EMC-tested DIN EN ISO 9001 Interference suppression Class B Hyamat VP with Movitec Illustration shows variant without acoustic cladding Hyamat   V P Type Series Booklet 1953.52-10 Pressure Boosting Units/Fire-fighting Systems with Continuously Variable Speed Adjustment Using Frequency Inverters for each Pump to DIN 1988 Fields of Application Residential buildings Department stores Hospitals Industry Office buildings and other applications Hotels Fluid Handled Drinkin g water, utility water, fire-fighting water, cooling water, wher e there is no chemical and mechanical corrosive action on the system materials. Operating Data Capaci ty Q up to 200 m 3  /h , 55 l/ s with max. 4 pumps *) Dischar ge head H up to 130 m Temperature of fluid handl ed up t o 70 o C  up to 25 o C to DIN 1988 (DVGW)  Ambi en t te mp er at ur e up t o 40 o C System discharge pressure p d  up to 16 bar Inlet pressure p inlet  up to 10 bar Suppl y vol tage 3/N/PE, AC 400 V , 50 Hz 5-wire system < 2.2 kW  *) with stand-by pump as peak lo ad pump Materials Pumps Suct ion/ dischar ge ca si ng st ainless steel Hydraulic s ystem stainless s teel Mechanical seal to EN 12756 Spring-loaded r ing silicon carbide Seat ring hard carbon Elastomer EPDM Hydraulic Design: Distributor pipe stainless steel Valves copper-base alloy/brass, DVGW-approved  Accumulator connection made of stainless steel Membrane approved for drinking water to DIN 4807-5 Drive Electric motor 50 Hz, 2-pole, special KSB model, for three-phase mains. Standard IEC motors can only be used after consultation with KSB. Design Fully automatic pressure boosting package unit, with 2 to 4 vertical high-pressure pumps, with continuously variable speed adjustment of each pump for fully electronic control to ensure the required supply pressure, with standard volt-free contact for lack of water indication, general fault indication or reporting of system’s availability as well as live-zero monitoring of the connected sensors. Design and function as per DIN 1988, Part 5.  Hyamat VP System Equipment (Standard) - 2- 4 vertical high -pre ssure cen trifu gal pumps (sta ndard pu mps) Movitec 2, 4 und 10 with oval flange/ Movitec 18 und 32 with round flange - Hydra ulic comp onent s made of st ainless s teel - 1 check valve and shut-off e lement f or each p ump to D IN / DVGW - Membrane-type a ccumulator on t he discharge s ide as c ontrol tan k (direct flow) to DIN 4807-5, approved for drinking water - Pressu re trans mitter on the disc harge pre ssure side - Pressure indi cation v ia press ure ga uge - Steel basepl ate powder- coate d/epo xy resin-coa ted - Pump siz es 2, 4 and 10 are fi xed to th e basep late on anti-vibration mounts - Pump sizes 18 and 32 ar e supplie d with level -adj ustab le feet and anti-vibration pads (supplied, but not fitted) - Contr ol cabinet IP 54, EMC int erfer ence suppr ession class B - Pressu re transmitter on the inlet pressu re side (dry-r unnin g protection and energy-optimized cut-out of PBU ) - CE cer ti fi cate Control cabinet equipment (Standard) - Manua l-0-a utomatic selector switch - PLC - LEDs indic ating ope ration al availabi lity and fault of the syst em - Frequ ency inv erter for ea ch pump - Motor prote ction switch or safety cut-out for each pump - Master switch, lockable (rep air swit ch) - T ermin als with identifi cation for all connec tions - Circuit diagram acc. to VDE, settings for freque ncy inverter (FI) and parts list for electrical parts - Emerg ency OFF connection For supplementary equipment and special designs see pages 16 to 18.

HyamatVP Bh En

  • Upload
    leed-en

  • View
    212

  • Download
    0

Embed Size (px)

Citation preview

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 1/24

EMC-tested

DIN EN ISO 9001

Interference suppression Class B

Hyamat VP with Movitec

Illustration shows variant without acoustic cladding

Hyamat  VPType Series Booklet1953.52-10

Pressure Boosting Units/Fire-fighting Systemswith Continuously Variable Speed Adjustment

Using Frequency Inverters for each Pumpto DIN 1988

Fields of Application Residential buildings Department stores Hospitals Industry Office buildings and other applications Hotels

Fluid HandledDrinking water, utility water, fire-fighting water, cooling water, wherethere is no chemical and mechanical corrosive action on thesystem materials.

Operating Data

Capacity Q up to 200 m3 /h, 55 l/s with max. 4 pumps *)Discharge head H up to 130 mTemperature offluid handled up to 70 oC  up to 25 oC to DIN 1988 (DVGW)

 Ambient temperature up to 40 oCSystem dischargepressure pd  up to 16 barInlet pressure pinlet  up to 10 barSupply voltage 3/N/PE, AC 400 V, 50 Hz

5-wire system < 2.2 kW

 *) with stand-by pump as peak load pump

MaterialsPumps

Suction/discharge casing stainless steelHydraulic system stainless steelMechanical seal to EN 12756Spring-loaded ring silicon carbideSeat ring hard carbonElastomer EPDM

Hydraulic Design:Distributor pipe stainless steelValves copper-base alloy/brass,

DVGW-approved Accumulator connection made of stainless steelMembrane approved for drinking water to

DIN 4807-5

DriveElectric motor 50 Hz, 2-pole, special KSB model, for three-phase

mains. Standard IEC motors can only be used after consultation withKSB.

DesignFully automatic pressure boosting package unit, with 2 to 4 vertical

high-pressure pumps, with continuously variable speed adjustment of 

each pump for fully electronic control to ensure the required supply

pressure, with standard volt-free contact for lack of water indication,

general fault indication or reporting of system’s availability as well as

live-zero monitoring of the connected sensors.

Design and function as per DIN 1988, Part 5.

 Hyamat VP System Equipment (Standard)- 2- 4 vertical high-pressure centrifugal pumps (standard pumps)

Movitec 2, 4 und 10 with oval flange/ 

Movitec 18 und 32 with round flange- Hydraulic components made of stainless steel- 1 check valve and shut-off element for each pump to DIN / DVGW- Membrane-type accumulator on the discharge side as control tank

(direct flow) to DIN 4807-5, approved for drinking water- Pressure transmitter on the discharge pressure side- Pressure indication via pressure gauge- Steel baseplate powder-coated/epoxy resin-coated- Pump sizes 2, 4 and 10 are fixed to the baseplate on

anti-vibration mounts- Pump sizes 18 and 32 are supplied with level-adjustable feet and

anti-vibration pads (supplied, but not fitted)- Control cabinet IP 54, EMC interference suppression class B- Pressure transmitter on the inlet pressure side (dry-running

protection and energy-optimized cut-out of PBU)

- CE certificateControl cabinet equipment (Standard)- Manual-0-automatic selector switch- PLC- LEDs indicating operational availability and fault of the system- Frequency inverter for each pump- Motor protection switch or

safety cut-out for each pump- Master switch, lockable (repair switch)- Terminals with identification for all connections- Circuit diagram acc. to VDE, settings for frequency inverter (FI)

and parts list for electrical parts- Emergency OFF connection

For supplementary equipment and special designssee pages 16 to 18.

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 2/24

Hyamat VP

2

Standard scope Extended scopecf. supplementary equipment

Hyamat VPwith control panel

Hyamat VPwith display and keyboard

Settings

Set pressure Potentiometer on the PLC Display: Set value in plain languageInlet pressure >0.5 bar Pressure transmitter on inlet pressure

side (dry running protection andenergy-optimized cut-out of PBU)

Pressure transmitter on inlet pressureside (dry running protection andenergy-optimized cut-out of PBU)

Second set value Activation via customer-provided volt-freecontact or timer

 Activation via timer in the display set ac-cordingly or activation via customer-pro-vided volt-free contact or timer

 All other values are set at the factory in accordance with the purchase order specifications for

water supply applications.

Reporting Reporting via display, multi-line(using keyboard)

 Actual value Pressure gauge Pressure gauge and display

Inlet pressure >0.5 bar Pressure gauge Pressure gauge and displayOperational availability of the system Green lamp Green lamp

General faultis triggered in the case of:- Pump fault- FI fault (for each pump)- Sensor fault (live zero)- Lack of water

Red lamp Red lamp and plain language

Operation/fault, each pump - Display: Status indication

Operating hours counter per pump - Display: Operating hours with resetfacility

Indication of flow rate - Display: Actual value (approximate)

Reporting via volt-free contacts on isolating terminals

Operational availability of the system(trouble-free operation of the sys-tem)

NO contact NO contact

General faultis triggered in the case of:- Pump fault- FI fault (for each pump)- Sensor fault (live zero)- Lack of water- Power failure

NC contact NC contact

Lack of water NC contact NC contact

Operation per pump NO contact, optional NO contact, optional

Fault per pump NC contact, optional NC contact, optional

Fault acknowledgement: Via reset key Display and keyboard

Miscellaneous

Functional check run Supplementary equipment, via timer Display: may be set to daily or weekly

Pump change-over Base load pump change-over, this func-tion is triggered via a customer-providedvolt-free contact or timer(supplementary equipment)

Display: may be set to daily or weekly

Second set value Supplementary equipment - via timer Display: may be set to daily or weekly

Manual mode With optional manual-0-automatic selec-tor switch or operating on the frequencyinverter with open control cabinet

With optional manual-0-automatic selec-tor switch or manual mode via display

Remote control from controlstation

- Automatic ON-OFF- Second set value- Emergency OFF- Remote acknowledgement- Functional check run- Pump change-over

- Automatic ON-OFF- Second set value- Emergency OFF- Remote acknowledgement- Functional check run- Pump change-over

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 3/24

Hyamat VP

3

Terminal Connections

   S   i  g  n  a   l ,   d   i  s  c   h  a  r  g  e  p  r  e  s  s  u  r  e

   S   i  g  n  a   l ,   i  n   l  e   t  p  r  e  s  s  u  r  e

   P  r  e  s  s  u  r  e  s  w   i   t  c   h ,

   d   i  s  c   h  a  r  g  e  p  r  e  s  s  u  r  e

   E  m  e  r  g  e  n  c  y   O   F   F

Optional

OptionalDry-running protection if inlet tank is used / for suction lift operation

   S  e   t  v  a   l  u  e  c   h  a  n  g  e  -  o  v  e  r

   A  u   t  o  m  a   t   i  c   O   N   /   O   F   F

   O  p  e  r  a   t   i  o  n  m  e  s  s  a  g  e

   P  u  m  p  c   h  a  n  g  e  -  o  v  e  r

   F  u  n  c   t   i  o  n  a   l  c   h  e  c   k  r  u  n

   I  m  m  e  r  s   i  o  n

  e   l  e  c   t  r  o   d  e  s

   F   l  o  w

  m  o  n   i   t  o  r   i  n  g ,

  s  u  c   t   i  o  n  s   i   d  e

   R  e  m  o   t  e  a  c   k  n  o  w   l  e   d  g  e  m  e  n   t

   P  u  m  p   /   F   I

   P  r  e  s  s  u  r  e  o  r   f   l  o  a   t  s  w   i   t  c   h ,

  s  u  c   t   i  o  n  s   i   d  e

Designation  3,2 Hyamat VP 4 / 0408 / 1,2 - 3,5

Type seriesNumber of pumpsPump sizeNumber of stagesMinimum inlet pressure, barMax. effective inlet pressure, bar

FunctionTwo to four pumps are controlled and monitored by a PLC.Each pump is connected to a frequency inverter and controlledby the PLC in order to ensure a constant system dischargepressure. As the demand increases or decreases, the peak load pumpswill be switched on and off automatically. As soon as the demand increases after one pump has beenswitched off, another pump which has not been in operationbefore is switched on. After the last pump has been switched off and the demandincreases again, the next pump in line is switched on andconnected to the frequency inverter.The stand-by pump is also part of the alternating cycle but isswitched on only in case of need. As a standard, the system is switched on automaticallydepending on the pressure; the actual pressure is measured byan analog pressure measuring device (pressure transmitter).The function of this pressure transmitter is monitored(live-zero). As long as the system is in operation, the pumps are switchedon and off depending on the demand (standard setting).In this way it is ensured that the individual pumps operate only

in line with the actual demand. The use of speed-controlledpumps reduces wear as well as the pumps’ switching frequency

in parallel operation. If a duty pump fails, the next pump will beswitched on immediately. There will a general fault indicationwhich can be reported via volt-free contacts (e..g. to the controlstation).If the demand drops towards 0, the system slowly approaches

the switch-off point.

Manual Mode A manual-0-automatic selector switch is available for eachpump installed.In manual mode, the pumps are operated on the frequencyinverter independently of the installed PLC and run at aconstant speed chosen by the operator. As a standard, they runat full speed.For this mode of operation no pressure control and nolack-of-water monitoring will be effected.Caution!

Please observe minimum flow rates!In the case of closed consumer installations, the pumpsproduce the max. pressure acc. to the characteristic curvewhen running at full speed in manual mode.

Commissioning / Start-up

Commissioning by specialist KSB staff is effected againstextra charge.

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 4/24

DVGW-testedvalves

High operating reliabilitythanks to continuousfunctional monitoring

of the connectedsensors

General fault reportingvia volt-free contact

Corrosion-resistantstainless steel piping

Installation free from solid-bornesound transmission due to anti-vibration mounts

Accumulatorto DIN 4807-5,DVGW-approved

Manual-0-automaticselector switch per pump

Equal distribution ofpump operating hours byautomatic pumpchange-overAcoustic cladding

(supplementary equipment)

- Retrofittable andeasy to service

- Protects againstcontamination

- Appealing design

Automatic matchingto the demandthanks to a continuouslyspeed-controlledbase load pump

System Features with Movitec 2, 4 and 10

Reliable, service-friendlyshaft seal

- Standardised mechanicalseal to EN 12756- High-alloy steel shaft

Low noise,since the flow noise is dampedby water-filled shroud

Movitec Features

Corrosion resistant All wetted components, hydrauliccomponents and pump shroudare made of high-alloy stainlesssteel

Display(supplementary equipment)- Operating hours counter- Flow rate indicator

Hyamat VP

4

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 5/24

High operating reliabilitythanks to continuousfunctional monitoringof the connected

sensors

General fault reportingvia volt-free contact

Corrosion-resistantstainless steel piping

Installation free from solid-bornesound transmission due to anti-vibration mounts

Accumulatorto DIN 4807-5,DVGW-approved

Manual-0-automaticselector switch per pump

Equal distribution ofpump operating hours byautomatic pumpchange-overAcoustic cladding

(supplementary equipment)

- Retrofittable andeasy to service

- Protects againstcontamination

- Appealing design- Low-noise operation

Automatic matchingto the demandthanks to a continuouslyspeed-controlledbase-load pump

System Features with Movitec 18, 32 and 45

Reliable, service-friendlyshaft seal- Standardised mechanical

seal to EN 12756- High-alloy steel shaft

Low noise,since the flow noise is dampedby water-filled shroud

Movitec Features

Corrosion resistant All wetted components, hydraulic com-ponents and pump shroud are made of high-alloy stainless steel

Display(supplementary equipment)- Operating hours counter- Flow rate indicator

Hyamat VP

5

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 6/24

Set value Set value

Hyamat VP

6

Modes of Operation

Cascade: Hyamat K Variable: Hyamat V Variable: Hyamat VP Other combinationsand control modes

Two to six pumps are started upand switched off by the PLC inline with the actual demand.

 A base load pump is continu-ously controlled, with the peakload pumps being started up and

switched off in line with the de-mand.

 All pumps are continuously con-trolled. The peak load pumpsare started up and switched off 

in line with the demand. All pumps run at the samespeed.

 Available upon request.(Example: 1 or 2 jockey pumpsas low load pumps)

Standard Pressure Boosting Units (PBU)

1 Pump2 Ball valve3 Combined non-return/

shut-off valve4 Pressure gauge5 Pressure transmitter6 Accumulator7 Control cabinet

Modes of Connection:

Direct Indirect Indirect

Unpressurized inlet tank at the same orat a higher level

Unpressurized inlet tank at a lower level(suction-lift operation) 1)

Inlet pressure monitoring by pressure transmitter fitted on the inlet pressure side

at pvor >0.5 bar (min. 1 bar; DIN 1988)- pressure sensor (standard)at pvor <0.5 bar- flow monitoring

- float switch- set of electrodes and relay- dry running protection set for

PE-inlet tank- flow monitoring

- flow monitoring- float switch- set of electrodes and relay- dry running protection set for

PE inlet tank

1) Non-self-priming pumps; suitable for suction-lift operation (for selection, please consult KSB)

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 7/24

H m PBU discharge head at Qsoll

5 bar

Characteristic curvesand tolerances to ISO 9906

including astand-bypump toDIN 1988

Pumps per system

withoutstand-by

pump

Max.effective

inletpressureincrease∆pvormax.in bar

referred to the char-acteristic

curve

Hyamat VP

7

Work sheet for selection

Basic data:

H = (pE  - pvor)   10 mpE = pvor + (H : 10) barQsoll = PBU capacity at pE m3 /hH = PBU discharge head at Qsoll m

pE = Start- up pressure for PBU at Qsollincluding inlet pressure pvor

pvor = inlet pressure upstream of PBUH0 = PBU discharge head at Q = 0p0max = PBU discharge pressure at Q = 0 (=H0 + pvor)

Catalogue data always refer to inlet pressure = 0.

Selection exampleRequirementQ = 18 m3 /h, pE = 5 bar, pvor = 0

Found solution to DIN 1988, Part 5

1. Hyamat VP 3/0409

The ∆pvor value can be read directly fromthe table by drawing a vertical line fromthe design point to the ∆pvor axis of the

pump.

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 8/24

Hyamat VP

8

 Hyamat VP Performance Chart (Complete Overview)

Systems with higher power ratings are available on request.

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 9/24

Hyamat VP

9

Movitec 2 Movitec 4 n = 2900 1/min

Movitec 10 Movitec 18

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 10/24

Hyamat VP

10

Movitec 32 n = 2900 1/min

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 11/24

Characteristic curvesand tolerances to ISO 9906

including astand-bypump toDIN 1988

withoutstand-by

pump

Pumps per system

Max.effective

inletpressureincrease∆pvor max.

in barreferred

to the char-acteristic

curve

Hyamat VP

11

Characteristic curves Movitec 2

pvor = 0p0 max  = 16 barpA = max. switch-off pressure

Systems with higher power ratings are available on request.

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 12/24

Characteristic curvesand tolerances to ISO 9906

including astand-bypump toDIN 1988

withoutstand-by

pump

Pumps per system

Max.effective

inletpressureincrease∆pvor max.

in barreferred

to the char-acteristic

curve

Hyamat VP

12

Characteristic curves Movitec 4

pvor = 0p0 max  = 16 barpA = max. switch-off pressure

Systems with higher power ratings are available on request.

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 13/24

Characteristic curvesand tolerances to ISO 9906

including astand-bypump toDIN 1988

withoutstand-by

pump

Pumps per system

Max.effective

inletpressureincrease∆pvor max.

in barreferred to the char-acteristic

curve

Hyamat VP

13

Characteristic curves Movitec 10

pvor = 0p0 max  = 16 barpA = max. switch-off pressure

Systems with higher power ratings are available on request.

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 14/24

Characteristic curvesand tolerances to ISO 9906

including astand-bypump toDIN 1988

withoutstand-by

pump

Pumps per system

Max.effective

inletpressureincrease∆pvor max.

in barreferred to the char-acteristic

curve

Hyamat VP

14

Characteristic curves Movitec 18

pvor = 0p0 max  = 16 barpA = max. switch-off pressure

Systems with higher power ratings are available on request.

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 15/24

Characteristic curvesand tolerances to ISO 9906

including astand-bypump toDIN 1988

withoutstand-by

pump

Pumps per system

Max.effective

inletpressureincrease∆pvor max.

in barreferred to the char-

acteristiccurve

Hyamat VP

15

Characteristic curves Movitec 32

pvor = 0p0 max  = 16 barpA = max. switch-off pressure

Systems with higher power ratings are available on request.

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 16/24

Hyamat VP

16

Accessories / Supplementary Equipment *) Hyamat VPDry Running Protection

Part No. Ident. No.

Dry running protection for suction lift operation(flow monitoring)IFM sensor with tripping electronics

Retrofit option 1)as separateswitchgear

E 201 19 070 923

Set of electrodes and relayRelay fitted in the control cabinetElectrodes with 1.5 m cableand fastening element

(Both ident. nos. are required)

Retrofit option 1)if sufficientspace is avail-able in controlcabinet

E 420 00 198 09800 533 947

Dry running protection, float switch1)with H 07 RN-F cable 3x1.5 mm2

for lack-of-water monitoring in combination with areservoir provided by the customer, KTW-approvedCable length 5 m

10 m20 m

Scope of supply:- Float switch with connection cable

11 037 63011 037 63111 037 632

Dry running protection, float switch1)with H 07 RN-F cable 3x1.5 mm2

for lack-of-water monitoring in combination with areservoir provided by the customerCable length 5 m

10 m20 m

Scope of supply:- Float switch with connection cable

11 037 74311 037 74411 037 746

Dry running protection  5 m

with weight and PG cable gland, 10 mKTW-approved 20 mSpecial lengths upon request 

19 071 650

19 070 39519 071 651

Weight for adjusting the float switch level

Scope of supply:- Weight with mounting elements

18 040 615

1) As accessory. A trained electrician must effect additional wiring.

Accessories / Supplementary Equipment *)

Part No. Ident. No.

Display, multi-lineReporting and value setting using the keyboard(Timer function - battery service life, i. e. backup for approx. 10 years)

E 511 19 072 447

Ammeter per pump

 Voltmeter per system

 always combined 

E 340

E 341

 *) Accessories (Ident. No.) are included in the scope of supply but not fitted.Supplementary equipment / options (E No.) come fitted to the unit.

76

76

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 17/24

Hyamat VP

17

Accessories / Supplementary Equipment *) (continued)

Part No. Ident. No.

Operating hours counter per pump

 

E 330

Functional check run, pump change-over or second set value:Timer for daily functional check run

E 040 18 040 617

Functional check run, pump change-over or second set value: Digital timer for weekly programme

E 050 18 040 618

Reporting via volt-free contacts on isolating terminalsOperation per pumpFault/malfunction per pump (frequency inverter)

E 051

Equipment for temperature monitoring 

of fluid pumped at hydraulic section for each pump

E 360 19 071 510

Acoustic cladding for Hyamat 2 / 4 / 10 Number of pumps- Protects against contamination 2- Appealing design 3- Low-noise operation

E 120E 121

18 040 61018 040 611

Acoustic cladding for Hyamat 18 / 32 Number of pumpsHyamat 18 up to 5.5 kW 2Hyamat 32 up to 7.5 kW 3

4

Hyamat 18 up to 7.5 kW 2

Hyamat 32 up to 15.0 kW 34

- Protects against contamination- Appealing design- Noise-reduced operation

E 123E 124E 125

E 128

E 129E 130

19 071 63319 071 63419 071 635

19 071 663

19 071 66419 071 665

Telecommunications module,for fault signalling via telephone lines, with battery buffer

E 043 19 072 308

Emergency power connection on second terminal stripExternal activation

E 058

Control cabinet lighting with 230 V socketfor cabinets sized 1000 x 600 x 250 and above E 059

Control cabinet heating for special climatic conditions(high air humidity)

E 039

Phase monitoring relay incl. direction of rotation monitoringand phase failure safety device

E 320

Over-voltage protection E 060

Thermistor connection for PTC thermistors in motor winding if available.

 *) Accessories (Ident. No.) are included in the scope of supply but not fitted.Supplementary equipment / options (E No.) come fitted to the unit.

36

24

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 18/24

Hyamat VP

18

Supplementary Equipment (upon request)

Control cabinet equipmentIndividual indications via volt-free contacts on special isolating terminalsEmergency power connection with automatic activationMotor with PTC thermistors and PTC thermistor trip device in the control cabinetSwitch position indication (master switch or manual-0-automatic selector switch)

Control cabinet with cylinder lockSpecial paintingExtra space in control cabinetControl cabinet air-conditioningCommunication via an RS 232C interfaceProfibus / LON bus interface

Indications for control station (on isolating terminals)Operating pressure, analog 4 - 20 mAOperating pressure, digital, volt-freeInlet pressure, analog 4 - 20 mAPower input for each pump, analog (for example, signal 0/4 - 20 mA / 0 - 10 V)Position of manual-0-automatic selector switch per pump, volt-free

Special designsOther special designs not documented are available upon request, e. g.:

1. Different frequency2. Different connection diameters3. System discharge pressure pd up to 40 bar4. Systems for industry (for example, also for other fluids)5. Systems for suction-lift operation6. Jockey pumps: low-flow operation (on weekends, in case of extremely fluctuating demand etc.)7. Combined systems (drinking water and fire-fighting systems), booster systems8. Customer-specific special circuit diagrams

Remote control from control stationBasic set value is set via alert (0 - 10 V)

Please note:Separate control cabinet installation is possible. Max distance pump-frequency inverter = 15 m.A transfer control unit must not be used.

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 19/24

Hyamat VP

19

Electrical Performance Data

Hyamat VP Rated powerper motor (P2)

Rated currentper motor for

Total rated power requirementin kVA Hyamat VP

with pumps 3~400 V Number of pumps (motors)

Movitec kW A 2 3 4

0202 0.37 1.4 2.72 3.74 4.76

0203 0.37 1.4 3.96 5.94 7.92

0204 0.55 1.5 3.96 5.94 7.92

0205 0.55 1.5 3.96 5.94 7.92

0206 0.75 2.1 3.96 5.94 7.92

0207 0.75 2.1 3.96 5.94 7.92

0208 1.1 2.9 6.16 9.24 12.32

0209 1.1 2.9 6.16 9.24 12.32

0210 1.1 2.9 6.16 9.24 12.32

0212 1.1 2.9 6.16 9.24 12.32

0213 1.5 4.4 8.76 13.14 17.52

0215 1.5 4.4 8.76 13.14 17.52

0402 0.37 1.4 3.96 5.94 7.92

0403 0.55 1.5 3.96 5.94 7.92

0404 0.75 2.1 3.96 5.94 7.920405 0.75 2.1 3.96 5.94 7.92

0406 1.1 2.9 6.16 9.24 12.32

0407 1.1 2.9 6.16 9.24 12.32

0408 1.5 4.4 8.76 13.14 17.52

0409 1.5 4.4 8.76 13.14 17.52

0410 1.5 4.4 8.76 13.14 17.52

0411 2.2 6.0 8.76 13.14 17.52

0413 2.2 6.0 8.76 13.14 17.52

0415 2.2 6.0 8.76 13.14 17.52

1002 0.75 2.1 3.96 5.94 7.92

1003 1.1 2.9 6.16 9.24 12.32

1004 1.5 4.4 8.76 13.14 17.52

1005 2.2 6.0 8.76 13.14 17.52

1006 2.2 6.0 8.76 13.14 17.521007 3.0 7.0 12.56 18.84 25.12

1008 3.0 7.0 12.56 18.84 25.12

1009 4.0 9.0 13.76 20.64 27.52

1010 4.0 9.0 13.76 20.64 27.52

1802 2.2 6.0 8.76 13.14 17.52

1803 3.0 7.0 8.76 13.14 17.52

1804 4.0 9.0 12.56 18.84 25.12

1805 5.5 11.8 13.76 20.64 27.52

1806 5.5 11.8 13.76 20.64 27.52

1807 7.5 14.3 25.56 38.34 51.12

1808 7.5 14.3 25.56 38.34 51.12

3202 4.0 9.0 13.76 20.64 27.52

3203 5.0 11.8 20.76 31.14 41.52

3204 7.5 14.3 25.56 38.34 51.12

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 20/24

Hyamat VP

20

Weight of units in kg (approx.)

Hyamat VP Number of stages

02 03 04 05 06 07 08 09 10 11 13 15

2/02../. 121 125 127 131 133 143 145 145 153 153 155 173

3/02../. 154 160 163 169 172 187 190 190 202 202 205 232

4/02../. 179 187 191 199 203 223 227 227 243 243 247 2832/04../. 121 125 127 129 133 133 145 145 147 153 155 157

3/04../. 154 160 163 166 172 172 190 190 193 202 205 208

4/04../. 179 187 191 195 203 203 227 227 231 243 247 251

2/10../. 137 141 153 161 161 181 183 197 197 - - -

3/10../. 178 184 202 214 214 244 247 268 268 - - -

4/10../. 211 219 243 259 259 299 303 331 331 - - -

2/18../. 279 301 321 378 380 390 392 - - - - -

3/18../. 371 404 434 497 500 515 518 - - - - -

4/18../. 493 537 577 651 655 675 679 - - - - - -

2/32../. 374 433 447 - - - - - - - - -

3/32../. 516 582 603 - - - - - - - - -

4/32../. 708 786 814 - - - - - - - - -

Noise levels of units 2 / 4 / 10

Hyamat VPwith pumps

withoutacoustic cladding

withacoustic cladding

Movitec 2 60 - 65 dB(A) 51 - 56 dB(A)

Movitec 4 60 - 67 dB(A) 51 - 56 dB(A)

Movitec 10 65 - 69 dB(A) 56 - 61 dB(A)

Noise levels for units with Movitec 18 / 32 on request.

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 21/24

Plan view

Control cabinet doorhinged on the left

 Acoustic cladding(supplementary equipment)

Suctionside

Dischargeside

Hyamat VP

21

Dimensions Hyamat VP with Movitec 2, 4 und 10

Dimension Table (in mm)

Number of pumps 2 3 / 4

with Movitec 2 and 4 10 2 and 4 10

B 770 875 770 875

B1 630 735 630 7354

H1 115 145 115 145

L 770 1270

L1 645 1145

DN external thread R 2 1 / 2 (DN 65)

Painting:Baseplate RAL 5002Control cabinet RAL 7032

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 22/24

Control cabinet doorhinged on the left

 Acoustic cladding(supplementary equipment)

see control cabinets

Plan view

Suctionside

Dischargeside

Hyamat VP

22

Dimensions Hyamat VP with Movitec 18 and 32

Movitec 18/.. and 32/..

Number of pumps

2 3 4 5 6 Pump

B 1085 1085 1085 1085 1238 18/..

1105 1105 1255 1255 1255 32/..

B1 865 865 865 865 953 18/..885 885 970 970 970 32/..

B2 405 405 405 405 448 18/..

415 415 458 458 458 32/..

B3 460 460 460 460 505 18/..

470 470 515 515 515 32/..

L1 886 1296 1706 2116 2526

L2 - - 820 820 1230

L3 820 1230 820 1230 1230

L4 820 1230 1640 2050 2460

DN 100 100 100 100 150 18/..

DN 150 150 32/..

H1 287 287 287 287 287 18/..

302 302 302 302 302 32/..

Flanges drilled to EN 1092-1 PN 16

8/20/2019 HyamatVP Bh En

http://slidepdf.com/reader/full/hyamatvp-bh-en 23/24

Controlcabinet doorhinged on the left

Controlcabinet doorhinged on the left

Hyamat VP

23

Control Cabinets Dimensions1000 x 600 x 250 1200 x 800 x 300

Hyamat Power Design

 VP 2 - VP 3 up to 4 kW StandardTimerReporting via volt-freecontactsManual-0-automatic selectorswitchOperating hours counterPTC thermistor analysisTemperature monitoring Ammeter and voltmeter

 VP 4 up to 4 kW Standard Ammeter and voltmeterDisplay

Hyamat Power Design

 VP 4 up to 7.5 kW Timer  -

 VP 2 - VP 4 5.5 to 7.5 kW4 kW *)

Reporting via volt-freecontactsManual-0-automatic selectorswitchOperating hours counterPTC thermistor analysisTemperature monitoring Ammeter and voltmeter

 *) Units with Movitec 1010