Upload
rindarayna
View
72
Download
12
Embed Size (px)
Citation preview
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
1/35
MiCOM C264 Human
Interface
PCL
PACiSPACiSPACiSPACiS TechnicalTechnicalTechnicalTechnical TrainingTrainingTrainingTraining
CS&PCS&PCS&PCS&P Support TeamSupport TeamSupport TeamSupport Team
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
2/35
Schneider Electric 2- CS&P C264 HMI E01
Front Face Description
LED Description
LCD Description
Menu Tree
Content
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
3/35
Schneider Electric 3- CS&P C264 HMI E01
Front Face Description
LED Description
LCD Description
Menu Tree
Content
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
4/35
Schneider Electric 4- CS&P C264 HMI E01
C264C With LCD
MiCOM C264C
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
5/35
Schneider Electric 5- CS&P C264 HMI E01
C264 With LCD
MiCOM C264
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
6/35
Schneider Electric 6- CS&P C264 HMI E01
C264C Without LCD
MiCOM C264C
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
7/35
Schneider Electric 7- CS&P C264 HMI E01
C264 Without LCD
MiCOM C264
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
8/35
Schneider Electric 8- CS&P C264 HMI E01
Large illuminated display
Pre-affected LED
Operating keys
Settable LED
Open/Close command
Local/Remote
command
Navigationkeys
MiCOM C264 Front FaceLarge graphic Display control
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
9/35
Schneider Electric 9- CS&P C264 HMI E01
C264M 80TE(4U-170mm)
Local Control PanelLiquid Crystal Display12 Push Buttons
C264C 40TE(4U-170mm)
4/5 System LED
12/13 Configurable LED
LED OverviewFRONT FACE
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
10/35
Schneider Electric 10- CS&P C264 HMI E01
Front Face Description
LED Description
LCD Description
Menu Tree
Content
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
11/35
Schneider Electric 11- CS&P C264 HMI E01
FAULTY OFF No faultON DB error, Hardware error
LED 0 FLASHING Slow Not usedFLASHING Fast ISaGRAF Fault (cycle too long,Queue overflow, POU faulty
ALARM OFF No AlarmON Alarm acknowledged
LED 1 FLASHING Slow Alarm inactive acknowledgedFLASHING Fast At least one alarm not acknowledged
MODE OFF Reboot
ON Operational modeFLASHING Slow Maintenance mode
LED 2 FLASHING Fast Test mode
LOCAL/REMOTEOFF All bays are in remote modesimple HMI ON All bays are in local mode
only FLASHING Slow At least one bay in local mode
LED 4 FLASHING Fast Not used
POWER OFF power offON power on
FLASHING Slow Not usedLED 3 FLASHING Fast Not used
System LEDs
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
12/35
Schneider Electric 12- CS&P C264 HMI E01
OFF Event Not Present, Reset, Remote, Disable
ON Event Present, Set, Local, Enable
BLINK SLOW Event Invalid (Fault, unknown, undefined, Invalid,..)
BLINK FAST Events of high gravity
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
LED 11
LED 12
LED 13
LED 14LED 15
LED 16
LED from 5 to LED 16 are controlled via SPS or DPS
SET off / on / flashing slow / flashing fast
RESET off / on / flashing slow / flashing fast
INVALID off / on / flashing slow / flashing fast
Examples
SPS or DPS state
Configurable LEDs
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
13/35
Schneider Electric 13- CS&P C264 HMI E01
Front Face Description
LED Description
LCD Description Menu Tree
Content
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
14/35
Schneider Electric 14- CS&P C264 HMI E01
Bay Name12 char
+Bay L/R
Animated objectNote : Transformer +
Tap Changer
(min, max, current)
Bay Topology :Use extra short name
Representation withtwo drawing sets
Computer
Time
Optional AI Mini listup to 4 MV
Configuration : included into PACiS SCE Graphic Editor
M = MeasurementsS = States
C = Controls
LCD OverviewDefault View : Bay panel
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
15/35
Schneider Electric 15- CS&P C264 HMI E01
ENTER
PAGE
CLEAR/CANCEL
SERVICEPAGE
LOCAL/REMOTE
OPEN/OFFSELECTION CLOSE/ON
LEFT/RIGHTswitch panels
UP/DOWNscroll Lists
Front Face Buttons
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
16/35
Schneider Electric 16- CS&P C264 HMI E01
LCD Panels Arrangement Bay Panels (up to 12)
monitor and control devices, access to measurements and status
Alarm Panel
acknowledgement and alarm clearing
Event Panel
FIFO list of 200 events
Fault Panel
C264 faults
Disturbance Panel
IED and C264 disturbance files
Services Panel
general information I/O status Panel
DI couplers and DO contacts status on DI, DO and CCU boards
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
17/35
Schneider Electric 17- CS&P C264 HMI E01
Bay panels1 to 12
MeasurementsBAY_01 Alarms
panel
Eventspanel
Fault panel
DisturbanceRecord panel
Services panels :General Info
Input/Outputpanel
MenuTreePanel
LCD Panels Arrangement
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
18/35
Schneider Electric 18- CS&P C264 HMI E01
On Bay Panel, Operator can :
Access other bay panels by pressing on or
Select devices for command by pressing on
Control switching devices : Put in ON or CLOSED by pressing on
Put in OFF or OPEN by pressing on
Then for execution (SBO case)
Control Tap Position : Raise by pressing on
Lower by pressing on
GoToMax by pressing on
GoToMin by pressing on Then same button again for execution (SBO case)
G
I
O
G
G
G
G
LCD Bay Panels
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
19/35
Schneider Electric 19- CS&P C264 HMI E01
EVENTS
047----------------------------------
01/04/02 *12:15:10.123
FEEDER 63kV
SW63-5-2BB1
POSITION DPS
OPEN
048----------------------------------
01/04/02 *12:05:10.123
FEEDER 63kV
SW63-5-2BB1
POSITION DPS
CLOSED
Event Rank in circular queue
Event date time withsynchronisation attribute (*)
Bay / Module / Datapoint / Status
LCD Events Panel
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
20/35
Schneider Electric 20- CS&P C264 HMI E01
A L A R M S
0 1 / 0 4 / 0 2 *1 2 : 1 5 : 1 0 . 1 2 3
A C T I V E - U N A C K 3
F E E D E R 6 3 k V / 5
S W 6 3 - 5 - 2 B B 1
P O S I T I O N D P S
O P E N
0 1 / 0 4 / 0 2 *1 2 : 1 5 : 1 2 . 8 2 4
A C T I V E - U N A C K 3
F E E D E R 6 3 k V / 5
S W 6 3 - 5 - 2 B B 2
P O S I T I O N D P S
O P E N
Alarm appearance date withsynchronisation attribute (*)
Alarm State and Gravity
Alarm Selection Acknowledge selected
alarm (password)
Clear selected inactive,
ack. alarm (password)
Bay / Module / Datapoint / Status
LCD Alarms Panel
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
21/35
Schneider Electric 21- CS&P C264 HMI E01
LCD Service PanelGeneral Services :
MAC @
Software version
Database version
Operating Mode
...
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
22/35
Schneider Electric 22- CS&P C264 HMI E01
Other Panels :
DISTURBANCE
Is showing disturbance records from IED or CT/VT waveforms
INPUT/OUPUT
Is showing every I/O board channel status
LCD Other Panels
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
23/35
Schneider Electric 23- CS&P C264 HMI E01
LCD Fault PanelsFault type display
Is showing DISCONN if an IED is not connected
Is showing HARDWARE if an hardware problem (boards, ) occurs
Fault List
By selecting the Fault Type, it will display the list of faults
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
24/35
Schneider Electric 24- CS&P C264 HMI E01
Front Face Description
LED Description
LCD Description Menu Tree
Content
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
25/35
Schneider Electric 25- CS&P C264 HMI E01
Services Panel
Baypanels1 to 12
Input/Output
Panel
Events
panel
Alarms
panel
Disturbance
Record panel
BAY_01
Faultpanel
Menu
TreePanel
Menu Tree Panel Access
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
26/35
Schneider Electric 26- CS&P C264 HMI E01
CONFIG
COMMAND
MENU TREE
Menu Tree Main Menu
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
27/35
Schneider Electric 27- CS&P C264 HMI E01
Main
Counter
COMMAND
MENU TREE Reset Operating HoursChange operatingmode
Global Alarm ACKGlobal Alarm CLRDateTimeDB Switch
Language
Change Value
Menu Command
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
28/35
Schneider Electric 28- CS&P C264 HMI E01
ComputerMain
Bay
Comm
port
CONFIG
HMIMain
Bay
COMMAND
MENU TREE
Menu Config
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
29/35
Schneider Electric 29- CS&P C264 HMI E01
ComputerMain
Bay
Commport
CONFIG
Menu Config / Computer
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
30/35
Schneider Electric 30- CS&P C264 HMI E01
ComputerMain
Bay
Comm
port
IP Address (read only)
Menu Config / Computer
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
31/35
Schneider Electric 31- CS&P C264 HMI E01
ComputerMain
Bay
Comm
port
IP Address (read only)
Internal SCARDEVICESBIMV
List configured Bay
------------------------------------------------------------------
Menu Config / Computer
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
32/35
Schneider Electric 32- CS&P C264 HMI E01
Internal SCARDEVICES
BIMV
SC delay
AR delays (cycles, reclaim time,..)
AR type (1P-3P-3P, 3P-3P,.)
Devices list Time open
Time close
Devices listMotion 00 filteringMotion 11 filtering
persistence Closepersistence openToggling option
Devices list
HysteresisDeadbandThresholds 1 to 6
Menu Config / Computer
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
33/35
Schneider Electric 33- CS&P C264 HMI E01
ComputerMain
Bay
Commport
PORTSpeedparitystop..
List configured ports
Menu Config / Computer
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
34/35
Schneider Electric 34- CS&P C264 HMI E01
CONFIG
HMIMain
Bay
COMMAND
MENU TREE
Computer
Menu HMI
5/20/2018 L1-V4-04-MiCOM C264 HMI-E-01
35/35
Schneider Electric 35- CS&P C264 HMI E01
HMIMain
Bay
menu tree timeoutLCD lightness timeoutdevices selection timeout
PasswordPassword validity timeout
Bay list
Suppression activationof devices names
Menu HMI