document.xlsx FONCODES OFICINA ZONAL HUANCAYO CALCULOS DE BOMBAS NOMBRE DEL PROYECTO AGUA POTABLE HUAYLLAY NUMERO DEL EXPEDIENTE OFICINA ZONAL PASCO 1. DISENO DE LA LINEA DE IMPULSION Q max.diario Qmd = 8.96 l/s 0.00896 m3/seg N Horas funcionamiento bomba N = 8.00 Horas CAUDAL DE IMPULSION ( Qi ) Qi = Qmd * 24 / N Qi = 0.02688 m3/seg 26.88 l/s DIAMETRO DE IMPULSION ( Di ) Usando la formula de Bresse 1.1 < K < 1.3; K = 1.1 D = K * ( Qi )^1/2 Di = 0.180346 mt. Di = 7.10 pulg DIAMETRO DE TUBERIA A UTILIZAR: 8.00 pulg 2. DISENO DE LA POTENCIA DE LA BOMBA POTENCIA DE LA BOMBA Pot. Bomba = ( Pe x Qimp. x Ht ) / (75 x n1 n2 ) = 18.53 H.P. BOMBA A UTILIZAR = 20 H.P. Pe = 1000 kg/cm3. Peso Especifico del agua Qimp. = 26.88 lts./sg.Caudal de Impulsion Ht. = 34.91 mts. Altura Perdida de Carga Total n1 = 0.9 O.K. Eficiencia de la Bomb 85 % < n1 < 90 % n2 = 0.75 O.K. Eficiencia del Motor 70 % < n2 < 85 % CALCULO DE PERDIDA DE CARGA Ht. = himp. + hf. + hc. + hac = 34.91 mts. Perdida de Carga de Impuls h imp = 27.00 mts. Cota Nivel Agua Tanque Elevado 4,630.00 Cota Nivel de Fondo de Cistern 4,603.00 Perdida de Carga por Fricc hf = 0.91 mts. Longitud de Tuberia de Impulsi 0.28 Coeficiente de Hazen-Williams 140 Carga por altura de llegad hc = 5.00 mts. carga Estimada por accesorh acc. = 2.00 mts.

Bombas

Embed Size (px)

DESCRIPTION

bombas

Citation preview

Page 1: Bombas

document.xlsx

FONCODES 0OFICINA ZONAL HUANCAYO 280

CALCULOS DE BOMBAS

NOMBRE DEL PROYECTO AGUA POTABLE HUAYLLAYNUMERO DEL EXPEDIENTEOFICINA ZONAL PASCO

1. DISENO DE LA LINEA DE IMPULSION

Q max.diario Qmd = 8.96 l/s 0.00896 m3/seg

N Horas funcionamiento bomba N = 8.00 Horas

CAUDAL DE IMPULSION ( Qi )Qi = Qmd * 24 / N Qi = 0.02688 m3/seg 26.88 l/s

DIAMETRO DE IMPULSION ( Di )

Usando la formula de Bresse 1.1 < K < 1.3; K = 1.1

D = K * ( Qi )^1/2 Di = 0.18035 mt.

Di = 7.10 pulg

DIAMETRO DE TUBERIA A UTILIZAR: 8.00 pulg

2. DISENO DE LA POTENCIA DE LA BOMBA

POTENCIA DE LA BOMBAPot. Bomba = ( Pe x Qimp. x Ht ) / (75 x n1 n2 ) = 18.53 H.P.

BOMBA A UTILIZAR = 20 H.P.

Pe = 1000 kg/cm3. Peso Especifico del aguaQimp. = 26.88 lts./sg. Caudal de Impulsion

Ht. = 34.91 mts. Altura Perdida de Carga Totaln1 = 0.9 O.K. Eficiencia de la Bomba 85 % < n1 < 90 %n2 = 0.75 O.K. Eficiencia del Motor 70 % < n2 < 85 %

CALCULO DE PERDIDA DE CARGA

Ht. = himp. + hf. + hc. + hacc = 34.91 mts.

Perdida de Carga de Impulsi h imp = 27.00 mts.Cota Nivel Agua Tanque Elevado 4,630.00 m.s.n.m.Cota Nivel de Fondo de Cisterna 4,603.00 m.s.n.m.

Perdida de Carga por Friccio hf = 0.91 mts.Longitud de Tuberia de Impulsio 0.28 Km.Coeficiente de Hazen-Williams 140

Carga por altura de llegada hc = 5.00 mts.

carga Estimada por accesori h acc. = 2.00 mts.