f.t. Electroandes

Embed Size (px)

DESCRIPTION

ELECTROANDES

Citation preview

C.H. OROYAELECTROANDESFICHA TCNICACENTRALC.H. OROYAGRUPOG-1G-2G-31.- DISPONIBILIDADPOTENCIA EFECTIVAMW3.142.762.94POTENCIA NOMINALMW333POTENCIA NOMINALMVA3.753.753.75POTENCIA MXIMAMW3.142.762.94POTENCIA MNIMAMW0.370.370.372.- TIEMPOSVELOCIDAD TOMA DE CARGAMW/min.2.52.52.5VELOCIDAD DE DESCARGAMW/min.2.52.52.5TIEMPO SINCRONIZACINmin.666TIEMPO MXIMO OPERACIN A MN. CARGAHrs.5553.- TENSINTENSIN MNIMA GENERACINKV.2.252.252.25TENSIN MXIMA GENERACINKV.2.452.452.45TENSIN MN. DE EXCITACIN VDCV.150150150TENSIN MX. DE EXCITACIN VDCV.3503503504.- CAPACIDAD GENERACIN REACTIVACAPACITIVAen mnimo tcnicoMVAR0.50.50.5al 50 %MVAR0.50.50.5al 100 %MVAR0.50.50.5INDUCTIVAen mnimo tcnicoMVAR0.20.20.2al 50 %MVAR1.81.81.8al 100 %MVAR1.81.81.85.- RESTRICCIONESCARGA MNIMAMW0.370.370.37TIEMPO DE CARGA MNIMAHrs.5556.- CAUDALCAUDAL MNIM0 TURBINABLEm3/seg.0.250.250.25CAUDAL MXIMO TURBINABLEm3/seg.2.1351.8771.9997.- ESTATISMOVALOR ACTUAL%555RANGO DE VARIACIN%8.- CONCENTRACIN MXIMA DE SLIDOS PERMISIBLESgr/l.9.- RENDIMIENTOMW/m3/seg1.4711.4701.47110.- CURVA DE CAPABILIDADCURVA DE CAPACIDAD DE LA C.H. OROYA11- ARRANQUE EN BLACK START (SI / NO)SISISIPOTENCIA EFECTIVA DE LA CENTRALMW9.48RENDIMIENTO DE LA CENTRALMW/m3/seg1.4706SERVICIOS AUXILIARESMW0.091EL G3 DE LA C.H. OROYA FUE RETIRADO DE LA OPERACIN COMERCIAL EL 23.06.04 Y HA SIDO REEMPLAZADO POR EL G4 DE LA C.H. PACHACHACA

CURVA DE CAPACIDAD DE LA C.H. OROYA

C.H. PACHACHACAELECTROANDESFICHA TCNICACENTRALC.H. PACHACHACAGRUPOG-1G-2G-3G-4G-41.- DISPONIBILIDADRETIRADO DE LA OPERACIN COMERCIAL EL 01.08.04TRASLADADO A LA C.H. OROYAPOTENCIA EFECTIVAMW3.113.13.132.94POTENCIA NOMINALMW3333POTENCIA NOMINALMVA3.753.753.753.75POTENCIA MXIMAMW3.113.13.132.94POTENCIA MNIMAMW0.370.370.370.372.- TIEMPOSVELOCIDAD TOMA DE CARGAMW/min.2.52.52.52.5VELOCIDAD DE DESCARGAMW/min.2.52.52.52.5TIEMPO SINCRONIZACINmin.6666TIEMPO MXIMO OPERACIN A MN. CARGAHrs.55553.- TENSINTENSIN MNIMA GENERACINKV.2.252.252.252.25TENSIN MXIMA GENERACINKV.2.452.452.452.45TENSIN MN. DE EXCITACIN VDCV.150150150150TENSIN MX. DE EXCITACIN VDCV.3503503503504.- CAPACIDAD GENERACIN REACTIVACAPACITIVAen mnimo tcnicoMVAR0.50.50.5al 50 %MVAR1.80.50.50.5al 100 %MVAR1.80.50.50.5INDUCTIVAen mnimo tcnicoMVAR0.20.20.20.2al 50 %MVAR1.81.81.81.8al 100 %MVAR1.81.81.81.85.- RESTRICCIONESCARGA MNIMAMW0.370.370.370.37TIEMPO DE CARGA MNIMAHrs.55556.- CAUDALCAUDAL MNIM0 TURBINABLEm3/seg.0.250.250.250.25CAUDAL MXIMO TURBINABLEm3/seg.2.1152.1082.1281.9997.- ESTATISMOVALOR ACTUAL%5555RANGO DE VARIACIN%8.- CONCENTRACIN MXIMA DE SLIDOS PERMISIBLESgr/l.9.- RENDIMIENTOMW/m3/seg1.4701.4711.4711.47110.-CURVA DE CAPABILIDADCURVA DE CAPACIDAD DE LA C.H. PACHACHACA11- ARRANQUE EN BLACK START (SI / NO)SISISISIPOTENCIA EFECTIVA DE LA CENTRALMW9.65RENDIMIENTO DE LA CENTRALMW/m3/seg1.4706SERVICIOS AUXILIARESMW0.08612/12/0512/7/02EL G4 DE LA C.H. PACHACHACA HA SIDO TRALADADO A LA C.H. OROYA NUEVA PARA REEMPLAZAR AL G3

C.H. MALPASOELECTROANDESFICHA TCNICACENTRALC.H. MALPASOGRUPOG-1G-2G-3G-41.- DISPONIBILIDADPOTENCIA EFECTIVAMW12.0812.7811.2311.9312.0812.7811.2311.93POTENCIA NOMINALMW13.613.613.613.61111POTENCIA NOMINALMVA1717171712121212POTENCIA MXIMAMW12.0812.7811.2311.93POTENCIA MNIMAMW11111.478 / 17.8611.478 / 18.8961.478 / 16.6041.478 / 17.6392.- TIEMPOS0.6760.6760.6760.676VELOCIDAD TOMA DE CARGAMW/min.10101010VELOCIDAD DE DESCARGAMW/min.10101010TIEMPO SINCRONIZACINmin.5555TIEMPO MXIMO OPERACIN A MN. CARGAHrs.121212123.- TENSINTENSIN MNIMA GENERACINKV.6.66.66.66.6TENSIN MXIMA GENERACINKV.7777TENSIN MN. DE EXCITACIN VDCV.100100100100TENSIN MX. DE EXCITACIN VDCV.1401401401404.- CAPACIDAD GENERACIN REACTIVACAPACITIVAen mnimo tcnicoMVAR2222al 50 %MVAR2222al 100 %MVAR2222INDUCTIVAen mnimo tcnicoMVAR1111al 50 %MVAR10.210.210.210.2al 100 %MVAR10.210.210.210.25.- RESTRICCIONESCARGA MNIMAMW1111TIEMPO DE CARGA MNIMAHrs.121212126.- CAUDALCAUDAL MNIM0 TURBINABLEm3/seg.1.4791.4791.4791.479CAUDAL MXIMO TURBINABLEm3/seg.17.86118.89616.60417.6397.- ESTATISMOVALOR ACTUAL%3333RANGO DE VARIACIN%8.- CONCENTRACIN MXIMA DE SLIDOS PERMISIBLESgr/l.9.- RENDIMIENTOMW/m3/seg0.6760.6760.6760.67610.- CURVA DE CAPABILIDADCURVA DE CAPABILIDAD C.H. MALPASO11- ARRANQUE EN BLACK START (SI / NO)SISISISIPOTENCIA EFECTIVA DE LA CENTRALMW48.021RENDIMIENTO DE LA CENTRALMW/m3/seg0.6763SERVICIOS AUXILIARESMW0.0577/20/02

CURVA DE CAPABILIDAD C.H. MALPASO

C.H. YAUPIELECTROANDESFICHA TCNICACENTRALC.H. YAUPIGRUPOG-1G-2G-3G-4G-51.- DISPONIBILIDADPOTENCIA EFECTIVAMW21.89221.55122.11422.22522.426POTENCIA NOMINALMW21.621.621.621.621.6POTENCIA NOMINALMVA2424242424POTENCIA MXIMAMW20.9920.7621.2121.0820.88POTENCIA MNIMAMW1.51.51.51.51.52.- TIEMPOSVELOCIDAD TOMA DE CARGAMW/min.2020202020VELOCIDAD DE DESCARGAMW/min.2020202020TIEMPO SINCRONIZACINmin.55555TIEMPO MXIMO OPERACIN A MN. CARGAHrs.555553.- TENSINTENSIN MNIMA GENERACINKV.13.113.113.113.313.3TENSIN MXIMA GENERACINKV.1414141414TENSIN NOMINAL GENERACINKV.13.813.813.813.813.8TENSIN MN. DE EXCITACIN VDCV.120120120130130TENSIN MX. DE EXCITACIN VDCV.2502502502502504.- CAPACIDAD GENERACIN REACTIVACAPACITIVAen mnimo tcnicoMVARal 50 %MVARal 100 %MVARINDUCTIVAen mnimo tcnicoMVAR33333al 50 %MVAR10.4610.4610.4610.4610.46al 100 %MVAR10.4610.4610.4610.4610.465.- RESTRICCIONESCARGA MNIMAMW1.51.51.51.51.5TIEMPO DE CARGA MNIMAHrs.555556.- CAUDALCAUDAL MNIM0 TURBINABLEm3/seg.0.470.470.470.470.47CAUDAL MXIMO TURBINABLEm3/seg.4.954.954.954.954.957.- ESTATISMOVALOR ACTUAL%55555RANGO DE VARIACIN%8.- CONCENTRACIN MXIMA DE SLIDOS PERMISIBLESgr/l.9.- RENDIMIENTOMW/m3/seg4.2404.1944.2854.2594.21810.-CURVA DE CAPABILIDADCURVA DE CAPACIDAD DE LA C.H. YAUPI11- ARRANQUE EN BLACK START (SI / NO)SISISISISIPOTENCIA EFECTIVA DE LA CENTRALMW110.207RENDIMIENTO DE LA CENTRALMW/m3/seg4.2372SERVICIOS AUXILIARESMW0.17712/7/02

CURVA DE CAPACIDAD DE LA C.H. YAUPI

Retiro de Unidades

Sheet1