37
A PRACTICAL GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS November 10, 2015 Author and Presenter: Bipasha Barman, P.E. POWER Engineers Other Authors: Jason Clack, P.E. POWER Engineers Vernon Padaca, P.E. POWER Engineers

A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

  • Upload
    lambao

  • View
    228

  • Download
    2

Embed Size (px)

Citation preview

Page 1: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

A PRACTICAL GUIDE TO

PERFORMING WIDE-AREA

COORDINATION ANALYSIS

November 10, 2015

Author and Presenter:

Bipasha Barman, P.E. – POWER Engineers

Other Authors:

Jason Clack, P.E. – POWER Engineers

Vernon Padaca, P.E. – POWER Engineers

Page 2: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

2

Challenging…..

Page 3: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

3

Page 4: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Presentation Overview

Intro to Wide-Area Coordination

Methodology

Data Management

Short-Circuit Model

Evaluation Criteria

Approach Selection

Analysis

Conclusions

4

Page 5: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Introduction to Wide-Area Coordination

Definition:

Wide-area coordination (WAC)

analysis is the evaluation of protective

device selectivity and sensitivity at a

system level (multiple layers of

adjacent terminals) with a goal of

improving system reliability.

Page 6: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Background

Reasons to Perform a WAC Study

Increase System Reliability

Responsive Action to Unexplained

Outages

Meet Regulatory Requirements

6

Page 7: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

WAC Analysis vs. Protection Evaluation

Page 8: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Methodology (Part 1)

8

Page 9: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Methodology (Part 2)

9

Page 10: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Planning Stage

Define Scope of Analysis

System Boundaries

Operating Conditions

Protective Devices and Elements

10

Page 11: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Data Management

11

More Data Required for

WAC Analysis

Establish File/Folder

Structure

Consider Using

Revision Control

Software

Use for Living

Documents

Page 12: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Short-Circuit Model

Determine If System Model Exists

Yes -> Is model complete and up-to-

date?

Gain Familiarity with Software Package

Automation Tools?

Additional Data Required?

12

Page 13: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Short-Circuit Model

Typical Data Needed

Protective Device Settings

CT and VT Ratios

Single-Line & Three-Line Drawings

System Boundary Source Equivalents

Ratings & Impedances for Apparatus

13

Page 14: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Evaluation Criteria Document

Serves as Starting Point for Evaluation

Not Intended to Standardize Protection

Sections to Include:

Description of Study Boundaries

Operating Configurations

Contingencies

Selected Approach

Evaluation Criteria by Protection Type

Critical Notes and Assumptions

14

Page 15: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Evaluation Criteria Document

Define General Trip Times to Use as Rule of

Thumb:

15

Page 16: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Evaluation Criteria Document

Define Criteria in Terms of Ranges:

Z1PMIN = 60% ZLINE

Z1PMAX = 80% ZLINE

Z1PPREF = 70% ZLINE

16

Page 17: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Considerations for Approach Selection

17

Factors Driving Approach Selection:

System Topology

Schedule Constraint

Variables:

Operating Scenarios

Protection Schemes

Protective Elements

Page 18: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Approach Selection

18

Page 19: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Subset Boundaries

19

Establish

Criteria for

Subset

Boundaries

Example

Page 20: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Operating Scenarios

20

Develop Strategy with Focus on Selectivity

Goal is to Define Maximum, Normal and

Minimum Fault Levels

Factors:

Weak or Strong Source

Seasonal Generation

N-1 Contingencies

Page 21: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Protective Element Evaluation Sequence

21

Develop Strategy with Focus on Selectivity

Determine Sequence of Evaluating

Protective Elements

Primary Then Backup Elements

Underreaching Then Overreaching

Page 22: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Coordination Analysis: Flowchart (Pt. 1)

22

• Focus on Selectivity

Page 23: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Coordination Analysis: Flowchart (Pt. 2)

23

• Focus on Selectivity

Page 24: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Ways to Gain Efficiency

24

Automate Calculation Tools

Streamline Short-Circuit Analysis

Utilize Coordination Checking Tool

Page 25: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Develop Calculation Spreadsheet

Input Data

Automated Tool

25

Page 26: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Develop Calculation Spreadsheet

Line Data

Sequence Impedance

Maximum Torque Angle

Automated Tool

26

Page 27: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Calculate Results

Fault Analysis

Input

Programmed

Cells

Automated Tool

27

= Z1Line • 1.2

= Apparent Z •

0.9

Page 28: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Utilize to Calculate Final Setting

Evaluate:

Existing

Preferred

Recommended

Automated Tool

28

Page 29: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Streamlining Short-Circuit Analysis

29

Defining Points of Fault Placement

Line

Apparatus

Fault Type

Balanced Faults

Unbalanced Faults

Page 30: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Automated Coordination Checking Tool

30

Overcurrent/Distance Coordination

Select Primary Relay

Program its Backup Relay Group

Select Type of Faults and their Placement

Enter Desired CTI

Check Coordination

Against the Relays Serving as Backup

Against the Relays that it Backs up

Page 31: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Automated Coordination Tool

31

Reports Miscoordination

Flags the Elements

Margin of Violation

Fault Type

Improve Coordination

Adjust Time Dial, Pickup and Curve

Adjust Reaches, Timers

Re-evaluate Coordination

Page 32: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

32

Example - Looped System

Time-Delayed

Directional

Overcurrent

Ground

Elements

Coordination Challenge

Page 33: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Solution to Coordination Challenge

Overcurrent Coordination Checking Tool

Helped:

Decide Close-in SLG Fault Placement

Strategize Mitigation

Set Pickups at 30% of the Smallest

Ground Fault at the Remote Bus

Choose Time Dials to Trip after 39

cycles

Page 34: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Conclusions

WAC Analysis is Not Trivial.

The Following Helps to Improve Project

Outcome:

Careful Upfront Planning

Documenting Evaluation Criteria

Keeping Files Organized

Establishing a Systematic Approach

Using Automated Tools

Page 35: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Questions

35

Bipasha Barman, P.E. – POWER Engineers

[email protected]

(208) 288 6306

Page 36: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Challenges

Larger Scale Study

Collecting and Managing Data

More Upfront Planning Required to Be

Efficient

37

Page 37: A P GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS · PDF fileDevelop Calculation Spreadsheet ... Utilize to Calculate Final Setting ... Select Primary Relay

Presentation Overview

Intro to Wide-Area Coordination

Methodology

Data Management

Short-Circuit Model

Evaluation Criteria

Approach Selection

Analysis

Conclusions

38