    53-1002727-01

    14 October 2012

    Non-port Side Fixed RackMount Kit (24)Installation Procedure

    Supporting the Brocade 5100, 5300, and 6520

    53-1002727-01

    *53-1002727-01*

  • 7/25/2019 53 1002727 01 NonportSideDeepRackMountKit

    2/8

    2 of 8 Non-port Side Fixed Rack Mount Kit (24) Installation Procedure

    53-1002727-01

    Copyright 2010-2012 Brocade Communications Systems, Inc. All Rights Reserved.

    Brocade, Brocade Assurance, the B-wing symbol, BigIron, DCX, Fabric OS, FastIron, MLX, NetIron, SAN Health, ServerIron, TurboIron, VCS, and VDXare registered trademarks, and AnyIO, Brocade One, CloudPlex, Effortless Networking, ICX, NET Health, OpenScript, and The Effortless Networkare trademarks of Brocade Communications Systems, Inc., in the United States and/or in other countries. Other brands, products, or servicenames mentioned may be trademarks of their respective owners.

    Notice: This document is for informational purposes only and does not set forth any warranty, expressed or implied, concerning any equipment,equipment feature, or service offered or to be offered by Brocade. Brocade reserves the right to make changes to this document at any time,without notice, and assumes no responsibility for its use. This informational document describes features that may not be currently available.Contact a Brocade sales office for information on feature and product availability. Export of technical data contained in this document mayrequire an export license from the United States government.

    The authors and Brocade Communications Systems, Inc. shall have no liability or responsibility to any person or entity with respect to any loss,cost, liability, or damages arising from the information contained in this book or the computer programs that accompany it.

    The product described by this document may contain open source software covered by the GNU General Public License or other open sourcelicense agreements. To find out which open source software is included in Brocade products, view the licensing terms applicable to the opensource software, and obtain a copy of the programming source code, please visithttp://www.brocade.com/support/oscd .

    Brocade Communications Systems, Incorporated

    Document History

    Corporate and Latin American HeadquartersBrocade Communications Systems, Inc.130 Holger WaySan Jose, CA 95134Tel: 1-408-333-8000Fax: 1-408-333-8101E-mail: [email protected]

    Asia-Pacific HeadquartersBrocade Communications Systems China HK, Ltd.No. 1 Guanghua RoadChao Yang DistrictUnits 2718 and 2818Beijing 100020, ChinaTel: +8610 6588 8888Fax: +8610 6588 9999E-mail: [email protected]

    European HeadquartersBrocade Communications Switzerland SrlCentre SwissairTour B - 4me tage29, Route de l'Aroport

    Case Postale 105CH-1215 Genve 15SwitzerlandTel: +41 22 799 5640Fax: +41 22 799 5641E-mail: [email protected]

    Asia-Pacific HeadquartersBrocade Communications Systems Co., Ltd. (Shenzhen WFOE)Citic PlazaNo. 233 Tian He Road NorthUnit 1308 13th Floor

    Guangzhou, ChinaTel: +8620 3891 2000Fax: +8620 3891 2111E-mail: [email protected]

    Title Publication number Summary of changes Date

    Non-port Side Fixed Rack Mount Kit (24)Installation Procedure

    53-1002727-01 New document. October 2012

  • 7/25/2019 53 1002727 01 NonportSideDeepRackMountKit

    3/8

    Non-port Side Fixed Rack Mount Kit (24) Installation Procedure 3 of 8

    53-1002727-01

    IntroductionThis document provides instructions to install a Brocade 5100, 5300, or 6520 switch in a 19-inch (48.3 cm) EIA rackusing the Non-port Side Fixed Rack Mount Kit (24). The document is organized as follows:

    Installation requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Time and items required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    The supported switches are listed in Table 1 . The rack kit is designed so that the switch is installed with the non-portside flush with the front posts of the rack. A single height (1U) switch is shown for illustration purposes. The doubleheight (2U) installation is similar.

    Installation requirementsAllow 15 to 30 minutes to complete this procedure. Note the following requirements to ensure correct installationand operation:

    Provide space in a 19-inch (48.3 cm) EIA rack, as required for the switch type, with a minimum distance of 24inch (60.96 cm) and a maximum distance of 32 inch (81.28 cm) between the front and back uprights.

    Verify that the additional weight of the switch does not exceed the racks equipment load rating. Ensure that an electrical branch circuit with the following characteristics is available:

    Required voltage and frequency as indicated in the hardware reference manual (200-230 VAC is alwayspreferred).

    Protection by a circuit breaker in accordance with local electrical codes. Supply circuit, line fusing, and wire size that conform to the electrical rating on the switch nameplate. Grounded outlet compatible with the power cord and installed by a licensed electrician.

    Ensure that all equipment installed in the rack is grounded through a reliable branch circuit connection. Do notrely on a secondary connection to a branch circuit, such as a power strip.

    Ensure that the rack is mechanically secured to ensure stability. Ensure that the air temperature at the fan inlet is less than 40 oC (104 oF) during switch operation. Ensure that the airflow available at the air vents meets the minimum requirements for the switch.

    Time and items requiredAllow 15 to 30 minutes to complete this procedure.

    The following items are required to install a switch using the Non-port Side Fixed Rack Mount Kit (24):

    Rack mount kit Clamps or other means of temporarily supporting the switch in the rack

    TABLE Supported switches

    Switch height Switch model

    1U Brocade 5100

    2U Brocade 5300, 6520

  • 7/25/2019 53 1002727 01 NonportSideDeepRackMountKit

    4/8

    4 of 8 Non-port Side Fixed Rack Mount Kit (24) Installation Procedure

    53-1002727-01

    #2 Phillips screwdriver with torque capability

    ATTENTION

    Use only the screws specified for use with the switch. Longer screws can damage the switch.

    Parts list Ensure that the items listed in Figure 1 are included in the kit.

    FIGURE Items in the Non-port Side Fixed Rack Mount Kit (24)

    Installation procedure

    ATTENTION

    The switch must be turned off and disconnected from the fabric during the installation procedure.

    1 Front brackets, right and left 5 Screw, 10-32 x 5/8-in., panhead Phillips (8)

    2 Short rear brackets, right and left 6 Retainer nut, 10-32 (8)

    3 Screw, 8-32 x 5/16-in. , panhead Phill ips (12) 7 Clip nuts, 10-32, for round-hole rack posts (8)

    4 Screw, 6-32 x 1/4-in., flathead Phillips (8)

  • 7/25/2019 53 1002727 01 NonportSideDeepRackMountKit

    5/8

    Non-port Side Fixed Rack Mount Kit (24) Installation Procedure 5 of 8

    53-1002727-01

    NOTE

    Although this document describes how to install both single height (1U) and double height (2U) switches, singleillustrations may show either switch type as examples. The only significant difference between single-height anddouble-height installation is that the double-height installation uses five screws to attach the front bracket to theswitch.

    Complete these tasks to mount the switch:

    Attaching front brackets Installing the switch in the rack Attaching rear brackets to front brackets Attaching the rear brackets to the rack posts

    Attaching front brackets

    Complete the following steps to attach the front brackets to the switch.

    1. Position the right front bracket with the flat side against the right side of the switch ( Figure 2 ). Be sure that thearrowhead is pointing upward when mounted.

    2. Insert two 8-32 x 5/16-in. screws into the front pair of vertically aligned holes in the bracket and then into thepair of holes on the side of the switch.

    3. Insert four more 8-32 x 5/16-in. screws through the holes in the bracket and into the corresponding holes in theswitch as shown in Figure 2 .

    4. Tighten all the 8-32 x 5/16-in. screws to a torque of 15 in-lbs. (17 cm-kgs).

    5. Repeat step 1 through step 4 to attach the left front bracket to the left side of the switch. Again, be sure that thearrowhead is pointing upward when mounted.

    FIGURE 2 Positioning the front bracket

    1 Screws, 8-32 x 5/16-in., panhead Phill ips (4) 2 Bracket, front right

  • 7/25/2019 53 1002727 01 NonportSideDeepRackMountKit

    6/8

    6 of 8 Non-port Side Fixed Rack Mount Kit (24) Installation Procedure

    53-1002727-01

    Installing the switch in the rack

    Complete the following steps to install the switch in the rack.

    1. Position the switch in the rack, providing temporary support under the switch until the switch is secured to therack.

    2. Attach the right front bracket to the right front rack upright using two 10-32 x 5/8-in. screws and two retainernuts as shown in Figure 3 . Select the correct nuts for either square or round holes in the rack posts. A singleheight switch is shown, but the installation for a double height switch is the same.

    3. Attach the left front bracket to the left front rack upright using two 10-32 x 5/8-in. screws and two nuts asshown in Figure 3 .

    4. Tighten all the 10-32 x 5/8-in. screws to a torque of 25 in-lbs. (29 cm-kgs).

    FIGURE 3 Positioning the switch in the rack

    1 Screws, 10-32 x 5/8-in., panhead Phillips (2) 3 Bracket, front right

    2 Retainer nuts, 10-32 (2)

  • 7/25/2019 53 1002727 01 NonportSideDeepRackMountKit

    7/8

    Non-port Side Fixed Rack Mount Kit (24) Installation Procedure 7 of 8

    53-1002727-01

    Attaching rear brackets to front brackets

    Complete the following steps to attach the rear brackets to the front brackets.

    1. Position the right rear bracket inside the right front bracket.

    2. Attach the brackets using four (4) 6-32 x 1/4-in. screws as shown in Figure 4 .3. Adjust the brackets to the rack depth and tighten the 6-32 x 1/4-in. screws to a torque of 9 in-lbs. (10 cm-kgs).

    4. Repeat step 1 through step 3 to attach the left rear bracket to the left front bracket.

    FIGURE 4 Attaching the rear brackets to the front brackets

    1 Bracket, front right 3 Bracket, rear right

    2 Screws, 6-32 x 1/4-in., flathead Phillips (4)

  • 7/25/2019 53 1002727 01 NonportSideDeepRackMountKit

    8/8

    8 of 8 Non-port Side Fixed Rack Mount Kit (24) Installation Procedure

    53-1002727-01

    Attaching the rear brackets to the rack posts

    Complete the following steps to attach the rear brackets to the rack posts.

    1. Attach the right rear bracket to the right rear rack post using two 10-32 x 5/8-in. screws and two retainer nuts asshown in Figure 5 .

    2. Attach the left rear bracket to the left rear rack post using two 10-32 x 5/8-in. screws and two retainer nuts.

    3. Tighten the 10-32 x 5/8-in. screws to a torque of 25 in-lbs. (29 cm-kgs).

    FIGURE 5 Attaching the rear brackets to the rack posts

    1 Bracket, front right 3 Retainer nuts, 10-32 (2)

    2 Bracket, shor t rear right 4 Screws, 10-32 x 5/8-in., panhead Phi ll ips (2)