  • #GridAsia

    Communication Issues in Distribution Automation the CESC experience

    Debasis GuptaDCE (Distribution Automation)

    CESC Limited, [email protected]

    www.cesc.co.in

    GridWeek Asia 2012

  • #GridAsia Mumbai, India Jan 16-18, 2012 2

    CESC Limited - Powering Kolkata since 1899

    Year ending 31.3.11

    Units Sold: 8135 MU (HT 36%, LT 64%)System Met: 1657 MWT&D Losses : 13 %Energy Generated = 7995 MUEnergy Imported = 1485 MUEnergy Exported = 110 MU

    HT Consumers: 1763LT Consumers: 2.48 Million

    Licensed Area: 567 Sq Kms

    Installed Generation Capacity: 1225 MW

    India's first fully integrated electrical utility, generating and distributing electrical power in Kolkata and Howrah since 1899.

    GridWeek Asia 2012

  • #GridAsia Mumbai, India Jan 16-18, 2012 3

    6 kV

    11 kV

    33 kV

    132 kV

    220 kV

    Substations19 Nos

    Distribution Stations100 Nos

    DTs7000+

    5 ImportPoints

    4 CESC Gen StnsInstalled Capacity= 1225 MW

    400 /230 VMV / LV

    Transmission SCADA Distribution SCADA/DMS system

    RMUAutomation

    AMR DTs

    AMR High end Tariff Meters & Street Lights

    RMUs3500+

    Distribution Automation Activities in CESC

    Communications: WirelineFibre Optic Transmission System

    Communications: WirelessGPRS/ CDMA

    Excellent communications- SDH STM4- Gigabit Ethernet- CESC owns 500 Kms of OF lines

    POOR throughputOK for AMR applicationsNOT yet suitable for Feeder Automation

    GridWeek Asia 2012

  • #GridAsia Mumbai, India Jan 16-18, 2012 4

    Working well SCADA Systems on Fibre Optic Communications

    Transmission SCADA MCC Distribution SCADA/DMS MCC RTU & MDF at a Distribution Station

    PDH / SDH (STM4) Panels PDH / SDH NMS Data Centre with Gigabit Ethernet

    Mostly from Siemens, Sinaut-Spectrum, AK1703 & TM 1703 RTUs IEC 870-5-101 & IEC-870-5-104 protocols Tight response times on Fibre Optic Transmission Systems

    CESCs own OF cables ~ 500 Kms including OPGW SDH/PDH from ABB At 35 Nodes - Fox 515, Fox 515T Gigabit Ethernet At 100 Nodes - CISCO products

    GridWeek Asia 2012

  • #GridAsia Mumbai, India Jan 16-18, 2012 5

    Working reasonably well AMR systems on GSM/ GPRS

    Mostly from Secure Meters & Genus Majority on GPRS, some on GSM

    More than 8000 meters read at present GPRS throughputs better than GSM, but re-runs required at times

    Communicable Meters being tested Tariff Meter at HT Consumer premises Meter Reading Setup for GSM Modems

    Street Lighting AMR/ Controller Meter Reading Setup for GPRS ModemsAMR at DTs

    GPRS

    GridWeek Asia 2012

  • #GridAsia Mumbai, India Jan 16-18, 2012 6

    Problem Area RMU (Feeder) Automation on GPRS/ CDMA

    ABB Areva Schneider

    Over 3500 Nos 11 kV & 6 kV RMUs commissioned in CESC network over the last 3 years.

    Installation of RMUs has reduced restoration time on HT faults to < 1 hour:3-way and 4-way Ring Main UnitsIsolators not CBs in legs: load-break, fault-makeFault Passage Indicators (FPIs) fitted on all legsRestoration time of 11 kV & 6 kV Feeders already reduced from 4 hours to less than 1 hour by installing & manually operating the RMUs

    Automation will further reduce restoration time to 15 minutes:Status of FPIs to be transmitted to SCADA/ DMSRetro-fitting of Motors to remotely operate Isolators through SCADA/ DMS. 24V DC Motors used.IEC-870-5-104 protocol

    Issues:In CESC, all RMUs installed outdoorson roadsidesPoor, unreliable cellular data communications

    GridWeek Asia 2012

  • #GridAsia Mumbai, India Jan 16-18, 2012 7

    HMIClient Initiated VPN: Preferred SIMs can be from any service

    provider Security/ Encryption in our control Dynamic IPs M2M technology used

    through Internet

    Service Provider Initiated VPN

    HMI

    SIMs must be from any ONE service provider

    Security/ Encryption in Service Providers control

    Static IPs no Internet needed

    We have commissioned pilot projects using both options Facing major communications issues with poor throughputs

    VPN

    VPN

    LL

    IEC 104

    Static IP

    FRTUModem

    RMU

    RMUStatic IP

    RMU

    Static IP

    HMI

    CDMA/ GPRS

    VPN

    M2M Server

    Public Static IP

    VPN

    VPNVPN

    IEC 104

    LL

    Dynamic IP

    VPN

    RMU

    FRTUModem

    RMU

    Dynamic IP

    RMU

    Dynamic IP

    Problem Area RMU (Feeder) Automation on GPRS/ CDMA

    GridWeek Asia 2012

  • #GridAsia Mumbai, India Jan 16-18, 2012 8

    Problem Area RMU (Feeder) Automation on GPRS/ CDMA

    Equipment INTERNALLY mounted Equipment EXTERNALLY mounted

    SchematicDiagramIssues:

    Internally mounted arrangement impracticalPoor, unreliable cellular data communications using IEC-870-5-104 protocol

    GridWeek Asia 2012

  • #GridAsia Mumbai, India Jan 16-18, 2012 9

    Problem Area RMU (Feeder) Automation on GPRS/ CDMA

    Sample throughputs shown

    Continuous efforts by all our partners to fine-tune system/ communication network

    Dis-satisfied end users: we have put large-scale deployment on hold till more reliable solutions are available

    Path forward ?

    GridWeek Asia 2012

  • #GridAsia Mumbai, India Jan 16-18, 2012 10

    Problem Area RMU (Feeder) Automation on GPRS/ CDMA

    We are automating RMU clusters where possible on Fibre Optic cables.

    This will be possible only in limited locations.

    RMU cluster at Writers Building area communication using Fibre Optics