The control and distribution of the electrical energy generated by generators are effected by power distribution equipment, i.e. switchboards.

Page 3: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Switchboards are either:(a) Main switchboards( 主配电盘 ), to which the main generators are connected,

Page 4: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

(b) Emergency switchboards(应急配电盘 ), to which the emergency generator or emergency battery is connected,

Page 5: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

(c) Section boards (or Sub-boards(区域配电板 ))or(d) Distribution boards(分配电板或箱 ).

Page 6: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

In small equipment, particularly in small cargo ships, most of the motors can be fed directly from the main switchboard,

Page 7: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

but as the size and multiplicity(多样性 ) of services increase, it becomes necessary to reduce the number of outgoing( 引出的 ) circuits on the main board.

Page 8: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

This is done by grouping some services on one or more section boards (sometimes referred to as sub-boards), supplied by a feeder( 馈线、馈电板 ) from the main board.

Page 9: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Still further splitting up(分解 ) particularly in the case of lighting and heating, is usually necessary and

Page 10: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

and this takes the form of distribution boards of small capacity which may be fed either direct from the main board or from a section board.

Page 11: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

G1G1

G2G2

GeneratorsGenerators

E. GeneratorE. Generator

Bar-busBar-bus

Main switchboardMain switchboard

E. switchboardE. switchboard

LightingLighting

Distribution boardDistribution board

E. LightingE. Lighting

MotorMotor

MotorsMotors

Section/sub boardSection/sub board

TransformerTransformer

Page 12: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Switchboard are divided into two classes: i.e. those for a.c. systems and those for d.c. systems.

Page 13: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Switchboards may be of the open type in which all the essential switch gears(开关设备、交换机 ) are exposed on the front of the panel( 仪表盘 , 控制面板 ),

Page 14: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

or of the deadfront type(正面无接线式、不带电式、安全式 ) in which all the live(带电的 ) parts are installed behind the panels and only the operating handles and instruments are on the front.

Page 15: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

The switchboards for a.c. systems differ from the d. c. switch gear in that the open type panels are generally not permissible.

Page 16: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Deadfront boards can be either of two patterns,

Page 17: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

one having manually-operated switches and circuit-breakers(断路器 ) with the handles on the front of panels and all the live(带电的 ) parts at the rear;

Page 18: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

and the other having electrically operated circuit-breakers operated by push-buttons on the front of the panels.

Page 19: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Usually the panels are interlocked with isolators( 绝缘子、隔离开关 ) so that the devices can be made dead(不带电的 ) before the doors are opened.

Page 20: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

The voltages most commonly adopted for a.c. systems are either 440V or 220V three-phase.

Page 21: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

For d.c. switchboards, there are ammeters, voltmeters, circuitbreakers, tipping devices( 跳闸装置 ) and so on,

Page 22: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

but a.c. requires additional equipment as compared with d.c., such as frequency meters, synchroscope, wattmeters,

Page 23: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

voltage and current transformers(电压互感器和电流互感器 ), ammeter switches( 安培表的转换开关 ), voltage regulators(稳压器、电压调节器 ), etc..

Page 24: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Circuit breakers and switches will be three-pole as compared with two-pole for d.c..

Page 25: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

However, in spite of the additional equipment an a.c. switchboard is usually smaller and lighter than the corresponding( 相应的 ) d.c. board

Page 26: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

because of the higher voltage and lower currents and smaller bus-bars(母排、汇流排 ), etc.

Page 27: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Electrical supply is always needed, even if only for lighting.

Page 28: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

So after a ship goes into service it is extremely rare for the main bus-bars to be made dead,

Page 29: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

it therefore follows that the bus-bars are continuously alive(带电的 ) throughout the life of the ship.

Page 30: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Even when in a shipyard for repair, a shore supply will usually be taken.

Page 31: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Reading Materials

A.  Emergency Generator supply

Page 32: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

In the event of a main generating system failure an emergency supply of electricity is required for essential services.

Page 33: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

This can be supplied by batteries, but most merchant ships have an emergency generator.

Page 34: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

The unit is diesel driven and located outside of the machinery space.

Page 35: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

The emergency generator must be rated to provide power for the driving motors of

Page 36: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

of the emergency bilge pump, fire pumps, steering gear, watertight doors and possibly fire fighting equipment.

Page 37: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Emergency lighting for occupied areas(居住区 ), navigation lights(航行灯 ), communications systems and alarm systems must also be supplied.

Page 38: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Where electrical control devices are used in the operation of main machinery, these too may require a supply from the emergency generator.

Page 39: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Usually only one emergency switchboard is installed;

Page 40: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

however, for safety reasons large passenger vessels may have two emergency sources of power, thus requiring two emergency switchboards.

Page 41: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Emergency switchboards normally consist of a generator control panel, a bus tie and distribution panel (汇电板和配电盘 ) and

Page 42: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

and 24-volt, 120-volt, and 450-volt distribution panels in size and number as required.

Page 43: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Emergency generator switchboards include those devices noted in the foregoing for main switchboard generator control panel plus the following:

Page 44: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

1. A white light to indicate that the normal supply is available.

2. A green light to indicate that all devices are “set up” for automatic operation.

Page 45: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

3. A normal supply circuit breaker, unless the automatic bus transfer(主送电器 ) is of the contactor type.

Page 46: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

4. A feed back switch when the automatic bus transfer is of the contactor type.

Page 47: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

It is not usual for an emergency generator to require paralleling, so no equipment is provided for this purpose.

Page 48: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Automatic start up of the emergency generator at a low voltage value is usual on modern installations.

Page 49: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

B. Maintenance of electrical equipments

Page 50: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

With all types of electrical equipment cleanliness is essential for good operation.

Page 51: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Electrical connections must be sound(完好的,可靠的 ) and any signs of sparking should be investigated.

Page 52: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Parts subject to wear must be examined and replaced when necessary.

Page 53: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

The danger from a.c. equipment in terms of electric shocks( 触电 ) is far greater than for similar d.c. voltages.

Page 54: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Also a.c. equipment often operates at very high voltages.

Page 55: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Care must therefore be taken to ensure isolation of equipment before any inspections or maintenance is undertaken.

Page 56: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

The accumulation of dirt on electrical equipment will result in insulation breakdown and leakage currents, possibly even an earth fault.

Page 57: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Moisture or oil deposits will likewise(同样地 ) affect insulation resistance.

Page 58: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Regular insulation resistance measurement and the compiling( 汇集 ) of records will indicate(预示 ) the equipment requiring attention.

Page 59: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Ventilation passages or ducts may become blocked, with resultant lack of cooling and overheating.

Page 60: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Oil deposits from a direct coupled diesel engine driving an open generator can damage windings and should therefore be removed if found.

Page 61: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Totally enclosed machines should be periodically opened for inspection and cleaning since carbon dust will remain inside the machine and deposit on the surfaces.

Page 62: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Brushgear should be inspected to ensure adequate brush pressure and the springs adjusted if necessary.

Page 63: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

New brushes should be ‘bedded in( 研配 )’ to the commutator(整流子,换向器 ) or slipring shape with fine glass paper( 精细玻璃砂纸 ).

Page 64: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Sparking at the commutator will indicate poor commutation(换向、整流 ).

Page 65: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

This may require polishing of a roughened( 粗糙的 ) commutator surface.

Page 66: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

The mica( 云母 ) insulation between commutator segments( 换向片、整流片 ) may require undercutting(剔槽 ) if it protrudes(凸出 ), or simply cleaning if deposits have built up.

Page 67: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Control equipment, such as starters, will require attention to contacts which may be worn or pitted(有凹痕的 ) as a result of arcing(电弧放电 ).

Page 68: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

Contactors( 接触器,触头 ) usually have a moving or wiping(磨擦 ) action as they come together.

Page 69: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

This helps clean the surfaces to provide good electrical contact, and also the arc produced during closing and opening is not at the finally closed position.

Page 70: Jimei university Lesson 24 Switchboard ( 配电板 ). Jimei university The control and distribution of the electrical energy generated by generators are effected

Jimei university

The contactor contact surfaces of frequently used equipment should therefore be subject to regular inspections.