    Main Menu Default Value Unit

    Display Contrast 32

    System

    Language Options NA

    Arms

    First Arm Number 1

    RIT Panel

    RIT Panel Enable

    Lamps State Boot ALL OFF

    Lamp State Idle RED Steady

    Lamp State Auth AMBER Steady

    Lamp State Wait Ack Amber Flashing

    Lamp State Wait Start GREEN Flashing

    Lamp State Loading GREEN Steady

    Lamp State Error RED Flashing

    Lamp State Batch Over AMBER Flashing

    System of Units

    System of Units Metric - ISO units

    Corrected base Temp Base 15 deg C

    Litre/Liter Spelling Litre

    Volume Decimals 1

    Batch TypeBatch Type Gross

    Transaction Number

    Transaction Number xxxx

    Overwrite oldest trans Enable

    Clock

    Year xxxx

    Month xx

    Day xx

    Hours xx

    Minutes xx

    Display Date Format DD/MM/YYYY

    Authorizations / Pins

    Setup Password 6789

    Manager Reset 9876

    PIN password 1234

    W&M password 4321

    Personnel Authorization PIN

    Vehicle Authorization None

    master Authorization PIN

    Master to TAS override Enable

    Hardware test via 8 key Enable

    Timeouts

    Keyboard time out 0

    Clear / Reconnect 0

    Bay Number

    Bay Number xxx

    Power Fail restart

    Restart after power fail Enable

    Show officer Card

    Show officer Card Enable

    Test Mode Disable

    Demo Mode Disable

    Automated Proving Disable

    Illegal Access Disable

    Alarm on Fault Enable

    Ask Compt number Enable

    Ask return quantity Disable

    Ask Load number Disable

    BATCH CONTROLLER CONFIGURATION PARAMETERS

    General Setup

    LOADING OPTIONS

    Submenus

    Page 1 OF 7

  • 8/12/2019 BC-Config

    2/7

    Ask Truck Number Enable

    Multiple loads per arm Enable

    Ask Preset quantity Enable

    Max preset quantity Enable

    GP Input 1 - CA20/CA19

    Input type Permissive

    Input function Emergency Stop

    Loading effect Pause Loading

    GP Input 2 - CA21/CA19

    Input type Permissive

    Input function Overfill/Ground

    Loading effect Pause Loading

    GP Input 3 - CA22/CA19

    Input type None

    GP Input 4 - CA23/CA19

    Input type Arm input

    Input function Arm input 1

    Select Arm Arm 1

    Loading effect Pause Loading

    GP Input 5 - CA25/CA24

    Input type None

    GP Input 6 - CA26/CA24

    Input type NoneGP Input 7 - CA27/CA24

    Input type None

    GP Input 8 - CA28/CA24

    Input type None

    GP Input 9 - CB20/CB19

    Input type None

    GP Input 10 - CB21/CB19

    Input type None

    GP Input 11 - CB22/CB19

    Input type RIT Input

    Input function RIT Start

    Select Arm Arm 1

    GP Input 12 - CB23/CB19

    Input type RIT Input

    Input function RIT Ack

    Select Arm Arm 1

    GP Input 13 - CB25/CB24

    Input type RIT Input

    Input function RIT STOP

    Select Arm Arm 1

    GP Input 14 - CB26/CB24

    Input type None

    GP Input 15 - CB27/CB24

    Input type None

    GP Input 15 - CB28/CB24

    Input type None

    GP Output 1 A9/A10 None

    GP Output 2 A11/A12 None

    GP Output 3 A13/A17

    GP Output 3 Stream ControlStream Control Pump demand

    Pump demand Stream 1

    GP output 3 Condition Normally open

    GP Output 4 A14/A17

    GP Output 4 Stream Control

    Stream Control Pump demand

    Pump demand Stream 2

    GP output 4 Condition Normally open

    GENERAL PURPOSE INPUTS

    GENERAL PURPOSE OUTPUTS

    Page 2 OF 7

  • 8/12/2019 BC-Config

    3/7

    GP Output 5 A15/A17 None

    GP Output 6 A16/A17 None

    GP Output 7 BA1/BA2

    GP Output 7 Control Valve

    Control Valve DCV Inlet/ Slow flow

    DCV Inlet/ Slow flow Stream 1

    GP output 7 Condition Normally open

    GP Output 8 BA3/BA2

    GP Output 8 Control Valve

    Control Valve DCV Outlet/ High flow

    DCV Outlet/ High flow Stream 1

    GP output 8 Condition Normally open

    GP Output 9 BA4/BA5

    GP Output 9 Control Valve

    Control Valve DCV Inlet/ Slow flow

    DCV Inlet/ Slow flow Stream 2

    GP output 9 Condition Normally open

    GP Output 10 BA6/BA5

    GP Output 10 Control Valve

    Control Valve DCV Outlet/ High flow

    DCV Outlet/ High flow Stream 2

    GP output 10 Condition Normally open

    GP Output 11 BA7/BA8

    GP Output 11 Internal AdditiveInternal Additive Int Addtv pulse

    Int Addtv pulse Additive 1

    GP output 11 Condition Normally open

    GP Output 12 BA9/BA8

    GP Output 12 Internal Additive

    Internal Additive Int Addtv pulse

    Int Addtv pulse Additive 2

    GP output 12 Condition Normally open

    GP Output 13 BA10/BA11 None

    GP Output 14 BA12/BA11 None

    GP Output 15 BA13/BA14

    GP Output 15 Internal Additive

    Internal Additive Int Additive pump

    Int Additive pump Additive 1

    GP output 15 Condition Normally open

    GP Output 16 BA15/BA14

    GP Output 16 Internal Additive

    Internal Additive Int Additive pump

    Int Additive pump Additive 2

    GP output 16 Condition Normally open

    GP Output 17 BA16/BA17 None

    GP Output 18 BA18/BA17 None

    GP Output 19 BB1/BB2 None

    GP Output 20 BB3/BB2 None

    GP Output 21 BB4/BB5 None

    GP Output 22 BB6/BB5 None

    GP Output 23 BB7/BB8 None

    GP Output 24 BB9/BB8 None

    GP Output 25 BB10/BB11

    GP Output 25 RIT

    RIT RIT GreenRIT Green Arm 1

    GP output 25 Condition Normally Open

    GP Output 26 BB12/BB14

    GP Output 26 RIT

    RIT RIT Amber

    RIT Amber Arm 1

    GP output 26 Condition Normally Open

    GP Output 27 BB13/BB14

    Page 3 OF 7

  • 8/12/2019 BC-Config

    4/7

    GP Output 27 RIT

    RIT RIT RED

    RIT RED Arm 1

    GP output 27 Condition Normally Open

    GP Output 28 BB15/BB14 None

    GP Output 29 BB16/BB17 None

    GP Output 30 BB18/BB17 None

    Deadman Timer Disable

    Port 1

    Comms Device Computer

    Comms Mode RS 485

    Baud Rate 19200 BPS

    Parity None

    Stop bits 1

    Unit Address xx

    Port 2

    Comms Device Computer

    Comms Mode RS 485

    Baud Rate 19200 BPS

    Parity None

    Stop bits 1

    Unit Address xxPort 3

    Comms Device Computer

    Comms Mode RS 485

    Baud Rate 19200 BPS

    Parity None

    Stop bits 1

    Unit Address xx

    Terminal Automation mode

    Terminal Automation mode Load Scheduling

    Comms Time out 30 Sec

    Options

    Debug Response Disable

    Initial Message

    Initial Message Connect Earth

    Manager Messages

    Manager Reset message Standard

    Deadman messages

    Deadman timeout message Standard

    GP input message

    Arm Messages Standard

    Permissive messages Standard

    System Messages Standard

    Opto outputs Flowmeter A

    Alarm Loading effects Standard

    Loading Arms

    Name

    Select Arm DefaultEdit HM Classif 1

    Setup

    Enable Arm 1 Enable

    Units L & L / min

    Maximum Preset 8000 Lit

    Flow Control

    Arm Slow Flow 300 L/Min

    Slow Start Quantity 300 L

    COMMUNICATIONS

    CONFIGURE MESSAGES

    OPTO OUTPUTS

    ALARM LOADING EFFECTS

    CONFIGURE ARM 1

    CONFIGURE DEADMAN

    Page 4 OF 7

  • 8/12/2019 BC-Config

    5/7

    Arm Full flow 1500 L/Min

    Alarm Setup

    Blend tollerence alarm Enable

    Low percentage 5

    High percentage 5

    Minimum Blend volume 1 L

    Slow flow alarm Enable

    Low percentage 20

    High percentage 20

    Slow flow Alarm delay 10 Sec

    High Flow alarm Enable

    Low percentage 20

    High percentage 20

    High flow Alarm delay 10 Sec

    Low Flow alarm Enable

    Low percentage 20

    High percentage 20

    Low flow Alarm delay 10 Sec

    Additive Setup

    Cont Add Batch On Alarm Disable

    Metering Lines

    Name Meter 1

    K factorK Factor type Non Linear

    K Factor 1 1

    Freq 2 25 Hz

    K Factor 2 1

    Freq 3 50 Hz

    K Factor 3 1

    Freq 4 75 Hz

    K Factor 4 1

    Freq 5 100 Hz

    K Factor 5 1

    Signal Type

    Min Linear Flow Rate 200 L/Min

    Signal type meter 1 Dual

    Cutoff Meter 1 1 Hz

    Flowmeter input meter1 Resistor pull up

    Flowmeter filter meter 1 Debounce inactive

    Correction

    Meter 1 Commodity type none

    Pre Batch Stop quantity

    Pre Batch Stop quantity 0 L

    Unauthorized Flow threshold

    Unauthorized Flow thr 10 L

    Minimum Preset

    Minimum Preset 10 L

    Accumulated totals xxxx

    Meter Factor

    Meter 1 factor 1

    Overrun quantity

    Overrun quantity 10 L

    Name Meter 2K factor

    K Factor type Non Linear

    K Factor 1 1

    Freq 2 25 Hz

    K Factor 2 1

    Freq 3 50 Hz

    K Factor 3 1

    Freq 4 75 Hz

    CONFIGURE LINE 2

    CONFIGURE LINE 1

    Page 5 OF 7

  • 8/12/2019 BC-Config

    6/7

    K Factor 4 1

    Freq 5 100 Hz

    K Factor 5 1

    Signal Type

    Min Linear Flow Rate 5 L/min

    Signal type meter 2 Dual

    Cutoff Meter 2 1 Hz

    Flowmeter input meter 2 Resistor pull up

    Flowmeter filter meter 2 Debounce inactive

    Correction

    Meter 1 Commodity type none

    Pre Batch Stop quantity

    Pre Batch Stop quantity 0 L

    Unauthorized Flow threshold

    Unauthorized Flow thr 10 L

    Minimum Preset

    Minimum Preset 1 L

    Accumulated totals xxxx L

    Meter Factor

    Meter 2 factor 1

    Overrun quantity

    Overrun quantity 10 L

    Product Streams

    No Flow time out 5 Sec

    Valve type Digital

    Deadband 20 L/Min

    Valve slow flow 230 L/Min

    Valve low flow 270 L/Min

    Valve response 0.7

    PreStop quantity 300 L/Min

    Auto high flow Enable

    Valve full flow 1500 L/min

    High flow time out 10 Sec

    Pump Off delay 0 Sec

    No Flow time out 5 Sec

    Valve type Digital

    Deadband 5 L/Min

    Valve slow flow 20 L/Min

    Valve low flow 20 L/Min

    Valve response 0.7

    PreStop quantity 300 L/Min

    Auto high flow Enable

    Valve full flow 400 L/min

    High flow time out 10 Sec

    Pump Off delay 0 Sec

    Additive Lines

    Injection point 1

    Name / Setup

    Enable Injector 1 Enable

    Enable Injector 1 Arm 1

    Edit Additive 1 code ADDCODE 1

    Pacing volume 200 LPump off delay 0 Sec

    Alarm Setup

    Inj 1 leaking soleniod Enable

    Leaking Sol time period 5 Sec

    Leaking sol vol limit 100 ml

    Inj 1 No flow alarm enable

    No additive flow time out 2 Sec

    No of solenoid retries 2

    STREAM 1

    STREAM 2

    INTERNAL ADDITIVE LINES

    Page 6 OF 7

  • 8/12/2019 BC-Config

    7/7

    Inj 1 Additive deviation enable

    Additive deviation basis 10

    Additive volume deviation 10

    K factor

    Inj 1 K factor 2

    Meter Factor

    Inj 1 Meter Factor 1

    Injection point 2

    Name / Setup

    Enable Injector 2 Disable

    Injection point 3

    Name / Setup

    Enable Injector 3 Disable

    Injection point 4

    Name / Setup

    Enable Injector 4 Disable

    Additive type

    Additive Inject None

    Additive Line setup No Available

    Recipies

    Edit Recipe Name xxxxx

    Enable Recipe X Enable / DisableAssociated Loading Arm 1

    Target Blend percentage 0

    Additive Amount 1 x.x ppm

    Additive Amount 2 x.x ppm

    Additive flush volume 100 L

    EXTERNAL ADDITIVE LINES

    RECIPE 1 to 16

    Page 7 OF 7