MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 1

Approved by: JW

LOCALFIRE FIGHTINGMANUAL

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 2

Approved by: JW

CONTENTS

1. Blank Form 2

2. A sample of “Main engine side Fire Fighting Manual” 4

3. A sample of “Diesel generator side Fire Fighting Manual” 10

4. A sample of “Main turbine side Fire Fighting Manual” 16

5. A sample of “Main boiler side Fire Fighting Manual” 23

6. A sample of “Galley area Fire Fighting Manual” 30

7. A sample of “Accommodation area Fire Fighting Manual” 37

8. A sample of “Pump Room Fire Fighting Manual” 44

9. A sample of “Paint Store Fire Fighting Manual” 50

Note:

*A : Engine room area

*B : Galley area

*C : Accommodation area

*D : Pump Room

*E : Paint Store

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 3

Approved by: JW

Local Fire F ighting Manual

Main Engine Side Fire F ighting Manual

1) Floor plan : See plan below 2) Area: m²

3) Dangerousness :

3) WATCH ORGANIZATION:

4) Means of communication:

5) Fire Alarm etc.: See plan below 6) Gate Way(Escape Route):See plan below

7) Adjacent Area:

8) S/B Area:

9) Electric Equipment: See plan below 10) Location of equipment: See plan below

11) Ventilation Equipment:

12) Approach/Escape route:

13) Shelters:

14) Check list

Location of the fire:

Time of the breaking out of the fire:

Crew members on duty:

The aspect of the fire (What’s burning?):

Ventilation control procedure:

Fire fighting procedure:

Access and escape routes:

Rescue routes:

Overhaul/Salvage procedure (Restoration of propulsion):

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 4

Approved by: JW

Floor Plan - 4 th Deck

(Legend)

1) :

2) :

3) :

4) :

15) Ventilation control

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 5

Approved by: JW

16) Fire Fighting Procedure

<Sheet 1> Discovery → Initial Fire Fighting

Report the leakage to the space supervisor and/or bridge.

Securing the Leakage.1) Stop the main engine promptly.2) Stop oil pumps on the leaking line.3) Slow the leakage or deflect it from hot surface

with old blanket or rag.

Discovery

Start Initial Fire Fighting1) Fight the fire with water fog.2) Fight the fire with portable fire extinguishers.

* Foam and dry chemical are probably the two most effective extinguishing agents available for use against combustible or flammable liquid hydrocarbon fire.

Complete Extinguishment

Initial fire fighting

Is Fire Spreading?

Size up Fire(see Sheet 2)

Yes

No

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 6

Approved by: JW

<Sheet 2> Size up Fire

Fire Fighting

Does fire occupy a large area?

Is fuel out of control?

Yes

No

Yes

Yes

No

Size up Fire

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 7

Approved by: JW

<Sheet 3> Evacuating →

Fire Fighting with Fixed CO2 Fire Extinguishing System

Is fire threatening fire fighting or

escape?

Are large amounts of smoke filling space?

Continue Initial Fire Fighting Fire is out of control

Evacuate Space(See Sheet 3)

Yes

No

No

Complete Extinguishment

Fire is out of control.

Evacuate space1) Space supervisor directs space evacuation.2) Leave space by nearest safe exit.

Secure all doors and accesses to space when all personnel are out of space.

Secure fuel at remote shut off as applicable.

Fight the Fire with Fixed CO2 Fire Extinguishing System.

1) Check the presence of all personnel.2) Activate fixed CO2 fire extinguishing system.3) Cool down the inside of the engine room by pouring

water in the adjoining areas.4) Regularly measure temperature in various locations of

the engine room to monitor how it is cooling.

Close ventilation dampers and doors.

Stop the generators, boiler and ventilators.

Evacuating

Fire Fighting with Fixed CO2

Fire Extinguishing

System

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 8

Approved by: JW

Local Fire F ighting Manual

Diesel Generatror Side Fire F ighting Manual

(In case of a fire caused by the leakage of fuel oil)

1) Floor plan : See plan below 2) Area: m²

3) Dangerousness :

3) WATCH ORGANIZATION:

4) Means of communication:

5) Fire Alarm etc.: See plan below 6) Gate Way(Escape Route):See plan below

7) Adjacent Area:

8) S/B Area:

9) Electric Equipment: See plan below 10) Location of equipment: See plan below

11) Ventilation Equipment:

12) Approach/Escape route:

13) Shelters:

Complete Extinguishment

Is Fire Out?

Abandon Ship

No

Yes

14) Check list

Location of the fire:

Time of the breaking out of the fire:

Crew members on duty:

The aspect of the fire (What’s burning?):

Ventilation control procedure:

Fire fighting procedure:

Access and escape routes:

Rescue routes:

Overhaul/Salvage procedure (Restoration of propulsion):

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 9

Approved by: JW

Floor Plan - (5th Deck)

(Legend)

1) :

2) :

3) :

4) :

15) Ventilation Control

1) Set up openings in the upper portion of the engine room.

2) Ventilation control for burning diesel generator space

Operate exhaust fans or reversible fans in the exhaust mode.

→ Set negative ventilation

3) Ventilation control in unaffected machinery space

Keep running supply fans.

→ Set positive ventilation

* Maintain the engine room at positive pressure in order to remove smoke and heat; never make it negative.

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 10

Approved by: JW

16) Fire Fighting Procedure

< Sheet 1> Discovery → Initial Fire Fighting

Report the leakage to the space supervisor and/or bridge.

Securing the Leakage.

1) Slow the leakage or deflect it from hot surface with old blanket or rag.

2) Change over to another generator and stop the relevant one.

3) If oil leaking at a high rate, or an urgent response is required as in the case of the outbreak of a fire, press the emergency stop button for the generator.

Start initial fire fighting1) Fight the fire with water fog.2) Fight the fire with portable fire extinguishers.

*Foam and dry chemical are probably the two most effective extinguishing agents available for use against combustible or flammable liquid hydrocarbon fire.

Discovery

Initial Fire Fighting

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 11

Approved by: JW

<Sheet 2> Size up Fire

Complete Extinguishment

Fire fighting

Is fire spreading?

Size up Fire(see Sheet 2)

Size up fire

Yes

No

Does fire occupy a large area?

Is fuel out of control?

Is fire threatening fire fighting or escape?

Are large amounts of smoke filling space?

Yes

No

Yes

Yes

Yes

No

No

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 12

Approved by: JW

<Sheet 3> Evacuating →

Fire Fighting with Fixed CO2 Fire Extinguishing System

Continue Initial Fire Fighting Fire is out of control

Evacuate Space(see Sheet 3)

Evacuate Space

1) Space supervisor directs space evacuation.

2) Leave space by nearest safe exit.

Secure all doors and accesses to space when all personnel are out of space.

No

Complete Extinguishment

Fire is out of control

Evacuating

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 13

Secure fuel at remote shut off as applicable.

Fight the Fire with Fixed CO2 Fire Extinguishing System.1) Check the presence of all personnel.

2) Activate fixed CO2 fire extinguishing system.

3) Cool down the inside of the engine room by pouring water in the adjoining areas.

4) Regularly measure temperature in various locations of the engine room to monitor how it is cooling.

Close ventilation dampers and doors.

Stop the generators, boiler and ventilators.

Complete Extinguishment

Fire Fighting with fixed CO2

Fire Extinguishing

System

IS FIRE OUT?

ABANDON SHIP

No

Yes

Approved by: JW

Local Fire F ighting Manual

Diesel Generatror Side Fire F ighting Manual

(In case of a fire caused by the leakage of fuel oil)

1) Floor plan : See plan below 2) Area: m²

3) Dangerousness :

3) WATCH ORGANIZATION:

4) Means of communication:

5) Fire Alarm etc.: See plan below 6) Gate Way(Escape Route):See plan below

7) Adjacent Area:

8) S/B Area:

9) Electric Equipment: See plan below 10) Location of equipment: See plan below

11) Ventilation Equipment:

12) Approach/Escape route:

13) Shelters:

14) Check list

Location of the fire:

Time of the breaking out of the fire:

Crew members on duty:

The aspect of the fire (What’s burning?):

Ventilation control procedure:

Fire fighting procedure:

Access and escape routes:

Rescue routes:

Overhaul/Salvage procedure (Restoration of propulsion):

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 14

Approved by: JW

Floor Plan - (3rd Deck)

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 15

Approved by: JW

(4th Deck)

(Legend)

1)

2)

3)

4)

5)

6)

7)

8)

9)

10)

15) Ventilation Control

2) Set up openings in the upper portion of the engine room.

3) Ventilation control for main turbine space

Operate exhaust fans or reversible fans in the exhaust mode.

→ Set negative ventilation

4) Ventilation control in unaffected machinery space

Keep running supply fans.

→ Set positive ventilation

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 16

Approved by: JW

16) Fire Fighting Procedure

<Sheet 1> Discovery → Initial Fire Fighting

Report the leakage to the space supervisor and/or bridge.

Securing the Leakage.

1) Stop the main turbine promptly.

2) Shut down oil leaks. Otherwise, prevent the spray of oil by shielding.

3) Stop the main steam line to cut off main steam as a heat source.

4) Remove the insulation soaked with oil.

Discovery

* Maintain the engine room at positive pressure in order to remove smoke and heat; never make it negative.

Start Initial Fire Fighting

1) Fight the fire with water fog.

2) Fight the fire with portable fire extinguishers.*Foam and dry chemical are probably the two most effective extinguishing agents available for use against combustible or flammable liquid hydrocarbon fire.

Complete Extinguishment

Initial Fire Fighting

Is fire spreading?

Size up fire(See Sheet 2)

Yes

No

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 17

Approved by: JW

<Sheet 2> Size up fire

Fire Fighting

Does fire occupy a large area?

Is fuel out of control?

Is fire threatening fire fighting or escape?

Yes

No

Yes

Yes

No

No

Size up Fire

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 18

Approved by: JW

<Sheet 3> Evacuating →

Fire Fighting with Fixed CO2 Fire Extinguishing System

Are large amounts of smoke filling space?

Continue Initial Fire Fighting Fire is out of control

Evacuate Space(see Sheet 3)

Evacuate Space1) Space supervisor directs space evacuation.

2) Leave space by nearest safe exit.

Yes

No

Complete Extinguishment

Fire is out of control.

Evacuating

Secure all doors and accesses to space when all personnel are out of space.

Secure fuel at remote shut off as applicable.

Fight the Fire with fixed CO2 Fire Extinguishing System.

1) Check the presence of all personnel.

2) Activate fixed CO2 fire extinguishing system.

3) Cool down the inside of the engine room by pouring water in the adjoining areas.

4) Regularly measure temperature in various locations of the engine room to monitor how it is cooling.

Close ventilation dampers and doors.

Stop the generators, boiler and ventilators.

Complete Extinguishment

Fire Fighting with fixed CO2

Fire Extinguishing

System

Is Fire Out?

Abandon ship

No

Yes

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 19

Approved by: JW

Local Fire F ighting Manual

Main Boiler Side Fire F ighting Manual

(In case of a fire caused by the leakage of fuel oil)

1) Floor plan : See plan below 2) Area: m²

3) Dangerousness :

3) WATCH ORGANIZATION:

4) Means of communication:

5) Fire Alarm etc.: See plan below 6) Gate Way(Escape Route):See plan below

7) Adjacent Area:

8) S/B Area:

9) Electric Equipment: See plan below 10) Location of equipment: See plan below

11) Ventilation Equipment:

12) Approach/Escape route:

13) Shelters:

14) Check list

Location of the fire:

Time of the breaking out of the fire:

Crew members on duty:

The aspect of the fire (What’s burning?):

Ventilation control procedure:

Fire fighting procedure:

Access and escape routes:

Rescue routes:

Overhaul/Salvage procedure (Restoration of propulsion):

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 20

Approved by: JW

Floor Plan - (2nd Deck)

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 21

Approved by: JW

(2nd Deck)

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 22

Approved by: JW

(Legend)

1) :3.5kg Dry powder portable fire extinguisher

2) :Fire & General alarm bell with red lamp

3) :Ionization detector

4) :Alarm lamp box

5) :Electric horn

6) :Flashing light

7) :Fire hose rack

8) :Fire damper

9) :Air horn for Fire & General alarm

10) :Flame detector

15) Ventilation Control

1) Set up openings in the upper portion of the engine room.

2) Ventilation control for boiler space

Operate exhaust fans or reversible fans in the exhaust mode.

→ Set negative ventilation

3) Ventilation control in unaffected machinery space

Keep running supply fans.

→ Set positive ventilation

*Maintain the engine room at positive pressure in order to remove smoke and heat; never make it negative.

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 23

Approved by: JW

16) Fire Fighting Procedure

<Sheet 1> Discovery → Initial Fire Fighting

Report the leakage to the space supervisor and/or bridge.

Securing the Leakage.1) Stop the main turbine promptly.

2) Manually trip the boiler where the leak is occurring.

3) Stop the fuel intake valve and take measure to rectify the situation.

Start initial Fire Fighting

1) Fight the fire with water fog.

2) Fight the fire with portable fire extinguishers.*Foam and dry chemical are probably the two most effective extinguishing agents available for use against combustible or flammable liquid hydrocarbon fire.

Discovery

Initial fire fighting

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 24

Approved by: JW

<Sheet 2> Size up fire

Complete Extinguishment

Fire Fighting

Is fire spreading?

Size up Fire(See Sheet 2)

Size up Fire

Yes

No

Does fire occupy a large area?

Is fuel out of control?

Is fire threatening fire fighting or escape?

Are large amounts of smoke filling space?

Yes

No

Yes

Yes

Yes

No

No

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 24

Approved by: JW

<Sheet 3> Evacuating →

Fire Fighting with Fixed CO2 Fire Extinguishing System

Continue initial Fire Fighting Fire is out of control

Evacuate Space(see Sheet 3)

Evacuate Space1) Space supervisor directs space evacuation.

2) Leave space by nearest safe exit.

Secure all doors and accesses to space when all personnel are out of space.

Stop the generators, boiler and ventilators.

No

Complete Extinguishment

Fire is out of control

Evacuating

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 25

Approved by: JW

Secure fuel at remote shut off as applicable.

Fight the Fire with Fixed CO2 fire Extinguishing System.

1) Check the presence of all personnel.

2) Activate fixed CO2 fire extinguishing system

3) Cool down the inside of the engine room by pouring water in the adjoining areas.

4) Regularly measure temperature in various locations of the engine room to monitor how it is cooling.

Close ventilation dampers and doors.

Complete Extinguishment

Fire Fighting with fixed CO2

Fire Extinguishing

System

Is Fire Out?

Abandon Ship

No

Yes

Local Fire F ighting Manual

Galley Area Fire F ighting Manual

(In case of a fire in galley)

1) Floor plan : See plan below 2) Area: m²

3) Dangerousness :

3) WATCH ORGANIZATION:

4) Means of communication:

5) Fire Alarm etc.: See plan below 6) Gate Way(Escape Route):See plan below

7) Adjacent Area:

8) S/B Area:

9) Electric Equipment: See plan below 10) Location of equipment: See plan below

11) Ventilation Equipment:

12) Approach/Escape route:

13) Shelters:

14) Check list

Location of the fire:

Time of the breaking out of the fire:

Crew members on duty:

The aspect of the fire (What’s burning?):

Ventilation control procedure:

Fire fighting procedure:

Access and escape routes:

Rescue routes:

Overhaul/Salvage procedure (Restoration of propulsion):

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 26

Approved by: JW

Floor Plan - (A deck)

The Upper Floor (B Deck)

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 27

Approved by: JW

Floor of the Scene (A Deck)

The Lower Floor (Upper Deck)

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 28

Approved by: JW

(Legend)

1) :Fire & General alarm bell with red lamp

2) :Ionization detector

3) :Fire hose rack

4) :Fire damper

⑯15) Ventilation Control

1) Close all doors.

2) Stop the ventilation system including the air conditioning plant.

MOL TANKSHIP MANAGEMENT LTD Title: Search, Rescue & First Aid Manual

Local Fire Fighting Manual Section No: 1 - Page No: 30

Approved by: JW

16) Fire Fighting Procedure

<Sheet 1> Discovery → Initial Fire Fighting

Report the fire to bridge.Push the button for fire alarm in the galley.

Start Initial Fire Fighting

1) Cover the fire with a fire blanket.

2) Fight the fire with portable fire extinguishers.

3) If the fire is large enough or a fire attack with portable extinguishers is difficult, fight the fire with fog water.

Discovery

Initial Fire Fighting

Confine the Fire1) Close all Fire Resisting Doors in the vicinity.

2) Close all doors, ports and dampers to prevent convection.

ExposureProtection

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 31

Approved by: JW

<Sheet 2> Full Scale Fire Fighting

Complete Extinguishment

Start Full scale fire fighting

Is Fire Spreading?

Full scale Fire Fighting(see Sheet 2)

Full scale Fire Fighting

Size up Fire

Yes

No

Does fire occupy a large area?

Is fire threatening fire fighting or escape?

Are large amounts of smoke filling space?

Continue Full Scale Fire FightingFire is out of control

Yes

No

Yes

Yes

No

No

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 32

Approved by: JW

<Sheet 3> Evacuating → Abandon ship

Evacuate Space(See Sheet 3)

Evacuate Space

1) Space supervisor directs space evacuation.

2) Leave space.

Close ventilation dampers and a door when all personnel are out of space.

Complete Extinguishment

Fire is out of control.

Evacuating

ABANDON SHIP

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 33

Approved by: JW

Local Fire F ighting Manual

Accommodation Area Fire F ighting Manual

(In case of a fire in the Officer’s Laundry)

1) Floor plan : See plan below 2) Area: m²

3) Dangerousness :

3) WATCH ORGANIZATION:

4) Means of communication:

5) Fire Alarm etc.: See plan below 6) Gate Way(Escape Route):See plan below

7) Adjacent Area:

8) S/B Area:

9) Electric Equipment: See plan below 10) Location of equipment: See plan below

11) Ventilation Equipment:

12) Approach/Escape route:

13) Shelters:

14) Check list

Location of the fire:

Time of the breaking out of the fire:

Crew members on duty:

The aspect of the fire (What’s burning?):

Ventilation control procedure:

Fire fighting procedure:

Access and escape routes:

Rescue routes:

Overhaul/Salvage procedure (Restoration of propulsion):

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 34

Approved by: JW

Floor Plan - (D deck)

The Upper Floor - (E Deck)

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 35

Approved by: JW

Floor of the Scene - (D Deck)

The Lower Floor - (C Deck)

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 36

Approved by: JW

(Legend)

1) :Fire & General alarm bell with red lamp

2) :Ionization detector

3) :Fire hose rack

4) :Fire damper

16) Ventilation Control

1) Close all doors.

2) Stop the ventilation system including the air conditioning plant.

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 37

Approved by: JW

16) Fire Fighting Procedure

<Sheet 1> Discovery → Initial Fire F ighting

Report the Fire to Bridge.Push the button for fire alarm in the stair case or on D Dk.

Start Initial Fire Fighting

1) Fight the fire with portable fire extinguishers.

Discovery

Initial Fire Fighting

Is Fire Spreading?

Yes

Confine the Fire

1) Close all fire Resisting Doors in the Vicinity.

2) Close all doors, ports and dampers to prevent convection.

ExposureProtection

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 38

Approved by: JW

<Sheet 2 > Full Scale Fire Fighting

Complete Extinguishment

Start Full Scale Fire Fighting1) In case of an incipient or free burning fire, fight the

base of the fire with directing a solid stream of water.

2) In case of an intense condition such as excessive heat or potential flashover, fight the fire with the indirect attack.

Full Scale Fire Fighting(See Sheet 2)

Full Scale Fire Fighting

No

Does fire occupy a large area?

Is fire threatening fire fighting or escape?

Are large amounts of smoke filling space?

Continue Full Scale Fire Fighting Fire is out of control

Evacuate Space(See Sheet 3)

Yes

Yes

Yes

No

No

No

Complete Extinguishment

Size up Fire

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 39

Approved by: JW

<Sheet 3> Evacuating → Abandon Ship

Evacuate Space

1) Space supervisor directs space evacuation.

2) Leave space.

Close ventilation dampers and a door when all personnel are out of space.

Fire is out of control.

Evacuating

ABANDON SHIP

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 40

Approved by: JW

Local Fire F ighting Manual

Pump Room Fire F ighting Manual

(In case of a fire in caused by the Leakage of Cargo Oil)

1) Floor plan : See plan below 2) Area: m²

3) Dangerousness :

3) WATCH ORGANIZATION:

4) Means of communication:

5) Fire Alarm etc.: See plan below 6) Gate Way(Escape Route):See plan below

7) Adjacent Area:

8) S/B Area:

9) Electric Equipment: See plan below 10) Location of equipment: See plan below

11) Ventilation Equipment:

12) Approach/Escape route:

13) Shelters:

14) Check list

Location of the fire:

Time of the breaking out of the fire:

Crew members on duty:

The aspect of the fire (What’s burning?):

Ventilation control procedure:

Fire fighting procedure:

Access and escape routes:

Rescue routes:

Overhaul/Salvage procedure (Restoration of propulsion):

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 41

Approved by: JW

Floor Plan - (Lower F loor)

Upper Deck

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 42

Approved by: JW

3 rd Deck

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 41

Approved by: JW

(Legend)

1) :Fire & General alarm bell with red lamp

2) :Ionization detector

3) :Fire hose rack

4) :Fire damper

5) :Air horn for Fire & General alarm

6) :Flame detector

15)Ventilation Control

1) Keep running the pump room exhaust fan.

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 44

Approved by: JW

16) Fire Fighting Procedure

<Sheet 1> Discovery → Initial Fire Fighting

Report the leakage to the space supervisor and/or bridge.

Securing the Leakage.

1) Slow the leakage or deflect it from hot surface with old blanket or rag.

2) Stop all cargo operation and shut all valves on the cargo piping system.

Start initial fire fighting1) Fight the fire with portable fire extinguishers.

※ Foam and dry chemical are probably the two most effective extinguishing agents available for use against combustible or flammable liquid hydrocarbon fire.

Discovery

Initial Fire Fighting

Yes

Remove combustibles in adjoining compartments.1) Remove combustibles in adjoining compartment of the

pump room.

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 45

Approved by: JW

<Sheet 2> Evacuating →

Fire Fighting with Fixed CO2 Fire Extinguishing System

Complete Extinguishment

Evacuate Space

1) Space supervisor directs space evacuation.

2) Leave space by entrance.

Secure entrance doors when all personnel are out of space.

Is Fire Spreading?

Fire is out of control(See Sheet 2)

No

Fire is out of control.

Evacuating

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 46

Fight the fire with fixed CO2 fire extinguishing system.

1) Check the presence of all personnel.

2) Activate fixed CO2 fire extinguishing system.

3) Cool down the inside of the pump room by pouring water in the adjoining areas.

4) Regularly measure temperature in various locations of the pump room to monitor how it is cooling.

Close Ventilation Dampers.

Complete Extinguishment

Fire Fighting with fixed CO2

Fire Extinguishing

System

Is Fire Out?

Abandon Ship

No

Yes

Approved by: JW

Local Fire F ighting Manual

Paint Store Fire F ighting Manual

(In case of a Paint Fire)

1) Floor plan : See plan below 2) Area: m²

3) Dangerousness :

3) WATCH ORGANIZATION:

4) Means of communication:

5) Fire Alarm etc.: See plan below 6) Gate Way(Escape Route):See plan below

7) Adjacent Area:

8) S/B Area:

9) Electric Equipment: See plan below 10) Location of equipment: See plan below

11) Ventilation Equipment:

12) Approach/Escape route:

13) Shelters:

14) Check list

Location of the fire:

Time of the breaking out of the fire:

Crew members on duty:

The aspect of the fire (What’s burning?):

Ventilation control procedure:

Fire fighting procedure:

Access and escape routes:

Rescue routes:

Overhaul/Salvage procedure (Restoration of propulsion):

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 46

Approved by: JW

Floor Plan - (Upper deck)

The Upper Floor - (A Deck)

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 48

Approved by: JW

Floor of the Scene - (Upper Deck)

The Lower Floor - (2 nd Deck)

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 49

Approved by: JW

(Legend)

1) :3.5kg Dry powder portable fire extinguisher

2) :Fire & General alarm bell with red lamp

3) :Ionization detector

4) :Alarm lamp box

5) :Electric horn

6) :Fire hose rack

7) :Fire damper

8) :Air horn for Fire & General alarm

15) Ventilation Control

Open fire dampers and a door of the paint store.

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 50

Approved by: JW

16) Fire Fighting Procedure

<Sheet 1> Discovery → Initial Fire Fighting

Report the fire to bridge.Push the button for fire alarm in the Hydraulic pump room.

Start Initial Fire Fighting

1) Fight the fire with portable fire extinguishers.*Foam and dry chemical are probably the two most effective extinguishing agents available for use against combustible or flammable liquid hydrocarbon fire.

2) If the fire is large enough or a fire attack with portable extinguishers is difficult, fight the fire with fog water.

Discovery

Initial Fire Fighting

Yes

Remove combustibles in adjoining compartments. 1) Take out the drums in L.O. and hydraulic oil store.

ExposureProtection

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 51

Approved by: JW

<Sheet 2> Full Scale Fire Fighting

Complete Extinguishment

Start Full Scale Fire Fighting

Is Fire Spreading?

Full Scale Fire Fighting(See Sheet 2)

Full Scale Fire Fighting

Size up Fire

No

In case the fixed CO2 fire extinguishing system or the sprinkler was equipped in the paint store, these systems should be used effectively as the full scale fire fighting.

Does fire occupy a large area?

Is fire threatening fire fighting or escape?

Are large amounts of smoke filling space?

Fire is out of control

Yes

Yes

Yes

No

No

No

MOL TANKSHIP MANAGEMENT LTD

Local Fire Fighting Manual

Title: Search, Rescue & First Aid Manual

Section No: 1 - Page No: 52

Approved by: JW

<Sheet 3> Evacuating → Abandon Ship

Continue Full Scale Fire Fighting

Evacuate Space(See Sheet 3)

Evacuate Space

1) Space supervisor directs space evacuation.

2) Leave space.

Close ventilation dampers and a door when all personnel are out of space.

Complete Extinguishment

Fire is out of control.

Evacuating

ABANDON SHIP