    PZ-1000 DISTANCE PROTECTION RELAY

  • 7/27/2019 Catalogo Familia PZ1000

    2/16

    I

    N

    TR

    OD

    UC

    CIO

    N

    The PZ1000 family of relays are digital distance protection devices especially suitablefor primary protection of simple or double overhead transmission and subtransmission

    lines (high & medium voltage). Their advanced multiprocessor design and rapid signal

    processing algorithms make them fast acting and safe. They maintain the reliability and

    performance required to handle transmission and distribution networks.

    The family is made up of 3 groups of equipment: advanced, intermediate, and basic,with different functions, which enable more or less advanced applications to be imple-mented.

    PZ1000-A (Advanced): The PZ1000-A features a full range of protection functions

    which enable it to be used in applications of all types, including transmission lines. It

    has 4 MHO characteristic zones plus 5 quadrangular characteristic zones for

    phase-phase and phase-earth faults. It also has pilot protection schemes, breaker

    failure protection and stub protection.

    PZ1000-I (Intermediate): The PZ1000-I is the intermediate protection device in the

    PZ1000 family. It has 3 MHO characteristic zones for phase-phase and phase-earth

    faults. It also has overvoltage unit, a triple pole recloser and syncrocheck. These fea-

    tures enable it to be used for primary and/or back-up protection in transmission and

    sub-transmission lines.

    PZ1000-B (Basic):The PZ1000-B is the basic protection device in the PZ1000 family.

    It comprises 2 forward MHO characteristic zones for phase-phase and phase-earth

    faults, and an additional directional overcurrent unit for phases and neutral. This model

    can be used to protect sub-transmission lines.

    The following characteristics are common to all three units:

    Trip and close circuit supervision (highly useful for system maintenance work).

    Measurement of electrical magnitudes, events, fault reports, oscillograph data

    recorder, fault locator, local & long-distance communications, etc., enabling them

    to be applied in a wide range of installations.

    Possibility of integration in IPC (Integrated Protection & Control) systems through an

    open protocol.

    One front serial port and two rear serial ports for local or remote communications.

    Time synchronisation via demodulated IRIG-B.

    Front panel with 12 programmable LEDs and one red/green LED indicating protec-

    tion status, plus display and keyboard, enabling information on protection to be

    seen and modified.

    4 front push-button for breaker maneuver.

    The advanced model has more digital inputs and outputs and also has 4 fast digi-

    tal outputs for pilot protection.

    INTRODUCTION

    2

    PZ - 1000 DISTANCE PROTECTION RELAY

  • 7/27/2019 Catalogo Familia PZ1000

    3/163

    PZ - 1000 DISTANCE PROTECTION RELAY

    The PZ1000-A is the most advanced member of the PZ1000

    family. It incorporates 4 MHO and/or quadrangular trip charac-

    teristic zones and a 5th additional quadrangular zone for phase-

    phase and phase-earth faults plus pilot protection schemes,

    supervision alarms (pole by pole) and other functions, making it

    a top level distance protection.

    It also has a breaker failure protection unit and a single pole/triple

    pole recloser with up to 4 shots and an increased number of

    inputs/outputs. Breaker monitor functions, number of trips, etc.

    work pole by pole.

    Hardware

    4 analogue inputs for voltage and 4 for current (closed

    terminals, under request)

    16 programmable digital inputs

    20 programmable digital outputs: 9 for trips and 11 for sig-

    nalling

    4 fast outputs for pilot protection

    PZ1000-A (Advanced)

    Distance protection

    Distance protection (21P/21N) with 4 MHO and 5 quadran-gular zones for phase-phase and phase-earth faults: 1for-ward zone, 1 backward zone and 3 programmable forward

    / backward Zone 1 extension Negative sequence directional Pilot protection schemes (85) (by fast outputs or by serial

    communication) Enable by single-phase and phase-phase overcurrent

    (50P/50PP) Fuse failure (68FF) Power swing (68PS) Load encroachment (68LE) Switch-onto-fault (SOF)

    Other protections

    Phase and neutral directional overcurrent (67/67N) (2 units)Overvoltage (59) and undervoltage (27) Breaker failure protection (pole by pole) (50BF) Stub protectionThermal image (49) Current unbalance (46/67Q) Homopolar overvoltage (59N)

    Monitoring

    Breaker monitor (pole by pole) Excessive number of trips (pole by pole)Trip and close circuit supervision (pole by pole) (74TC/CC)Open phase alarm CTs monitoring

    Automatisms and commands

    Single pole / triple pole recloser (79) Syncrocheck (25) Dead line detection (DLD)Open and close commands Pole discrepancy Programmable logic functions

    Data acquisition

    V, I, P, Q, cos, frequency and energy measurementOscillograph data recorder Event records Fault records Historical reports Demand maximeter Fault locator (FL)

    Settings

    The relay has 4 independent setting groups

    Functions

  • 7/27/2019 Catalogo Familia PZ1000

    4/164

    PZ - 1000 DISTANCE PROTECTION RELAY

    The PZ1000-I protection is the intermediate version of the

    PZ1000 family. It has 3 MHO characteristic zones for both

    phase-phase and phase-earth faults.

    It also includes phase overvoltage and undervoltage protection,

    a triple pole recloser with up to 4 shots and a syncrocheck unit.

    Hardware

    4 analogue inputs for voltage and 4 for current (closed

    terminals, under request)

    8 programmable digital inputs

    12 programmable digital outputs

    PZ1000-I (Intermediate)

    Distance protection

    Distance protection (21P/21N) with 2 forward zones and 1

    programmable forward/backward zone with MHO type trip

    characteristic for phase-phase and phase-earth faults. Zone 1 extension

    Negative sequence directional

    Enable by single-phase and phase-phase overcurrent

    (50P/50PP)

    Fuse failure (68FF)

    Load encroachment (68LE)

    Switch-onto-fault (SOF)

    Other protections

    Phase and neutral directional overcurrent (67/67N)

    Overvoltage (59) and Undervoltage (27)

    Thermal image (49)

    Current unbalance (46/67Q)Homopolar overvoltage (59N)

    Monitoring

    Breaker monitor

    Excessive number of trips

    Trip and close circuit supervision (74TC/CC)

    Open phase alarm

    CTs monitoring

    Automatisms and commands

    Triple pole recloser (79)

    Syncrocheck (25)

    Dead line detection (DLD)

    Open and close commandsProgrammable logic functions

    Data acquisition

    V, I, P, Q, cos, frequency and energy measurement

    Oscillograph data recorder

    Event records

    Fault records

    Historical reports

    Demand maximeter

    Fault locator (FL)

    Setting groups

    The relay has 4 independent setting groups

    Functions

  • 7/27/2019 Catalogo Familia PZ1000

    5/16

    PZ - 1000 DISTANCE PROTECTION RELAY

    The PZ1000-B protection device is the basic version of the

    PZ1000 family. It has two MHO characteristic zones for phase-

    phase and phase-earth faults. It is used mainly to protect sub-

    transmission lines.

    PZ1000-B (Basic)

    5

    Distance protection

    Distance protection (21P/21N) with 2 basic forward zones

    with MHO type trip characteristic, for phase-phase and

    phase-earth faults. Zone 1 extension

    Negative sequence directional

    Enable by single-phase and phase-phase overcurrent

    (50P/50PP)

    Fuse failure (68FF)

    Load encroachment (68LE)

    Switch-onto-fault (SOF)

    Other protections

    Phase and neutral directional overcurrent (67/67N)

    Thermal image (49)

    Current unbalance (46/67Q)

    Monitoring

    Breaker monitor

    Trip and close circuit supervision (74TC/CC)

    CTs monitoring

    Automatisms and commands

    Dead line detection (DLD)

    Open and close commands

    Programmable logic functions

    Data acquisition

    V, I, P, Q, cos, frequency and energy measurement

    Oscillograph data recorder

    Event records

    Fault records

    Historical report

    Demand maximeter

    Fault locator (FL)

    Setting groups

    The relay has 4 independent setting groups

    Functions

    It includes various distance protection supervision functions and

    a directional overcurrent protection as a back-up.

    Hardware

    3 analogue inputs for voltage and 4 for current (closed

    terminals, under request)

    8 programmable digital inputs

    12 programmable digital outputs

  • 7/27/2019 Catalogo Familia PZ1000

    6/16

    PZ - 1000 DISTANCE PROTECTION RELAY

    Extension of zone 1

    Zone 4 is used for tripping and pilot protection

    The use of direct sequence voltage as polarization, produces

    a backward expansion of MHOs.

    Directional overcurrent units

    The PZ1000 has 2 additional protection units for phase directio-

    nal overcurrent and for neutral directional overcurrent as bac-

    kups for the main distance units, thus increasing the operational

    reliability of the relay.

    Overvoltage / Undervoltage units

    The PZ1000 has two three-phase voltage units: one for overvol-

    tage and the other for undervoltage. Each phase is analysed

    separately.

    Homopolar overvoltage

    This function protects against faults to earth.

    Breaker failure protection

    This device cuts in if the switch open signal is not received wit-

    hin a programmable time of the order to open being received, or

    if current continues to flow.

    Stub protection

    This protects against faults between current transformers andline isolators configured with a breaker and a half scheme. It is

    an overcurrent unit which is activated when the line isolator is

    open.

    Thermal image

    It protects the line against thermal overloads, calculating the

    temperature depending on the current and recent load condi-

    tions of the protected unit.

    Current unbalance

    This device protects the line against unbalances produced in the

    current as consequence of power system anomalies or unba-

    lance loads. This function is selected by setting as directional or

    no directional.

    All these characteristics are supported by other protection

    and supervision functions which ensure the safe operation of

    the protection device.

    Negative sequence directional unit

    All impedance units are supervised by a negative sequence

    directional unit which indicates the direction of the fault.

    Pilot protection schemes

    Via communication with other terminals, the following protection

    schemes are possible:

    I Staggered tripI Permissive overreach: POTT

    I Permissive underreach: PUTT

    I Directional block: DCB

    I Directional unblock: DCUB

    Additional schemes:

    I ECHO (for permissive schemes)

    I Reverse direction blocking

    I Weak infeed

    I Direct transfer trip

    The pilot protection is executed via digital inputs or serial com-

    munication

    Enable by single-phase and phase-phase overcurrent

    This enables the distance unit if the current exceeds pre-set sin-

    gle-phase or phase-phase thresholds.

    Fuse failure

    This blocks the distance unit if the disappearance of any voltageis detected. The directional unit and/or the voltage unit can also

    be locked depending on settings.

    Power swing

    This blocks the phase-phase distance units and gives power

    swing trip, if power oscillation is detected.

    Load encroachment

    This blocks the phase-phase distance units if the impedance

    detected is within the load zone defined by the user.

    Switch-Onto-Fault

    This sets off an instant non directional three-phase trip when the

    switch closes on a fault in the line.

    DISTANCE PROTECTION

    OTHER PROTECTION

    FUNCTIONS

    6

  • 7/27/2019 Catalogo Familia PZ1000

    7/16

    Breaker monitoring (for each pole)

    An event is generated when the SkI2 meter for any phase exce-eds the threshold set.

    Trip and close circuit supervision (for each pole)

    This detects any anomaly in the circuits with the switch open orclosed.

    Excessive number of trips (for each pole)

    This generates an event and sends a signal to the control unit

    when the trips per phase exceed a preset number in a set time.

    It blocks the recloser when the set number is exceeded.

    Open phase alarm

    This sets off an alarm when an open phase is detected.

    CTs monitoringThis generates an alarm when detecting a failure in a current

    input channel (only for models with In calculated in the own line).

    Single pole/triple pole recloser

    Programmable up to 4 shots

    The first shot is single/triple pole and the rest are triple pole

    (single pole only on PZ1000-A)

    Different times for each shot

    Operation counter for each shot

    Engaged/disengaged by setting, input andcommunications

    Syncrocheck

    This function compares the voltage signals for one phase (in

    modulus and argument) on both sides of the switch, and permits

    the switch to be closed when the pre-set conditions are met. It

    can be used for both manual and automatic closing.

    The angle difference is calculated compensating the breakers

    closing time.

    Dead line detection (DLD)

    This function detects the disconnected phases of a line, genera-

    ting a signal.

    Pole discrepancy

    This unit checks the pole status concordance, causing three pole

    opening after exceeding the set time with any pole (not the three)

    opened.

    Programmable logic functions

    The user can configure up to 6 logic signals which can be assig-

    ned to output relays and LEDs via the SIPCON Protections soft-

    ware.

    MONITORING FUNCTIONS

    AUTOMATISMS AND COMANDS

    7

    Measurement

    The PZ1000 protection relay measures the following magnitudesin real time:

    Per phase and neutral currents (1%)

    Average current (1%)Single and compound voltages per phase (0,5%)

    Average single and compound voltages (0,5%)

    Frequency (0,01Hz)

    Active and reactive power levels and power factor (1%)

    Two-way energy (Class 5)

    Note1: Other accuracies on demand.

    Note2: Depending on models, equipments include external battery

    voltage measurement.

    Oscillograph data recorder

    Depending on the model, the non volatile memories of PZ1000units can store:

    I 20 records for 30 cyclesI 10 records for 60 cycles

    Each record comprises the samples from 8 analogue signalsand the status of 16 selectable digital signals

    Tripping and preliminary start-up are configurable

    The disturbances are collected and exported in COMTRADE

    format.

    Event records

    Queue of 200 events stored in non volatile memory can be reco-vered in text format on PC.

    Each event is accompanied by:

    I Date and time of occurrenceI Descriptive code of eventI Level of electrical parameters (voltage and current) at the time

    of occurrence

    Fault records

    The last 9 faults are stored in the non volatile memory with thefollowing data:

    I Date and time of start-up, beginning and end of faultI Pre-fault and fault levels of electrical parametersI Duration and type of faultI Units engagedI Fault distanceITrip zone and / or pilot trip

    Historical reports

    A queue of 100 historical reports is stored in the non volatilememory, covering maximum and minimum average current andaverage voltage levels within a programmable time window.

    Fault locator

    The fault locator processes the information gathered on each faultand calculates the distance to the fault location.

    Self-testing

    The PZ1000 digital protection relay runs the following ongoingself-diagnostic checks:

    Software running

    Power supply voltage

    HardwarePicking-up of measurements

    Failures detected by self-testing, are signalled by any of the dou-ble outputs (configurable).

    PZ - 1000 DISTANCE PROTECTION RELAY

    DATA ACQUISITION

  • 7/27/2019 Catalogo Familia PZ1000

    8/16

    The PZ1000 units have the following user communication ele-

    ments:

    Display / keyboard

    Featuring:

    2 line, 16-character LCD

    16-key keyboard

    12 programmable LED indicators and 1 two-colour alarm LED

    4 push-button that can be deactivated by setting:

    This permits:

    Displaying of inputs, measurements, dates and times, statisti-

    cal data and latest fault.

    Displaying and modification of settings and active table, assig-

    nation of inputs, outputs and LEDs.

    Comunications

    The unit has:

    1 front serial port

    2 rear serial ports (1 optional), for local and/or remote access to

    protection and monitoring information.

    These outputs can provide all the information available on the

    protection device, and can be used to modify settings of all typesvia SIPCON-protections software by TEAM ARTECHE.

    The PZ1000-A also features an optional rear series output for

    pilot protection.

    MAN-MACHINE INTERFACE

    8

    TEAM ARTECHE uses the SIPCON-Protections program, devel-

    oped for PCs running under WINDOWS. This program allows

    clear, simple dialogue with the unit for access to the information

    stored in it and for adjustment.

    All configuration accesses are password protected to preventtampering by unauthorised personnel.

    The outstanding features of the SIPCON-Protections program

    include the following:

    Automatic detection of the unit with which it is in dialogue.

    Unit status display via status screens

    Presentation and modification of settings

    Filling and presentation of all information stored by the relay:events, faults, historical data, oscilloscope readings, etc.

    SIPCON Protections is compatible with the software used inTEAM ARTECHEs integrated protection and monitoring sys-

    tems, and can be incorpora-ted into them as just one more func-

    tion module.

    SOFTWARE

    PZ - 1000 DISTANCE PROTECTION RELAY

    Breaker closure

    Breaker open

    Local / Remote

    Maneuver permission

  • 7/27/2019 Catalogo Familia PZ1000

    9/16

    The illustration shows the application of a PZ1000-A relay to

    protect overhead lines powered from both ends.

    In this protection scheme the pilot protection function is used. If

    rapid clearance on 100% of the line is not needed, model

    PZ1000-I, which does not have remote protection, can be used.

    The illustration shows the application of an advanced model

    PZ1000-A unit, to protect a breaker and a half scheme, in wich

    stub protection is used to protect against faults between current

    transformers and the isolator, when that isolator is open.

    The existence of three switches and the need for a breaker fai-

    lure unit, recloser and syncrocheck for each of them, is handled

    by using TEAM ARTECHEs PL-70 single function devices:

    PL-70 SY: For the syncrocheck function.

    PL-70 FI: For the breaker failure function.

    PL-70 IT: For the recloser function.

    APLICATIONS

    9

    PROTECTION OF OVERHEAD LINES WITH POWER SUPPLY FROM BOTH ENDS

    STUB PROTECTION

    PZ - 1000 DISTANCE PROTECTION RELAY

  • 7/27/2019 Catalogo Familia PZ1000

    10/16

    DISTANCE PROTECTION (21)

    Settings Range Step

    Phase to earth Zones 1 to 4 () 0.01-300.00 0.01

    Phase to phase Zones 1 to 4 () 0.01-300.00 0.01

    Note: Settings for all 4 zones are independient

    MHO Reach

    Settings Range Step

    Phase to earth reactance Zones 1 to 5 () 0.01-300.00 0.01

    Phase to earth resistance Zones 1 to 5 () 0.01-300.00 0.01

    Phase to phase reactance Zones 1 to 5 () 0.01-300.00 0.01

    Phase to phase resistance Zones 1 to 5 () 0.01-300.00 0.01

    Note: Settings for all 4 zones are independient

    Settings Range Step

    Zone 1 modulus 0.01-50.00 0.01

    Zone 1 angle (deg) 0-3590 10

    Zone 2 modulus 0.01-50.00 0.01

    Zone 2 angle (deg) 0-3590 10

    Other zones modulus 0.01-50.00 0.01

    Other zones angle (deg) 0-3590 10

    Mutual comp. zone 1 KMO modulus 0.01-300.00 0.01

    Mutual comp. zone 1 KMO angle 0-3590 10

    Mutual comp. zone 2 KMO modulus 0.01-300.00 0.01

    Mutual comp. zone 2 KMO angle 0-3590 10

    Mutual comp. other zones KMO modulus 0.01-300.00 0.01

    Mutual comp. other zones KMO angle 0-3590 10

    Cuadrilateral Reach

    Zero Sequence Compensation

    Settings Range Step

    Zone 1 phase to earth (s) 0.0-100 0.01

    Zone 2 phase to earth (s) 0.0-100 0.01

    Zone 3 phase to earth (s) 0.0-100 0.01

    Zone 4 phase to earth (s) 0.0-100 0.01

    Zone 5 phase to earth (s) 0.0-100 0.01Zone 1 phase to phase (s) 0.0-100 0.01

    Zone 2 phase to phase (s) 0.0-100 0.01

    Zone 3 phase to phase (s) 0.0-100 0.01

    Zone 4 phase to phase (s) 0.0-100 0.01

    Zone 5 phase to phase (s) 0.0-100 0.01

    Timming

    Settings

    Phase to earth fault unit MHO, Cuadrilateral

    MHO & cuadrilateral, nonePhase to phase fault unit MHO, Cuadrilateral

    MHO & cuadrilateral, none

    Single pole trip YES/NO

    General Setting

    Settings

    Enable (independient) YES/NO

    Single phase threshold (A) (0.2-30) In 0.1

    Phase-phase threshold (A) (0.2-30) In 0.1

    Def. time (s) (independient) 0.00-10 0.01

    Settings Range

    Zone 2 No

    Fordward

    Backward with tripBackward without trip

    Zone 3 No

    Fordward

    Backward with trip

    Backward without trip

    Zone 4 No

    Backward with trip

    Backward without trip

    Zone 5 No

    Fordward

    Backward

    Non-directional

    Single Phase / Phase-Phase Overcurrent

    Settings Range Step

    Scheme type - Staggered trip

    - Permissive overreach

    - Permissive underreach

    - Directional block

    - Directional unblockRTP input dropout time 0.00-1.00 0.01

    Block additional delay (s) 0.00-1.00 0.01

    Loss of guard delay 0.00-0.15 0.01

    ECHO enabled YES/NO

    Min. RTP delay fo ECHO (s) 0.00-10 0.01

    Reverse zone block enable YES/NO

    Reverse zone block delay 0.00-10 0.01

    Weak infeed enable YES/NO

    Direct trip enable YES/NO

    Pilot Protection Schemes

    Overreaching Direction

    Settings Range Step

    Enable YES

    NO

    YES + Z5

    YES - Z5

    Inner X () 0.01-300.00 0.01

    Inner R () 0.01-300.00 0.01

    Outer X () 0.01-300.00 0.01

    Outer R () 0.01-300.00 0.01

    Direct sequence threshold (A) (0.2-30) In 0.1

    Activation time (s) 0.01-50.00 0.01

    Imax threshold (A) (0.2-30) In 0.1

    I2/Imax ratio 10-50 0.1

    Z1, Z2, Z3, Z4, Z5 zone lockout YES/NO

    Power Swing (68PS)

    SETTINGS

    10

    PZ - 1000 DISTANCE PROTECTION RELAY

    Settings Range Step

    Enable YES/NO

    Negative seq. threshold (V) 10.00-165.00 0.1

    Negative seq. threshold (A) (0.2-30) In 0.1

    Fuse Failure (68FF)

    Settings Range Step

    Enable YES/NO

    Negative sequence threshold (V) 10.00-165.00 0.1

    Negative sequence threshold (A) (0.2-30) In 0.1

    Open Phase Alarm

    Settings Range Step

    Enable YES/NO

    I1 threshold (A) (0.2-30) In 0.1

    Impedance ()

    (indepen. forward & reverse)

    0.01-300 0.1

    Angle + (gnd)

    (indepen. forward & reverse)

    0-3590 10

    Angle - (gnd)

    (indepen. forward & reverse)

    0-3590 10

    Load Enroachment (68LE)

    Settings Range Step

    Enable NO

    YES+Z2

    YES+Z5

    Posit ive sequence threshold (V) 10.00-165.00 0.1

    Positive sequence threshold (A) (0.2-30) In 0.1

    Switch-Onto-Fault

  • 7/27/2019 Catalogo Familia PZ1000

    11/16

    PHASE AND NEUTRAL DIRECTIONAL ELE-MENTS (67)

    RECLOSER (79)Settings Range Step

    Reclose type selection Single pole, triple pole, sin-

    gle/triple pole, dependent

    Number of programmed shots 1-4 1

    Single pole 1st

    shot time (s) 0.1-20 0.1

    Triple pole 1st

    shot time (s) 0.1-20 0.1

    2nd

    shot time (s) 1-300 0.1

    3rd

    shot time (s) 1-300 0.1

    4th

    shot time (s) 1-300 0.1

    Sec. t. after single pole closing 1-300 0.1

    Sec. t. after triple pole closing 1-300 0.1

    Sec. t. after manual pole closing 1-100 0.1

    Synchronism time delay (s) 1-300 0.1

    CLOSURE PERMISSION AFTER TRIPSettings Range Step

    Zone 1 YES/NO

    Zone 2 YES/NO

    Zone 3 YES/NO

    Zone 4 YES/NO

    Phase inst. YES/NO

    Phase timed YES/NONeutral inst. YES/NO

    Neutral timed YES/NO

    Enable extension zone 1 YES/NO

    Ext. factor of zone 1 phase to phase fault 0.1-3 0.1

    Ext. factor of zone 1 phase to earth fault 0.1-3 0.1

    Inst . neutral locking after monopolar trip YES/NO

    1st timed neutral locking after monopolar trip YES/NO

    Inst. unbalance locking after monopolar trip YES/NO

    Timed unbalance locking after monopolar trip YES/NO

    Settings Range Step

    Timed enable NO, YES, YES + DropoutTimed pickup (0.2-4) In 0.1

    Response type Definite time

    Normal inverse IEC

    Very inverse IEC

    Extr. inverse IEC

    User IEC (mod.)

    Normal inverse ANSI

    Very inverse ANSI

    Extr. inverse ANSI

    User ANSI (mod.)

    Time index

    ANSI

    IEC-BSC

    0.5-30

    0.05-1.09

    0.1

    0.01

    Definite time 0-100 0.1Torque control YES/NO

    Instantaneous enable YES/NO

    Instantaneous pickup (0.2-30) In 0.1

    Instantaneous additional time 0-10 0.01

    Torque control YES/NO

    Negative/zero sequence angle 0-3590 10

    Directional lockout Vpol