8
Tehničko veleučilište u Zagrebu GSK - Industrijsko kabliranje Goran Belamarić, 2012 1 Predavač: Goran Belamarić email: [email protected] Generički sustavi kabliranja Industrijsko kabliranje TVZ 2009 - Goran Belamarić: Industrijske RM dio 2-4 Str.2 Dva područja – uredsko i industrijsko kabliranje Uredski (komercijalni) prostori – Generičko kabliranje uglavnom pokriva uredske prostorije i opće prostore Industrijski prostori (Industrial Premises) Industrijsko kabliranje uglavnom pokriva područja u i između otoka automacije (automation islands) Postoje poveznice i prekrivanja područja Office Premises Industrial Premises ISO/IEC 11801 ISO/IEC 24702 ISO/IEC 14763-2 Automation Specific Cabling Between and in Automation Islands IEC 61158 Series and IEC 61784-1,2 IEC 61918 (common requirements) IEC 61784-5-X Installation profiles (Selections + Add / Replace / Modifications) Generic Cabling Between and in Automation Islands Areas of Coverage Design Planning and Installation ODVA EtherNet/IP TM DeviceNet TM , EtherNet/IP TM and ControlNet TM TIA 1005 TIA 568 series

GSK Predavanje Industrijsko Kabliranje

Embed Size (px)

DESCRIPTION

Industrijsko kabliranje GSk

Citation preview

  • Tehniko veleuilite u Zagrebu GSK - Industrijsko kabliranje

    Goran Belamari, 2012 1

    Predava:Goran Belamari

    email: [email protected]

    Generiki sustavi kabliranja

    Industrijsko kabliranje

    TVZ 2009 - Goran Belamari: Industrijske RM dio 2-4 Str.2

    Dva podruja uredsko i industrijsko kabliranje

    Uredski (komercijalni)prostori Generiko kabliranje

    uglavnom pokriva uredske prostorije i ope prostore

    Industrijski prostori(Industrial Premises) Industrijsko kabliranje

    uglavnom pokriva podruja u i izmeu otoka automacije (automation islands)

    Postoje poveznice i prekrivanja podruja

    Office Premises

    Industrial Premises

    ISO/IEC 11801

    ISO/IEC 24702

    ISO/IEC14763-2

    Automation Specific Cabling Between and in

    Automation Islands

    IEC 61158Series and IEC

    61784-1,2

    IEC 61918(common requirements)

    IEC 61784-5-XInstallation profiles (Selections + Add /

    Replace /Modifications)

    Generic Cabling

    Between and in Automation

    Islands

    Areas of Coverage Design Planning and Installation

    ODVAEtherNet/IPTM DeviceNetTM, EtherNet/IPTM

    and ControlNetTM

    TIA 1005

    TIA 568series

  • Tehniko veleuilite u Zagrebu GSK - Industrijsko kabliranje

    Goran Belamari, 2012 2

    TVZ 2009 - Goran Belamari: Industrijske RM dio 2-4 Str.3

    Povezivanje uredske i industrijske mree

    TVZ 2009 - Goran Belamari: Industrijske RM dio 2-4 Str.4

    Fazu dizajna ind. kabliranja pokriva 5 normi

    Meunarodne norme ISO 11801 ISO/IEC 24702 IEC 61158 and IEC 61784-1,2

    Europa EN 50173-1 i 50173-2 EN 50173-3 EN 50310 EN 50174

    "Amerike" norme TIA 568B, TIA 569 & TIA 606,

    TIA 607a TIA 1005

    Office Premises

    Industrial Premises

    ISO/IEC 11801

    ISO/IEC 24702

    ISO/IEC14763-2

    Automation Specific Cabling Between and in

    Automation Islands

    IEC 61158Series and IEC

    61784-1,2

    IEC 61918(common requirements)

    IEC 61784-5-XInstallation profiles (Selections + Add /

    Replace /Modifications)

    Generic Cabling

    Between and in Automation

    Islands

    Areas of Coverage Design Planning and Installation

    ODVAEtherNet/IPTM DeviceNetTM, EtherNet/IPTM

    and ControlNetTM

    TIA 1005

    TIA 568series

    IEC 61158Series and IEC

    61784-1,2

  • Tehniko veleuilite u Zagrebu GSK - Industrijsko kabliranje

    Goran Belamari, 2012 3

    TVZ 2009 - Goran Belamari: Industrijske RM dio 2-4 Str.5

    Odnos ISO/IEC i EN normi kabliranja

    Europske norme Meunarodne Podruje primjene

    EN 50173-1 ISO/IEC 11801 Ope smjernice

    EN 50173-2 ISO/IEC 11801 Uredske zgrade

    EN 50173-3 ISO/IEC 24702 Industrija

    EN 50173-4 ISO/IEC 15018 Stanovi i kue

    EN 50173-5 ISO/IEC 24764 Raunalski centri

    EN 50310:2006 IEC 60364-5-548 EM utjecaji i zatita

    EN 50346 IEC61935-1 Testiranje izvedenog kabliranja

    TVZ 2009 - Goran Belamari: Industrijske RM dio 2-4 Str.6

    MICE tablica utjecaji okolia

    ISO/IEC 11801 / EN 50173-1

    Heavy Industrial Light Industrial

  • Tehniko veleuilite u Zagrebu GSK - Industrijsko kabliranje

    Goran Belamari, 2012 4

    TVZ 2009 - Goran Belamari: Industrijske RM dio 2-4 Str.7

    MICE parametri se razlikuju u pojedinim dijelovima sustava

    TVZ 2009 - Goran Belamari: Industrijske RM dio 2-4 Str.8

    Struktura generikog kabliranjaIEC 24702 / EN 50173-3

    IEC 61918IEC/ISO 24702

  • Tehniko veleuilite u Zagrebu GSK - Industrijsko kabliranje

    Goran Belamari, 2012 5

    TVZ 2009 - Goran Belamari: Industrijske RM dio 2-4 Str.9

    Tipina industrijska topologija

    TVZ 2009 - Goran Belamari: Industrijske RM dio 2-4 Str.10

    Tipina industrijska topologija - primjeri

  • Tehniko veleuilite u Zagrebu GSK - Industrijsko kabliranje

    Goran Belamari, 2012 6

    TVZ 2009 - Goran Belamari: Industrijske RM dio 2-4 Str.11

    Bus topologija spojena na generiko kabliranje

    TVZ 2009 - Goran Belamari: Industrijske RM dio 2-4 Str.12

    Bakreno kabliranje metode oklapanja

  • Tehniko veleuilite u Zagrebu GSK - Industrijsko kabliranje

    Goran Belamari, 2012 7

    TVZ 2009 - Goran Belamari: Industrijske RM dio 2-4 Str.13

    Pouzdanost Uzroci ispada mree

    Oko 75% svih kvarova u mrei uzrokovano je neodgovarajuim komponentama, nekvalitetnom instalacijom i nepravilnim rukovanjem osoblja

    Hardware, System

    Pogreno rukovanjeSoftverske pogrekeVirusi

    Pogonski uvjeti

    TVZ 2009 - Goran Belamari: Industrijske RM dio 2-4 Str.14

    Poveani utjecaj okolia MICE:Vibracija M2, M3

    IDC meuspoj oteenje kontakata

    raskrimpano

    deformirano

  • Tehniko veleuilite u Zagrebu GSK - Industrijsko kabliranje

    Goran Belamari, 2012 8

    TVZ 2009 - Goran Belamari: Industrijske RM dio 2-4 Str.15

    Poveani utjecaj MICE:IP-zatita I2, I3

    IP67 utika

    IP54 zatita

    IP54razdjelnik

    TVZ 2009 - Goran Belamari: Industrijske RM dio 2-4 Str.16

    Poveani utjecaj MICE:EM utjecaj E2, E3

    Optika tehnologija

    S/FTP Kabel

    oklopljene RJ-Komponente