMeter ing and prot ec t ion
Meteringbull Incoming linebull Voltage magnitude and angle each phasebull Current magnitude and angle each phasebull Frequency
bull Powerbull Power Active Power Pbull Reactive Power Qbull Apparent Power S
bull Power factor
Protectionbull 87T main protection element
bull 5051 (50G51G) for transformer primarybull 5051 (50G51G) for transformer secondarybull 51G for transformer Y sec neutral protectionbull 27 line and bus (also for control purpose)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1346
13
GOOSE Double-Ended SubCont ro l
Manual breaker operations Auto transfer operations
Auto retransfer operations (if needed) 25 function for breaker closing supervision LTC controls if needed Maintenance switch (change settings disable auto
transfer function etc) Arc flash sensor to incoming source breaker Other controls (load shed load management etc)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1446
14
GOOSE Double-Ended SubDig i t a l ou tput a r rangem ent
Relay 1 output to both 52M1 and 52T breaker control circuits Relay 2 output to 52M2 breaker control circuit only Logic for controlling 52M1 and 52T breakers is programmed in Relay
1 but control commands can go there from Relay 2 to Relay 1 through
GOOSE Logic for controlling 52M2 is programmed in Relay 2 butcontrol command can go from Relay 1 to Relay 2 through GOOSE Relay 1 can control 52M2 through GOOSE For example using front
pushbuttons located at Relay 1 to close or open 52M2 breaker Relay 2 can control 52M1 and 52T through GOOSE For example
using front pushbuttons located at Relay 2 to close or open 52M1breaker or 52T breaker
By careful selection of relay part numbers and program the relay logictrip circuit monitoring function for the output contacts used for breakertripopen purpose can be obtained in these relays No need forseparate trip coil monitoring devices
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1546
15
GOOSE Double-Ended SubDig i t a l input s needed for Relay 1
52A and TOC for 52M1 52A and TOC for 52T HRG GF from Transformer 1 (if using HRG system)
94T1 upstream schemebreaker trip (94T1 may come fromGOOSE instead) Transformer 1 common trip or individual trip signal 63X 26HH
71LL etc Bell alarm for 52M1 and 52T (for LVCB applications if needed) Local control switch CO commands for 52M1 and 52T Physical 10-Switch used to select 52M1 or 52T as the breaker
to trip [instead they may come from VIs (or RBs) or local PBs] Optional Remote closeopen commands for 52M1 and 52T
from remote (SCADA DCS HMI etc) through communicationpath
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1346
13
GOOSE Double-Ended SubCont ro l
Manual breaker operations Auto transfer operations
Auto retransfer operations (if needed) 25 function for breaker closing supervision LTC controls if needed Maintenance switch (change settings disable auto
transfer function etc) Arc flash sensor to incoming source breaker Other controls (load shed load management etc)
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1446
14
GOOSE Double-Ended SubDig i t a l ou tput a r rangem ent
Relay 1 output to both 52M1 and 52T breaker control circuits Relay 2 output to 52M2 breaker control circuit only Logic for controlling 52M1 and 52T breakers is programmed in Relay
1 but control commands can go there from Relay 2 to Relay 1 through
GOOSE Logic for controlling 52M2 is programmed in Relay 2 butcontrol command can go from Relay 1 to Relay 2 through GOOSE Relay 1 can control 52M2 through GOOSE For example using front
pushbuttons located at Relay 1 to close or open 52M2 breaker Relay 2 can control 52M1 and 52T through GOOSE For example
using front pushbuttons located at Relay 2 to close or open 52M1breaker or 52T breaker
By careful selection of relay part numbers and program the relay logictrip circuit monitoring function for the output contacts used for breakertripopen purpose can be obtained in these relays No need forseparate trip coil monitoring devices
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1546
15
GOOSE Double-Ended SubDig i t a l input s needed for Relay 1
52A and TOC for 52M1 52A and TOC for 52T HRG GF from Transformer 1 (if using HRG system)
94T1 upstream schemebreaker trip (94T1 may come fromGOOSE instead) Transformer 1 common trip or individual trip signal 63X 26HH
71LL etc Bell alarm for 52M1 and 52T (for LVCB applications if needed) Local control switch CO commands for 52M1 and 52T Physical 10-Switch used to select 52M1 or 52T as the breaker
to trip [instead they may come from VIs (or RBs) or local PBs] Optional Remote closeopen commands for 52M1 and 52T
from remote (SCADA DCS HMI etc) through communicationpath
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1446
14
GOOSE Double-Ended SubDig i t a l ou tput a r rangem ent
Relay 1 output to both 52M1 and 52T breaker control circuits Relay 2 output to 52M2 breaker control circuit only Logic for controlling 52M1 and 52T breakers is programmed in Relay
1 but control commands can go there from Relay 2 to Relay 1 through
GOOSE Logic for controlling 52M2 is programmed in Relay 2 butcontrol command can go from Relay 1 to Relay 2 through GOOSE Relay 1 can control 52M2 through GOOSE For example using front
pushbuttons located at Relay 1 to close or open 52M2 breaker Relay 2 can control 52M1 and 52T through GOOSE For example
using front pushbuttons located at Relay 2 to close or open 52M1breaker or 52T breaker
By careful selection of relay part numbers and program the relay logictrip circuit monitoring function for the output contacts used for breakertripopen purpose can be obtained in these relays No need forseparate trip coil monitoring devices
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1546
15
GOOSE Double-Ended SubDig i t a l input s needed for Relay 1
52A and TOC for 52M1 52A and TOC for 52T HRG GF from Transformer 1 (if using HRG system)
94T1 upstream schemebreaker trip (94T1 may come fromGOOSE instead) Transformer 1 common trip or individual trip signal 63X 26HH
71LL etc Bell alarm for 52M1 and 52T (for LVCB applications if needed) Local control switch CO commands for 52M1 and 52T Physical 10-Switch used to select 52M1 or 52T as the breaker
to trip [instead they may come from VIs (or RBs) or local PBs] Optional Remote closeopen commands for 52M1 and 52T
from remote (SCADA DCS HMI etc) through communicationpath
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1546
15
GOOSE Double-Ended SubDig i t a l input s needed for Relay 1
52A and TOC for 52M1 52A and TOC for 52T HRG GF from Transformer 1 (if using HRG system)
94T1 upstream schemebreaker trip (94T1 may come fromGOOSE instead) Transformer 1 common trip or individual trip signal 63X 26HH
71LL etc Bell alarm for 52M1 and 52T (for LVCB applications if needed) Local control switch CO commands for 52M1 and 52T Physical 10-Switch used to select 52M1 or 52T as the breaker
to trip [instead they may come from VIs (or RBs) or local PBs] Optional Remote closeopen commands for 52M1 and 52T
from remote (SCADA DCS HMI etc) through communicationpath
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1646
16
GOOSE Double-Ended SubDig i t a l input needed for Relay 2
52A and TOC for 52M2
HRG GF from Transformer 2 (if HRG system)
94T2 upstream scheme trip (94T2 may come from GOOSEinstead)
Transformer 2 common trip or individual trip signal 63X 26HH71LL etc
Bell alarm for 52M2 (for LVCB applications if needed)
Local control switch CO commands for 52M2
Physical 10-Switch used to select 52M2 as the breaker to trip[instead they may come from a VI (or RB) or a local PB]
Optional Remote closeopen commands for 52M2 from remote(SCADA DCS HMI etc) through communication path
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1746
17
GOOSE Double-Ended SubAuto t rans fer p rocess
Example Transfer power from two sources to only Source 2
Open-transition (Break-Before-Make) transfer
Line 1 voltage drops for some time (1-3s)
52M1 opens automatically Before closing 52T need to ensure
bull Bus 1 voltage (residual voltage) decays to a safe level
bull And 52M1 is already open
bull And 52M2 is already closedbull And Line 2 voltage is healthy
bull And Line 2 Tx 2 has no fault Then 52T closes
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1846
18
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer power from two sources to only Source 2 Open-transition (Break-Before-Make) transfer Line 1 voltage drops for some time (1-3s) 52M1 opens automatically
Before close 52T needbull Bus 1 voltage (residual voltage) decays to a safety
levelbull And 52M1 is already openbull And 52M2 is already closed
bull And Line 2 voltage is healthybull And Line 2Tx 2 has no fault
Then 52T closes Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 1946
19
GOOSE Double-Ended SubAuto t rans fer p rocess
Transfer from two sources to only Source 1 Open-transition (Break-Before-Make) transfer
Line 2 voltage drops for some time (1-3s)
52M2 opens automatically Before close 52T need
bull 52M1 is already closedbull And Line 1 voltage is healthybull And Line 1 Tx 1 has no fault
bull And 52M2 is already openbull And Bus 2 voltage (residual voltage) decays to a safety
level Then 52T closes
Where do I get these signals(Note 52T control logic is in Relay 1)These signals are in Relay 2
Use GOOSE MESSAGE (DIGITAL)
Link IEC61850 GOOSE message setup for Relay 1 and 2 in relay setup programs
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2046
20
GOOSE Double-Ended SubLog ic w i t h rem ote point s
Example Partial logic for 52T closing command in Relay 1 with remote points (or virtual bits) through GOOSE
These are remote points from aremote device (Relay 2)
through GOOSE messaging
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2146
21
GOOSE Double-Ended SubHow m any 25 sync c hec k needed
For a comprehensive transfer scheme three 25sync check elements are needed
25-M1 for closing 52M1 breaker 25-M2 for closing 52M2 breaker
For 25-M1 and 25-M2bull Manual mode LL amp LB or LL amp DBbull Auto RETRF mode (Closed-Transition) LL ampLBbull Sync check needs to get done between line source and bus It has no problem for each relay since
a three-phase line PT and a sing-phase bus PT are wired to each relay
25-T for closing tie breakerbull No strong need for auto TRF and auto RETRF modebull It is needed for manual mode in order to close tie breaker manuallybull Sync check needs to get done between Bus 1 and Bus 2 THIS IS THE CONCERN
52M1 52M2
52T
SOURCE 1 SOURCE 2
BUS 1 BUS 2
25-M1 25-M2
25-T
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2246
22
GOOSE Doub le-Ended Sub25-T funct ion fo r t ie break er c los ing
Where can I get 25-T for closing tie breaker Need voltage from Bus 1 and also voltage from Bus 2 Bus 1 voltage is on Relay 1 Bus 2 voltage is on Relay 2 Comparison must be made in Relay 1 since 52T control
logic is in Relay 1 Solution use GOOSE This time they are analog GOOSE
messages Get Bus 2rsquos voltage magnitude frequency andangle from Relay 2 GOOSE them to Relay 1 compare
them in Relay 1 with local (in Relay 1) parameters to makea 25 function for the tie breaker closing The GOOSE analog messages from Relay 2 are the
remote analog inputs (or virtual analog Inputs) for Relay 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2346
23
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 1 Compare remote analogs to local ones in order to convert them to digital tagsbull Remote device = Relay 2bull Local device = Relay 1
bull GOOSE Analog 1 in Relay 1 = Bus 2rsquos voltage magnitude from remote Relay 2bull GOOSE Analog 2 in Relay 1 = Bus 2rsquos frequency from remote Relay 2bull GOOSE Analog 3 in Relay 1 = Bus 2rsquos voltage angle from remote Relay 2
bull In Relay 1bull Setup a maximum voltage difference threshold compare GOOSE Analog 1 to the local
relayrsquos bus 1 voltage magnitudebull Setup a maximum frequency difference threshold compare GOOSE Analog 2 to the local
relayrsquos bus 1 frequency magnitudebull Setup a maximum angle difference threshold compare GOOSE Analog 3 to the local relayrsquos
bus 1 voltage angle
bull In Relay 1bull Setup a digital tag to indicate Bus 2 voltage is healthy or not This tag is created bycomparing GOOSE Analog 1 to a fix value (threshold)
bull Setup a digital tag to indicate Bus 1 voltage is healthy or not This tag is created bycomparing Bus 1 voltage to a fix value (threshold)
bull These two digital tags are used for live Bus 1 amp dead Bus 2 as well as dead Bus 1 and LiveBus 2 situations
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2446
24
GOOSE Double-Ended SubMak e 25-T for t ie break er c los ing
Step 2 Program relay 25-T logic in Relay 1
bull Closing tie breaker is only allowed when 25-T is passed at the following situationsbull Both buses are alive with their voltage magnitude frequency and angle differences are within
the preset limitbull Live Bus 1 and dead Bus 2bull Dead Bus 1 and live Bus 2
bull 25-T is blocked when both buses are deadbull This means closing tie breaker is not allowed if both buses are dead
Step 3 Apply the newly created 25-T function to tie breaker closing logic
Link GOOSE analog message and 25-T logic setup in setup program
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2546
25
Double-Ended Sub GOOSE Cos t Com pari son
Hard wiring connections savingsbull Cost for each hard wiring about $34 (data from last year)
bull Link By using three SEL 351S relays (This does not even include 87T and LTC)bull Link By using three GE SR750 relays (This does not even include 87T and LTC)bull Link By using two substation super relays (With even more features than the above two)
bull See how much cost saving there
Hard wire components savingsbull No need for
bull Physical 10-switchbull Physical breaker control switchesbull Physical lockout relays
Device cost comparisonbull By using traditional seven devices
bull Three feeder relays (typical) $3k x 3 = $9kbull Plus Two transformer relays (typical) $45k x 2 = $9kbull Plus 2 LTC (typical) $15k x 2= $3kbull Total $21k
bull By using two super devices about $9k x 2 = $18k
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2646
26
Double-Ended Sub GOOSE t o feeders
52M1 52M2
3PH
D or Y
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
3PH
CT
INPUT
NC NC
NO
FEEDERS
ON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2746
27
Double-Ended Sub Ex pand t o feeders t hough GOOSE
Trip zone interlocking
Feeder load shedding
Load management for uneven incoming
sources
Fast bus trip scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2846
28
GOOSETr ip zone int er loc k ing
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
1
Power flow
2
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main Incoming
Princip le o f reverse in t er lock(ANSI ndash num bers)
M
OC-Feed3OC-Feed2
OC-Feed4
OC-Feed1
T = 50 - 100ms
+ ++
Blocking-
signal
11
Power flow
222
50-1 picked up
- F1
5050--11 pickedpicked upup
ndash ndash F2F25050--11 pickedpicked upup
ndash ndash F3F3
gtBlock 50-2
Main IncomingOvercurrent protection of outgoingfeeders blocks the50-2 stage (Igtgt) of the overcurrentprotection of the incoming feeder (OC-Feed4) with the pick-up signal of OC-
functions 50-1 (Igt)
50-2 (Igtgt) stage of theovercurrent protection of theincoming feeder sends a tripsignal after 50-100 ms when no
blocking signal is received fromone or more overcurrentprotection of the outgoingfeeders
1
2
Exchange of digital GOOSE message between main and feeder relaysbull50ms for lt 3 cycle berakers
bull100ms for 5 cycle breakers
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 2946
29
GOOSETr ip zone int er loc k ing
Review of Buff Bookfor relay coordinationsummary of CTI(Coordination TimeInterval) requirement
Coordination TimeInterval (CTI) betweenupstream static relayand down streamstatic relay gt=200ms
Main breaker shouldnot use 50 function inorder to coordinatewith feeder breakerovercurrent protection
Bus Relays (Main Breaker or Partial Differential) Pickup set between 100 and 125 FLA (150 FLA maximum)Set to coordinate with transformer primary protective relaying
Do not enable the instantaneous overcurrent element on main breaker relays
(From presentation by Dominik Pieniazek and Doug Durand onovercurrent protection coordination on 0216mdash02172010)
Link CTI table by Buff Book
TRADITIONAL WAY TO COORDINATE FEEDER AND MAIN RELAYS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3046
30
GOOSETr ip zone int er loc k ing
Compare to GOOSE trip zone interlocking CTI 50-100msFor 5 cycle breaker breaker operation time 83msLAN relay response and input recognition and output time 8-14msTotal lt100ms
And main breaker protection can use 50 function instead of 51
Benefit for using GOOSE trip zone interlockingbull Reduction of arc flash hazard
bull Ease of relay coordination workbull No hard wiring between relaysbull Easy setup and configuration through softwarebull Peer to peer and multicast communication
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3146
31
Double-Ended Sub GOOSE Feeder l oad shed Feeder load shed by under frequency
(81U) or under voltage (27) orcombination of UF and UV from thesource relay (not from the local feederrelay)
Load shed priority depends on how low81U or 27 goes
Flexible load shed level (LSL) is setup atfeeder relays Shed entire load when the source is lost
Example under frequency elements setup in the source relay
Element Freq (Hz) Time (s) Purpose
UF1 5970 15 UF alarm local or GOOSE out
UF2 5950 10 GOOSE out for UF level 1 LSL1
UF3 5900 10 GOOSE out for UF level 2 LSL2
UF4 5850 05 Trip main CB shed entire load
UF5 5800 05 Start a generator if needed
UF6 Not used Use it if necessary
Main
SourceRelay
UF A ND
OR
UV
Fdr
G O O S E ME S S A GI N G
Each fdr relay
also sets its loadshed level
Voltage and frequencymeasurement
Fdr
FdrRelay
FdrRelay
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3246
32
Double-Ended Sub GOOSE Feeder l oad shed log ic
Pushbutton assignmentsbull PB5=local close commandbull PB6=local open commandbull PB7=Set this load to load shed level 1 with UF2 from remote device through GOOSEbull PB8=Set this load to load shed level 2 with UF3 from remote device through GOOSEbull PB7 and PB8 are interlocked each other (not shown here) Each feeder can be set to either LSL1 or LSL2 but not both
VO1 is used to drive a relay output to control breaker coils or a motor contactor (setup not shown here) Virtual Inputs (or Virtual Bits) may also be added in order to control the feeders in remote mode
One relay may control one load feeder or may even control up to three load feeders
These areremote points ofunder frequencysignals from thesource relaythrough GOOSE
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3346
33
Double-Ended Sub GOOSE Uneven inc om ing sou rc es
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3446
34
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
GOOSE communications between feeder relays and maintierelays through Ethernet network
Feeder relays tell maintie relays that if a fault is on feeder If the fault is on feeder associate feeder relay operates to clear
the fault If maintie relay sees the fault but feeder relays do not the fault
is not on feeder it must be on the bus Then maintie relay takesresponsibility
Time delay in maintie relay to coordinate and maintain selective Every relay can just use 50 function reduce arc flash hazard
Maintie relay can also use 50 instead of 51 Fast bus trip Set itwell below maximum fault current but far above maximum loadcurrent
Directional element for tie protection makes the scheme better Replace bus differential scheme
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3546
35
Double-Ended Sub GOOSE Fast bus t r ip sc hem e
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3646
36
IEC61850 Double-Ended Sub
Ot her t ype of inc om ing sources What do we call these two super IEC61850 capable relays
Substation IED =gt SubIED
How to select SubIED depends on the needed main protection features
bull For two power transformers as incoming sources the needed main relay protectionfunction is 87TSo SubIED = Transformer Management Relay
bull Other types of incoming source can we do the same thingYes we can same principle and same concept apply
bull SubIED selected needs to meet the following basic requirementsbull Required protection features are availablebull Enough PTCT inputs
bull Enough DIsDOsbull Communication capabilitybull GOOSE capablebull Comprehensive logic capability
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3746
37
Double-Ended SubOne generat or and one t ransformer
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
TransformerManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Tx 2
L I N
E 1
BUS 1 BUS 2
L I N
E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NO NC
NC FEEDERSON BUS 2
FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3846
38
Double-Ended SubTw o genera to rs
SubIED 1 =GeneratorManagementRelay
SubIED 2 =
GeneratorManagementRelay
52M1 52M2
3PHD or Y
SOURCE 1 SOURCE 2
Gen 1 Gen 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
1PHPT
INPUT
3PHCT
INPUT
3PHCT
INPUT
NC NC
NO FEEDERSON BUS 2
FEEDERSON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 3946
39
Double-Ended SubOne t ransformer and n generat ors
52M1 52M2
3PH
D or Y
SOURCE 1
SOURCE 2
Gen 1 Tx 2
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
1PH
PT
INPUT
3PH
CT
INPUT
NO NC
NC FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4046
40
Double-Ended SubGenera t ors on bo t h sides 2 SubIEDs
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PH
D or Y
NC
NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4146
41
Double-Ended SubGenerat ors on bot h s i des 1 SubIED
52M1 52M2
SOURCE 1 SOURCE 2
Gen 1
L I N E 1
BUS 1 BUS 2
L I N E 2
3PHD or Y
NC NC
NO FEEDERS
ON BUS 2FEEDERS
ON BUS 1
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4246
42
Double-Ended SubTw o m ains only no t ieNo tie breaker
No problem
Principle and concept arethe same
No need for third 25 elementfor the tie closing
No need for 10-Switcheither physical or soft
No need to use SubIED 1 tocontrol tie breaker SubIED1 and SubIED 2 are nowequal
Apply load shed to feedersfrom SubIEDs UFUVthrough GOOSE
Apply load managementlogic to feeder breakersthrough GOOSE beforeclosing the low capacitysource when loss of the
high-capacity source unlockthe feeders when high-capacity main returns
No need for GOOSE analogmessaging digital only
Depending on what type thesources are SubIEDs couldbe transformer generator orfeeder management relays
52M1 52M2
3PH
D or Y
SOURCE 1
Tx or Gen
L I N E
1
BUS BUS
L I N E
2
3PH
D or Y
1PH
PT
INPUT
3PHCT
INPUT
3PH
CT
INPUT
NC NO
FEEDERS
ON BUSFEEDERS
ON BUS
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4346
43
GOOSE Double-Ended SubOt her benef i t w i t h SubIEDs
Built-in event recorder to track back what have been happening in the system Built-in Waveform captures to help analysis of system faults Use the relay built-in network channel failure tags to get notifications for the status of relay
communications Use user programmable pushbuttons locally with a time delay or use virtual inputs (remote
bits) remotely to close or open breakers No need for PPE
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup virtual 10-Switch No physical 10-switch is needed Reduce production cost
Use user programmable pushbuttons locally or use virtual inputs (remote bits) remotely tosetup auto transfer enabledisable and auto retransfer enabledisable switches No physicalswitches are needed Reduce production cost
Use relay internal logic to trip and block closing breaker no physical 86 switch is neededReduce production cost (subject to customerrsquos choice)
Assign custom LEDs to help operators to check operation status
Use force contact inputs force virtual inputs (remote bits) and force contact output etcfeatures (these are normally PLC features but now they are merged in to protection relays)to ease factory test procedures
Make your own digital tags by using analog comparison feature (This is usually a PLCfeature now it is in the relay too)
Some relays offer online logic monitoring This would be a great tool for programmingdevelopment and trouble shooting
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4446
44
GOOSE Double-Ended SubSubIEDs redundanc y
Communication redundancybull Use two fiber cables (for Communication Method 1)
Orbull Use two Ethernet switches (for Communication Method 2)
Relay redundancy
bull Use total 4 SubIEDs instead of 2bull Two for primary service and the other two for backup service
bull Backup service is triggered bybull Either relay in primary service is failed (through hardwire contact)
Orbull Both communication ports failed indicated by
Both Operand PRI ETHERNET FAIL and operand SEC ETHERNET FAILare turned on at the same time for a preset period of time
Result System reliability increases with the price of added costand system complexity
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4546
45
Fac i l i ty fo rDeve lopment and Sim ula t ion Test ing
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin
822019 4 GooseTexasAMPresR01
httpslidepdfcomreaderfull4-goosetexasampresr01 4646
THANK YOUFOR YOUR TIME AND ATTENTION
Acknowledgements
Powell Electrical Systems Inc
GE Digital Energy Multilin