    Moeller HPL0211-2007/2008

    8/2

    http://catalog.moeller.net

    motor-protectivecircuit-breakers

    System overviewMotor-protective circuit-breakers

    Motor protection, transformer protection, conductor and cable protection

    66

    2

    1

    5

    4

    6

    3

    27

    Basic devices Add-on functions Mounting accessories

    PKZM01 motor-protective circuit-breakers

    1 Standard auxiliary contacts 6 Door coupling rotary handle IP65 4

    aPage 8/3 aPage 8/8 aPage 8/17

    PKZM0 motor-protective circuit-break-ers

    Voltage releases 5 Insulated enclosures

    aPage 8/4 2 aPage 8/11 aPage 8/14

    PKZM4 motor-protective circuit-break-ers

    3 Current limiter 7 Mounting/wiring

    aPage 8/4 aPage 8/11 aPage 8/19

    PKZM01, PKZM0, PKZM4

  • 8/9/2019 Kapitel 08 G Online

    3/59

    8/3

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    Motor-protectivecircuit-breakers

    PKZM01,

    PKZM

    0,

    PKZM4

    OrderingMotor-protective circuit-breakers

    Screw terminals

    Max. motor rating Rateduninterruptedcurrent

    Setting range Part no.Article no.

    Pricesee pricelistRG

    Std. pack

    AC-3 Overload releases Short-circuit releases

    220 V

    230 V240 V

    380 V

    400 V415 V

    440 V

    P P P I u Ir Irm

    kW kW kW A A A

    Motor-protective circuit-breakers, Type "1" and Type "2" coordination

    0.16 0.10.16 2.2 PKZM01-0,16278475

    1 off

    0.06 0.06 0.25 0.160.25 3.5 PKZM01-0,25278476

    0.06 0.09 0.12 0.4 0.250.4 5.6 PKZM01-0,4278477

    0.09 0.12 0.18 0.63 0.40.63 8.8 PKZM01-0,63

    278478

    0.12 0.25 0.25 1 0.631 14 PKZM01-1278479

    0.25 0.55 0.55 1.6 11.6 22 PKZM01-1,6278480

    0.37 0.75 1.1 2.5 1.62.5 35 PKZM01-2,5278481

    0.75 1.5 1.5 4 2.54 56 PKZM01-4278482

    1.1 2.2 3 6.3 46.3 88 PKZM01-6,3278483

    2.2 4 4 10 6.310 140 PKZM01-10278484

    3 5.5 5.5 12 812 168 PKZM01-12278485

    4 7.5 9 16 1016 224 PKZM01-16283390

    Notes

    L

    T

    I>

    Accessories Page

    3 Standard auxiliary contact a8/8

    5 Trip-indicating auxiliary contact a8/11

    6 Shunt release, undervoltage release a8/11

    Single-phasing sensitivity according to IEC/EN 60947-4-1, VDE 0660 Part 102.

    Can be snap-fitted to IEC/EN 60715 top-hat rail with 7.5 or 15 mm height

    6

    3

    53

    PKZM01

  • 8/9/2019 Kapitel 08 G Online

    4/59

    Moeller HPL0211-2007/2008

    8/4

    http://catalog.moeller.net http://catalog.moeller.net

    Ordering Motor-protective circuit-breakers

    Screw terminals Incoming side screw terminalsoutgoer side springloaded termi-nals

    Spring-loaded terminals

    Max. motor rating Rateduninterruptedcurrent

    Part no.Article no. see price list

    Std. packArticle no. see price list Article no. seAC-3 Overload

    releasesShort-circuitreleases220 V

    230 V240 V

    380 V400 V415 V

    440 V 500 V 660 V690 V

    P P P P P I u r rm

    kW kW kW kW kW A A A

    Motor-protective circuit-breakers, Type 1 and Type 2 coordination 0.06 0.16 0.10.16 2.2 PKZM0-0,16 off PKZM0-0,16-SC PKZM0-0,16-C

    PKZM0-0,25

    229829 229670

    0.06 0.09 0.12 0.12 0.18 0.4 0.250.4 5.6 PKZM0-0,4072732

    PKZM0-0,4-SC229830

    PKZM0-0,4-C229671

    0.09 0.12 0.18 0.25 0.25 0.63 0.40.63 8.8 PKZM0-0,63 PKZM0-0,63-SC PKZM0-0,63-C

    PKZM0-1 PKZM0-1-SC PKZM0-1-C

    PKZM0-1,6 PKZM0-1,6-SC PKZM0-1,6-C

    PKZM0-2,5 PKZM0-2,5-SC PKZM0-2,5-C

    PKZM0-4 PKZM0-4-SC PKZM0-4-C

    PKZM0-6,3 PKZM0-6,3-SC PKZM0-6,3-C

    PKZM0-10 PKZM0-10-SC PKZM0-10-C

    PKZM0-12 PKZM0-12-SC PKZM0-12-C

    PKZM0-16 PKZM0-16-SC PKZM0-16-C

    PKZM0-20

    PKZM0-25

    PKZM0-32

    Motor-protective circuit-breakers, Type 1 and Type 2 coordination

    PKZM4-16

    PKZM4-25

    PKZM4-32

    PKZM4-40

    PKZM4-50

    PKZM4-58

    PKZM4-63

    L

    T

    I>

    L

    T

    I>

    PKZM0, PKZM4

  • 8/9/2019 Kapitel 08 G Online

    5/59

  • 8/9/2019 Kapitel 08 G Online

    6/59

    8/8 Ordering Standard auxiliary contacts

    Contacts Contact diagram Contact sequence For use withOrder number forseparate orders

    see pricelist

    Std. pack

    N/O =Normallyopen

    N/C =Normallyclosed

    Standard auxiliary contacts

    For motor-protective circuit-breakers

    1 N/O 1 N/C Screwterminals

    PKZM01PKZM0PKZM4PKZM0-TPKM0

    NHI11-PKZ0

    AGM, NHI-E-... trip-indicating auxiliary contact

    1 N/O 1 N/C Spring-loadedterminals

    229680

    1 N/O 2 N/C Screwterminals 072895

    2 N/O 1 N/C072894

    1 N/O 1 N/C NHI-E-11-PKZ0

    The 45 mm (PKZM0) or 55 mm (PKZM4) widths ofthe motor-protective circuit-breakers remainunchanged.

    1 N/O082884

    1 N/O Spring-loadedterminals

    229681

    1 N/C Spring-loadedterminals

    229682

    NHI11

    L1L2L3

    1.14 1.22

    1.13 1.21

    I >

    1 Motor-prot

    5 Trip-indica

    Additional a

    NHI11

    L1L2L3

    1.14 1.22

    1.13 1.21

    I >

    L1L2L3

    NHI12

    1.13

    1.14 1.22

    1.21 1.31

    1.32

    I>

    L1L2L3

    NHI21

    1.13 1.21 1.33

    1.14 1.22 1.34

    I >

    L1L2L3

    NHI-E-11

    1.53

    1.54

    1.61

    1.62

    I>

    L1L2L3

    NHI-E-10

    1.53

    1.54

    I >

    L1L2L3

    NHI-E-10

    1.53

    1.54

    I >

    L1L2L3

    NHI-E-01

    1.51

    1.52

    I >

  • 8/9/2019 Kapitel 08 G Online

    7/59

  • 8/9/2019 Kapitel 08 G Online

    8/59

    Moeller HPL0211-2007/2008

    8/12

    http://catalog.moeller.net

    p

    EngineeringAccessories for motor-protective circuit-breaker in enclosure

    Enclosures Accessories

    Part no. Part no. Degree

    ofprotect

    Handle

    colour

    NHI..-

    PKZ0

    AGM2-..-

    PKZ0

    NHI-E..-

    PKZ0

    VHI..-PKZ0 VHI..-

    PKZ01

    U-PKZ0

    orA-PKZ0

    L-PKZ0

    Surface mounting enclosures

    Motor-protective circuit-breaker PKZM01

    CI-PKZ01 IP40

    CI-PKZ01-G IP65

    CI-PKZ01-PVT

    CI-PKZ01-PVS

    IP65 Red-

    yellow

    CI-PKZ01-SVB IP65

    CI-PKZ01-SVB-V IP65 K1)

    Motor-protective circuit-breaker PKZM0

    CI-K2-PKZ0 IP41

    CI-K2-PKZ0-G IP65 Black

    CI-K2-PKZ0-GR IP65 Red-

    yellow

    CI-PKZ0-M IP40

    CI-PKZ0-GM IP55 Black

    CI-PKZ0-GRM IP55 Red-yellow

    Motor-protective circuit-breaker PKZM0 +early-make auxiliary contact VHI-PKZ0

    CI-K2-PKZ0-GV IP65 Black

    CI-K2-PKZ0-GRV IP65 Red-yellow

    CI-K2-PKZ0-GVM IP55 Black

    CI-K2-PKZ0-GRVM IP55 Red-yellow

    Notes The combination possibilities of circuit-breakers in an enclosure with accessory modules are identified by a 1) always necessary

    PKZM01, PKZM0

  • 8/9/2019 Kapitel 08 G Online

    9/59

    8/13

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    Motor-protectivecircuit-breakers

    EngineeringAccessories for motor-protective circuit-breaker in enclosures

    Enclosures Accessories

    Part no. Part no. Degree

    ofprotect

    Handle

    colour

    NHI..-

    PKZ0

    AGM2-..-

    PKZ0

    NHI-E..-

    PKZ0

    VHI..-PKZ0 VHI..-

    PKZ01

    U-PKZ0

    orA-PKZ0

    L-PKZ0

    Surface mounting enclosures

    Motor-protective circuit-breaker PKZM4

    CI-K4-PKZ4-G IP65 Black

    CI-K4-PKZ4-GR IP65 Red-yellow

    Installation enclosure

    motor-protective circuit-breaker PKZM01

    E-PKZ01 IP40

    E-PKZ01-G IP65

    E-PKZ01-PVTE-PKZ01-PVS

    IP65 Red-yellow

    E-PKZ01-SVB IP65

    E-PKZ01-SVB-V IP65 K1)

    Motor-protective circuit-breaker PKZM0

    E-PKZ0 IP40

    E-PKZ0-G IP55 Black

    E-PKZ01-GR IP55 Red-yellow

    Notes The combination possibilities of circuit-breakers in an enclosure with accessory modules are identified by a 1) always necessary

    PKZM4, PKZM01, PKZM0

  • 8/9/2019 Kapitel 08 G Online

    10/59

    Moeller HPL0211-2007/2008

    8/14

    http://catalog.moeller.net

    PKZM01,PKZM

    0,PKZM4

    OrderingInsulated enclosures

    Protectiontype

    For use with Part no.Article no.

    Pricesee pricelist

    Std. pack

    Insulated enclosures for surface mounting

    For PKZM01 motor-protective circuit-breakers

    IP40 PKZM01+NHI-E orVHI-PKZ01+U or A orNHI+L (2 off)

    CI-PKZ01281403

    1 off Integrated terminal for PE(N)connection, two M25 cable entryknockouts at top and at bottom.

    With actuation membrane IP65 CI-PKZ01-G281404

    Lockable in off position PKZM01+NHI-E or+U or A (undervoltageor shunt release)+L (2 off)

    CI-PKZ01-SVB281405

    Lockable in off position incombination with VHI-

    PKZ01

    CI-PKZ01-SVB-V281944

    1 off

    With emergency-stop pushbutton actuator, stay-put

    CI-PKZ01-PVT281406

    1 off

    With emergency-stop pushbutton actuator, releasewith key

    CI-PKZ01-PVS281407

    For extension of CI/E-PKZ01-X... unit

    as unit PKZM01 CI-PKZ01-X289934

    1 off Integrated terminal for PE(N)connection, two M25 cable entryknockouts at top and at bottom.

    For PKZM0 motor-protective circuit-breakers

    Cover with aperture

    dimensioned toaccommodate front ofbreaker. IP40, whenmounted turned through

    IP41

    whenmountedvertically

    PKZM0-...

    +NHI or AGM+U or A (undervoltageor shunt release)+NHI-E+L-PKZ0 (2 off)

    CI-K2-PKZ0

    219653

    1 off M25 metric cable entry knockout,

    top and bottomPush-through cable entrydiaphragm top, bottom, in theback plate and for control cableentry.CI-K2 insulated enclosureincludes N and PE terminal.

    With black/grey rotaryhandle

    IP65 CI-K2-PKZ0-G219654

    With red/yellow rotaryhandle for use asemergency-stop switches toIEC/EN 60204

    CI-K2-PKZ0-GR219655

    Cover with aperturedimensioned toaccommodate front ofbreaker

    IP40 PKZM0-...+NHI or U or A+L-PKZ0 (2 off)

    CI-PKZ0-M267083

    Integrated terminal for PE(N)connection, two M25 cable entryknockouts at top and at bottom.

    With black/grey rotaryhandle

    IP55 PKZM0-...+NHI-E+NHI or U or A+L-PKZ0 (2 off)

    CI-PKZ0-GM260089

    1 off

    With red/yellow rotaryhandle for use asemergency-stop switches toIEC/EN 60204

    CI-PKZ0-GRM260104

    For PKZM0 motor-protective circuit-breakers with early-make VHI auxiliary contacts

    With black/grey rotaryhandle

    IP65+NHI or AGM+U or A+L-PKZ0 (2 off)

    CI-K2-PKZ0-GV219657

    1 off M25 metric cable entry knockout,top and bottomPush-through cable entrydiaphragm top, bottom, in theback plate and for control cableentry.CI-K2 insulated enclosureincludes N and PE terminal.

    With red/yellow rotaryhandle for use asemergency-stop switches toIEC/EN 60204

    CI-K2-PKZ0-GRV219656

    With black/grey rotaryhandle IP55 PKZM0-... and VHI+U or A (undervoltageor shunt release)+L-PKZ0 (2 off)

    CI-PKZ0-GVM263526 1 off Integrated terminal for PE(N)connection, two M25 cable entryknockouts at top and at bottom.With red/yellow rotary

    handle for use asemergency-stop switches toIEC/EN 60204

    CI-PKZ0-GRVM263525

    CI-PKZ

  • 8/9/2019 Kapitel 08 G Online

    11/59

    8/15

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    Motor-protectivecircuit-breakers

    PKZM01,

    PKZM

    0,

    PKZM4

    OrderingInsulated enclosures

    Protectiontype

    For use with Part no.Article no.

    Pricesee pricelist

    Std. pack

    For PKZM4 motor-protective circuit-breakers

    With black/grey rotary

    handle

    IP65

    +VHI or NHI-E+NHI or AGM+U or A+L-PKZ0 (2 off)

    CI-K4-PKZ4-G

    225524

    1 off Metric knockout:

    top and bottom: M25/M32in the back plate: M25/M32Control cable entry: M20CI-K4 insulated enclosureincluding insulated PE terminal

    With red/yellow rotaryhandle for use asEmergency-Stop switches toIEC/EN 60204

    IP65 CI-K4-PKZ4-GR225525

    1 off

    Insulated enclosures for flush mounting

    For PKZM01 motor-protective circuit-breakers

    Front IP40 PKZM01+ NHI or U or A+NHI-E or VHI+L (2 off)

    E-PKZ01281633

    1 off Integrated terminal for PE(N)connection.

    With actuation membrane Front IP65 E-PKZ01-G281634

    Lockable in off position PKZM01+U or A+L (2 off)

    E-PKZ01-SVB281635

    Lockable in off position incombination with VHI-PKZ01

    PKZM01+U or A+NHI-E or VHI+L (2 off)PKZM01+NHI-E or VHI-PKZ01+U or A+L (2 off)

    E-PKZ01-SVB-V281943

    With Emergency-Stop pushbutton actuator, stay-put

    E-PKZ01-PVT281636

    With Emergency-Stop pushbutton actuator, releasewith key

    E-PKZ01-PVS281637

    For extension of CI/E-PKZ01-X... units as unit PKZM01 E-PKZ01-X289935

    For PKZM0 motor-protective circuit-breakers

    Cover with aperturedimensioned toaccommodate front ofbreaker

    Front IP40 PKZM0-... +NHI or Uor A +L-PKZ0 (2 off)

    E-PKZ0072906

    1 off Integrated terminal for PE(N)connection.

    With black/grey rotaryhandle

    Front IP55 PKZM0-. ..+NHI or U or A+NHI-E+L-PKZ0 (2 off)

    E-PKZ0-G072907

    With red-yellow rotaryknob, for use asEMERGENCY STOP switch inaccordance with EN 60204

    E-PKZ0-GR072908

    E-PKZ

  • 8/9/2019 Kapitel 08 G Online

    12/59

    Moeller HPL0211-2007/2008

    8/16

    http://catalog.moeller.net

    PKZM01,PKZM

    0,PKZM4

    OrderingInsulated enclosures

    Protectiontype

    For use with Part no.Article no.

    Pricesee pricelist

    Std. pack

    Insulated enclosures for surface mounting

    Padlocking featureFor up to 3 padlocks with 3 6 mm hasp thickness, for use as main switch to IEC/EN 60204

    Lockable in the 0-position of thePKZM0 or PKZM4 motor-protectivecircuit-breaker.

    CI-K2-PKZ0-G(R)(V)CI-PKZ0-G(R)(V)M

    SVB-PKZ0-CI035129

    3 off

    CI-K4-PKZ4-G(R) SVB-PKZ4-CI225526

    1 off

    E-PKZ0-G(R) SVB-PKZ0-E035127

    3 off

    Neutral terminalFor connection of a 5th conductor

    Flexible, 1 4 mmB CI-K2-PKZ0-... K-CI-K1/2207451

    20 off

    63 A, flexible, 6 16 mm2 CI-K4-PKZ4-G(R) K25/1096200

    10 off

    E-PKZ0(-G)(-GR)E-PKZ01(-G)

    N-PKZ0082160

    20 off

    Units for insulated enclosures for PKZ01

    Can be combined with CI-PKZ01-X and E-PKZ01-X.

    With operating membrane Front IP65 PKZM01+NHI-E or VHI-PKZ01+U or A orNHI+L (2 off)

    CI/E-PKZ01-XG289936

    1 off

    Can be locked in O position PKZM01+NHI-E+U or A+L (2 off) CI/E-PKZ01-XSVB

    289939

    Lockable in off position incombination with VHI-PKZ01

    PKZM01VHI-PKZ01+U or A+L (2 off) CI/E-PKZ01-XSVB-V289980

    With Emergency-Stop mushroom-headed pushbutton, stay-put

    PKZM01+NHI-E or VHI-PKZ01+U or A+L(2 off)

    CI/E-PKZ01-XPVT289937

    With EMERGENCY STOPmushroom-headed pushbutton,with key-release

    PKZM01+NHI-E or VHI-PKZ01+U or A+L(2 off)

    CI/E-PKZ01-XPVS289938

    SVB-PKZ, CL/EPKZ01

  • 8/9/2019 Kapitel 08 G Online

    13/59

    8/17

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    Motor-protectivecircuit-breakers

    PKZM01,

    PKZM

    0,

    PKZM4

    OrderingAccessories

    Cable entry Hole diameter External diameterof cable

    Part no.Article no.

    Pricesee pricelist

    Std. pack

    mm mm

    Metric cable glands to EN 50262

    With lock nut and integral strain relief

    IP68 up to 5 bar, halogen freeM20 20.5 6 13 V-M20

    20691020 off

    M25 25.5 9 17 V-M25206911

    M32 32.5 13 21 V-M32206912

    M32 32.5 18 25 V-M32G226156

    Metric diaphragm grommets

    IP65 With integral push-through diaphragm

    M20 20.5 1 13 KT-M20207602

    100 off

    M25 25.5 1 18 KT-M25207603

    M32 32.5 1 24 KT-M32207604

    Colour For use with Part no.Article no.

    Pricesee pricelist

    Std. pack Notes

    Door coupling handle IP65

    Can be used with PKZM0 and PKZM4

    For use as main switch to IEC/EN 60204

    Black PKZ0-XH106132

    1 off Plug-in extension shaft A-H-PKZ0can be cut to desired length formounting depths of 100 240 mm.

    Carrier with extension shaftincluded in delivery.With ON/OFF switch position and+ (tripped), lockableWith 3 padlocks, 4 8 mm hasp.Prepared for locking in ON.

    For use as a main switch withEmergency-Stop function, toEN 60204

    Red-yellow

    PKZ0-XRH106133

    For use as a main switch to EN60204 in MCC powerdistribution systems and withPKZM0 installed whenrotated by 90

    Black PKZ0-XH-MCC106136

    For use as a main switch withEmergency-Stop function toEN 60204 in MCC powerdistribution systems and withPKZM0 installed rotated by90

    Red-yellow

    PKZ0-XRH-MCC106137

    Terminal shroud

    For enhancement of thedegree of protection of thePKZM4 to IP2x

    PKZM4 HB-PKZ4256581

    1 off

  • 8/9/2019 Kapitel 08 G Online

    14/59

    Moeller HPL0211-2007/2008

    8/18

    http://catalog.moeller.net

    PKZM01,PKZM

    0,PKZM4

    OrderingAccessories

    Part no.Article no.

    Pricesee pricelist

    Std. pack

    Telescopic adapters

    With 45 mm top-hat rail to IEC/EN 60715, for compensating of the mounting

    depth of rear mounted devices in CI-K.. enclosures and cabinets.

    Telescopic adapter M22-TA226161

    1 off Steplessly adjustable bymeans of a scale, from 75 115 mm.

    Lockable rotary handle

    For connection of the motor-protective circuit-breakerPKZM0 and PKZM4 as a main switch to EN 60204.Can be padlocked in the 0 position with a padlock.Hasp thickness: 3 6.35 mm

    AK-PKZ0030851

    5 off Cannot be combined withVHI-PKZ0.

    Sealing facility

    To prevent tampering with the overload release and the testfunction, it can be sealed using industry standard sealingwireFor use with motor-protective circuit-breakers PKZM0 andPKZM4

    PL-PKZ0203599 5 off

    Documentation

    PKZM0 motor-protective circuit-breakers, overloadmonitoring of EEx e motors

    AWB1210-1458D/GB266164

    1 off German/English

    PKZM4 motor-protective circuit-breakers, overloadmonitoring of EEx e motors

    AWB1210-1457D/GB266165

    1 off German/English

    Blade terminal to DIN 46244

    For connection of insulated ferrules for:main cables up to 25 A, 1 x 6.3 mm (DIN 46245)control circuit cables up to 6 A, 2 x 2.8 mm (DIN 46247)

    BT483

    059904

    100 off Use insulated ferrules to DIN

    46245.

    Colour Voltage Part no.Article no.

    Pricesee pricelist

    Std. pack

    V

    Indicator lights with neon bulb

    CI-K2-PKZ0-...CI-K4-PKZ4E-PKZ0-...

    CI-PKZ01E-PKZ01

    white 110 230 L-PKZ0(230V)082151

    10 off

    230 400 L-PKZ0(400V)082152

    10 off

    415 500 L-PKZ0(500V)082153

    5 off

    CI-K2-PKZ0-...CI-K4-PKZ4E-PKZ0-...CI-PKZ01E-PKZ01

    green 110 230 L-PKZ0-GN(230V)082154

    10 off

    230 400 L-PKZ0-GN(400V)082155

    10 off

    415 500 L-PKZ0-GN(500V)082156

    5 off

    CI-K2-PKZ0-...CI-K4-PKZ4E-PKZ0-...CI-PKZ01E-PKZ01

    red 110 230 L-PKZ0-RT(230V)082157

    10 off

    230 400 L-PKZ0-RT(400V)082158

    10 off

  • 8/9/2019 Kapitel 08 G Online

    15/59

    8/19

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    Motor-protectivecircuit-breakers

    PKZM01,

    PKZM

    0,

    PKZM4

    OrderingBusbar adapter

    Ratedoperational voltage

    Ratedoperational current

    Terminalcapacity

    Adap-terwidth

    Adap-terlength

    DIN rail For use with Part no.Article no.

    Pricesee pricelist

    Std.pack

    Notes

    Ue Ie

    V A mm mm Quan-tity

    Component adapter, 3 pole

    Approved to UL 508.For fitting to flat Cu-busbars with 60 mm between busbar centres, suitable for 5 mm and 10 mmbusbar thickness.

    For direct-on-line starters

    690 25 AWG 12(4 mmB)

    45 200 1 PKZM0 + DILM7PKZM0 + DILM9PKZM0 + DILM12PKZM0 + DILM15MSC-D-0,25-M7...bis MSC-D-16-M15...

    BBA0-25101451

    4

    In combination withindividual componentsPKZM0 and DILM DOLstarter use PKZM0-XDM12.

    690 32 AWG 10(6 mmB) 45 200 2 PKZM0 + DILM17PKZM0 + DILM25PKZM0 + DILM32MSC-D-16-M17...bis MSC-D-32-M32...

    BBA0-32101452

    In combination withindividual componentsPKZM0 and DILM useelectrical contact modulePKZM0 XM32DE.

    690 63 AWG 8(10 mmB)

    55 260 2 PKZM4 + DILM17PKZM4 + DILM25PKZM4 + DILM32PKZM4 + DILM40PKZM4 + DILM50PKZM4 + DILM65

    BBA4L-63101459

    For electrical connection forPKZM4 + DILM17 DILM32: MVS-LB0-0M-GPKZM4 + DILM40 DILM65: PKZM4-XM65DEcan be used.

    690 63 AWG 8(10 mmB)

    72 260 2 PKZ2 + DILM7PKZ2 + DILM9PKZ2 + DILM12PKZ2 + DILM15PKZ2 + DILM17PKZ2 + DILM25PKZ2 + DILM32PKZ2 + DILM40

    BBA2L-63101480

    For electrical connection forPKZ2 + DILM7 DILM12:MVS-LB0-00M-GPKZ2 + DILM15 DILM32:MVS-LB0-0M-Gcan be used.

    For reversing starters

    690 25 AWG 12(4 mmB)

    90 200 1 PKZM0 + 2xDILM7-01PKZM0 + 2xDILM9-01PKZM0 + 2xDILM12-01MSC-R-0,25-M7...bis MSC-R-12-M12...

    BBA0R-25101453

    2 In combination withindividual componentsPKZM0 and DILM DOLreversing starter usePKZM0-XRM12.

    690 32 AWG 10(6 mmB)

    90 200 2 PKZM0 + 2xDILM17-01PKZM0 + 2xDILM25-01PKZM0 + 2xDILM32-01MSC-R-16-M17...bis MSC-R-32-M32...

    BBA0R-32101454

    2 In combination withindividual componentsPKZM0 and DILM useelectrical contact modulePKZM0 XM32DE andreversing wiring set DILM32-XRL.

    BBA

  • 8/9/2019 Kapitel 08 G Online

    16/59

    Moeller HPL0211-2007/2008

    8/20

    http://catalog.moeller.net

    PKZM01,PKZM

    0,PKZM4

    OrderingBusbar adapter

    Ratedoperational voltage

    Ratedoperational current

    Terminalcapacity

    Adap-terwidth

    Adap-terlength

    DINrail

    For use with Part no.Article no.

    Pricesee pricelist

    Std.pack

    Notes

    Ue Ie

    V A mm mm Quan-tity

    Component adapter, 3 pole

    Approved to UL 508.For fitting to flat Cu-busbars with 60 mm between busbar centres, suitable for 5 mm and 10 mmbusbar thickness.

    For starters with springloaded terminals

    690 16 AWG 14(2.5 mmB)

    45 200 2 PKZM0-C + DILMC7PKZM0-C + DILMC9PKZM0-C + DILMC12

    BBA0C-16101455

    4 off According to UL 508: Ie= 12 A

    690 16 AWG 14

    (2.5 mmB)

    90 200 2 PKZM0-C + 2x

    DILMC7-01PKZM0-C + 2xDILMC9-01PKZM0-C + 2xDILMC12-01

    BBA0RC-16

    101456

    2 off According to UL 508: Ie

    = 12 A

    Motor-protective circuit-breakers

    690 63 AWG 8(10 mmB)

    54 200 1 PKZM4 BBA4-63101457

    4 off

    690 63 AWG 8(10 mmB)

    72 200 1 PKZ2 BBA2-63101458

    4 off

    Universal adapterFor universal use

    690 25 AWG 12(4 mmB)

    45 200 2 BBA0-25/2TS101481

    4 off Mounting rail can beoffset on 1.25 mm grid.

    Empty moduleWithout electrical contacts

    45 200 2 BBA0/2TS-L101482

    4 off Mounting rail can beoffset on 1.25 mm grid.For use withimplementation ofreversing and star-deltastarters.

    54 200 2 BBA4/2TS-L101483

    4 off

    Side mounted moduleCan be plugged into both sides

    9 200 BBA-XSM101484

    10 off Can be grouped on thebusbar adapter toextend mounting width

    BBA

  • 8/9/2019 Kapitel 08 G Online

    17/59

    8/21

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    Motor-protectivecircuit-breakers

    PKZM01,

    PKZM

    0,

    PKZM4

    OrderingWiring sets

    For use with Part no.Article no.

    Pricesee pricelist

    Std. pack Notes

    Wiring set

    DOL starters

    PKZM0 + DILM7PKZM0 + DILM9PKZM0 + DILM12PKZM0 + DILM15

    PKZM0-XDM12283149

    1 off Comprised of: Mechanical connection element for PKZM0 and contactor Main current wiring between PKZM0 and contactor in tool-less plug

    connection Cable routingAs auxiliary contact DILA-XHIT...usea5/29

    PKZM0 + DILM17PKZM0 + DILM25PKZM0 + DILM32

    PKZM0-XDM32283153

    1 off Comprised of: Top-hat rail adapter plate Main current wiring between PKZ and contactor

    Reversing starters

    PKZM0 + DILM7-01PKZM0 + DILM9-01

    PKZM0 + DILM12-01

    PKZM0-XRM12283185

    1 off Comprised of: Mechanical connection element for PKZM0 and contactor

    Reversing starter main current wiring in tool-less plug connection Control cables for electrical interlocking in tool-less plug connection: K1M: A1 K2M: 21 K1M: 21 K2M: A1 K1M: A2 K2M: A2

    Cable routingAs auxiliary contact DILA-XHIT...usea5/29Cannot be combined with AGM-PKZ0.

    PKZM0 + DILM17PKZM0 + DILM25PKZM0 + DILM32

    PKZM0-XRM32283189

    1 off Comprised of: Top-hat rail adapter plate Reversing starter main current wiring

    Star-delta starterPKZM0 + DILM7PKZM0 + DILM9PKZM0 + DILM12PKZM0 + DILM15

    PKZM0-XSM12239346

    1 off Comprised of: Top-hat rail adapter plate Main current wiring between PKZM0 and contactor Electrical interlock between delta and star contactor Use as contactor auxiliary switch DILA-XHIT...a5/29

    PKZM0 + DILM17PKZM0 + DILM25PKZM0 + DILM32

    PKZM0-XSM32239347

    1 off Comprised of: Top-hat rail adapter plate Main current wiring between PKZM0 and contactor

    Electric contact module

    PKZM0 + DILM17PKZM0 + DILM25PKZM0 + DILM32

    PKZM0-XM32DE239349

    5 off Main current wiring between PKZM0 and contactor Use only in combination with busbar adapter

    PKZM4 + DILM40PKZM4 + DILM50PKZM4 + DILM65

    PKZM4-XM65DE101056

    5 off Main current wiring between PKZM4 and contactor Use only in combination with busbar adapter

    Top-hat rail adapter plate

    PKZM0-XDM12PKZM0-XRM12

    PKZM0-XC45283132

    4 off Comprised of: 45 mm wide adapter plate Connection element for side-by-side positioning of further plates

    PKZM4 + DILM40PKZM4 + DILM50PKZM4 + DILM65

    PKZM4-XC55/2101054

    4 off Comprised of: 55 mm wide adapter plate Connection cams for further plates

    For use with reversing and star-delta starters

    Side mountedmodule

    PKZM0-XS239354

    10 off Can be grouped on the top-hat rail adapterExpansion of the mounting width by 9 mm.

    Connection element PKZM0-XCM239359

    50 off For connection of several top-hat rail adapter

    PKZM0, PKZM4

  • 8/9/2019 Kapitel 08 G Online

    18/59

    Moeller HPL0211-2007/2008

    8/22

    http://catalog.moeller.net

    PKZM01,PKZM

    0,PKZM4

    OrderingThree-phase commoning links

    Circuit-breaker Length Unit width Part no.Article no.

    Pricesee pricelist

    Std. pack Notes

    Number mm mm

    Three phase commoning link, power feed to terminals 1, 3, 5

    Protection against direct contact (touch-proof), Ue = 690 V, Iu = 63 Acan be lengthened by rotated mounting

    For PKZM0-... without side mounted auxiliary contacts or voltage releases

    2 90 45 B3.0/2-PKZ0063961

    10 off For parallel power feed to severalmotor-protective circuit-breakerson terminals 1, 3, 53 135 45 B3.0/3-PKZ0

    232289

    4 180 45 B3.0/4-PKZ0063960

    5 225 45 B3.0/5-PKZ0232290

    For motor-protective circuit-breaker each with an auxiliary contact or trip-indicatingauxiliary contact fitted on the right

    2 99 45 + 9 B3.1/2-PKZ0044945 10 off For parallel power feed to severalmotor-protective circuit-breakerson terminals 1, 3, 53 153 45 + 9 B3.1/3-PKZ0

    044946

    4 207 45 + 9 B3.1/4-PKZ0044947

    5 261 45 + 9 B3.1/5-PKZ0044948

    For PKZM0-... with one auxiliary contact each and a trip-indicating auxiliary contactfitted on right or a voltage release fitted on left

    2 108 45 + 18 B3.2/2-PKZ0063963

    10 off For parallel power feed to severalmotor-protective circuit-breakerson terminals 1, 3, 54 234 45 + 18 B3.2/4-PKZ0

    06395910 off

    Shroud for unused terminals

    Protection against direct contact.For closing off non-used connections on the three phase commoning link B3...-PKZ0

    H-B3-PKZ0032721

    20 off

    Incoming terminal

    BK25/3-PKZ0032720

    5 off For three-phase commoning link,protected against accidentalcontact, Ue = 690 V, Iu = 63 AFor conductor cross-sections:2.5 25 mm2 stranded2.5 16 mm2 flexible with ferrulesAWG 14 6, for use on terminals 1,3, 5

    Three phase commoning link, power feed to terminals 2, 4, 6

    Protection against direct contact (touch-proof), Ue = 690 V, Iu = 63 Acan be lengthened by rotated mounting

    For PKZM0-... without side mounted auxiliary contacts or voltage releases

    2 90 45 B3.0/2-PKZ0-U292387

    5 off For paral lel power feed to severalmotor-protective circuit-breakerson terminals 2, 4, 63 135 45 B3.0/3-PKZ0-U

    292388

    4 180 45 B3.0/4-PKZ0-U292389

    5 225 45 B3.0/5-PKZ0-U

    292880

    B3PKZ0, B3PKZ0-U

  • 8/9/2019 Kapitel 08 G Online

    19/59

    8/23

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    Motor-protectivecircuit-breakers

    PKZM01,

    PKZM

    0,

    PKZM4

    OrderingThree-phase commoning links

    Circuit-breaker

    Length Unit width Part no.Article no.

    Priceseeprice list

    Std. pack

    Number mm mm

    For motor-protective circuit-breaker each with an auxiliary contact or trip-indicatingauxiliary contact fitted on the right

    2 99 45 + 9 B3.1/2-PKZ0-U292881

    5 off For parallel power feed toseveral motor-protectivecircuit-breakers on terminals2, 4, 6

    3 153 45 + 9 B3.1/3-PKZ0-U292882

    4 207 45 + 9 B3.1/4-PKZ0-U292883

    5 261 45 + 9 B3.1/5-PKZ0-U292884

    Shroud for unused terminals

    Protection against direct contact.For closing off non-used connections on the three phase commoning link B3...-PKZ0-U

    H-B3-PKZ0-U292885

    10 off

    Incoming terminal

    BK25/3-PKZ0-U292886

    10 off For three-phase commoninglink, protected againstaccidental contact,Ue = 690 V,Iu = 63 AFor conductor cross-sections:2.5 25 mm2 stranded2.5 16 mm2 flexible withferrulesFor use on the terminals 2, 4, 6

    Three-phase commoning link

    Protection against direct contact (touch-proof), Ue = 690 V, Iu = 128 A

    For motor-protective circuit-breakers/(high-capacity) compact starters without side-fittedauxiliary contact or voltage releases

    2 110 55 B3.0/2-PKZ4220220

    1 off

    3 165 B3.0/3-PKZ4220221

    4 220 B3.0/4-PKZ4220222

    For PKZM4 each with an auxiliary contact or trip-indicating auxiliary contact fitted on theright

    2 119 55 + 9 B3.1/2-PKZ4220223

    1 off

    3 183 B3.1/3-PKZ4220224

    4 247 B3.1/4-PKZ4220225

    For PKZM4 with one auxiliary contact each or trip-indicating auxiliary contact fitted on rightor a voltage release fitted on left

    2 128 55 + 18 B3.2/2-PKZ4220226

    1 off

    4 274 55 + 18 B3.2/4-PKZ4220227

    1 off

    Shroud for unused terminals

    Protection against direct contact.To cover unused terminals on three-phase commoning link

    H-B3-PKZ4220228

    10 off

    B3PKZ0-U, B3-PKZ4

  • 8/9/2019 Kapitel 08 G Online

    20/59

    Moeller HPL0211-2007/2008

    8/24

    http://catalog.moeller.net

    motor-protectivecircuit-breakers

    OrderingActuating voltages

    Shunt release, undervoltage release

    When ordered separately

    AC A-PKZ0(...) U-PKZ0(...)

    Article no.1) Article no.1)

    Standard voltage see price list see price list

    24V 50Hz 073181 073129

    110V 50Hz 073184 073132

    220V 50Hz 073186 073134

    230V 50Hz 073187 073135

    240V 50Hz 073188s 073136

    380V 50Hz 073189 073137

    400V 50Hz 073190 073138

    415V 50Hz 073191 073139

    120V 60Hz 073195 073143

    240 V 60 Hz 073198 073146

    440V 60Hz 082164 082161

    480V 60Hz 073199 073147

    Non-standard voltages with the exception of the shown stand-

    ard voltages2).see price list see price list

    ...V 50Hz (24 500V)3) 982162

    ...V 60Hz (24 600V)3) 982163

    DC

    Standard voltage see price list see price list

    24V DC 073200

    073203

    Notes 1) The article no. is formed from the combination of part no. and actuating voltage.2) With non-standard voltages the required actuating voltage from the defined range (......V) must be stated.3) Minimum order quantity: 10 off

  • 8/9/2019 Kapitel 08 G Online

    21/59

    8/25

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    Motor-protectivecircuit-breakersPKZ2

    System overviewMotor-protective circuit-breakers

    Motor protection, system protection, conductor and cable protection

    1

    4

    5

    6

    7

    8

    2

    3

    10

    10

    9

    Basic units

    Motor-protective circuit-breakers 1

    aPage 8/27

    Circuit-breakers 1

    aPage 8/27

    Add-on functions

    Contact module 6

    aPage 8/41

    High-capacity contact module 7

    aPage 8/41

    Auxiliary contacts 10

    aPage 8/35

    Current limiter 8

    aPage 8/35

    Voltage releases 4

    aPage 8/37

    Remote operators 5

    aPage 8/39

    Mounting accessories

    Mounting/wiring 2

    aPage 8/44

    Door coupling handle IP65 9

    aPage 8/33

    Insulated enclosures 3

    aPage 8/33

    PKZ2

  • 8/9/2019 Kapitel 08 G Online

    22/59

    Moeller HPL0211-2007/2008

    8/26

    Moeller HPL0211-2007/2008http://catalog.moeller.net http://catalog.moeller.net

    Ordering Motor-protective circuit-breakers, circuit-breakers Mot

    Max. motor rating Rateduninterruptedcurrent

    Setting range Part no.Article no.

    Pricesee pricelist

    Std.pack

    Notes

    AC-3 Iu Overload releases Short-c ircuit releases

    220 V230 V240 V

    380 V400 V415 V

    440 V 500 V 660 V690 V

    A Ir Irm

    P P P P P A A

    kW kW kW kW kW

    Motor-protective circuit-breakers, Type 1 and Type 2 coordination

    0.09 0.12 0.18 0.25 0.25 0.6 0.40.6 58 PKZ2/ZM-0,6021859

    1 off Single-phasing sensitiviIEC/EN 60947-4-1

    Overload release, adjusIr = 0.6 1.0xIuShort-circuit release, adIrm = 8.5 14xIu fact12xIu

    World market devices tUL/CSA

    0.12 0.25 0.25 0.37 0.55 1 0.61 814 PKZ2/ZM-1026605

    0.25 0.55 0.55 0.75 1.1 1.6 11.6 1422 PKZ2/ZM-1,6028978

    0.37 0.75 1.1 1.1 1.5 2.4 1.62.4 2035 PKZ2/ZM-2,4031351

    0.75 1.5 1.5 2.2 3 4 2.44 3555 PKZ2/ZM-4033724

    1.1 2.2 3 3 4 6 46 5080 PKZ2/ZM-6036097

    2.2 4 4 5.5 7.5 10 610 80140 PKZ2/ZM-10038470

    4 7.5 9 9 12.5 16 1016 130220 PKZ2/ZM-16040843

    5.5 12.5 12.5 15 22 25 1625 200350 PKZ2/ZM-25043216

    7.5 15 17.5 22 22 32 2432 275425 PKZ2/ZM-32045589

    11 20 22 24 30 40 3240 350500 PKZ2/ZM-40

    047962

    Circuit-breakers

    For protection of cables and conductors

    10 610 5080 PKZ2/ZM-10-8050335

    1 off Overload release, adjusIr = 0.6 1.0xIuShort-circuit release, adIrm = 5.0 8.5xIu fact5xIu

    16 1016 80140 PKZ2/ZM-16-8052708

    25 1625 130210 PKZ2/ZM-25-8055081

    32 2432 160280 PKZ2/ZM-32-8057454

    40 3240 200350 PKZ2/ZM-40-8059827

    I>

    I>

    PKZ2

  • 8/9/2019 Kapitel 08 G Online

    23/59

  • 8/9/2019 Kapitel 08 G Online

    24/59

    Moeller HPL0211-2007/2008

    8/30

    http://catalog.moeller.net

    p

    OrderingMotor protection modules

    Rateduninterrupted current

    Part no.Article no.

    Pricesee pricelistRG

    Std.pack

    Iu

    A

    Basic unit, 3-pole

    40 PKZ2026606

    1 off

    PKZ2 basic unit with S-PKZ2 high-capacity contactmodule fitted (1 M, 1 B)Supplied on C-PKZ2 clipplate. Cannot be combinedwith Z...-0.6-PKZ2.

    40 PKZ2/S(230V50HZ)063572

    PKZ2 basic unit with SE1A/11-PKZ2 contact modulefitted (1 M, 1 B) Supplied onC-PKZ2 clip plate. Cannotbe combined with Z...-0.6-PKZ2.

    40 PKZ2/SE1A/11(230V50HZ)082142

    Circuit diagram forZM...PKZ2

    M...PKZ2

    ZMR...PKZ2

    Adjustable:

    Hq manual position or

    Aq automatic position

    For EEx e applications the 95/96 N/C contact must always be usedto de-energize the (high-capacity) contact module or contactor.

    Motor-protective trip blocks ZMR-...-PKZ2 cannot be combinedwith U/A voltage releases and RE/RS remote operators.

    Further actuating voltages a8/45

    Manual a8/44

    I> I>

    95

    96

    97

    98

    H A

    I>

    Max. motor rating Rateduninter-ruptedcurrent

    Setting range Part no.Article no.

    Pricesee pricelist

    Std.pack

    AC-3 Overloadreleases

    Short-circuitreleases

    220 V230 V240 V

    380 V400 V415 V

    440 V 500 V 660 V690 V

    P P P P P I u Ir Irm

    kW kW kW kW kW A A A

    Motor-protective trip blocks, 3-pole

    With overload release

    0.09 0.12 0.18 0.25 0.25 0.6 0.40.6 58 ZM-0,6-PKZ2024232

    1 off Single-phasing sensitivityto IEC/EN 60947-4-1

    Suitable for the protectionof EEx e motorsPTB Certificate No.: 3.53-388.299

    Extension to ATEX appliedfor

    Overload releases,adjustableIr = 0.6 1.0xIu

    Adjustable short-circuitrelease

    Irm = 8.5 14 xIuFactory set to 12xIu

    0.12 0.25 0.25 0.37 0.55 1 0.61 814 ZM-1-PKZ2028979

    0.25 0.55 0.55 0.75 1.1 1.6 11.6 1422 ZM-1,6-PKZ2031352

    0.37 0.75 1.1 1.1 1.5 2.4 1.62.4 2035 ZM-2,4-PKZ2033725

    0.75 1.5 1.5 2.2 3 4 2.44 3555 ZM-4-PKZ2036098

    1.1 2.2 3 3 4 6 46 5080 ZM-6-PKZ2038471

    2.2 4 4 5.5 7.5 10 610 80140 ZM-10-PKZ2040844

    4 7.5 9 9 12.5 16 1016 130220 ZM-16-PKZ2043217

    5.5 12.5 12.5 15 22 25 1625 200350 ZM-25-PKZ2045590

    7.5 15 17.5 22 22 32 2432 275425 ZM-32-PKZ2047963

    11 20 22 24 30 40 3240 350500 ZM-40-PKZ2050336

    PKZ2, PKZ2/S

  • 8/9/2019 Kapitel 08 G Online

    25/59

    8/31

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    PKZ2motor-pr

    otectivecircuit-breaker

    OrderingMotor protection modules

    220 240 V Rateduninterruptedcurrent

    Setting range Part no.Article no.

    Pricesee pricelist

    Std.pack

    AC-3 Overloadreleases

    Short-circuitreleases220 V

    230 V240 V

    380 V400 V415 V

    440 V 500 V 660 V690 V

    P P P P P I u Ir Irm

    kW kW kW kW kW A A A

    Motor-protective trip blocks, 3-pole

    With overload relay function, with Hand/Auto position

    0.09 0.12 0.18 0.25 0.25 0.6 0.40.6 58 ZMR-0,6-PKZ2033943

    1 off Phase-failure sensit ivityand overload/short-circuit release settingoptions and PTB, seeabove.When using motor-protective trip blockswith an overload relayfunction, the motor-protective circuit-breakerdoes not trip in the eventof an overload. Theoverload indication isproduced by means oftwo auxiliary contacts.Different potentials maybe applied to the twoauxiliary contacts.

    0.12 0.25 0.25 0.37 0.55 1 0.61 814 ZMR-1-PKZ2033950

    0.25 0.55 0.55 0.75 1.1 1.6 11.6 1422 ZMR-1,6-PKZ2033952

    0.37 0.75 1.1 1.1 1.5 2.4 1.62.4 2035 ZMR-2,4-PKZ2033955

    0.75 1.5 1.5 2.2 3 4 2.44 3555 ZMR-4-PKZ2

    033957

    1.1 2.2 3 3 4 6 46 5080 ZMR-6-PKZ2033966

    2.2 4 4 5.5 7.5 10 610 80140 ZMR-10-PKZ2033967

    4 7.5 9 9 12.5 16 1016 130220 ZMR-16-PKZ2033968

    5.5 12.5 12.5 15 22 25 1625 200350 ZMR-25-PKZ2033969

    7.5 15 17.5 22 22 32 2432 275425 ZMR-32-PKZ2033973

    11 20 22 24 30 40 3240 350500 ZMR-40-PKZ2033975

    Without overload release

    0.6 58 M-0,6-PKZ2004537

    1 off Adjustable short-ci rcuitreleaseIrm = 8.5 14 xIuFactory set to 12xIu

    1 814 M-1-PKZ2004538

    1.6 1422 M-1,6-PKZ2004539

    2.4 2035 M-2,4-PKZ2004540

    4 3555 M-4-PKZ2004541

    6 5080 M-6-PKZ2004542

    10 80140 M-10-PKZ2004543

    16 130220 M-16-PKZ2004544

    25 200350 M-25-PKZ2004545

    32 275425 M-32-PKZ2004546

    40 350500 M-40-PKZ2004547

    Notes When using the M-...-PKZ2 as short-circuit protection for motors with heavy starting duty, the rated operational current Ie must be up-ratedwhen engineering by the following factors:

    CLASS Factor

    5 1.0

    10 1.0

    15 1.22

    20 1.41

    25 1.58

    30 1.73

    35 1.89

    40 2.0

    ZM(R)-PKZ2, M-PKZ2

  • 8/9/2019 Kapitel 08 G Online

    26/59

    Moeller HPL0211-2007/2008

    8/32

    http://catalog.moeller.net

    p

    OrderingComponents for distribution circuit protection

    Rateduninterruptedcurrent

    Part no.Article no.

    Pricesee pricelist

    Std. pack

    Iu

    A

    Basic unit, 3-pole40 PKZ2

    0266061 off

    Basic unit, 4-pole

    40 PKZ24004521

    1 off Circuit diagram for

    ZM... -PKZ2(4) M... -PKZ2(4)

    I> I>

    Rateduninterruptedcurrent

    Setting range Part no.Article no.

    Pricesee pricelistRG

    Std. pack

    Overloadreleases

    Short-circuitreleases

    Iu Ir Irm

    A A A

    Trip block for distribution circuit protection

    3-pole

    With overload release

    10 610 5080 ZM-10-8-PKZ2062201

    1 off Overload releases, adjustableIr = 0.6 1.0 xIu

    Adjustable short-circuit releaseIrm = 5 8.5 xIu factory set to 5xIu

    16 1016 80140 ZM-16-8-PKZ2059828

    25 1625 130210 ZM-25-8-PKZ2057455

    32 2432 160280 ZM-32-8-PKZ2055082

    40 3240 200350 ZM-40-8-PKZ2052709

    4-pole

    With overload releases in all 4 poles

    10 610 5080 ZM-10-8-PKZ24004526

    1 off Overload releases, adjustableIr = 0.6 1.0 xIu

    Adjustable short-circuit releaseIrm = 5 8.5 xIu factory set to 5xIu

    Circuit-breakers PKZ24/ZM-...-8 protect in all 4-poles.

    16 1016 80140 ZM-16-8-PKZ24004525

    25 1625 130210 ZM-25-8-PKZ24004524

    32 2432 160280 ZM-32-8-PKZ24004523

    40 3240 200350 ZM-40-8-PKZ24004522

    PKZ2, PKZ24, ZM-PKZ

  • 8/9/2019 Kapitel 08 G Online

    27/59

    8/33

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    PKZ2motor-pr

    otectivecircuit-breaker

    OrderingInsulated enclosures

    Colour Part no.Article no.

    Pricesee pricelist

    Std. pack Notes

    For use with

    Insulated enclosures for surface mounting

    For motor-protective circuit-breakers, 3- or 4-pole circuit-breakers

    Degree of protection IP40 Coverwith aperture dimensioned toaccommodate front of breaker,comes with blanking strip

    PKZ2/ZM-... +NHI +AGM + U or A or RE orRS PKZ24/ZM-... + NHI+ AGM + U or A

    CI19EA-PKZ2026234 1 off Built-in IEC/EN 60715top-hat rail, separateterminals for PE(N)- andN

    incl. cable entry 2x PG16/21/29

    L-PKZ0 indicator lightcan be fitted

    Degree of protection IP54 Formounting of (R)H-PKZ2 doorcoupling handle

    PKZ2/ZM-... + NHI +AGM + U or A + (R)H

    CI19EB-PKZ2028607

    Degree of protection IP54 Formounting of (R)H-PKZ2 doorcoupling handle

    PKZ24/ZM-... + NHI +AGM + U or A + (R)H

    CI19ED-PKZ24005145

    For 3-pole compact starters, high-capacity compact starters, combination circuit-breakers (Kombi)

    Degree of protection IP40 Coverwith aperture dimensioned toaccommodate front of breaker,comes with blanking strip

    PKZ2/ZM-.../S(E1A) +NHI + AGM + RE or RSor U or A

    CI23EA-PKZ2087936

    1 off Complete with L3/5-CI23 mounting plate

    Will accept compactstarter or PKZ2/ZM-.../Shigh-capacity compactstarter without clipplate

    Degree of protection IP54 Formounting of (R)H-PKZ2 doorcoupling handle

    PKZ2/ZM-.../S + NHI +AGM + U or A + (R)H

    CI23EB-PKZ2090309

    Insulated enclosures for flush mounting

    For motor-protective circuit-breakers, 3- or 4-pole circuit-breakers

    Degree of protection IP41 Greyfront plate with retaining frameIntegral PE(N) terminal

    PKZ2/ZM-... + NHI +AGM PKZ2/ZM-... + Uor A PKZ24/ZM-...+ NHI + AGMPKZ2/ZM-...+U or A (undervoltageor shunt release)

    PKZ24/ZM-...

    E-PKZ2003218

    1 off For mounting in sideplate or door.Vertical mountingposition.L-PKZ0 indicator lightcan be fitted

    Degree of protection IP54 (R)H-PKZ2 door coupling handle alsorequired as standard

    PKZ2/ZM-... + NHI +AGM PKZ2/ZM-... + Uor A PKZ24/ZM-...+ NHI + AGMPKZ2/ZM-...+U or A (undervoltageor shunt release)PKZ24/ZM-...

    E54-PKZ2033939

    Neutral terminal

    For connection of a 5th conductor

    E-PKZ2E54-PKZ2

    N-PKZ2003219

    1 off

    Door coupling handlesDegree of protection IP65

    For use as main switch to IEC/EN 60204

    Black PKZ2-XH106127

    1 off Lockable in 0 or IpositionSuitable for 3 padlockswith 4 8 mm haspthickness

    For use in MCC distributionboards with PKZ2 turnedthrough 90. For use as mainswitch according to EN 60204

    Black PKZ2-XH-MCC106130

    For use as a main switch withEmergency-Stop function, toEN 60204

    Red-yellow

    PKZ2-XRH106128

    Plug-fit extension shaft for door coupling handle

    Can be extended as required for mounting depths from 171 - 300 mmPKZ2-XAH106129

    1 off

    CI-PKZ, E-PKZ

  • 8/9/2019 Kapitel 08 G Online

    28/59

  • 8/9/2019 Kapitel 08 G Online

    29/59

  • 8/9/2019 Kapitel 08 G Online

    30/59

  • 8/9/2019 Kapitel 08 G Online

    31/59

    Moeller HPL0211-2007/2008

    8/40

    Moeller HPL0211-2007/2008http://catalog.moeller.net http://catalog.moeller.net

    Ordering Contact module

    Contact sequence 220 240 V Auxiliary contacts For use with Part no.Article no.

    Pricesee pricelist

    Std. pack

    AC-3 N/O =Normally

    N/C =Normally

    220 V230 V240 V

    380 V400 V415 V

    440 V 500 V 660 V690 V

    P P P P P

    kW kW kW kW kW

    Contact module

    11 20 22 24 30 1 N/O 1 N/C PKZ2(4) SE1A/11-PKZ2(230V50HZ)063711

    1 off Clip platordered circuit-bcan be srail withheight.Can be mbelow), DC versiHI10-S-PconfigurchangedDC versiHigh-capsuitable

    11 20 22 24 30 2 M PKZ2(4) SE1A/20-PKZ2(230V50HZ)063718

    11 20 22 24 30 1 M PKZ2(4) SE1A-G-10-PKZ2(24VDC)058856

    High-capacity contact module with current limiting contacts

    11 20 22 24 30 1 N/O 1 N/C PKZ2(4) S-PKZ2(230V50HZ)063696

    1 off

    11 20 22 24 30 2 N/O PKZ2(4) S/HI20-S-PKZ2(230V50HZ)063703

    11 20 22 24 30 1 N/O PKZ2(4) S-G-PKZ2(24VDC)070921

    Suppressor circuit Varistor suppressor

    24 48 V AC S(E1A)-...-PKZ2 VGSPKZ48063974

    10 off For (highHz AC op

    110 250 V AC VGSPKZ250063973

    380 415 V AC VGSPKZ415

    063972

    Bases for separate mounting

    S(E1A)-...-PKZ2CL-PKZ2

    EZ-PKZ2028596

    1 off For retroor curren

    With sepfor HI11-Can be srail, or s

    T

    13 21

    2214A2

    A1

    T

    13 23

    14 24

    A1

    A2

    T

    13

    14

    A1

    24 V DC

    A2

    T

    13

    1422

    A1

    A2

    21

    I>>

    T

    1323

    1424

    A1

    A2

    I>>

    T

    A2

    13

    14

    24 V DC

    A1

    I>>

    A1

    A2

    SE/-PKZ, VGSPKZ

  • 8/9/2019 Kapitel 08 G Online

    32/59

    Moeller HPL0211-2007/2008

    8/42

    Moeller HPL0211-2007/2008http://catalog.moeller.net http://catalog.moeller.net

    Ordering Accessories for contact modules

    Contacts Contact diagram Contact sequence Part no.Article no.

    Pricesee price list

    Std. pack

    N/O = Normallyopen

    N/C = Normallyclosed

    Control circuit terminal

    ST-PKZ2010998

    3 off

    Auxiliary contacts for (high-capacity) contact module, separate mountingCan be fitted on side of base for separate mounting

    1 N/O 1 N/C HI11-S/EZ-PKZ2090305

    1 off

    Auxiliary contacts for (high-capacity) contact module

    Auxiliary contacts to replace integral auxiliary contacts in (high-capacity) contact module.Replacement not possible with SE1A-G-10-PKZ2 contact module or S-G-PKZ2 high-capacity contact module.

    1 N/O 1 N/C HI11-S-PKZ2033936

    1 off

    2 N/O HI20-S-PKZ2033935

    1 off

    Mechanical interlock

    For mechanically interlocking two separately mounted (high-capacity) contact modules or two (high-capacity) compact starters.

    Four end brackets suppliedCan be combined with S-PKZ2 high-capacity contact module Serial No. 01.

    MV-PKZ2033938

    1 off

    L1L2L3

    HI

    Off

    L1L2L3

    HI

    On

    32 44

    31 43

    HI-PKZ2

  • 8/9/2019 Kapitel 08 G Online

    33/59

    Moeller HPL0211-2007/2008

    8/44

    http://catalog.moeller.net

    p

    OrderingAccessories

    For use with Part no.Article no.

    Pricesee pricelist

    Std. pack

    Clip plate

    For optional snap fitting and M4 screw fixing of circuit-breaker with (high-capacity) contact module or current limiter

    Can be used with AD busbar adapter C-PKZ2052710 2 off Can be used with AD busbarCan be snap fitted to one IEC/EN 60715top-hat rail, height 15 mm, or two top-hat rails, greater than 10 mm

    Three-phase commoning link

    For wiring 3 PKZ2s, space is provided for either 2auxiliary contacts or 2 voltage releases

    B3.1/3-PKZ2033940

    5 off Can be extended to several PKZ2s byrotated mounting, protected againstaccidental contactUe = 690 V, Iu = 120 A, short-circuitproofFor wiring of 2 PKZ2s, space is provided for either

    1 auxiliary contact or 1 voltage release

    B3.1/2-PKZ2

    063969

    5 off

    Incoming terminal

    For three-phase commoning link, protected against accidental contactUe = 690 V, Iu = 120 A

    BK50/3-PKZ2033941

    2 off For connection of:max. 1x 50 mm2 or 2x 35 mm2;above one another min. 1 x 1mm2 or 2x 1 mm2

    Shroud for unused terminals

    Protection against direct contact.To cover unused terminals on three-phase commoning link

    H-B3-PKZ2063968

    10 off Snap-fitting option must be available onthe three-phase commoning link

    Padlocking feature

    For locking rear mounting circuit-breakers in the OFF position when thepanel door is open.

    SVB-PKZ2050337

    5 off Suitable for 3 padlocks with 5 8 mmhasp thickness

    Coding pins

    For coding the trip block to match the PKZ2(4) basic unit Coding in binary

    CS-PKZ2055083

    1 off

    Documentation

    PKZM2 motor-protective circuit-breakers, overloadmonitoring of EEx e

    German/English AWB1210-1485D/GB266166

    1 off

    C-PKZ, B3-PKZ

  • 8/9/2019 Kapitel 08 G Online

    34/59

    8/45

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    PKZ2motor-pr

    otectivecircuit-breaker

    OrderingActuating voltages

    Compact starterContact modules with 1 N/O and 1 N/C contact

    AC PKZ2/ZM-1/SE1A/11(...)

    PKZ2/ZM-1.6/SE1A/11(...)

    PKZ2/ZM-2.4/SE1A/11(...)

    PKZ2/ZM-4/SE1A/11(...)

    PKZ2/ZM-6/SE1A/11(...)

    Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)

    Standard voltage see price list see price list see price list see price list see price list

    230V 50Hz,240V 60Hz

    063364 063372 063382 063392 063402

    110V 50/60Hz 063408

    230V 50/60Hz 063369 063379 063389 063399 063409

    Compact starterContact modules with 1 N/O and 1 N/C contact

    AC PKZ2/ZM-10/SE1A/11(...)

    PKZ2/ZM-16/SE1A/11(...)

    PKZ2/ZM-25/SE1A/11(...)

    PKZ2/ZM-32/SE1A/11(...)

    PKZ2/ZM-40/SE1A/11(...)

    PKZ2/SE1A/11(...)

    Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)

    Standard voltage see price list see price list see price list see price list see price list see price list

    230V 50Hz,240V 60Hz

    063412 063422 063432 063442 063452 082142

    110V 50/60Hz 063418 063428 063438 063448 063458

    230V 50/60Hz 063419 063429 063439 063449 063459 082148

    High-capacity compact starterContact modules with 1 N/O and 1 N/C auxiliary contact

    AC PKZ2/ZM-1/S(...) PKZ2/ZM-1.6/S(...) PKZ2/ZM-2.4/S(...) PKZ2/ZM-4/S(...) PKZ2/ZM-6/S(...)

    Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)

    Standard voltage see price list see price list see price list see price list see price list

    230V 50Hz,

    240V 60Hz

    063472 063482 063492 063502 063512

    110V 50/60Hz 063478 063488 063498 063508 063518

    230V 50/60Hz 063479 063489 063499 063509 063519

    High-capacity compact starterContact modules with 1 N/O and 1 N/C auxiliary contact

    AC PKZ2/ZM-10/S(...)

    PKZ2/ZM-16/S(...)

    PKZ2/ZM-25/S(...)

    PKZ2/ZM-32/S(...)

    PKZ2/ZM-40/S(...)

    PKZ2/S(...)

    Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)

    Standard voltage see price list see price list see price list see price list see price list see price list

    110V 50Hz,120V 60Hz

    063570

    230V 50Hz,240V 60Hz

    063522 063532 063542 063552 063562 063572

    24V 50/60Hz 063577

    110V 50/60Hz 063528 063538 063548 063558 063568

    230V 50/60Hz 063529 063539 063549 063559 063569 063579

    Notes 1) The article no. is formed from the combination of part no. and actuating voltage. Devices with dual-voltage coils are to beordered under a single order number.

    PKZ/S

  • 8/9/2019 Kapitel 08 G Online

    35/59

    Moeller HPL0211-2007/2008

    8/46

    http://catalog.moeller.net

    p

    Motor-protective circuit-breaker PKZ2Actuating voltages

    Undervoltage release

    When ordered separately

    AC U-PKZ2(...) U-HI20-PKZ2(...) UVHI-PKZ2(...)

    Article no.1) Article no.1) Article no.1)

    Standard voltage see price list see price list see price list

    24V 50Hz 055085 063649

    110V 50Hz,

    120V 60Hz

    063655

    220V 50Hz,

    240V 60Hz

    065685 063656

    230V 50Hz,

    240V 60Hz

    065766 065768 065770

    400V 50Hz,

    440V 60Hz

    065767

    24V 50/60Hz 063659

    Non-standard voltages with the exception of the shown

    standard voltages2).

    see price list

    ...V 50Hz (24 600V) 9075373)

    ...V 60Hz (24 600V) 9075383)

    DC

    Standard voltage see price list

    24V DC 014463

    48V DC 028701

    Notes 1) The article no. is formed from the combination of part no. and actuating voltage.Devices with dual-voltage coils are to be ordered under a single order number.

    2) With non-standard voltages the required actuating voltage from the defined range (......V) must be stated.3) Minimum order quantity: 10 units.

    (High capacity)contact moduleSingle coil for (high-capacity) contact module

    AC S-PKZ2(...) S/HI20-S-PKZ2(...) SE1A/11-PKZ2(...) SE1A/20-PKZ2(...)

    Article no.1) Article no.1) Article no.1) Article no.1)

    Standard voltage see price list see price list see price list see price list

    24V 50Hz 026609

    48V 50Hz 062651 056383

    240V 50Hz 001882 057048 058716 058717

    24V 60Hz 062501

    110V 50Hz,

    120V 60Hz

    063694 063701 063709 063716

    190V 50Hz,

    220V 60Hz

    063695 063710 063717

    220V 50Hz,

    240V 60Hz

    063699 063706

    230V 50Hz,

    240V 60Hz

    063696 063703 063711 063718

    400V 50Hz,

    440V 60Hz

    063697 063712 063719

    24V 50/60Hz 062500 058720 058721

    110V 50/60Hz 058696

    230V 50/60Hz 065103 056395 058712 058713

    DC S-G-PKZ2(...) SE1A-G-10-PKZ2(...)

    Article no.1) Article no.1)

    Standard voltage see price list see price list

    24V DC 070921 058856

    Notes 1) The article no. is formed from the combination of part no. and actuating voltage.Devices with dual-voltage coils are to be ordered under a single order number.

    2) With non-standard voltages the required actuating voltage from the defined range (......V) must be stated.

    U-PKZ, S-PKZ

  • 8/9/2019 Kapitel 08 G Online

    36/59

    8/47

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    PKZM01,

    PKZM

    0,

    PKZM4,

    PKZ2

    motor-protectivecircuit-breakers

    EngineeringMotor-protective circuit-breakers

    PKZM0, PKZM4 and PKZ2 in 1 and 2 pole circuitsfoe DC and AC

    Protection of PVC insulated cables against thermal overload with short-circuits

    The table indicates which minimum cable cross-sections are protected by PKZ(M) motor-protective circuit-breakersup to their rated conditional short-circuit current Iq.

    Fuseless installation with PKZ(M), back-up-protection diagrams

    1 3 5

    2 4 6

    I> I> I>

    1 3 5

    2 4 6

    I> I> I>

    Min. cross-section protected

    380 415 V, 50 Hz, Cu mm2

    Device

    Part no.

    4 2,5 1,5 1 0,75

    PKZM0-0.16

    .

    .

    .

    PKZM0-6.3

    PKZM0-10PKZM0-12

    PKZM0-16

    PKZM0-20

    PKZM0-25

    PKZM0-32

    PKZM4-16

    PKZM4-25

    PKZM4-32

    PKZM4-40

    PKZM4-50

    PKZM4-58

    PKZM4-63

    Min. cross-section protected

    380 415 V, 50 Hz, Cu mm2

    Device

    Part no.

    4 2,5 1,5 1 0,75

    PKZ2/ZM-0,6

    .

    .

    .

    PKZ2/ZM-2.4

    PKZ2/ZM-4PKZ2/ZM-6

    PKZ2/ZM-10

    PKZ2/ZM-16

    PKZ2/ZM-25

    PKZ2/ZM-32

    PKZ2/ZM-40

    Icc

    Icn

    PKZM0

    PKZM0

    415 V AC

    Inherentlyshort-circuitproof

    I

    ccrms

    [kA]

    Back-upprotectionrangewith CL-PKZ 0

    Ratedshort-circuitbreakingcapacityrange

    100

    50

    30

    20

    16

    10

    6

    0.16... 10 16 20 25

    PKZM0-...

    +CL-PKZ0

    PKZM0-...

    PKZM0

    Ratedcurrent In[A]

    Inherentlyshort-circuit-proof

    I I

    I

    cn

    cc

    PKZ2/ZM

    at

    Back-upprotectionrangewith CL-PKZ2or S-PKZ2

    Ratedshort-circuitbreakingcapacityrange

    Inherentlyshort-circuitproof

    [kA]

    ccrms

    PKZ2

    415 V AC

    100

    50

    30

    20

    4

    10

    6

    0.6... ...16 25

    PKZ2/ZM-.../SPKZ2/ZM-...+CL

    PKZ2/ZM-...

    32 40

    PKZ2

    Ratedcurrent In[A]

    Inherentlyshort-circuit-proof

    Icc

    Icn

    PKZM4

    PKZM4

    415 V AC

    Inherentlyshort-circuitproof

    I

    ccrms

    [kA]

    Back-upprotectionrangewith CL-PKZ 0

    Ratedshort-circuitbreakingcapacityrange

    100

    50

    30

    20

    16

    10

    6

    16... 3225 40 50 63

    In [A]

    PKZM4-... +CL-PKZ0

    PKZM4-...

    Rated

    current

    Inherently

    short-circuit-proof

    PKZ, PKZM

  • 8/9/2019 Kapitel 08 G Online

    37/59

    Moeller HPL0211-2007/2008

    8/48

    http://catalog.moeller.net

    motor-protectivecircuit-breakers

    EngineeringCharacteristic curves

    PKZM0-...T tripping characteristics (not for PKM0-...), PKZM01

    Let-through characteristics, motor-protective circuit-breaker, transformer-protective circuit-breaker, circuit-breaker for starter combinations

    Motor-protective circuit-breaker let-through characteristics

    PKZM0...-T

    PKZM0-...,PKZM01

    2

    5

    20

    50

    200

    1

    2

    5

    1020

    401

    2

    5

    10

    202 h

    1.5 2 3 4 6 8 10 15 20 30

    x Rated operational current

    Seconds

    Milliseconds

    Minutes

    2

    5

    20

    50

    200

    1

    2

    5

    1020

    401

    2

    5

    10

    202 h

    1.5 2 3 4 6 8 10 15 20 30

    PKZM4-...

    x Rated operational current

    Seconds

    Milliseconds

    Minutes

    [kA]

    xD

    1

    2

    3

    6

    4

    8

    10

    4.0 A

    6.3 A

    2.5 A

    1.6 A

    0.25 A

    10 A/12 A

    0.1

    0.2

    0.3

    0.4

    0.6

    0.8

    0.01

    0.02

    0.015

    0.03

    0.04

    0.06

    0.08

    1 21.5 3 4 6 8 10 2015 30 40 60 80100

    Ue = 400 V

    16 A20 A25 A32 A

    1 A

    0.4 A

    0.63 A

    PKZM0-....

    PKZM01-....

    PKM0-....

    2Ic

    c

    Icc rms

    [kA]

    Ue = 400 V

    PKZM01PKZM0-....PKM0-....

    104

    1.5

    2

    3

    6

    4

    8105

    4.0 A

    6.3 A

    2.5 A

    1.6 A

    1.0 A

    10 A/12 A

    103

    2

    1.5

    3

    4

    6

    8

    102

    2

    1.5

    3

    4

    6

    8

    1 21.5 3 4 6 8 10 2015 30 40 60 80 100

    16 A20 A25 A32 A

    [kA]

    [A2 s]

    yZ

    1st

    half

    -wav

    e

    Icc rms

    Ue = 400 V

    10

    10 100

    63/58 A50/40/32 A

    25 A

    16 A

    PKZM4

    11

    100

    [kA]D

    2Ic

    c

    Icc rms [kA]

    105

    106

    104

    102

    1 10 100

    103

    Ue = 400 V

    63/58 A50/40/32 A

    25 A

    16 A

    PKZM4y

    [kA]

    [A2 s]

    Z

    1st ha

    lf-w

    ave

    Icc rms

    PKZM

  • 8/9/2019 Kapitel 08 G Online

    38/59

    8/49

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    PKZM01,

    PKZM

    0,

    PKZM4

    motor-protectivecircuit-breakers

    EngineeringSwitching capacity

    Circuit-breaker switching capacity from serial no. 04

    Rated uninterrupted current Iu

    Rated conditional short-circuit current Iq IEC/EN 60947-4-1

    Rated ultimate short-circuit breaking capacity IcuIEC/EN 60947-2

    Rated service short-circuit breaking capacity Ics

    230 V 400 V 440 V 500 V 690 V

    Iu Iq Icu Ics Iq Icu Ics Iq Icu Ics Iq Icu Ics Iq Icu Ics

    A kA kA kA A1) kA kA kA A1) kA kA kA A1) kA kA kA A1) kA kA kA A1)

    PKZM0, PKZM0...-T, PKM0 with classification type 1 and 2

    0,16 1 150 150 150 N 150 150 150 N N N N

    1,6 150 150 150 N 150 150 150 N N N N

    2,5 150 150 150 N 150 150 150 N N N 5 5 5 50

    4 150 150 150 N 150 150 150 N N N 3 3 3 50

    6,3 150 150 150 N 150 150 150 N N 42 42 6 50 3 3 2 50

    10 150 150 150 N 150 150 150 N 42 42 10 50 42 42 6 50 3 3 2 50

    12 50 50 10 50 50 50 10 50 15 15 10 50 15 15 6 50 3 3 2 50

    16 50 50 10 50 50 50 10 50 15 15 10 50 15 15 6 50 3 3 2 50

    20 50 50 10 50 50 50 10 50 10 10 10 50 6 6 6 50 3 3 2 5025 50 50 10 50 50 50 10 50 10 10 10 50 6 6 6 50 3 3 2 50

    32 50 50 10 50 50 50 10 50 10 10 10 50 6 6 6 50 3 3 2 50

    PKZM0 (PKZM0...-T, PKM0) + CL-PKZ0

    0,16 1 N N N N 20 N

    1,6 N N N N 20 N

    2,5 N N N N 20 20 20 N

    4 N N N N 20 20 20 N

    6,3 N N N 50 N 20 20 20 N

    10 N N N 20 N 20 20 20 N

    12 N N N 20 N 5 5 2,5 N

    16 N N N 20 N 5 5 2,5 N20 N N N 10 10 10 N 5 5 2,5 N

    25 N N N 10 10 10 N 5 5 2,5 N

    32 N N N 10 10 10 N 5 5 2,5 N

    PKZM0 (PKZM0...-T, PKM0) + 2 CL-PKZ0

    0,16 1 N N N N 20 N

    1,6 N N N N 20 N

    2,5 N N N N 40 40 20 N

    4 N N N N 40 40 20 N

    6,3 N N N 50 N 20 20 20 N

    10 N N N 40 N 20 20 20 N

    12 N N N 40 N 10 10 2,5 N

    16 N N N 40 N 10 10 2,5 N

    20 N N N 20 20 20 N 10 10 2,5 N

    25 N N N 20 20 20 N 10 10 2,5 N

    32 N N N 20 20 20 N 10 10 2,5 N

    Notes

    N

    No upstream protective devicerequired, as it is the auto-protected range (100/150 kA)

    Not required

    1) Necessary back-up fuse when the short-circuit currentexceeds the rated conditional short-circuit current of the device (IccIq).

    PKZM0

  • 8/9/2019 Kapitel 08 G Online

    39/59

    Moeller HPL0211-2007/2008

    8/50

    http://catalog.moeller.net

    motor-protectivecircuit-breakers

    EngineeringSwitching capacity

    Circuit-breaker switching capacity

    Rated uninterrupted current Iu

    Rated conditional short-circuit current Iq IEC/EN 60947-4-1

    Rated ultimate short-circuit breaking capacity IcuIEC/EN 60947-2

    Rated service short-circuit breaking capacity Ics

    230 V 400 V 440 V 500 V 690 V

    Iu Iq Icu Ics Iq Icu Ics Iq Icu Ics Iq Icu Ics Iq Icu Ics

    A kA kA kA A1) kA kA kA A1) kA kA kA A1) kA kA kA A1) kA kA kA A1)

    PKZM01 with classification type 1 and 2

    0.16 1 50 50 50 50 50 50 50 50 50 50 50 50

    1.6 50 50 50 50 50 50 50 50 50 50 50 50

    2.5 50 50 50 50 50 50 50 50 50 50 50 50

    4 50 50 50 50 50 50 50 50 50 50 50 50

    6.3 50 50 50 50 50 50 50 50 50 50 50 50

    10 50 50 50 50 50 50 50 50 42 42 10 50

    12 50 50 10 50 50 50 10 50 15 15 10 50

    16 50 50 10 50 50 50 10 50 15 15 10 50PKZM4 with classification type 1 and 2

    16 150 150 25 N 150 150 25 N 45 45 25 100 15 15 100 8 8 2.5 100

    25 150 150 25 N 150 150 25 N 45 45 25 100 15 15 100 8 8 2.5 100

    32 50 50 25 100 50 50 25 100 45 45 25 100 15 15 100 5 5 2.5 100

    40 50 50 25 100 50 50 25 100 45 45 25 100 15 15 100 5 5 2.5 100

    50 50 50 25 100 50 50 25 100 45 45 25 100 15 15 100 5 5 2.5 100

    58 50 50 25 160 50 50 25 160 45 45 25 160 15 15 160 5 5 2.5 160

    63 50 50 25 160 50 50 25 160 45 45 25 160 15 15 160 5 5 2.5 160

    Notes

    N

    No upstreamprotective device necessary,as it is the auto-protected range(150 kA)

    Not necessary

    1) Fuse (A gG/gL) for enhancing theswitching capacity of the motor-protective circuit-breaker to100 kA

    PKZM01, PKZM4

  • 8/9/2019 Kapitel 08 G Online

    40/59

    8/51

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    PKZ2motor-pr

    otectivecircuit-breaker

    EngineeringCharacteristic curves

    Tripping characteristic, motor-protective circuit-breakers (high-capacity)compact starters

    Tripping characteristics, cable and conductor protection

    Let-through characteristics, circuit-breaker, compact starters

    High-capacity compact starter and circuit-breaker + CL current limiter let-through characteristics

    2

    5

    20

    50

    200

    1

    2

    5

    10

    2040

    1

    2

    5

    20

    10

    2h

    1,5 2 3 4 6 8 10 15 20 30

    PKZ2/ZM-...PKZ2/ZM-.../SPKZ2/ZM-.../SE1A

    Seconds

    Milliseconds

    Minutes

    x Rated operational current

    2

    5

    20

    50

    200

    1

    2

    5

    10

    2040

    1

    2

    5

    20

    10

    2h

    1,5 2 3 4 6 8 10 15 20 30

    PKZ2/ZM-...-8

    Seconds

    Milliseconds

    Minutes

    xRated operational current

    PKZ2/ZM-...(-8)

    PKZ2/ZM-...(-8)/SE1A

    11

    1.5

    2

    3

    4

    6

    8

    10

    15

    20

    30

    40

    60

    80

    100

    1.5 2 3 4 6 8 10 15 20 30 40 60 80 100

    32/40 A

    25 A 16 A

    10 A

    6 A

    xD

    [kA]

    2Ic

    c

    Ue = 400 V

    Icc rms [kA]

    1 1.5 2 3 4 6 8 10 15 20 30 40 60 80 100

    4

    6

    8

    1.5

    2

    3

    4

    6

    8

    1.5

    2

    3

    4

    6

    8

    105

    104

    106

    PKZ2/ZM-...(-8)

    PKZ2/ZM-...(-8)/SE1A

    16 A

    10 A

    6 A

    32/40 A

    25 A

    i dtZ 2

    [A s]2

    Ue = 400 V

    [kA]

    1st h

    alf-

    wav

    e

    Icc rms

    1

    1

    1.5

    2

    3

    4

    6

    8

    10

    15

    20

    30

    40

    60

    80

    100

    1.5 2 3 4 6 8 10 15 20 30 40 60 80 100

    PKZ2/ZM-...(-8)/SPKZ2/ZM-...(-8)/S-GPKZ2/ZM-...(-8)+CLPKZ2/ZM-.../S-SP

    2I

    cc

    32/40 A25 A

    16 A

    10 A

    6 A

    = 400 Ve

    [kA]D

    U

    [kA]cc rmsI

    1st h

    alf-

    wav

    e

    Icc rms

    1 1.5 2 3 4 6 8 10 15 20 30 40 60 80 100

    4

    6

    8

    1.5

    2

    3

    4

    6

    8

    1,5

    2

    3

    4

    6

    8

    10

    10

    10

    16 A

    10 A

    PKZ2/ZM-...(-8)/SPKZ2/ZM-...(-8)/S-GPKZ2/ZM-...(-8)+CLPKZ2/ZM-.../S-SP

    6 A

    25 A32 A40 A

    [A s]2

    Ue = 400 V

    [kA]

    y

    5

    4

    6Z

    PKZ2

  • 8/9/2019 Kapitel 08 G Online

    41/59

    Moeller HPL0211-2007/2008

    8/52

    http://catalog.moeller.net

    p

    EngineeringCharacteristic curves

    S-PKZ2 high-capacity contact module, SE1A-PKZ2 contact module

    Normal switching dutyNormal AC induction motor

    Operatingcharacteristics:

    Starting:Stopping:

    from restduring running

    Typical applications: compressorspumpsfans

    valves

    liftsescalatorsconveyors

    bucket-elevators

    mixersagitatorscentrifuges

    air-conditioningsystems

    General drives for manufacturing and processingmachines

    Electrical characteristics: Starting:Stopping:

    up to6Xrated motor current1Xrated motor current

    Utilization category: 100 % AC-3

    Extreme switching duties

    Normal AC induction motor

    Operatingcharacteristics:

    Inching, plugging, reversing

    Typical applications: printing machineswire-drawing machinescentrifugesSpecial drives on manufacturing and processingmachines

    Electrical characteristics: Starting:Stopping:

    6Xrated motor current6Xrated motor current

    Utilization category: 100 % AC-4

    Light switching dutyNon-motor loads

    Operating

    characteristics:

    Non inductive and slightly inductive loads

    Typical applications: Electricalheaters

    Electrical characteristics: Starting:Stopping:

    up to1.5Xrated current1Xrated current

    Utilization category: 100 % AC-1

    Determination of the maximum operating frequency dependant on the rating and utilization category (recommended values)for (high capacity) contact modules

    PN = max. motor rating (kW) ops/h= max. operations per hour

    0.1 0.2 0.4 0.6 0.8 1 2 3 4 5 6 8 10

    0.811.051.42

    1.86

    2.65

    5.26.8

    8.811.415.4

    22.128.5

    35

    3.6

    0.250.370.55

    0.75

    1.1

    2.23

    45.57.5

    1115

    18.5

    1.5

    AC-3/400V

    kW A S(E1A)-PKZ2

    Ratedoutputofthree-p

    hase

    motors50...6

    0Hz

    Component lifespan (millions of operations)

    Ratedoperational

    current50...6

    0Hz

    Normal switching duty

    0.811.05

    1.42

    1.86

    2.65

    5.2

    6.8

    8.811.415.422.1

    28.535

    3.6

    0.250.37

    0.55

    0.75

    1.1

    2.2

    3

    45.57.511

    1518.5

    1.5

    AC-4/400V

    kW A

    0.01 0.02 0.03 0.04 0.06 0.1 0.2 0.3 0.4 0.6 1 2 3 4

    S(E1A)-PKZ2

    5

    Ratedoperational

    current50...6

    0Hz

    Ratedoutputofthree-p

    hase

    motors50...6

    0Hz

    Component lifespan (millions of operations)

    Extreme switching duty

    0,1 0,2 0,4 0,6 0,8 1 2 3 4 5 6 8 10

    0,811,051,42

    1,86

    2,65

    5,2

    6,8

    8,811,415,422,128,5

    35

    3,6

    AC-1/400V

    S(E1A)-PKZ2A

    40

    Breakingcurrent

    Component lifespan (millions of operations)

    Non-motor loads, 3-pole

    100

    150

    200

    300

    400500600

    800

    1000

    1500

    2000

    3000

    4000

    50006000

    70009000

    100 20 30 40 50 60 70 80 90 100%

    AC-3

    AC-4

    (kW)NP

    Ops./h

    PKZ2

  • 8/9/2019 Kapitel 08 G Online

    42/59

    8/53

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    PKZ2motor-pr

    otectivecircuit-breaker

    EngineeringSwitching capacity

    Motor-protective circuit-breaker switching capacity and (high-capacity) compact starter

    Rated uninterrupted current Iu

    Rated conditional short-circuit current Iq IEC/EN 60 947-4-1

    Rated ultimate short-circuit breaking capacity IcuIEC/EN 60 947-2

    Rated service short-circuit breaking capacity Ics

    1) 1) 1) 1) 1)230 V 400 V 440 V 500 V 690 V

    Iu Iq Icu Ics Iq Icu Ics Iq Icu Ics Iq Icu Ics Iq Icu Ics

    A kA kA kA A kA kA kA A kA kA kA A kA kA kA A kA kA kA A

    PKZ2/ZM with classification type 1 and 2

    0,16 1,6 N N N N N2,4 N N N N N4 N N N N 4,5 4,5 2,5 636 N N N N 4,5 4,5 2,5 8010 30 N 30 N 10 10 5 80 7 7 3,5 80 4,5 4,5 2,5 8016 30 N 30 N 10 10 5 100 7 7 3,5 100 4,5 4,5 2,5 10025 30 30 7,5 160 30 30 7,5 160 10 10 5 125 7 7 3,5 125 4,5 4,5 2,5 12532 30 30 7,5 160 30 30 7,5 160 10 10 5 160 7 7 3,5 160 4,5 4,5 2,5 16040 30 30 7,5 160 30 30 7,5 160 10 10 5 160 7 7 3,5 160 4,5 4,5 2,5 160

    PKZ2/ZM + CL-PKZ2 with classification type 1 and 2

    0,16 1,6 N N N N N2,4 N N N N N4 N N N N 10 4,5 2,5 N6 N N N N 10 4,5 2,5 N10 30 N 30 N 5 N 3,5 N 10 4,5 2,5 N16 30 N 30 N 5 N 3,5 N 10 4,5 2,5 N25 7,5 N 7,5 N 5 N 3,5 N 10 4,5 2,5 N32 7,5 N 7,5 N 5 N 3,5 N 10 4,5 2,5 N40 7,5 N 7,5 N 5 N 3,5 N 10 4,5 2,5 N

    PKZ2/ZM(R)-.../SE1A(-G)... with classification type 1

    0,16 1,6 N N N N N N N N N N N N N N N2,4 N N N N N N N N N N N N N N N4 N N N N N N N N N N N N 4,5 N N 636 N N N N N N N N N N N N 4,5 N N 8010 N N N N N N 10 N N 80 7 N N 80 4,5 N N 8016 N N N N N N 10 N N 100 7 N N 100 4,5 N N 10025 30 N N 160 30 N N 160 10 N N 125 7 N N 125 4,5 N N 12532 30 N N 160 30 N N 160 10 N N 160 7 N N 160 4,5 N N 16040 30 N N 160 30 N N 160 10 N N 160 7 N N 160 4,5 N N 160

    PKZ2/ZM-.../S(-G) with classification type 1 and 2

    0,6 2,4 N N N N N N N N N N4 6 N N N N N N N N 10 N N 8010 16 N N N N N N N N 10 N N 10025 40 N N N N N N N N 10 N N 160

    PKZ2/ZM-..-8 and PKZ2/ZM-..-8/SE1A(-G)

    0,16 1,6 N N N N N N N N N N2,4 N N N N N N N N N N4 N N N N N N N N N 4,5 2,5 636 N N N N N N N N N 4,5 2,5 8010 N 30 N N 30 N N 10 5 80 N 7 3,5 80 N 4,5 2,5 8016 N 30 N N 30 N N 10 5 100 N 7 3,5 100 N 4,5 2,5 10025 N 30 7,5 160 N 30 7,5 160 N 10 5 125 N 7 3,5 125 N 4,5 2,5 12532 N 30 7,5 160 N 30 7,5 160 N 10 5 160 N 7 3,5 160 N 4,5 2,5 16040 N 30 7,5 160 N 30 7,5 160 N 10 5 160 N 7 3,5 160 N 4,5 2,5 160

    PKZ2/ZM-...-8/S(-G)

    0,6 2,4 N N N N N N N N N N4 6 N N N N N N N N N 10 5 8010 16 N N N N N N N N N 10 5 10025 40 N N N N N N N N N 10 5 160

    Notes

    N

    No upstream protective devicerequired,as it is the auto-protected range (100 kA)

    Not necessary

    1) Fuse (A gG/gL) for enhancing the switchingcapacity of the motor-protective circuit-breakerto 100 kA

    PK22

  • 8/9/2019 Kapitel 08 G Online

    43/59

  • 8/9/2019 Kapitel 08 G Online

    44/59

    Moeller HPL0211-2007/2008

    8/56

    http://catalog.moeller.net

    PKZM01,PKZM

    0,PKZM4

    Technical DataAuxiliary contacts, voltage releases

    NHI...PKZ0 NHI-E-...PKZ0 VHI...PKZ0 AGM t ripindication

    Auxiliary contacts

    Rated impulse withstand voltage Uimp V AC 6000 4000 4000 6000

    Overvoltage category/pollution degree III/3 III/3 III/3 III/3

    Rated operational voltage Ue V AC 500 440 440 500

    Ue V DC 250 250 250 250Safe isolation to VDE 0106 Part 101 and Part 101/A1

    Between auxiliary contacts and main contacts V AC 690 690 690 690

    Rated operational current

    AC15

    220 240 V Ie A 3.5 1 1 3.5

    380 415 V Ie A 2 2

    440 500 V Ie A 1 1

    DC-13 L/R 100 ms

    24 V Ie A 2 2 2 2

    60 V Ie A 1.5 1.5

    110 V Ie A 1 1

    220 V Ie A 0.25 0.25

    LifespanLifespan, mechanical Operations x 106 0.1 0.1 0.1 0.01

    Lifespan, electrical Operations x 106 0.05 0.1 0.1 0.005

    Control circuit reliability (at Ue = 24 V DC, Umin = 17 V, Imin= 5.4 mA)

    Failure rate l < 10-8 < 1 failure at 1 x 108 operations

    Interlocked opposing contacts to ZH 1/457 Yes

    Short-circuit rating without welding

    Fuseless FAZ-B4/1-HI FAZ-B4/1-HI

    Fuse A gG/gL 10 10 10 10

    Terminal capacities

    Solid or flexible conductor with ferrule mm2 0.75 2.5 0.75 1.5 0.75 1.5 0.75 2.5

    Solid or stranded AWG 18 14 18 16 18 16 18 14

    U-PKZ...

    Undervoltage release

    Terminal capacities Solid or flexible conductor withferrule

    mm2 2 x (0.75 2.5)

    Solid or stranded AWG 2 x (18 14)

    Main conducting paths

    Rated operating voltage Ue V AC 42 480

    Rated operating voltage Ue V DC 24 250

    Pick-up voltage xUs 0.85 1.1

    Drop-out voltage xUs 0.7 0.35

    Power consumption Pick-up AC Pick-up VA 5

    Sealing AC Sealing VA 3

    A-PKZ...

    Shunt release

    Terminal capacities Solid or flexible conductor withferrule

    mm2 2 x (0.75 2.5)

    Solid or stranded AWG 2 x (18 14)

    Main conducting paths

    Rated operating voltage Ue V AC 42 480

    Rated operating voltage Ue V DC 24 250

    Operating range AC xUs 0.71.1

    DC xUs 0.71.1

    Power consumption

    AC Pick-up AC Pick-up VA 5Sealing AC Sealing VA 3

    DC Pick-up DC Pick-up W 3

    Sealing DC Sealing W 3

    NHIPKZ, AGM, U-PKZ, A-PKZ,

  • 8/9/2019 Kapitel 08 G Online

    45/59

    8/57

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    PKZ2motor-pr

    otectivecircuit-breaker

    Technical DataMotor-protective circuit-breakers

    PKZ2/ZM-...(8)

    PKZ2/ZM-...(8)/SE...

    PKZ2/ZM-...(8)/S(+CL)

    S(EA)...

    General

    Standards IEC/EN 60947, VDE 0660, UL 508, CSA C 22.2 No. 14, GL, LR, DNV,PRS, BV, RINA, RS, EZU, MEEI

    Climatic proofing Damp heat, constant, to IEC 60068-2-78;Cyclic to IEC 60068-2-30

    Ambient temperature Storage C -2570 -2570 -2570 -2570Open C 2560 2560 2560 2560

    Enclosed C 2540 2540 2540 2540

    Mounting position

    Direction of incoming supply As required

    Protection type IP00

    Mechanical shock resistance

    Half-sinusoidal shock 20 ms to IEC 60068-2-27 g 30 8 8 8

    Altitude m 2000

    Terminal capacities Solid or stranded mm2 1 x (1 16)2 x (1 6)

    Flexible with ferrule mm2 1x (1.5 10)2x (1.5 6)

    Solid or stranded AWG 14 6 14 6 14 6 14 6

    Specified tightening torquefor terminal screws

    Main cable Nm 1.8 1.8 1.8 1.8

    Control circuit cables Nm 1 1 1 1

    Main conducting paths

    Rated impulse withstand voltage Uimp V AC 6000 6000 6000 6000

    Overvoltage category/pollution degree III/3 III/3 III/3 III/3

    Rated operational voltage Ue V AC 690 690 690 690

    Rated uninterrupted current = rated operational current Iu = Ie A 40 40 40 40

    Rated frequency Hz 50 60 50 60 50 60 50 60

    Current heat loss (3-pole at operating temperature) W 14 23 23 9

    Lifespan, mechanical Operations x 106 0.1 5 5 5

    Lifespan, electrical 100 % AC-3 Operations x 106 0.05 1 1 1

    AC-4 Operations x 106 0.03 0.03 0.03

    Maximum operating frequency Operations/h Ops/h 60 aProjektieren Kennlinien

    Motor switching capacity AC-3 (up to 690 V) A 40 40 40 40

    DC-5 up to 250 V A 40 40 40 40

    DC application

    Rated short-circuit

    breaking capacity Icn

    Icn (250 V DC), L/R = 15 ms kA 30 30 50

    Icn (125 V DC), L/R = 15 ms kA 50 50 65Operating times under short-circuit conditions

    Minimum command time ms Approx. 2 Approx. 2 Approx. 2 Approx.

    Opening delay ms Approx. 0.5 Approx. 0.5 Approx. 0.5 Approx.

    Total opening delay ms 6 6 4

    Notes With dual-frequency coil 50/60 Hz, the mechanical lifespan reduces by 30%

    SCL

    SCL

    90

    90 90

    90

    90

    30

    PKZ2PKZ2/.../SPKZ2/.../+CL

    PKZ2/.../S

    PKZ2PKZ2/.../+CL{PKZ2

    ZM-...-PKZ2 ZMR-...-PKZ2 ZM-...-8-PKZ2(4)

    Releases

    Function Motor protection Motor protection System protection

    Temperature compensation

    to IEC/EN 60947, VDE 0660 C 540 540 540

    Operating range C 2560 2560 2560

    Temperature compensation residual error for T > 40 C %/K F 0.25 F 0.25 F 0.25

    Short-circuit release tolerance % g 20 g 20 g 20

    Setting range of overload releases xIu 0.6 1 0.6 1 0.6 1

    Short-circuit releases xIu 8.5 14 8.5 14 5 8.5

    PKZ2

  • 8/9/2019 Kapitel 08 G Online

    46/59

    Moeller HPL0211-2007/2008

    8/58

    http://catalog.moeller.net

    p

    Technical Data(High-capacity) contact module, current limiter

    S(EA)...

    (High-capacity) contact module

    Operating delays Closing delay ms 9 30

    Opening delay ms 4 12

    Duty factor % DF 100

    Rated making capacity c = 0.45 A 400Rated breaking capacity c = 0.45 A 400

    Magnet systems

    AC operation

    Operating range Pick-up voltage xUs 0.85 1.1

    Drop-out voltage xUs 0.4 0.6

    Power consumption Pick-up AC Pick-up VA 190

    Sealing AC Sealing VA 13

    DC operation

    Rated control voltage Us V DC 24

    Operating range Pick-up voltage xUs 0.85 1.1

    Power consumption Pick-up DC Pick-up VA 150Sealing DC Sealing VA 2.7

    Current consumption Pick-up A 6.3

    Sealing mA 113

    Rated operational current, open, enclosed

    AC-1 230 V Ie A 40

    400 V Ie A 40

    440 V Ie A 40

    500 V Ie A 40

    690 V Ie A 40

    AC-3 230 V Ie A 40

    400 V Ie A 40

    440 V Ie A 40

    500 V Ie A 40690 V Ie A 40

    AC-4 230 V Ie A 30

    400 V Ie A 30

    440 V Ie A 30

    500 V Ie A 28

    690 V Ie A 25

    CL-PKZ2

    Current limiter

    Rated making capacity c = 0.45 A 400

    Rated breaking capacity c = 0.45 A 400

    AC-1 duty Conventional thermal current Ith A 40

    SExPKZ, CL-PKZ

  • 8/9/2019 Kapitel 08 G Online

    47/59

    8/59

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    PKZ2motor-pr

    otectivecircuit-breaker

    Technical DataAuxiliary contacts

    NHI11(S)-PKZ2 NHI22(S)-PKZ2 NHI2-11S-PKZ2 AGM2-11-PKZ2

    Auxiliary contacts

    Rated impulse withstand voltage Uimp V AC 6000 6000 6000 6000

    Overvoltage category/pollution degree III/3 III/3 III/3 III/3

    Rated operational voltage Ue V AC 500 500 500 500

    Rated operational currentAC15 230 240 V Ie A 6 6 6 5

    400 415 V Ie A 3 1.5 3 3

    440 V Ie A 1.5 1.5 1.5 1.5

    500 V Ie A 1.5 1.5 1.5 1.5

    Lifespan, mechanical Operations x 106 0.1 0.1 5 0.01

    Lifespan, electrical Operations x 106 0.05 0.05 1 0.005

    Control circuit reliability (at Ue = 24 V DC, Umin =17 V, Imin= 10 mA)

    Failure rate l Control circuit reliability through the entire mechanical lifespan

    Interlocked opposing contacts to ZH 1/457 Yes Yes

    Short-circuit rating without weldingFuseless 240 V: PKZM0-6,3

    415 V: PKZM0-4500 V: PKZM0-1,6

    240 V: PKZM0-6,3415 V: PKZM0-4500 V: PKZM0-1,6

    240 V: PKZM0-6,3415 V: PKZM0-4500 V: PKZM0-1,6

    240 V: PKZM0-6,3415 V: PKZM0-4500 V: PKZM0-1,6

    Fuse A gG/gL 10 10 10 10

    Terminal capacities

    Solid or flexible conductorwith ferrule

    mm2 1 x (0.75 2.5)2 x (0.75 2.5)

    1x (0.75 2.5)2x (0.75 2.5)

    1 x (0.75 2.5)2 x (0.75 2.5)

    1 x (0.75 2.5)2 x (0.75 2.5)

    Solid or stranded AWG 1 x (22 14)2 x (22 14)

    1x (22 14)2x (22 14)

    1 x (22 14)2 x (22 14)

    22 14

    Safe isolation to VDE 0106 Part 101 and Part 101/A1

    Between auxiliary contacts and main contacts V AC 690 690 500

    HI...-S-PKZ2 HI11-S/EZ-PKZ2 ZMR-...(95 96) ZMR-...(97 98)

    Auxiliary contacts

    Rated impulse withstand voltage Uimp V AC 6000 6000 6000 6000

    Overvoltage category/pollution degree III/3 III/3 III/3 III/3

    Rated operational voltage Ue V AC 500 500 500 500

    Rated operational current

    AC15 230 240 V Ie A 6 6 1.5 1.5

    400 415 V Ie A 1.5 3 0.7 0.5

    440 V Ie A 1.5 1.5 0.5 0.3

    500 V Ie A 1.5 1.5 0.5 0.3

    Lifespan, mechanical Operations x 106 5 5 0.01 0.01

    Lifespan, electrical Operations x 106 1 1 0.005 0.005

    Control circuit reliability (at Ue = 24 V DC, Umin =17 V, Imin= 10 mA)

    Failure rate l Control circuit reliability through the entire mechanical lifespan

    Interlocked opposing contacts to ZH 1/457

    Short-circuit rating without welding

    Fuseless 240 V: PKZM0-6,3415 V: PKZM0-4500 V: PKZM0-1,6

    240 V: PKZM0-6,3415 V: PKZM0-4500 V: PKZM0-1,6

    Fuse A gG/gL 10 10 10 10

    Terminal capacities

    Solid or flexible conductor withferrule

    mm2 1 x (0.75 2.5)2 x (0.75 2.5)

    1x (0.75 2.5)2x (0.75 2.5)

    1 x (0.75 2.5)2 x (0.75 2.5)

    1 x (0.75 2.5)2 x (0.75 2.5)

    Solid or stranded AWG 22 14 22 14 22 14 22 14

    Safe isolation to VDE 0106 Part 101 and Part 101/A1

    Between auxiliary contacts and main contacts V AC 500 500

    NHIPKZ

  • 8/9/2019 Kapitel 08 G Online

    48/59

    Moeller HPL0211-2007/2008

    8/60

    http://catalog.moeller.net

    p

    Technical DataVoltage release

    U-PKZ2... U-HI20-PKZ2... UVHI-PKZ2

    Undervoltage release

    Rated impulse withstand voltage Uimp V AC 6000 6000 6000

    Overvoltage category/pollution degree III/3 III/3 III/3

    Terminal capacities

    Solid or flexible conductor with ferrule mm2 1 x (0.75 2.5)2 x (0.75 2.5)

    1x (0.75 2.5)2x (0.75 2.5)

    1 x (0.75 2.5)2 x (0.75 2.5)

    Solid or stranded AWG 22 14 22 14 22 14

    Rated operating voltage Ue V AC 24 600 24 600 24 600

    Rated operating voltage Ue V DC 24 125 24 125 24 125

    Drop-out voltage xUs V 0.7 0.35 0.7 0.35 0.7 0.35

    Power consumption

    AC

    Pick-up AC Pick-up VA 5 5 5

    Sealing AC Sealing VA 3 3 3

    DC

    Pick-up DC Pick-up W 3 3 3

    Sealing DC Sealing W 3 3 3

    Off-delay ms 200Rated operational current

    AC15

    230 V Ie A 6 6

    400 V Ie A 3 3

    440 V Ie A 1.5 1.5

    A-PKZ2...

    Shunt release

    Rated impulse withstand voltage Uimp V AC 6000

    Overvoltage category/pollution degree III/3Terminal capacities

    Solid or flexible conductor with ferrule mm2 1 x (0.75 2.5)2 x (0.75 2.5)

    Solid or stranded AWG 22 14

    Rated operating voltage Ue V AC 24 600

    Rated operating voltage Ue V DC 24 250

    Operating range

    Alternating voltage xUs 0.7 1.1

    DC xUs 0.7 1.1

    Power consumption

    AC

    Pick-up AC Pick-up VA 5

    Sealing AC Sealing VA 3DC

    Pick-up DC Pick-up W 3

    Sealing DC Sealing W 0.3

    BK...-PKZ2, B3.1/...-PKZ2

    Incoming terminal and three-phase current

    Rated impulse withstand voltage Uimp V AC 6000

    Overvoltage category/pollution degree III/3

    Rated operational voltage Ue V AC 690

    Rated uninterrupted current Iu A 120

    U-PKZ, A-PKZ

  • 8/9/2019 Kapitel 08 G Online

    49/59

    8/61

    http://catalog.moeller.net Moel ler HPL0211-2007/2008

    PKZ2motor-pr

    otectivecircuit-breaker

    Technical DataR...-PKZ2 remote operator

    RE-PKZ2 RS-PKZ2

    Remote operator

    Rated impulse withstand voltage Uimp V AC 6000 6000

    Overvoltage category/pollution degree III/3 III/3

    Rated operating voltage Ue V AC 380 440 380 440

    Rated operating voltage Ue V DC 24 240 24 240

    Safe isolation to VDE 0106 Part 101 and Part 101 A1 betweenauxiliary contacts and main contacts

    V AC 500 500

    Required short-time rating (30 ms) VA/W 700 700

    Control transformer short-time rating VA 1000 1000

    Shortcircuit voltage % 4.4 4.4

    Closing delay ms 30 30

    Opening delay ms 30 30

    Reset time to Off ms 30 30

    Maximum operating frequency Ops/h 60 60

    Operating range Alternating voltage xUs 0.85 1.1 0.85 1.1

    DC xUs 0.85 1 0.85 1

    Lifespan, electrical Operations x 106 0.05 0.05

    Integral auxiliary contacts (make contact 33/34 Hand/Autoindication)

    Conventional free air thermal current th Ith A 1.5 1.5

    Rated operational current

    AC-14 230/240 V Ie A 1.5 1.5

    400/415 V Ie A 1 1

    440 V Ie A 0.5 0.5

    Terminal capacities

    Solid or flexible conductor with ferrule mm2 1x (0.75 2.5)2x (0.75 2.5)

    1 x (0.75 2.5)2 x (0.75 2.5)

    Solid or stranded AWG 22 14 22 14

    BK...-PKZ2, B3.1/...-PKZ2

    Incoming terminal and three-phase current

    Rated impulse withstand volta