Upload
rahul-deva
View
219
Download
0
Embed Size (px)
Citation preview
7/28/2019 Barrera Beam1224
1/2
BEAM1224A(SA)Single-endedRefected TypeBeam Smoke Detector
Model BEAM1224A is uniquely suited or protecting open
areas with high ceilings areas where other methods
o smoke detection are difcult to install and maintain.
Features
16-to328-footprotectionrange
Single-ended,reflectivedesign
User-friendlyalignmentprocedure
Sixuserselectablesensitivitylevels
OptionalintegralNFPA72sensitivitytestfeature
Removableplug-interminalblocks
Digitaldisplayforeasyalignment
Built-inautomaticgaincontrolcompensatesforsignaldeterioration
fromdustbuild-up
Remoteteststationoption
Paintablecover
Easiestalignmentintheindustry
Heaterkitsfortransmitter/receiverandreflectoroption
System Sensor Model BEAM1224Aisafour-wireconventional
reectedbeamsmokedetector,whichisuniquelysuitedfor
protectingopenareaswithhighceilings,whereothermethods
ofsmokedetectionarediculttoinstallandmaintain.Itistobe
usedwithULCListedcontrolpanelsonly.Anadvantageofthis
single-endedreectivedesignisthatitismucheasiertoinstallthan
thedual-endedprojectedbeamdetectors.Alignmentisquickly
accomplishedviaanopticalsightandatwo-digitsignalstrength
meterincorporatedintotheproduct.AnotheradvantageoftheBEAM1224Aisthatitislistedforoperationintemperaturesranging
from30Cto55C.Thismeansitcanbeusedinopenareasto
provideearlywarninginenvironmentswheretemperatureextremes
mayexceedthecapabilityofothertypesofsmokedetectors.
BEAM1224Aconsistsofatransmitter/receiverunitandareector.
Whensmokeenterstheareabetweentheunitandthereector,
thesmokecausesareductioninthesignal.Whenthesmokelevel
reachesthepredeterminedthreshold,analarmisactivated.
BEAM1224Ahasfourstandardsensitivityselections,alongwithtwo
Acclimatesettings(adjustablesensitivity).Whenoneofthetwo
Acclimatesettingsisselected,thedetectorwillautomaticallyadjust
itssensitivityusingadvancedsoftwarealgorithmstochoosethe
optimumsensitivityforthespecicenvironment.
BEAM1224SAisalsoequippedwithanintegralsensitivitytestfeature,
whichconsistsofatestlterattachedtoaservomotorinsidethe
detectoroptics.WhentheremoteteststationRTS451isused,the
motorisactivatedandmovesthelterintothepathwayofthe
lightbeam,totestthedetectorssensitivity.Thisintegralsensitivity
testfeatureallowstheusertoquicklyandeasilymeettheannual
maintenanceandtestrequirementsofNFPA72.
Agency Listings
7/28/2019 Barrera Beam1224
2/2
Ordering InormationPart No. Description
BEAM1224A 4wireconventionalbeamsmokedetectorwith8
reector
BEAM1224SA 4wireconventionalbeamsmokedetectorwith8
reectorandintegralsensitivitytest
Accessories
BEAMLRK Longrangeaccessorykit(3)additionalreectors(Requiredforapplicationsinexcessof230ft.[70m])
BEAMMMK Multi-mountkit(Providesceilingorwallmount
capabilitywithincreasedangularadjustmentfor
eitherthebeamorthereector.Wheninstalledwith
thetransmitter/receiverunit,BEAMSMKmustbe
usedaswell)
BEAMSMK Sur facemountk it
6500-MMK Heavydutymulti-mountkit(forinstallationsproneto
vibrationorwherethereisdicultyinmaintaining
thesetangle.Wheninstalledwiththetransmitter/
receiverunit,6500-SMKmustbeusedaswell)
6500-SMK Surfacemountkitforusewiththe6500-MMK
BEAMHK Heaterkitfortransmitter/receiverunit(Seeelectrical
requirementsabove)BEAMHKR Heaterkitforreector(Seeelectricalrequirements
above)
RTS451KEY-A Remoteteststationwithkeylock
RTS451 RemoteteststationusedtoinitiatetheNFPA
sensitivitytestfunction
BEAM1224A(SA) SpeciicationsOperational Specifcations
Protection Range 16ft.to328ft.(5mto100m)
Adjustment Angle +/10Degreeshorizontal&vertical(Theopticsmoveindependentoftheunit)
Sensitivity Levels Level125%Level230%Level340%Level450%
AcclimateLevel13050%AcclimateLevel24050%
Fault Condition (Trouble) 96%ormoreobscurationblockageInalignmentmodeImproperinitialalignmentSelf-compensationlimitreached
Alignment Aid OpticalgunsightIntegralsignalstrengthindication2-digitdisplay
Alarm Indicator LocalredLEDandremotealarm
Trouble Indicator LocalyellowLEDandremotetrouble
Normal Indicator LocalashinggreenLED
Test/Reset Features IntegralSensitivityTestFilter(BEAM1224SAonly)Sensitivitylter(Incrementalscaleonreector)Localalarmtestswitch
LocalalarmresetswitchRemotetestandresetswitch(CompatiblewithRTS451andRTS451KEY-Ateststation)
Smoke Detector Spacing Onsmoothceilings,3060feetbetweenprojectedbeamsandnotmorethanone-halfthatspacingbetweenaprojectedbeamandasidewall.Otherspacingmaybeuseddependingonceilingheight,airowcharacteristics,andresponserequirements.SeeCAN/ULCS524.
Environmental Specifcations
Temperature 30Cto55C(22Fto131F)
Humidity 1093%RHNoncondensing
Electrical Specifcations
Voltage 10.2to32VDC(BEAM1224)15to32VDC(BEAM1224S)BEAM1224SAshouldnotbeusedwith12Vpowersources
Avg. Standby Current (24VDC) 17mAMax
Avg. Current During Testing 500mAMax
Avg. Alarm Current (24VDC) 38.5mAMax
Avg. Fault Current (24VDC) 8.5mAMax
Avg. Alignment Mode Current (24VDC) 28mAMax
Mechanical Specifcations
Detector Dimensions 10H7.5W3.3D(254mmH191mmW84mmD)
Refector Dimensions (16 to 230) 7.99.1(200230mm)
Refector Dimensions(beyond 230)
15.718.1(400460mm)
Electrical Specifcations (BEAMHK)Voltage 15to32V
Current 92mAat32V
Power Consumption 1.6W@24V;3W@32V
..
..
..
ALIGNMENT
SENSITIVITY
TEST
VERTICAL
OPTICS
ALIGNMENT
KNOB
OPTICAL
GUNSIGHT
HORIZONTAL
OPTICS
ALIGNMENT
KNOB
ALIGNMENT
SIGNAL
STRENGTH
METER
RESET
Activated Test Feature(BEAM1224SAonly)
+
SERVO MOTORTEST FILTER
Electrical Specifcations (BEAMHKR)
Voltage 15to32V
Current 450mAMaxat32V(perreflector)
Power Consumption 7.7W@24V;15W@32V(perreector)
POWER OUT ()
POWER OUT (+)
POWER IN()
POWER IN(+)
RESET INPUT
TEST INPUT
AUX ()
REMOTEALARMOUT
Not used
REMOTETROUBLEOUT
TROUBLECOM
TROUBLEN.C.
ALARMCOM
ALARMN.O.
ALARMCOM
ALARMN.O.
I
III
II
I
II
I I
II
I
BEAM1224A(SA) Parts
WiringTerminals
2006SystemSensor.
Productspecicationssubjecttochangewithoutnotice.Visitsystemsensor.comfor
currentproductinformation,includingthelatestversionofthisdatasheet.
A05-0365-0037/06#1676
6-6581KitimatRoadMississaugaON,L5N3T5