    Which size Daikin air handler is best for your project?

    Physical Data - 003 through 012

    DataUnit Size

    003 004 006 008 010 012

    Airflow range, cfm900

    2500

    1200

    3100

    1700

    4600

    2200

    6000

    2900

    7700

    3600

    9700

    cfm @ 500ft/min through large face area coil 1550 1950 2850 3750 4800 6050

    Height width, inches 26 38 30 40 30 52 34 58 36 64 42 66

    Cooling coil face area, sq ft

    Extended/staggered large 3.9 4.8 6.6 8.5 10.7 13.5

    Large 3.1 3.9 5.7 7.5 9.6 12.1

    Extended/staggered medium 2.6 3.4 4.7 6.4 8.3 9.8

    Medium 2.1 2.8 4.1 5.6 7.4 8.8

    Small N/A 2.3 3.3 4.7 6.4 7.7

    Fan sectiondepth, inches

    Largest housed fan & motor avail. w/ top hor.

    dischg.32 32 36 40 40 46

    Largest inline fan and motor available N/A N/A N/A N/A N/A 44

    Largest belt drive plenum fan & motor available N/A N/A N/A N/A 34 42

    Largest direct drive plenum fan & motor available N/A N/A N/A 20 20 54

    Largest twin fan and motor available N/A N/A N/A 50 56 56

    Largest 1 3 fan array and motor available N/A N/A N/A N/A N/A N/A

    Largest 2 2 fan array and motor available N/A N/A N/A N/A N/A N/A

    Largest 2 3 fan array and motor available N/A N/A N/A N/A N/A N/A

    Mixing boxdepth, inches

    Mixing box only 20 20 20 20 22 24

    Mixing box with flat filter 24 24 24 24 26 28

    Mixing box with angular filter 42 42 42 42 44 46

    Economizerdepth, inches

    40 40 40 40 44 48

    Blenderdepth, inches

    Largest Kees 18 20 24 26 28 34

    http://www.mcquay.com/index.phphttp://www.mcquay.com/parts.phphttp://www.mcquay.com/news.phphttp://www.mcquay.com/about.phphttp://www.mcquay.com/index.phphttp://www.mcquay.com/products.phphttp://www.mcquay.com/parts.phphttp://www.mcquay.com/service.phphttp://www.mcquay.com/sales.phphttp://www.mcquay.com/news.phphttp://www.mcquay.com/solutions.phphttp://www.mcquay.com/about.phphttp://www.mcquay.com/contact-us.phphttp://www.mcquay.com/search.php
  • 8/10/2019 DAIKIN PAHU

    2/7

    10/9/2014 Daikin Applied | The industry leader in environmental solutions

    http://www.mcquay.com/air-handlers-custom.php

    Largest Blender Products IV 18 22 26 30 34 38

    Side load filter sectionsdepth, inches

    Flat 2" and 4" 12 12 12 12 12 12

    2" angular 32 30 30 30 30 30

    Cartridge (12" deep w/2" pre-filter) 22 22 22 22 22 22

    Bag (36" w/2" pre-filter) 42 42 42 42 42 42

    Front load filter sectionsdepth, inches

    Cartridge (12" deep w/2" pre-filter) 16 16 16 16 16 16

    Bag (36" w/2" pre-filter) 40 40 40 40 40 40

    Face and bypassdepth, inches

    Internal 12 12 12 12 12 12

    External 18 18 18 20 22 24

    Coil sectionsdepth, inches

    Heating only (2-row water) 12 12 12 12 12 12

    Cooling only (4-row water) 18 18 18 18 18 18

    Cooling only (6-row water) 24 24 24 24 24 24

    Cooling & reheat (12-row cooling & 1-row heating) 36 36 36 36 36 36

    Vertical cooling only (6-row water) 30 30 30 30 36 36

    Multizone coil sectiondepth, inches

    3-deck horizontal with dampers N/A N/A 40 42 42 52

    Access sectionsdepth, inches

    16" deep 16 16 16 16 16 16

    24" deep 24 24 24 24 24 24

    30" deep 30 30 30 30 30 30

    36" deep 36 36 36 36 36 36

    42" deep 42 42 42 42 42 42

    48" deep 48 48 48 48 48 48

    54" deep 54 54 54 54 54 54

    Diffuserdepth, inches

    With housed fan 10 10 10 12 12 16

    With inline fan N/A N/A N/A N/A N/A 18

    Attenuatordepth, inches

    Short 40 40 40 40 40 40

    Medium 52 52 52 52 52 52

    Long 64 64 64 64 64 64

    Supply or return plenumdepth, inches

    Top, bottom or end opening 14 16 16 18 20 22

    * Based on typical industry sizes. Vision air handling units are available in 2 inch increments of height and width to fit the exact space requirements.

    Front load filter sections include 24" upstream plenum section with tread plate for heavy duty floor liner.

    Physical Data - 014 through 035

    DataUnit Size

    014 017 021 025 030 035

    Airflow range, cfm4200

    11,200

    5000

    13,500

    6000

    16,000

    7300

    19,400

    8500

    22,500

    10,000

    26,500

    cfm @ 500 ft/min through large face area coil 7000 8400 10,050 12,150 14,150 16,700

    Height width, inches 42 74 46 80 46 80 60 86 60 98 66 102

    Cooling coil face area, sq ft

    Extended/staggered large 15.4 18.3 21.9 27.4 31.9 37.1

    Large 14.0 16.8 20.1 24.3 28.3 33.4

    Extended/staggered medium 11.2 13.7 17.2 21.3 24.8 29.7

    Medium 10.2 12.6 15.8 18.2 21.2 24.1

    Small 8.9 11.2 14.4 16.7 19.5 22.3

    Fan sectiondepth, inches

  • 8/10/2019 DAIKIN PAHU

    3/7

    10/9/2014 Daikin Applied | The industry leader in environmental solutions

    http://www.mcquay.com/air-handlers-custom.php

    Largest housed fan & motor avail. w/ top hor.

    dischg.

    46 50 52 58 58 58

    Largest inline fan and motor available 44 50 54 64 64 70

    Largest belt drive plenum fan & motor available 42 48 52 56 58 62

    Largest direct drive plenum fan & motor available 54 54 54 66 78 84

    Largest twin fan and motor available 58 58 66 66 74 82

    Largest 1 3 fan array and motor available N/A 40 40 40 40 46

    Largest 2 2 fan array and motor available N/A N/A 40 40 40 46

    Largest 2 3 fan array and motor available N/A N/A 40 40 40 46

    Mixing boxdepth, inches

    Mixing box only 24 26 30 32 32 36

    Mixing box with flat filter 28 30 34 36 36 40

    Mixing box with angular filter 46 48 52 54 54 58

    Economizerdepth, inches

    48 52 60 64 64 72

    Blenderdepth, inches

    Largest Kees 36 38 42 46 48 58

    Largest Blender Products IV 40 46 48 52 60 64

    Side load filter sectionsdepth, inches

    Flat 2" and 4" 12 12 12 12 12 122" angular 30 30 30 32 32 32

    Cartridge (12" deep w/2" pre-filter) 22 22 22 22 22 22

    Bag (36" w/2" pre-filter) 42 42 42 42 42 42

    Front load filter sectionsdepth, inches

    Cartridge (12" deep w/2" pre-filter) 16 16 16 16 16 16

    Bag (36" w/2" pre-filter) 40 40 40 40 40 40

    Face and bypassdepth, inches

    Internal 12 12 12 12 12 12

    External 24 26 30 32 32 34

    Coil sectionsdepth, inches

    Heating only (2-row water) 12 12 12 12 12 12

    Cooling only (4-row water) 18 18 18 18 18 18

    Cooling only (6-row water) 24 24 24 24 24 24

    Cooling & reheat (12-row cooling & 1-row heating) 36 36 36 36 36 36

    Vertical cooling only (6-row water) 36 36 42 48 48 54

    Multizone coil sectiondepth, inches

    3-deck horizontal with dampers 52 54 56 60 60 70

    Access sectionsdepth, inches

    16" deep 16 16 16 16 16 16

    24" deep 24 24 24 24 24 24

    30" deep 30 30 30 30 30 30

    36" deep 36 36 36 36 36 36

    42" deep 42 42 42 42 42 42

    48" deep 48 48 48 48 48 48

    54" deep 54 54 54 54 54 54

    Diffuserdepth, inches

    With housed fan 16 16 16 24 24 24

    With inline fan 18 18 22 26 26 28

    Attenuatordepth, inches

    Short 40 40 40 40 40 40

    Medium 52 52 52 52 52 52

    Long 64 64 64 64 64 64

  • 8/10/2019 DAIKIN PAHU

    4/7

    10/9/2014 Daikin Applied | The industry leader in environmental solutions

    http://www.mcquay.com/air-handlers-custom.php

    Supply or return plenumdepth, inches

    Top, bottom or end opening 22 24 28 30 30 32

    * Based on typical industry sizes. Vision air handling units are available in 2 inch increments of height and width to fit the exact space requirements.

    Front load filter sections include 24" upstream plenum section with tread plate for heavy duty floor liner.

    Physical Data - 040 through 090

    DataUnit Size

    040 050 065 080 085 090

    Airflow range, cfm11,500

    31,000

    15,000

    40,000

    20,000

    54,000

    21,500

    57,500

    23,100

    61,600

    24,600

    65,600

    cfm @ 500 ft/min through large face area coil 19,300 24,500 33,300 35,900 38,450 41,000

    Height width, inches 68 116 80 120 92 136 98 136 104 136 110 136

    Cooling coil face area, sq ft

    Extended/staggered large 42.9 58.0 76.9 82.0 87.1 92.2

    Large 38.6 49.0 66.6 24.3 28.3 33.4

    Extended/staggered medium 34.3 40.1 61.5 71.8 76.9 82.0

    Medium 30.0 35.7 51.2 51.2 56.4 61.5

    Small 27.9 31.2 46.1 46.1 51.2 56.4

    Fan sectiondepth, inches

    Largest housed fan & motor avail. w/ top hor.

    dischg.70 80 92 92 92 92

    Largest inline fan and motor available 70 90 96 96 96 96

    Largest belt drive plenum fan & motor available 62 70 82 82 82 82

    Largest direct drive plenum fan & motor available 86 86 86 N/A N/A N/A

    Largest twin fan and motor available 82 82 N/A N/A N/A N/A

    Largest 1 3 fan array and motor available 52 52 52 52 52 52

    Largest 2 2 fan array and motor available 52 52 58 62 64 64

    Largest 2 3 fan array and motor available 52 52 52 52 52 52

    Mixing boxdepth, inches

    Mixing box only 36 40 46 50 54 56

    Mixing box with flat filter 40 44 50 54 58 60

    Mixing box with angular filter 58 62 68 72 76 78

    Economizerdepth, inches

    72 80 92 100 108 112

    Blenderdepth, inches

    Largest Kees 58 68 76 80 84 84

    Largest Blender Products IV 70 74 88 88 92 92

    Side load filter sectionsdepth, inches

    Flat 2" and 4" 12 12 12 12 12 12

    2" angular 32 32 32 32 32 32

    Cartridge (12" deep w/2" pre-filter) 22 22 22 22 22 22

    Bag (36" w/2" pre-filter) 42 42 42 42 42 42

    Front load filter sectionsdepth, inches

    Cartridge (12" deep w/2" pre-filter) 16 16 16 16 16 16

    Bag (36" w/2" pre-filter) 40 40 40 40 40 40

    Face and bypassdepth, inches

    Internal 12 12 12 12 12 12

    External 38 44 50 54 56 58

    Coil sectionsdepth, inches

    Heating only (2-row water) 12 12 12 12 12 12

    Cooling only (4-row water) 18 18 18 18 18 18

    Cooling only (6-row water) 24 24 24 24 24 24

    Cooling & reheat (12-row cooling & 1-row heating) 36 36 36 36 36 36

    Vertical cooling only (6-row water) N/A N/A N/A N/A N/A N/A

  • 8/10/2019 DAIKIN PAHU

    5/7

    10/9/2014 Daikin Applied | The industry leader in environmental solutions

    http://www.mcquay.com/air-handlers-custom.php

    Multizone coil sectiondepth, inches

    3-deck horizontal with dampers 70 76 88 N/A N/A N/A

    Access sectionsdepth, inches

    16" deep 16 16 16 16 16 16

    24" deep 24 24 24 24 24 24

    30" deep 30 30 30 30 30 30

    36" deep 36 36 36 36 36 36

    42" deep 42 42 42 42 42 42

    48" deep 48 48 48 48 48 48

    54" deep 54 54 54 54 54 54

    Diffuserdepth, inches

    With housed fan 30 30 30 30 30 30

    With inline fan 30 36 38 38 38 38

    Attenuatordepth, inches

    Short 40 40 40 40 40 40

    Medium 52 52 52 52 52 52

    Long 64 64 64 64 64 64

    Supply or return plenumdepth, inches

    Top, bottom or end opening 32 38 42 48 52 54

    * Based on typical industry sizes. Vision air handling units are available in 2 inch increments of height and width to fit the exact space requirements.

    Front load filter sections include 24" upstream plenum section with tread plate for heavy duty floor liner.

    Physical Data - 107 through 169

    DataUnit Size

    107 124 141 160 169

    Airflow range, cfm29,000

    77,500

    33,600

    89,500

    40,300

    107,400

    45,600

    121,800

    48,400

    129,000

    cfm @ 500 ft/min through large face area coil 48,500 55,900 67,100 76,200 80,600

    Height width, inches 108 168 108 192 122 192 122 216 122 228

    Cooling coil face area, sq ft

    Extended/staggered large N/A N/A N/A N/A

    Large 96.88 111.9 134.25 152.25 161.25

    Extended/staggered medium N/A N/A N/A N/A

    Medium 77.5 89.5 96.96 109.96 116.46

    Small N/A N/A N/A N/A

    Fan sectiondepth, inches

    Largest housed fan & motor avail. w/ top hor. dischg. 92 92 92 92 92

    Largest belt drive plenum fan & motor available 88 88 88 88 88

    Largest direct drive plenum fan & motor available 94 94 94 94 94

    Largest 1 3 fan array and motor available 58 62 62 64 64

    Largest 2 2 fan array and motor available 64 64 64 64 64

    Largest 2 3 fan array and motor available 58 62 62 64 64

    Mixing boxdepth, inches

    Mixing box only 64 64 72 72 72

    Economizerdepth, inches

    118 118 136 136 136

    Blenderdepth, inches

    Largest Kees 68 72 80 84 84

    Largest Blender Products IV 78 86 92 92 92

    Side load filter sectionsdepth, inches

    Flat 2" and 4" 22/24 22/24 22/24 22/24 22/24

    Cartridge (12" deep w/2"/4" pre-filter) 22/24 22/24 22/24 22/24 22/24

    Bag (36" w/2"/4" pre-filter) 44/46 44/46 44/46 44/46 44/46

  • 8/10/2019 DAIKIN PAHU

    6/7

    10/9/2014 Daikin Applied | The industry leader in environmental solutions

    http://www.mcquay.com/air-handlers-custom.php

    Locate Sales, Partsand Service

    BIM (Revit) FilesDesign ToolsProducts

    ChillersAir HandlersWater Source Heat PumpsRooftop SystemsFan CoilsModular Central Plants

    Integrated SystemsCoilsSelf-Contained SystemsUnit VentilatorsCondensing UnitsControlsVAV Terminal UnitsVRV Daikin

    Seismic CertificationTraining

    Front load filter sectionsdepth, inches

    Cartridge (12" deep w/2" pre-filter) 20/20 20/20 20/20 20/20 20/20

    Bag (36" w/2" pre-filter) 44/44 44/44 44/44 44/44 44/44

    Face and bypassdepth, inches

    Internal 12 12 12 12 12

    External 58 58 64 64 64

    Coil sectionsdepth, inches

    Heating only (2-row water) 12 12 12 12 12

    Cooling only (4-row water) 18 18 18 18 18

    Cooling only (6-row water) 18 18 18 18 18

    Cooling & reheat (12-row cooling & 1-row heating) 24 24 24 24 24

    Access sectionsdepth, inches

    16" deep 16 16 16 16 16

    24" deep 24 24 24 24 24

    30" deep 30 30 30 30 30

    36" deep 36 36 36 36 36

    42" deep 42 42 42 42 42

    48" deep 48 48 48 48 48

    54" deep 54 54 54 54 54

    Diffuserdepth, inches

    With housed fan 42 46 46 46 46

    Attenuatordepth, inches

    Short 40 40 40 40 40

    Medium 52 52 52 52 52

    Long 64 64 64 64 64

    Supply or return plenumdepth, inches

    Top, bottom or end opening 36 52 60 60 60

    * Based on typical industry sizes. Vision air handling units are available in 2 inch increments of height and width to fit the exact space requirements.

    Front load filter sections include 24" upstream plenum section with tread plate for heavy duty floor liner.

    http://www.mcquay.com/roadshow.phphttp://www.mcquay.com/training.phphttp://www.mcquay.com/seismic-certification.phphttp://www.daikinac.com/content/commercialhttp://www.mcquay.com/vav-terminal-units.phphttp://www.mcquay.com/controls.phphttp://www.mcquay.com/condensing-units-landing.phphttp://www.mcquay.com/unit-ventilators.phphttp://www.mcquay.com/self-contained-systems.phphttp://www.mcquay.com/coils.phphttp://www.mcquay.com/integrated-systems.phphttp://www.mcquay.com/modular-central-plant.phphttp://www.mcquay.com/fan-coils.phphttp://www.mcquay.com/rooftop-systems.phphttp://www.mcquay.com/water-source-heat-pumps.phphttp://www.mcquay.com/air-handlers.phphttp://www.mcquay.com/chillers.phphttp://www.mcquay.com/products.phphttp://www.mcquay.com/design-tools.phphttp://www.mcquay.com/bim-files.phphttp://www.mcquay.com/sales.php
  • 8/10/2019 DAIKIN PAHU

    7/7

    10/9/2014 Daikin Applied | The industry leader in environmental solutions

    http://www.mcquay.com/air-handlers-custom.php

    Contact

    Daikin Applied13600 Industrial Park BlvdMinneapolis, MN 55441800-432-1342 (Toll Free)763-553-5330 (Direct)Contact Us>

    Our Locations

    North AmericaLatin AmericaJapanChinaEurope, Middle East & Africa

    News

    See all news>

    Employment

    Employment Search>

    Search

    SearchDaikin Applied

    Subscribe

    Subscribeto Daikin newsletters, BIM file updates and more.

    Legal

    Sitemap

    Terms and Conditions

    2014 Daikin Applied

    http://www.mcquay.com/terms.phphttp://www.mcquay.com/site-map.phphttp://www.mcquay.com/subscribe.phphttp://www.mcquay.com/search.phphttp://www.mcquay.com/employment.phphttp://www.mcquay.com/news.phphttp://www.daikinapplied.eu/http://www.mcquay.com.cn/http://www.daikin.com/http://www.daikinlatam.com/http://www.daikinmcquay.com/http://www.mcquay.com/contact-us.php