    BEAM1224A(SA)Single-endedRefected TypeBeam Smoke Detector

    Model BEAM1224A is uniquely suited or protecting open

    areas with high ceilings areas where other methods

    o smoke detection are difcult to install and maintain.

    Features

    16-to328-footprotectionrange

    Single-ended,reflectivedesign

    User-friendlyalignmentprocedure

    Sixuserselectablesensitivitylevels

    OptionalintegralNFPA72sensitivitytestfeature

    Removableplug-interminalblocks

    Digitaldisplayforeasyalignment

    Built-inautomaticgaincontrolcompensatesforsignaldeterioration

    fromdustbuild-up

    Remoteteststationoption

    Paintablecover

    Easiestalignmentintheindustry

    Heaterkitsfortransmitter/receiverandreflectoroption

    System Sensor Model BEAM1224Aisafour-wireconventional

    reectedbeamsmokedetector,whichisuniquelysuitedfor

    protectingopenareaswithhighceilings,whereothermethods

    ofsmokedetectionarediculttoinstallandmaintain.Itistobe

    usedwithULCListedcontrolpanelsonly.Anadvantageofthis

    single-endedreectivedesignisthatitismucheasiertoinstallthan

    thedual-endedprojectedbeamdetectors.Alignmentisquickly

    accomplishedviaanopticalsightandatwo-digitsignalstrength

    meterincorporatedintotheproduct.AnotheradvantageoftheBEAM1224Aisthatitislistedforoperationintemperaturesranging

    from30Cto55C.Thismeansitcanbeusedinopenareasto

    provideearlywarninginenvironmentswheretemperatureextremes

    mayexceedthecapabilityofothertypesofsmokedetectors.

    BEAM1224Aconsistsofatransmitter/receiverunitandareector.

    Whensmokeenterstheareabetweentheunitandthereector,

    thesmokecausesareductioninthesignal.Whenthesmokelevel

    reachesthepredeterminedthreshold,analarmisactivated.

    BEAM1224Ahasfourstandardsensitivityselections,alongwithtwo

    Acclimatesettings(adjustablesensitivity).Whenoneofthetwo

    Acclimatesettingsisselected,thedetectorwillautomaticallyadjust

    itssensitivityusingadvancedsoftwarealgorithmstochoosethe

    optimumsensitivityforthespecicenvironment.

    BEAM1224SAisalsoequippedwithanintegralsensitivitytestfeature,

    whichconsistsofatestlterattachedtoaservomotorinsidethe

    detectoroptics.WhentheremoteteststationRTS451isused,the

    motorisactivatedandmovesthelterintothepathwayofthe

    lightbeam,totestthedetectorssensitivity.Thisintegralsensitivity

    testfeatureallowstheusertoquicklyandeasilymeettheannual

    maintenanceandtestrequirementsofNFPA72.

    Agency Listings

  • 7/28/2019 Barrera Beam1224

    2/2

    Ordering InormationPart No. Description

    BEAM1224A 4wireconventionalbeamsmokedetectorwith8

    reector

    BEAM1224SA 4wireconventionalbeamsmokedetectorwith8

    reectorandintegralsensitivitytest

    Accessories

    BEAMLRK Longrangeaccessorykit(3)additionalreectors(Requiredforapplicationsinexcessof230ft.[70m])

    BEAMMMK Multi-mountkit(Providesceilingorwallmount

    capabilitywithincreasedangularadjustmentfor

    eitherthebeamorthereector.Wheninstalledwith

    thetransmitter/receiverunit,BEAMSMKmustbe

    usedaswell)

    BEAMSMK Sur facemountk it

    6500-MMK Heavydutymulti-mountkit(forinstallationsproneto

    vibrationorwherethereisdicultyinmaintaining

    thesetangle.Wheninstalledwiththetransmitter/

    receiverunit,6500-SMKmustbeusedaswell)

    6500-SMK Surfacemountkitforusewiththe6500-MMK

    BEAMHK Heaterkitfortransmitter/receiverunit(Seeelectrical

    requirementsabove)BEAMHKR Heaterkitforreector(Seeelectricalrequirements

    above)

    RTS451KEY-A Remoteteststationwithkeylock

    RTS451 RemoteteststationusedtoinitiatetheNFPA

    sensitivitytestfunction

    BEAM1224A(SA) SpeciicationsOperational Specifcations

    Protection Range 16ft.to328ft.(5mto100m)

    Adjustment Angle +/10Degreeshorizontal&vertical(Theopticsmoveindependentoftheunit)

    Sensitivity Levels Level125%Level230%Level340%Level450%

    AcclimateLevel13050%AcclimateLevel24050%

    Fault Condition (Trouble) 96%ormoreobscurationblockageInalignmentmodeImproperinitialalignmentSelf-compensationlimitreached

    Alignment Aid OpticalgunsightIntegralsignalstrengthindication2-digitdisplay

    Alarm Indicator LocalredLEDandremotealarm

    Trouble Indicator LocalyellowLEDandremotetrouble

    Normal Indicator LocalashinggreenLED

    Test/Reset Features IntegralSensitivityTestFilter(BEAM1224SAonly)Sensitivitylter(Incrementalscaleonreector)Localalarmtestswitch

    LocalalarmresetswitchRemotetestandresetswitch(CompatiblewithRTS451andRTS451KEY-Ateststation)

    Smoke Detector Spacing Onsmoothceilings,3060feetbetweenprojectedbeamsandnotmorethanone-halfthatspacingbetweenaprojectedbeamandasidewall.Otherspacingmaybeuseddependingonceilingheight,airowcharacteristics,andresponserequirements.SeeCAN/ULCS524.

    Environmental Specifcations

    Temperature 30Cto55C(22Fto131F)

    Humidity 1093%RHNoncondensing

    Electrical Specifcations

    Voltage 10.2to32VDC(BEAM1224)15to32VDC(BEAM1224S)BEAM1224SAshouldnotbeusedwith12Vpowersources

    Avg. Standby Current (24VDC) 17mAMax

    Avg. Current During Testing 500mAMax

    Avg. Alarm Current (24VDC) 38.5mAMax

    Avg. Fault Current (24VDC) 8.5mAMax

    Avg. Alignment Mode Current (24VDC) 28mAMax

    Mechanical Specifcations

    Detector Dimensions 10H7.5W3.3D(254mmH191mmW84mmD)

    Refector Dimensions (16 to 230) 7.99.1(200230mm)

    Refector Dimensions(beyond 230)

    15.718.1(400460mm)

    Electrical Specifcations (BEAMHK)Voltage 15to32V

    Current 92mAat32V

    Power Consumption 1.6W@24V;3W@32V

    ..

    ..

    ..

    ALIGNMENT

    SENSITIVITY

    TEST

    VERTICAL

    OPTICS

    ALIGNMENT

    KNOB

    OPTICAL

    GUNSIGHT

    HORIZONTAL

    OPTICS

    ALIGNMENT

    KNOB

    ALIGNMENT

    SIGNAL

    STRENGTH

    METER

    RESET

    Activated Test Feature(BEAM1224SAonly)

    +

    SERVO MOTORTEST FILTER

    Electrical Specifcations (BEAMHKR)

    Voltage 15to32V

    Current 450mAMaxat32V(perreflector)

    Power Consumption 7.7W@24V;15W@32V(perreector)

    POWER OUT ()

    POWER OUT (+)

    POWER IN()

    POWER IN(+)

    RESET INPUT

    TEST INPUT

    AUX ()

    REMOTEALARMOUT

    Not used

    REMOTETROUBLEOUT

    TROUBLECOM

    TROUBLEN.C.

    ALARMCOM

    ALARMN.O.

    ALARMCOM

    ALARMN.O.

    I

    III

    II

    I

    II

    I I

    II

    I

    BEAM1224A(SA) Parts

    WiringTerminals

    2006SystemSensor.

    Productspecicationssubjecttochangewithoutnotice.Visitsystemsensor.comfor

    currentproductinformation,includingthelatestversionofthisdatasheet.

    A05-0365-0037/06#1676

    6-6581KitimatRoadMississaugaON,L5N3T5

    Phone:800-SENSOR2www.systemsensor.ca