  • 7/30/2019 KRB-0445b

    1/2

    Rear connection Flat bar

    Instruction Manual

    (Types): T2RP40, T2RP46

    TemBreak2

    This document has described the procedure which

    attaches stud unit in TemBreak2 series.

    Please retain this manual for future reference. The Manufacturer assumes no responsibility for

    damages resulting from non-application or incorrect application of the instructions provided herein.

    547-0002 7-2-10 7-2-10 Kamihigashi, Hiranoku, Osaka:06(6791)9320 547-0002, Japan:06(6791)9274 TEL:81-6-6791-9323/ FAX:81-6-6791-9274www.terasaki.co.jp Web Site: [email protected] Email: [email protected]

    2G0468SAB (KRBKRBKRBKRB----0445b0445b0445b0445b)

    3 Safety Notice

    Be sure to read these Instructions and other associated documents accompanying the product

    thoroughly to be familiarize yourself with the product handling, safety information, and all other

    precautions before mounting, using, servicing, or inspecting the product. In these Instructions,

    safety notices are divided into Warning and Caution according to the hazard level:

    Warning : A warning notice with this symbol indicates that neglecting the suggested procedure

    or practice could result in lethal or serious personal injury.

    Caution : A caution notice with this symbol indicates that neglecting the suggested procedure orpractice could result in moderate or slight personal injury and/or property damage.

    Note that failing to observe Caution notices could result in serious injury/damage in some situations.

    Because safety notices contain important information, be sure to read and observe them.

    Warning Operation Precautions

    Never touch live terminals. Doing so may result in electric shock.

    Caution Installation Precautions

    Installation work must be performed by competent persons.OFF

    Prior to commencing any work on the product, open an upstream circuit breaker or thelike to isolate all sources of power/voltage. Doing so may result in electric shock.

    Clean the rear conection stud bar mounting surface (contact surface with the breakerterminals). Otherwise, a fire may result.

    1 Applicable Breaker Types/ Packaged Items

    Rear connecction Flat bar

    Applicable Breaker Types Items

    MCCB ELCB

    Poles

    TypesA B C D

    3 T2RP403S 4 2 6 -E400, S400,ZAE400, ZAS400

    ZE400, ZS4004 T2RP404S 4 4 8 -3 T2RP463S 4 2 - 6E630-NE, S630-CE,

    S630-GE, S630-NN-

    4 T2RP464S 4 4 - 8

    A B

    C: M1020 D: M825

    2 Assembly tools

    Caution

    Installation PrecautionsInsert the Rear connection Flat bar to the full depth until the mounting surface comes intocontact with the breaker terminals, and tighten it with the stud fixing screws. Otherwise, afire may result.

    Tighten the Rear connection Flat bar fixing screws and the terminal screws to the torquespecified in this manual. Otherwise, a fire may result.

    Even when tightening the terminal screws and after conductor connection, do not applyexcessive force to the Rear connection Flat bar. Otherwise, a fire may result.

    Each connected conductor must be supported at a distance M. See following table.

    Rear connrcted Flat bar arrengement

    0 45, 90

    J Distance J J350mm J200mmWhen removing the installed breaker, loosen the terminal screws without loosing the Rearconnection Flat bar fixing screws.

    Operation PrecautionsONWhen the breaker trips open automatically, remove the cause; then close the b reaker.Otherwise, a fire may result.

    Maintenance Precautions

    Service and/or inspection of the product must be done by persons having expertknowledge.

    OFF

    Before service or inspection of this product, please ensure that no voltage is present onthe breaker supply side. Any device upstream of this breaker should be suitably isolatedotherwise electric shock may result.

    Regularly check that the Rear connection Flat bar fixing screws and the terminal screwsare tightened to torque values shown within this manual, failure to do so may result infire.

    T2RP

  • 7/30/2019 KRB-0445b

    2/2

    For mounting dimensions, refer to catalogue.

    Use packaged screws of breaker.

    H

    The 'H' screws and the conductors are not supplied.

    13

    C or D C or D

    A

    B

    A: RT for R and T phases

    B: SN for S and N phases

    A, B

    A, B

    0

    90

    45

    45

    E 1 2

    4 Rear connection Flat bar Mounting Procedure

    Attach Rear connection Flat bar in front connected breaker.

    1 E Removal of E

    E

    3P:6pcs

    4P:8pcs

    2 +3 F Removal of F

    F

    3P: 6pcs

    4P: 8pcs

    4 5 G Removal of G

    G

    3P: 6pcs

    4P: 8pcs

    2G0468SAB (KRBKRBKRBKRB----0445b0445b0445b0445b)

    5 Breaker Mounting Procedure for Rear Connected Type

    M61006.07.4Nm

    7 9 Arrangement set 12 Check contact state

    10 Cleaning 13 Tightening

    11 Insert

    M1020C

    18.629.4NmM825

    D8.814.7Nm

    6

    Conductor Connection Procedure for Rear Connected Type

    M12H40.265.7Nm

    I 13mm

    7 Support Mounting Procedure for Rear Connected Type

    Rear connection Flat bar arrengement

    0 45, 90

    J Distance J J350mm J200mm

    The supports are not supplied.