H3I ENVA ZTE Rectifier Integration Guide for Huawei Cabinet
INTERNAL
Product Name Security Level
WCDMA NodeB INTERNAL
Product Version Total 7 pages
All Version NodeB
H3I ENVA ZTE Rectifier Integration Guide for Huawei Cabinet
Huawei Technologies Co., Ltd.
2013-08-1 HUAWEI Confidential Page 1 of 7
H3I ENVA ZTE Rectifier Integration Guide for Huawei Cabinet INTERNAL
Contents
1. Physical configuration PMU ZTE rectifier.............3
2. Physical connection PMU ZTE to USLP.................4
3. Physical connection USLP ke UEIU.......................4
4. Configuration at PMU ZTE...................................5
5. Huawei BTS/ NodeB configuration ......................6
6. Testing and Alarm Handling................................7
2014-11-10 HUAWEI Confidential Page 2 of 7
H3I ENVA ZTE Rectifier Integration Guide for Huawei Cabinet INTERNAL
1. Physical Configuration in PMU ZTE rectifierCheck condition port in ZTE rectifier, for connection using X17, X18, and X19 as picture below use multimeter, select buzzer in multimeter to check condition on port,
2014-11-10 HUAWEI Confidential Page 3 of 7
H3I ENVA ZTE Rectifier Integration Guide for Huawei Cabinet INTERNAL
2. Physical connection PMU ZTE to USLP:
Physical connection on USLP:
3. Physical connection USLP ke UPEU:Connect LAN cable from USLP to UEIU board ,
UPEUEXT ALM0 To
USLPOUT0
EXT ALM1 To OUT1
2014-11-10 HUAWEI Confidential Page 4 of 7
X17
Port 6
ZTE Rect
X19
Port 5
Main failure
X18
Port 7
ZTE DC Low Vlt
H3I ENVA ZTE Rectifier Integration Guide for Huawei Cabinet INTERNAL
4. Configuration at PMU ZTE:Setting PMU configuration on PMU ZTE Rectifier,
Go to the MENU as below table, use pass 0000
2014-11-10 HUAWEI Confidential Page 5 of 7
H3I ENVA ZTE Rectifier Integration Guide for Huawei Cabinet INTERNAL
Setting parameter as table below (highlight yelow)
No. Setting Output Relay Relay marking1 AC AuxSwitch Off A42 AC-in Switch Off A43 AC power Off A44 Arrester-C Break A45 Arrester-D Break A49 SMR.n Alarm A2
10 DC Under Vol A312 DC Loop.n Break A313 Bat.n Fuse Break A314 Bat.n Under Vol A315 Ennv. alrm A5
5. Huawei BTS/NodeB configuration:
2014-11-10 HUAWEI Confidential Page 6 of 7
H3I ENVA ZTE Rectifier Integration Guide for Huawei Cabinet INTERNAL
Setting MML command in BTS/NodeB, and check to loop and unloop for alarm in NodeB
SET ENVALMPARA:ALMID=65046,ANM="ZTE Rectifier Main Failure",ALVL=CRITICAL,ASS=POWER;
SET ENVALMPARA:ALMID=65048,ANM="ZTE Rectifier Module Failure",ALVL=CRITICAL,ASS=POWER;
SET ENVALMPARA:ALMID=65049,ANM="ZTE Rectifier DC Low Voltage",ALVL=CRITICAL,ASS=POWER;
SET ALMPORT:CN=0,SRN=0,SN=18,PN=0,SW=ON,AID=65046,PT=BOOL,AVOL=LOW;
SET ALMPORT:CN=0,SRN=0,SN=18,PN=1,SW=ON,AID=65048,PT=BOOL,AVOL=LOW;
SET ALMPORT:CN=0,SRN=0,SN=18,PN=2,SW=ON,AID=65049,PT=BOOL,AVOL=LOW;
6. Testing and Handling:Since physical connection already connected and BTS/NodeB configuration done, check the alarm function
No. Alarm Handling Alarm Testing
1 ZTE Rectifier Main Failure
Switch Off AC power rectifier (PLN down)
2 ZTE Rectifier Module Failure
Unplug one Modeule rectifier (Unplug SMR Module)
3 ZTE Rectifier DC Low Voltage
Switch Off AC power rectifier (PLN down) and Swich off 1
battery breaker
2014-11-10 HUAWEI Confidential Page 7 of 7