Upload
bistok-marbun
View
221
Download
0
Embed Size (px)
Citation preview
8/10/2019 ASCE_7-05_Appendix11.pdf
1/8
Appendix A
QUALITY ASSUR ANCE PROVISIONS
1 A l QUALITY ASSURANCE
This section provides minimum requirements for quality assur-
ance for seismic force-resisting systems and other designated
seismic systems. These requirements are not directly related to
computation of earthquake loads, but they are deemed essential
for satisfactory performance in an earthquake where designing
with the loads determined in accordance with this standard, due
to the substantial cyclic inelastic strain capacity assumed to exist
by the load procedures in this standard. These requirements sup-
plement the testing and inspection requirements contained in the
reference documents given in Chapters 13 and 14.Thes e require-
ments form an integral part of Chapters 11 through 23.
l lA l l S c o p e As a minimu m, the quality assurance provisions
apply to the following:
I. The seismic force-resisting systems in structures assigned
to Seismic Design Categories C, D, E, or F.
2. Mechanical and electrical components as specified in Sec-
tion llA.1.3.10.
3. Designated seism ic systems in structures assigned to Seis-
mic Design C ategories D, E, or F.
EXCEPTIONS Structures that comply with the following criteria
are exempt from the preparation of a quality assu rance plan, but those
structures are not exempt from special inspection(s) or testing require-
ments:
i. The structure is constructed of light wood framing or light-gauge
cold-formed steel framing, SDs does not exceed 0.50, the height of
the structure does not exceed 35 ft above grade, and the structure
meets the requirem ents in items iii and iv in the following text.
or
ii. The structure is constructed using a reinforced m asonry structural
system or reinforced concrete structural system, SDs does not ex-
ceed 0.50, the height of the structure does not exceed 25 ft above
grade, and the structure meets the requirements in items iii and iv
in the followin g text.
iii. The structure is classified as Occupancy Ca tegory I o r 11.
iv. The structure does not have any of the following irregularities as
defined in Table 12.3-1 or 12.3-2:
(1) Torsional irregularity
(2) Extreme torsional irregularity
(3) Nonpa rallel systems irregularity
4)
Stiffness-soft story irreg ularity
(5) St i f fn es s~ xt re m e of t s tory i rregulari ty
6)
Discontinuity in lateral strength-weak story irregularity
7) Discontinuity in lateral strength-extreme weak story
ll A 1 2 Quality Assurance Plan A quality assurance plan
shall be submitted to the authority having jurisdiction.
llA 1 2 1 Details of Quality Assurance Plan The quality as-
surance plan shall specify the designated seismic systems or seis-
mic force-resisting system in accordance with Section 11A. I.1
that are subject to quality assurance. The registered design pro-
fessional in responsible charge of the design of a seismic force-
resisting system and a designated seismic system sh all be respon-
sible for the portion of the q uality assurance plan applicable to that
system. The special inspections and special tests needed to es-
tablish that the construction is in conformance w ith this standard
shall be included in the portion of the quality assurance plan ap-
plicable to the designated seismic system. Th e quality assurance
plan shall include
a. The seismic force-resisting systems and designated seismic
systems in accordance w ith this chapter that are subject to
quality assurance.
b. T he special inspections and testing to be provided as re-
quired by this standard and the reference documents in
Chapter 23.
c. The type and frequency of testing.
d. The type and frequency of special inspections.
e. The frequency and distribution of testing and special inspec-
tion reports.
f. The structural observations to be performed.
g. The frequency and distribution of structural observation re-
ports.
llA 1 2 2 Contractor Responsibility Each contractor respon-
sible for the construction of a seismic force-resisting system,
designated seismic system, or component listed in the quality
assurance plan shall submit a w ritten contractor s statement of
responsibility to the regulatory authority having jurisdiction and
to the owner prior to the commencement of work on the system
or component. The contractor s statement of responsibility shall
contain the following:
I. Acknow ledgment of awareness of the special requirements
contained in the quality assurance p lan.
2. Acknowledgment that control will be exercised to obtain
conformance with the design documents approved by the
authority h aving jurisdiction.
3. Procedures for exercising control w ithin the co ntractor s
organization, the method and frequency of reporting, and
the distribution of the reports.
4.
Identification and qualifications of the person(s) exercising
such control and their position(s) in the organization.
llA 1 3 Special Inspection and Testing The building owner
shall employ a special inspector(s) to observe the construction
of all designated seismic systems in accordance w ith the quality
assurance plan for the following construction work. T he authority
having jurisdiction shall have the option to ap prove the quality
assurance personnel of a fabricator as a special inspector. The
person in charge of the special inspector(s) and the testing services
shall be a registered d esign professional.
llA 1 3 1 Foundations Periodic special inspection is required
during the
a. Driving of piles.
b. Con struction of drilled piles, piers, and caisson s.
Minimum Design Loads for Buildings and Other Structures
8/10/2019 ASCE_7-05_Appendix11.pdf
2/8
c. Placement of reinforcing steel in piers, piles, caissons, and
shallow foundations.
d. Placement of concrete in piers, piles, caissons, and shallow
foundations.
l lA.1 .3 .2 Reinforcing Steel.
l lA.1 .3 .2 .1
Periodic Special Inspection. Periodic special in-
spection during and upon completion of the placement of reinforc-
ing steel in intermediate and special moment frames of concrete
and con crete shear walls.
11A.1.3.2.2
Continuous Special Inspection. Continuous
special inspection is required during the welding of reinforcing
steel resisting flexural and axial forces in intermediate and spe-
cial moment frames of concrete, in boundary mem bers of concrete
shear walls, and welding of shear reinforcement.
l lA.1 .3 .3
Structural Concrete. Periodic special inspection is
required during and on co mpletion of the placement of concrete in
intermediate and special momen t frames, and in boundary mem-
bers of concrete shear walls.
l lA.1 .3 .4
Prestressed Concrete. Periodic special inspection
during the placement and after the completion of placement of
prestressing steel and continuous special inspection is required
during all stressing and grouting operations and during the place-
ment of concrete.
l lA.1 .3 .5
Structural Masonry.
l lA.1 .3 .5 .1
Periodic Special Inspection. Periodic special in-
spection is required during the preparation of mortar, the laying
of masonry units, and placement of reinforcement; and prior to
placement of grout.
11A.1.3.5.2
Continuous Special Inspection. Continuous
special inspection is required during welding of reinforcement,
grouting, consolidation, and reconsolidation, and placement of
bent-bar anchors as required by Section 14.4.
l lA.1 .3 .6
Structural Steel.
l lA.1 .3 .6 .1 Continuous Special Inspection. Continuous
special inspection is required fo r all structural welding.
EXCEPTION: Periodic special inspection for single-pass fillet or re-
sistance welds and welds loaded to less than 50 perce nt of their design
strength shall be the m inimum requirement, provided the qualifications of
the welder a nd the welding electrodes are insp ected at the beginning of
the work and all welds are inspected for compliance with the approved
construction docum ents at the completion of welding.
11A.1.3.6.2 Periodic Special Inspection. Periodic special in-
spection is required in accordance with AISC LRFD or AISC A SD
for installation and tightening of fully tensioned high-strength
bolts in slip-critical connections and in connections subject to
direct tension. Bolts in connections identified as not being slip-
critical or sub ject to direct tension need not be inspected for bolt
tension other than to ensure that the plies of the connected ele-
ments have been brought into snug contact.
l lA.1 .3 .7 Structural Wood.
l lA.1 .3 .7 .1 Continuous Special Inspection. Continuous
special inspection is required during all field gluing operations
of elements of the seismic force-resisting system .
11A.1.3.7.2 Periodic Special Inspection for Components.
Periodic sp ecial inspection is required for nailing, bolting, anchor-
ing, and other fastening of compon ents within the seismic force-
resisting system including drag struts, braces, and hold downs.
11A.1.3.7.3 Periodic Special Inspection for Wood Sheath
ing. Periodic special inspections for nailing and other fastening
of wood sheathing used for wood shear walls, shear panels, and
diaphragms w here the required fastener spacing is 4 in. or less,
and that are includ ed in the seismic force-resisting system .
l lA.1 .3 .8
Cold Formed Steel Framing
l lA.1 .3 .8 .1 Periodic Special Inspection for Welding. Peri-
odic special inspection is required during all welding o perations
of eleme nts of the seismic force-resisting system .
11A.1.3.8.2 Periodic Special Inspection for Components.
Periodic special inspection is required for screw attachment, bolt-
ing, anchoring, and other fastening of components within the
seismic force-resisting system , includin g struts, braces, and hold-
downs.
l lA.1 .3 .9
Architectural Components. Special inspection for
architectural components shall be as follows:
I. Periodic special inspection during the erection and fastening
of exterior cladding, interior and exterior nonbearing w alls,
and interior and exterior veneer in structures assigned to
Seism ic Design Categories D, E or F.
EXCEPTIONS:
a. Architectural components less than 30 ft 9 m) above grade or wa ll-
ing surface.
b. Cladding and veneer weighing 5 lb/ft2 239 N/m 2) or less.
c. Interior nonbearing walls weighing 15 lb/ft2 718 N/m 2) or less.
2. Periodic special inspection during the anchorage of access
floors and the installation of suspended ceiling grids, and
storage racks
8
ft 2.5 m) or greater in height in structures
assigned to Seismic Design Categories D, E or F.
3.
Periodic special inspection during erection of glass
30
ft
9
m) or mo re above an adjacent grade or walking surface in
glazed curtain walls, glazed storefronts, and interior glazed
partitions in structures assigned to Seismic Design Cate-
gories D, E or
F.
l lA.1 .3 .10 Mechanical and Electrical Components. Special
inspection for mechanical and electrical components sh all be as
follows:
I. Periodic special inspection during the anchorage of electri-
cal equipment for emergency or standby power systems in
structures assigned to Seismic Design Categories C, D, E
or F.
2. Periodic special inspection during the installation of an-
chorage of all other electrical equipment in S eismic Design
Categories E or F.
3.
Periodic special inspection during the installation for
flammable, combustible, or highly toxic piping sy stems and
their associated mechanical units in Seismic Design C ate-
gories C, D, E o r F.
4. Periodic special inspection during the installation of HVAC
ductwork that w ill contain hazardous m aterials in Seism ic
Design Categories C, D, E or F.
5. Periodic special inspection during the installation of vibra-
tion isolation systems where the construction documents
indicate a maximum clearance air gap) between the equip-
ment support frame and restraint less than or equal to 114
in.
240 SCE
7 05
8/10/2019 ASCE_7-05_Appendix11.pdf
3/8
llA.1.3.11 Seismic Isolation System.
Periodic special inspec-
tion is required during the fabrication and installation of isolator
units and energy d issipation devices if used as part of the seism ic
isolation system.
1 1A 2 TESTING
The special inspector s) shall be responsible for verifying that the
special test requirements are performed by an approved testing
agency for the types of work in designated seismic sy stems listed
in the following text.
ll A .2 .1 Reinforcing and Prestressing Steel.
Special testing of
reinforcing and prestressing steel shall be as follows:
llA .2.1 .1 Certified Mill Test Reports.
Exam ine certified mill
test reports for each shipm ent of reinforcing steel used to resist
flexural and axial forces in reinforced concrete intermediate and
special moment frames and boundary m embers of reinforced con-
crete shear walls or reinforced masonry shear walls and determine
conformance w ith construction documents.
llA .2.1 .2 ASTM A615 Reinforcing Steel. Where ASTM A615
reinforcing steel is used to resist earthquake-induced flexural and
axial forces in special mom ent frames and in wall boundary el-
ements of shear walls in structures assigned to Seismic Design
Categories D, E, or F, verify that the requirements of Section
21.2.5.1 of ACI 318 have been satisfied.
llA .2.1 .3 Welding of ASTM A615 Reinforcing Steel. Where
AS TM A615 reinforcing steel is to be welded, verify that chemical
tests have been p erformed to determine w eld ability in accordance
with Section 3.5.2 of ACI 318.
llA.2.2 Structural Concrete. Samples of structural concrete
shall be obtained at the project site and tested in accordance w ith
requirements of Section 5.6 of ACI 3 18.
ll A. 2. 3 Structural Masonry.
Quality assurance testing of
structural masonry shall be in accordance with the requirements
of ACI 530lASCE 51TMS 402 or ACI 530.l lAS CE 6lTMS 6 02.
llA.2.4 Structural Steel. The testing needed to establish that
the construction is in conformance with this standard shall be
included in a quality assurance plan. The minimum testing con-
tained in the quality assurance plan shall be as required in AISC
Seism ic and the following requirements:
llA.2.5 Base Metal Testing.
Base metal thicker than 1.5 in.
38 mm), where subject to through-thickness weld shrinkage
strains, shall be ultrasonically tested for discontinuities behind
and adjacent to such welds after joint completion. Any m aterial
discontinuities shall be accepted or rejected on the basis of AS TM
A435, o r ASTM A898, and criteria as established by the registered
design professional s) in responsible charge and the construction
documents.
ll A .2 .6 Seismic Isolated Structures.
For required system
tests, see Section 17.8.
llA.2.7 Mechanical and Electrical Equipment.
The special
inspector shall examine mechanical and electrical equipment that
are a designated seismic system and shall determine w hether its
anchorages and label conform with the certificate of com pliance.
11A 3 STRUCTU RAL OBSERVATIONS
Structural observations shall be provided for those structures in-
cluded in Seismic Design Categories D, E, or F w here one or more
of the following cond itions exist:
I. The structure is included in Occupan cy Category I11 or IV.
2. The height of the structure is greater than 75 ft above the
base.
3. The structure is assigned to Seismic Design Category E and
Occupancy Category I or I1 and is greater than two stories
in height.
Structural observations shall be performed by a registered de-
sign professional. Observed deficiencies shall be reported in w rit-
ing to the o wner an d the authority having jurisdiction.
11A 4 REPORTING AND COMPLIANCE
PROCEDURES
Each special inspector shall furnish to the authority having ju-
risdiction, registered design professional in responsible charge,
the owner, the persons preparing the quality assurance plan, and
the contractor copies of regular weekly progress reports of his or
her observations, noting therein any uncorrected deficiencies and
correction s of previously reported deficien cies. All deficiencies
shall be brought to the imm ediate attention of the contractor for
correction. At completion of construction, each special inspec-
tor shall subm it a final report to the authority having jurisdiction
certifying that all inspected w ork was completed substantially in
accordance with approved construction documents. Work not in
compliance shall be described in the final report. At com pletion
of construction, the building contractor shall submit a final report
to the authority having jurisdiction certifying that all construc-
tion work incorporated into the seismic force-resisting system
and other designated seismic systems was constructed substan-
tially in accordance with the approved construction documents
and applicable workmans hip requirements. Work not in compli-
ance shall be described in the final report. The contractor shall
correct all deficiencies as required.
Minimum Design Loads for Buildings and Other Structures
8/10/2019 ASCE_7-05_Appendix11.pdf
4/8
8/10/2019 ASCE_7-05_Appendix11.pdf
5/8
Appendix B
EXISTING BUILDING PROVISIONS
l l B l S CO PE
The provisions of this appendix shall apply to the design and
construction of alterations and additions and to existing structures
with a change in use.
11 B 2 STRUCTURA LLY INDEPENDENT ADDITIONS
An addition that is structurally independent from an existing struc-
ture shall be designed and constructed in accordance with the
seismic requirements for new structures.
11 B 3 STRUCTURA LLY DEPENDENT ADDITIONS
Wh ere an addition is not structurally independent from an ex isting
structure, the addition and alterations to the existing structure
shall be designed and constructed such that the entire structure
conforms to the seismic force-resistance requirements for new
structures.
EXCEPTIONS The entire structure shall not be required to comply w ith
the seismic force-resistance requir eme nts for new structures where all of
the following conditions are met:
1. The addition complies with the requirements for new structures.
2. The addition does not increase the seismic forces in any structural
element of the existing structure by mo re than 10 percent unless
the capacity of the element subject to the increased forces is still in
compliance with this standard.
3. The addition does not decrease the s eismic resistance of any struc-
tural element of the existing structure unless the reduced resistance
is equal to o r greater than that required for new structures.
11 B 4 ALTERATIONS
Alterations are permitted to be made to any structure without
requiring the existing structure to comply with this standard pro-
vided the alterations comply with the requirements for a new
structure. Alterations that increase the seismic force in any exist-
ing structural element by m ore than 10 percent or decrease the
design strength of any existing structural elemen t to resist seis-
mic forces by m ore than 10 percent shall not be permitted unless
the entire seismic force-resisting system is determined to comply
with this standard for a new structure.
EXCEPTIONS
Alterations to existing structural elements or additions
of new structural elements that are not required by this standard and are
initiated forthe purpose of increasing he strength or stiffness of the seismic
force-resisting system of an existing structure shall not be required to be
designed for forces in accordance with this standard provided that an
engineering analysis is submitted indicating the following:
1. Th e desig n strengths of existing structural eleme nts required to resist
seismic forces are not reduced.
2. The seismic force to required existing structural elements is not
increased beyond their design strength.
3. New structural elements are detailed and connected to the existing
structural elemen ts as required by this standard.
4
New or relocated nonstructural elements ar e detailed and connected
to existing or new structural elements as req uired by this standard.
5
The alteration does not create a structural irregularity or make an
existing irregularity more severe.
11 B 5 CHANGE OF USE
Where a change of use results in a structure being reclassified
to a higher occupancy category as defined in Table 1-1 of this
standard, the structure shall conform to the seismic requirements
for new construction.
EXCEPTIONS
1. Where a change of use results in a structure being reclassified from
Occupancy Category
I
o r
I1
to Occupancy Category
111
and the struc-
t u re is lo ca ted i n a sei sm i c m ap a rea wh e re S D ~0.33, compliance
with the seismic requirements of this standard is no t required.
2.
Specific s eismic detailing requireme nts of this standard for a new
structure need not be met where it can be shown that the level of
performanc e and seismic safety is equivalent to that of a new struc-
ture. Such analysis shall consider the regularity, overstrength, re-
dundancy, and ductility of the structure within the context of the
existing and retrofit if any) detailing provided.
Minimum Design Loads for Buildings and Other Structures
8/10/2019 ASCE_7-05_Appendix11.pdf
6/8
8/10/2019 ASCE_7-05_Appendix11.pdf
7/8
Appendix
C
SERVICE BILITY CONSIDER TIONS
C. SERVICEABILITY CONSIDER ATIONS
This Appendix is not a mandatory part of the standard, but pro-
vides guidance f or design for serviceability in order to maintain
the function of a building and the com fort of its occupants during
normal usage. Serviceability limits e.g., maximum static defor-
mations, accelerations, etc.) shall be chosen with due regard to
the intended function of the structure.
Serviceability shall be checked using appropriate loads for the
limit state being considered.
C. l DEFLECTION VIBRATION AND DRIFT
C l l Vertical Deflections Deformations of floor and roof
members and systems due to service loads shall not impair the
serviceability of the structure.
C 1 2 Drift of W alls and Frames Lateral deflection or drift of
structures and deformation of horizontal diaphragms and bracing
systems due to w ind effects shall not impair the serviceability of
the structure.
C 1 3 Vibrations Floor systems supporting large open areas
free of partitions or other sources of damping, where vibration
due to pedestrian traffic might be ob jectionable, shall be designed
with due regard for such vibration.
Mechanical equipment that can produce objectionable vibra-
tions in any portion of an inhabited structure shall be isolated to
minimize the transmission of such vibrations to the structure.
Building structural systems shall be designed so that wind-
induced vibrations do not cause occupant discomfort or damage
to the building, its appurtenances o r contents.
C.2 DESIGN FOR LONG-TERM DEFLECT ION
Where required for acceptable building performance, members
and systems shall be designed to accommodate long-term irre-
versible deflections under sustained load.
C.3 CAMBER
Special camber requirements that are necessary to bring a loaded
member in to proper relations with the work of other trades shall
be set forth in the design docum ents.
Beams detailed without specified camber shall be positioned
during erection so that any minor camber is upward. If camber
involves the erection of any m ember under preload, this shall be
noted in the design documents.
C.4 EXPANSION AND CONTRACTION
Dimensional chan ges in a structure and its elements due to vari-
ations in temp erature, relative humidity, or other effects shall not
impair the serviceability of the structure.
Provision shall be made either to control crack widths or to
limit cracking by providing relief joints.
C.5 DURABILITY
Buildings and other structures shall be designed to tolerate long-
term environmental effects o r shall be protected against such ef-
fects.
Minimum Design Loads for Buildings and Other Structures
8/10/2019 ASCE_7-05_Appendix11.pdf
8/8