Mccb Eaton

Embed Size (px)

Citation preview

  • 8/20/2019 Mccb Eaton

    1/132

    CA08104001E For more information, visit: www.eaton.com/consultants

    December 2013

    Contents

    Molded-Case Circuit Breakers & Enclosures27

    Sheet 27001

       M  o

       l   d  e   d  -   C  a  s  e

       C   i  r  c  u

       i   t

       B  r  e  a   k  e  r  s   &

       E  n  c   l  o  s  u  r  e  s

     

    Molded-Case Circuit Breakers & Enclosures

    Breaker Type Comparison

     

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.0-2

    Table of Contents

     

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.0-3

    General Description

     

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.1-1Special Function Circuit Breakers

     

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.2-1

    Application Data

     

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.3-1

    Circuit Breaker Selection Data

     

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.4-1

    Specifications

     

    See Eaton’s Product Specification Guide 

     

    , available on CD or on the Web.

    CSI Format: . . . . . . . . . . . . . . . . . . . . . . . . . 1995 2010

    Molded-Case Circuit Breakers . . . . . . . . Section 16475 Section 26 28 11

     

    Electronic Trip Units. . . . . . . . . . . . . . . . Section 16904 Section 26 28 50

     

    Enclosed Circuit Breakers . . . . . . . . . . . Section 16476 Section 26 28 16.11

    Molded-Case Circuit Breakers 

  • 8/20/2019 Mccb Eaton

    2/132

     

    7.0-2

     

    For more information, visit: www.eaton.com/consultants

     

    CA08104001E

    December 2013

     

    Molded-Case Circuit Breakers & Enclosures

     

    Sheet 27

     

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    Breaker Type Comparison

     

    002

     

    Summary of Differences Between Low Voltage Power Circuit Breakers,Insulated-Case Circuit Breakers and Molded-Case Circuit Breakers

     

    There are two main classifications of low voltage circuitbreakers—molded-case circuit breakers and low voltagepower circuit breakers. All UL

     

    ®

     

    , NEMA

     

    ®

     

    and ANSI standards

    are for molded-case circuit breakers and low voltagepower circuit breakers.

    The industry recognizes three types of circuit breakers—molded-case circuit breakers (MCCB), insulated-case circuitbreakers (ICCB) and low voltage power circuit breakersLVPCB). Insulated-case circuit breakers are designed tomeet the standards for molded-case circuit breakers.

    Low voltage power circuit breakers comply with thefollowing standards:

     

     

    ANSI Std. C37.16—Preferred Ratings

     

     

    ANSI Std. C37.17—Trip Devices for LVPCB

     

     

    ANSI Std. C37.50—Test Procedures

     

     

    IEEE

     

    ®

     

    Std. C37.13—LVPCB Used in Enclosures

     

     

    UL 1066—LVPCB

    Molded-case circuit breakers and insulated-case circuitbreakers typically comply with the following standards:

     

     

    UL 489—MCCB

     

     

    UL 489—Molded-Case Switches (MCS)

     

     

    NEMA AB1—MCCB and MCS

     

     

    NEMA AB3—MCCB Application

     

    Table 27.0-1. Breaker Type Comparison Chart

    Description LVPCB

    (Type Magnum™ DS and Series NRX™)

    ICCB

    (Type Magnum SB and Series NRX)

    MCCB

    (QUICKLAG/Series C

     

    ®

     

    /Series G

     

    ®

     

    )

     

    Select tripshort-time rating

    Selective trip over full range of faultcurrents up to interrupting rating(high short-time ratings)

    Selective trip over partial range of faultcurrents within the interrupting rating(medium short-time ratings). Typicallyup to 35 kA

    Selective trip over a smaller range of faultcurrents within the interrupting rating (lowshort-time ratings). Typically 10–13 timesthe frame size

    Operator type Types of operators: mechanicallyoperated and electrically operatedtwo-step stored energy

    Types of operators: mechanicallyoperated and electrically operatedtwo-step stored energy

    Types of operators: mechanically operatedover-center toggle or motor operator

    Closing speed 5-cycle closing for electricallyoperated devices

    5-cycle closing for electricallyoperated devices

    Greater than 5-cycle closing for electricallyoperated devices

    Mounting Available in drawout constructionpermitting racking to a distinct “testposition” and removal for maintenance

    Available in drawout constructionpermitting racking to a distinct “testposition” and removal for maintenance

    Typically fixed-mounted but large framesizes may be available in drawoutconstruction

    Interrupting rating Interrupting duty at 635 Vac:42–100 kA and current limiting withor without fuses up to 200 kA

    Interrupting duty at 508 Vac:35 –150 kA

    Interrupting duty at 480 Vac:22–100 kA without fuses and upto 200 kA with integral fuses or forcurrent-limiting type

    Current limiting Special current limiting types availablewith or without fuses up to 200 kA

    Special current limiting types availablewithout fuses up to 150 kA

    Current limiting available with and withoutfuses up to 200 kA

    Relative cost Higher Medium Low

    Availableframe sizes

    Small number of frame sizes available.Typical 800–6000A

    Small number of frame sizes available.Typical 800–6000A

    Large number of frame sizes available.Typical 100–2500A

    Maintenance Extensive maintenance possible on allframe sizes

    Limited maintenance possible on largerframe sizes

    Very limited maintenance possible on largerframe sizes

    Enclosure types Used in enclosures, MCCs, switchboardsand switchgear

    Used in enclosures, MCCsand switchboards

    Used in enclosures, panelboards,switchboards, MCCs and control panels

    Series ratings Not available in series ratings Not available in series ratings Available in series ratings

    Enclosed rating 100% continuous current rated inits enclosure

    80% continuous-current rated, unlessspecifically stated to be rated 100% inan enclosure

    80% continuous-current rated, unlessspecifically stated to be rated 100% inan enclosure

    Standards ANSI/IEEE C37UL 1066

    NEMA AB1/AB3UL 489 or UL 1066

    NEMA AB1/AB3UL 489

  • 8/20/2019 Mccb Eaton

    3/132

     

    CA08104001E For more information, visit: www.eaton.com/consultants

     

    27

     

    December 2013

     

    Molded-Case Circuit Breakers & Enclosures

     

    Sheet 27

     

    Molded-Case Circuit Breakers

     

    003

     

    Molded-Case Circuit Breakers

     

    Series G 

     

    Table of Contents

     

    General Description

     

    Circuit Breaker Components and Functions . . . . .

     

    27.1-1

     

    Electronic RMS Trip Units . . . . . . . . . . . . . . . . . . . .

     

    27.1-2

     

    Accessories and Modifications . . . . . . . . . . . . . . . .

     

    27.1-7

    Special Function Circuit Breakers

     

    Molded-Case Switches . . . . . . . . . . . . . . . . . . . . . .

     

    27.2-1

     

    Motor Circuit Protectors . . . . . . . . . . . . . . . . . . . . .

     

    27.2-1

     

    Current Limiting Breakers . . . . . . . . . . . . . . . . . . . .

     

    27.2-3

     

    100% Rated Breakers. . . . . . . . . . . . . . . . . . . . . . . .

     

    27.2-5

     

    Series Rated Breaker Combinations. . . . . . . . . . . .

     

    27.2-8

     

    High Instantaneous Breakers forSelective Coordination . . . . . . . . . . . . . . . . . . . . .

     

    27.2-12

     

    Earth Leakage Circuit Breakers . . . . . . . . . . . . . . . .

     

    27.2-12

     

    AFCI Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.2-13

     

    DC Rated Breakers . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.2-14

     

    400 Hz Breaker Application . . . . . . . . . . . . . . . . . . .

     

    27.2-16

     

    HID Rated Breakers . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.2-19

     

    Lighting Control Solenoid Operated Breakers . . .

     

    27.2-19

     

    SWD Rated Breakers . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.2-19

     

    HACR Rated Breakers . . . . . . . . . . . . . . . . . . . . . . .

     

    27.2-19

     

    Engine Generator Circuit Breakers . . . . . . . . . . . . .

     

    27.2-19

     

    Mining Circuit Breakers . . . . . . . . . . . . . . . . . . . . . .

     

    27.2-20

     

    Naval/Marine Rated Breakers . . . . . . . . . . . . . . . . .

     

    27.2-20

     

    Welding Circuit Breakers. . . . . . . . . . . . . . . . . . . . .

     

    27.2-20

    Application Data

     

    Continuous Ampere Rating. . . . . . . . . . . . . . . . . . .

     

    27.3-1

     

    Circuit Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.3-1

     

    Interrupting Ratings. . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.3-1

     

    Circuit Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.3-2

     

    Number of Poles . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.3-2

     

    Ground Fault Protection . . . . . . . . . . . . . . . . . . . . .

     

    27.3-2

     

    Code Considerations . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.3-2

     

    Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.3-2

     

    Feeder Circuits . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.3-2

     

    Branch Circuits . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.3-2

     

    Circuit Breakers Not hp Rated . . . . . . . . . . . . . .

     

    27.3-3

     

    Motor Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.3-4

     

    Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.3-6

     

    Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.3-6

     

    Slash Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.3-7

     

    Cable Sizing/Selection . . . . . . . . . . . . . . . . . . . .

     

    27.3-8

     

    Time Current Curve Characteristics . . . . . . . . . . . .

     

    27.3-9

     

    Selective Coordination . . . . . . . . . . . . . . . . . . . . . .

     

    27.3-10

     

    Breaker Selection Table—100% Selective . . . .

     

    27.3-14

     

    Breaker Selection Table—0.1 Sec Selective . .

     

    27.3-22

     

    Arc Flash. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.3-35

     

    Arcflash Reduction Maintenance System . . . . . . .

     

    27.3-36

     

    Unusual Environmental Conditions . . . . . . . . . . . .

     

    27.3-37

     

    Reverse-Feed Applications . . . . . . . . . . . . . . . . . . .

     

    27.3-38

    Circuit Breaker Selection Data

     

    Overview Tables . . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.4-1

     

    QUICKLAG

     

    ®

     

    Industrial Circuit Breakers . . . . . .

     

    27.4-1

     

    Series G Industrial Circuit Breakers . . . . . . . . .

     

    27.4-4

     

    Series C Industrial Circuit Breakers. . . . . . . . . .

     

    27.4-5

     

    Current Limiting Industrial Circuit Breakers. . .

     

    27.4-6

     

    Industrial Circuit Breakers in Assemblies. . . . .

     

    27.4-7

     

    Electronic Trip Units . . . . . . . . . . . . . . . . . . . . . .

     

    27.4-8

     

    Digitrip OPTIM . . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.4-10

     

    Individual Circuit Breaker Selection Data . . . . . . .

     

    27.4-11

     

    QUICKLAG Industrial Circuit Breakers . . . . . . .

     

    27.4-11

     

    QUICKLAG Solenoid-OperatedCircuit Breakers . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.4-13

     

    Series G Industrial Circuit Breakers . . . . . . . . .

     

    27.4-19

     

    Series C Industrial Circuit Breakers. . . . . . . . . .

     

    27.4-25

     

    Series G Breaker Accessories . . . . . . . . . . . . . .

     

    27.4-33

     

    Series C Breaker Accessories . . . . . . . . . . . . . .

     

    27.4-34

     

    High Instantaneous Circuit Breakerfor Selective Coordination . . . . . . . . . . . . . . .

     

    27.4-35

     

    Motor Circuit Protectors (MCP) . . . . . . . . . . . . .

     

    27.4-38

     

    Motor Protector Circuit Breaker (MPCB). . . . . .

     

    27.4-40

     

    Power Monitoring and MeteringModule (PM3). . . . . . . . . . . . . . . . . . . . . . . . . .

     

    27.4-41

     

    Earth Leakage Circuit Breakers . . . . . . . . . . . . .

     

    27.4-44

     

    Current Limiting Modules and Breakers. . . . . .

     

    27.4-45

     

    Circuit Breaker Enclosures. . . . . . . . . . . . . . . . .

     

    27.4-50

  • 8/20/2019 Mccb Eaton

    4/132

     

    7.0-4

     

    For more information, visit: www.eaton.com/consultants

     

    CA08104001E

    December 2013

     

    Molded-Case Circuit Breakers & Enclosures

     

    Sheet 27

     

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    004

    This page intentionally left blank.

  • 8/20/2019 Mccb Eaton

    5/132

    CA08104001E For more information, visit: www.eaton.com/consultants

    27December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    Molded-Case Circuit Breakers

    General Description005

    General Description

    General CircuitBreaker Information

    Eaton’s molded-case circuit breakers

    are designed to provide circuitprotection for low voltage distributionsystems. They are described byNEMA as, “. . . a device for closingand interrupting a circuit betweenseparable contacts under both normaland abnormal conditions,” and further-more as, “. . . a breaker assembledas an integral unit in a supportingand enclosing housing of insulatingmaterial.” The NEC® describes themas, “A device designed to open andclose a circuit by non-automaticmeans, and to open the circuitautomatically on a predeterminedoverload of current, without injury

    to itself when properly applied withinits rating.”

    So designed, Eaton circuit breakersprotect conductors against overloadsand conductors and connectedapparatus, such as motors andmotor starters, against short circuits.

    Circuit Breaker Componentsand Functions

    Being essentially high interruptingcapacity switches with repetitiveelements, Eaton circuit breakersare comprised of three mainfunctional components. These are:

    1. Trip elements (thermal-magneticor electronic)

    2. Operating mechanism3. Arc extinguishers

    1. Trip Elements

    The function of the trip element is to tripthe operating mechanism in the eventof a prolonged overload or short-circuitcurrent. To accomplish this, a thermal-magnetic trip action is provided.

    Thermal-Magnetic Breakers

    Eaton thermal-magnetic breakers aregeneral purpose devices suitable forthe majority of breaker applications

    and are considered the industry stan-dard. Available from 15–800A, thermal-magnetic breakers provide accuratereliable overload and short-circuitprotection for conductors andconnected apparatus.

    Thermal trip action is achievedthrough the use of a bimetal heated bythe load current. On a sustained over-load, the bimetal will deflect, causingthe operating mechanism to trip.Because bimetals are responsive to

    the heat emitted by the current flow,they allow a long-time delay on lightoverloads, yet they have a fastresponse on heavier overloads.

    Magnetic trip action is achieved throughthe use of an electromagnet in serieswith the load current. This provides aninstantaneous tripping action when thecurrent reaches a predetermined value.Front-adjustable magnetic trip elementsare supplied as standard on 250A framecircuit breakers and above (except 100Aand 150A magnetic only breakers), allother thermal-magnetic breakers havenon-adjustable magnetic trip elements.

    Electronic RMS Trip BreakersEaton electronic trip breakers aregenerally applied for applicationswhere high levels of system coordina-tion are called for. Available from20–2500A, today’s electronic tripbreakers can provide superiorprotection and coordination as wellas system alarms and diagnostics,monitoring and communications.

    Both the overload trip action and theshort-circuit trip action of breakerswith Digitrip electronic trip unitsare achieved by the use of currenttransformers and solid-state circuitrythat monitors the current and initiatestripping through a flux shunt tripwhen an overload or a short circuitis present. All multiple-pole circuitbreakers have trip elements in eachpole and a common trip bar. Anabnormal circuit condition in anyone pole will cause all poles to opensimultaneously.

    Electronic RMS trip breakers caninclude trip features such as:

    ■ Adjustable long-time pickup

    ■ Adjustable short-time pickup

    ■ Adjustable long delay time

    ■ Adjustable short delay time

    ■ Adjustable instantaneous pickup

    ■ Adjustable ground fault pickup

    ■ Adjustable ground fault delay time

    ■ Zone selective interlocking

    ■ Communications

    Trip unit adjustments are made bysetting switches on the front of the tripunit or by programming the trip unitelectronically.

    All electronic RMS trip breakers areequipped with a manual push-to-trip

    mechanism.

    2. Operating Mechanism

    The function of the operating mecha-nism is to provide a means of openingand closing the breaker contacts. Allmechanisms are of the quick-make,quick-break type and are “trip free.”“Trip free” mechanisms are designedso that the contacts cannot be heldclosed against an abnormal circuitcondition and are sometimes referredto as an “overcenter toggle mechanism.” In addition to indicating whether thebreaker is “on” or “off,” the operatingmechanism handle indicates when the

    breaker is “tripped” by moving to aposition midway between the extremes.This distinct trip point is particularlyadvantageous where breakers aregrouped, as in panelboard applications,because it clearly indicates the faultycircuit. The operating mechanismcontains a positive on feature. In thenormal switching operation, thehandle of the circuit breaker will notbe capable of being left readily at or nearthe off position when the main contactsare closed.

    3. Arc Extinguishers

    The function of the DE-ION® arc

    extinguisher is to confine, divideand extinguish the arc drawn betweenopening breaker contacts. It consists ofspecially shaped steel grids isolatedfrom each other and supported by aninsulating housing. When the contactsare opened, the arc drawn induces amagnetic field in the grids, which inturn draws the arc from the contactsand into the grids. The arc is thus splitinto a series of smaller arcs and theheat generated is quickly dissipatedthrough the metal. These two actionsresult in a rapid removal of ions fromthe arc, which hastens dielectric build-up between the contacts and results in

    rapid extinction of the arc.

  • 8/20/2019 Mccb Eaton

    6/132

    7.1-2

    For more information, visit: www.eaton.com/consultants  CA08104001E

    December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    Molded-Case Circuit Breakers

    General Description—Trip Units006

    Electronic RMS Trip Unit

    General

    Eaton offers the most comprehensiverange of electronic trip units in theindustry for molded-case circuit

    breakers. All electronic trip units are rmssensing and can be applied from 70A upthrough 2500A. Eaton offers electronictrip units as standard for circuit breakersrated above 800A, and offers electronictrip units as optional for circuit breakers70A up through 800A.

    Digitrip electronic trip units are ACdevices that employ microprocessor-based technology that provides a truerms current sensing means for propercorrelation with thermal characteristicsof conductors and equipment. Theprimary function of the Digitripelectronic trip unit is to providecircuit protection. This is achievedby analyzing the secondary currentsignals received from the circuitbreaker current sensors and initiatingtrip signals to the circuit breaker  shunttrip when pre-set current levels andtime delay settings are exceeded. AllEaton electronic trip units use a higheffective sampling rate to maintainmeasurement accuracy, monitoring,and protection with nonlinear loadshaving harmonic content up to the27th order.

    Electronic trip units are applied todistribution systems when high stan-dards of protection and coordination

    are called for. In addition, electronictrip units can provide further enhancedfeatures such as alarming, diagnostics,system monitoring and communications.

    Eaton RMS sensing trip units fall intotwo main categories:

    ■ Front adjustable trip units(Digitrip™ RMS 310, 310+,510, 610, 810 and 910)

    ■ Programmable trip units(Digitrip OPTIM™ 550 and 1050)

    Front-Adjustable Trip Units

    Front-adjustable trip units areelectronic trip units that have up tonine time-current setting options thatare set by switches mounted on thefront of the trip unit. The application

    for front adjustable trip units wouldbe distribution systems that can becoordinated within the range ofsettings available and that do notrequire sophisticated coordinationstrategies to be applied downthrough the distribution system tosmall rated breakers.

    Programmable Trip Units (OPTIM)

    Programmable trip units are electronictrip units that have up to 10 time-current setting options that areprogrammed electronically by theuse of a programming device. Theapplication for programmabletrip units would be high integritydistribution systems that requiresuperior levels of system coordinationcoupled with system alarming,diagnostics and monitoring.

    Rating Plugs

    Rating plugs provide a means toestablish the breaker’s continuouscurrent rating. Rating plugs are color-coded and interchangeable to make iteasy to match the correct rating plug

    with the correct trip unit. The samerating plug can be applied to both 50and 60 Hz distribution systems. Somerating plugs are fixed and some havean adjustable range of amperagevalues for greater flexibility. Digitrip310, 510, 610, 810 and 910 trip unitscan be supplied with either a fixed oradjustable rating plug. Digitrip 310+trip units are equipped with adjustablerating plugs. OPTIM style trip units arefurnished with fixed rating plugs buthave a programmable Long TimePickup rating to allow applicationover a range of amperage values.

    Cause of Trip Indication

    All OPTIM and Digitrip 510, 610, 810and 910 trip units include Cause-of-Trip indication LEDs. Breakers usingthe RMS 310+ electronic trip unithave the ability to output cause-of-tripinformation through the test port. TheCause-of-Trip LED module providestrip information via LED indication.The Digiview and PanelmountDigiview can be installed in theRMS 310+ test port to provide bothcause-of-trip information and phasecurrent through an LCD display.

    Cause-of-Trip LED Module Digiview  

  • 8/20/2019 Mccb Eaton

    7/132

    CA08104001E For more information, visit: www.eaton.com/consultants

    27December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    Molded-Case Circuit Breakers

    General Description—Trip Units007

    Table 27.1-1. The Digitrip Family of Low Voltage Electronic Trip Units

    Optional features.

    Additional Protection Features

    Discriminator/Making Current Release

    Eaton’s Digitrip RMS electronic tripunits are designed and built withsafety and reliability in mind, both toprotect the user and the equipment, as

    well as to make sure the trip functionswithin its design parameters. Byproviding a discriminator circuit toDigitrip RMS 510, 610, 810 and 910 tripunits, as well as to Digitrip OPTIM 550and 1050 trip units that do not havean instantaneous setting, the user isprotected should a faulted circuit exist.The discriminator (or making currentreleases as it is often called) is set at11 times the rating plug ampere ratingand is enabled for approximately thefirst 10 cycles of current flow. Shoulda fault condition exist, the breaker willtrip with no intentional time delay onclosing, protecting the user from apotentially unsafe condition.

    Instantaneous Override

    In addition to a discriminator, aninstantaneous override is present inall molded-case and insulated-casecircuit breakers to provide additionalprotection for the breaker. Theinstantaneous override is factoryset nominally just below the breakerwithstand rating.

    Trip Unit Overtemperature

    Digitrip electronic trip units can operatereliably in ambient temperatures thatrange from –20° to 85°C. In the unlikelyevent that temperatures exceed thisambient, the trip unit has a built-inovertemperature trip to protect the trip

    unit should the temperature exceedthese design parameters.

    Thermal Memory

    Digitrip RMS and Digitrip OPTIMelectronic trip units incorporatepowered thermal memory, i.e., theunits remember recent overcurrentevents that may have initiated the triptiming sequence, and then returned tonominal levels, halting the sequenceprior to trip initiation. In the event thatthe current levels again exceed thepickup set point within a few cycles ofthe original pickup, the unit’s memoryrecalls the previous near trip andautomatically imposes a shorterdelay time. In effect, the unit treatsmultiple time-related events as asingle continuous event therebypreventing system damage due tocumulative overheating.

    As a further enhancement, the tripunits incorporate an unpoweredthermal memory feature. In the eventthat current levels cause the breakerto trip and the breaker is immediatelyreclosed, the trip unit remembers theprevious overcurrent trip and again

    imposes a shorter delay time shouldan additional overcurrent occurbefore a sufficient cooldown periodhas elapsed.

    Thermal memory protects thedistribution system from cumulativeoverheating caused by repeated over-

    current conditions. OPTIM trip unitsallow this to be turned ON or OFF.

    System Alarms

    Digitrip RMS 610, 810 and 910electronic trip units incorporate ahigh load alarm capability. Set at 85%of Ir, the alarm will be initiated oncethe load current exceeds 85% for40 seconds. Once this occurs, theHILD message will flash in the displaywindow and the power/relay modulewill operate to send a remote signal.

    Digitrip OPTIM electronic trip unitsalso offer a high load alarm capabilitybut with more flexibility. OPTIM tripunits have a high load alarm that canbe programmed to operate between50% and 100% of Ir.

    Digitrip OPTIM electronic trip unitsincorporate a ground fault alarmcapability. Settings available for groundfault alarm are the same as for groundfault trip. Once a ground fault alarmoccurs, both local and remote signalindication is available (OPTIM 550is remote only).

    RMS 310 RMS 310+ RMS 510 OPTIM 550 RMS 610 RMS 810 RMS 910 OPTIM 1050

    rms sensing—5 functions—Front adjustable

    rms sensing—6 functions—Front adjustable—Optional displayfor diagnosticsand loadmonitoring—Zone selectiveinterlocking—OptionalArcflashReductionMaintenanceSystem™

    rms sensing—9 functions—Front adjustable—Zone selectiveinterlocking—Diagnostics

    rms sensing—10 functions—Programmable—Load monitoring—Diagnostics—Zone selectiveinterlocking

    —Communications

    rms sensing—9 functions—Front adjustable—Zone selectiveinterlocking—Load monitoring—Diagnostics

    rms sensing—9 functions—Front adjustable—Zone selectiveinterlocking—Load monitoring—Diagnostics—Communications—Power and energymonitoring

    rms sensing—9 functions—Front adjustable—Zone selectiveinterlocking—Load monitoring—Diagnostics—Communications—Power and energymonitoring—Harmonics

    rms sensing—10 functions—Programmable—Zone selectiveinterlocking—Load monitoring—Diagnostics—Communications—Power and energymonitoring—Harmonics

  • 8/20/2019 Mccb Eaton

    8/132

    7.1-4

    For more information, visit: www.eaton.com/consultants  CA08104001E

    December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    Molded-Case Circuit Breakers

    General Description—Trip Units008

    System Diagnostics

    Whenever a circuit breaker trips, it isnormally imperative that the cause oftrip be determined quickly, the faultyconditions rectified, and the breakerput back into service. Digitrip RMS

    510, 610, 810 and 910, and DigitripOPTIM electronic trip units incorporatea complete package of systemsdiagnostics to meet this challenge.

    Four cause-of-trip LEDs are embeddedin the front of the trip unit case,indicating that the cause-of-tripwas either a long delay, short delay,instantaneous or ground fault. Remotesignal indication for cause of trip aswell as magnitude of trip informationis also available.

    Breakers using the RMS 310+electronic trip unit have the abilityto output cause-of-trip information

    through the test port. The Cause-of-Trip LED module provides tripinformation via LED indication. TheDigiview and Panelmount Digiviewcan be installed to provide bothcause-of-trip information and phasecurrent through an LCD display.

    Systems Monitoring

    Digitrip RMS and Digitrip OPTIMelectronic trip units offer a completemenu of monitoring capability toinclude current, power and energy,power factor, power quality harmonics,and other related parameters with ahigh level of accuracy.

    Digital Display

    Digitrip RMS 610, 810 and 910 havea large, easy-to-read four-digit alpha-numeric display mounted on the tripunit. The display is supported by LEDsthat indicate which parameter is beingdisplayed along with the unit the valueis displayed in, e.g., kA and so on.

    Current Monitoring

    Digitrip RMS 610, 810 and 910 trip unitsare capable of monitoring currentsin individual phases (A, B, C) as wellas ground currents. Digitrip OPTIM550 and 1050 trip units are capable

    of monitoring currents in individualphases (A, B, C) as well as neutraland ground currents.

    Values are displayed in the digitaldisplay window in kA. Accuracy of thecurrent monitored values is ±2% of fullscale sensor rating.

    Breakers using the Digitrip 310+electronic trip unit have the abilityto output phase current monitoringinformation through the test port. TheDigiview or Panelmount Digiview canbe installed to provide phase currentthrough an LCD display.

    For current and voltage monitoringwith 0.5% accuracy of reading that canbe used with thermal-magnetic orelectronic trip units, refer to the PowerMonitoring/Metering Module (PM3)on Page 27.4-41.

    Power and Energy Monitoring

    For the trip unit to calculate truepower and energy values, a PotentialTransformer Module (PTM) is required.This PTM is mounted internally(R-Frame and larger) or externally(N-Frame or smaller) to the breaker,and provides voltage to the trip unit.

    Digitrip RMS 810 and 910 trip units

    are capable of monitoring peak powerdemand, present power demand, andreverse power flow in MW. Addition-ally, both forward and reverse energyconsumption in MWh can be moni-tored. Digitrip OPTIM 1050 trip unitscan also monitor the same power andenergy parameters, but the units aredisplayed in kW and kWh.

    The accuracy of power monitoredvalues is ±4% of full scale sensor/ frame rating.

    The accuracy of energy monitoredvalues is ±5% of full scale sensor/ frame rating.

    Both the RMS 910 and OPTIM 1050report power factor. Digitrip RMS 910trip units have the additional capabilityof monitoring line-to-line voltage.

    For Real Power and Reactive Powermonitoring with ANSI C12.1 revenueclass accuracy that can be used withthermal-magnetic or electronic tripunits, refer to the Power Monitoring/ Metering Module (PM3) onPage 27.4-41.

    Harmonics Monitoring

    Digitrip RMS 910 and Digitrip OPTIM1050 trip units are capable of monitor-

    ing values of current harmonics.Percentage of total harmonic contentcan be monitored for each level ofharmonic content up to the 27thharmonic. Additionally, a totalharmonic distortion (THD) value canbe calculated and displayed providingthe user with total system currentharmonic monitoring capability.

  • 8/20/2019 Mccb Eaton

    9/132

    CA08104001E For more information, visit: www.eaton.com/consultants

    27December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    Molded-Case Circuit Breakers

    General Description—Trip Units009

    Time-Current Curve Shaping

    Figure 27.1-1. Time-Current Curve Shaping

    Note: See selection guide charts foravailability of adjustments.

    Long Delay (L)

    1. Long Delay PickupDetermines the continuousampere rating of the breaker.

    2. Long Delay TimeDetermines the amount of timethe breaker will carry a low leveloverload before tripping.

    a. I2t ResponseI2t in: For coordination with other circuit breakers with electronictrip devices and for coordinationwith thermal-magneticcircuit breakers.

    b. I4t ResponseI4t in: For coordination withfuses and upstream trans-former damage curves.

    7B

    7A

    6

         T     i    m    e

    5

    1

    4B

    4A

    2A

    2B2

    3

    Current in Multiples

    4

    7

    Short Delay (S)

    3. Short Delay PickupDetermines or sets the levelof fault current at which theshort-time trip delay countdownis actuated.

    4. Short DelaySets the amount of time the breakerwill carry both a low level and highfault currents before tripping.

    a. Flat ResponseI2t out: For coordination withother circuit breakers withelectronic trip devices.

    b. I2t ResponseI2t in: For coordination withfuses and thermal-magneticbreakers.

    Instantaneous (I)

    5. Instantaneous Pickup

    Determines the level of faultcurrent that will actuate a tripwith no time delay.

    Ground Fault (G)

    6. Ground Fault PickupDetermines the level of faultcurrent at which the ground faulttrip delay countdown is actuated.

    7. Ground Fault DelayDetermines the amount of timethe breaker will carry a groundfault before tripping.

    a. Flat ResponseI2t out: For coordination with

    other circuit breakers withelectronic ground fault settings.

    b. I2t ResponseI2t in: For coordination withzero sequence ground faultrelays, fuses and thermal-magnetic breakers.

    Curve Shaping

    Eaton Digitrip RMS 310 trip units areavailable with up to five phase andground adjustments on the front of thetrip unit. Digitrip RMS 310+ trip unitsare available with up to six phase and

    ground adjustments on the front of thetrip unit. Selective system coordinationwith both upstream and downstreamdevices can be achieved to provide aneconomic solution for less sophisticateddistribution systems.

    For more sophisticated selectivecoordination systems Digitrip RMS510, 610, 810 and 910 trip units areavailable with up to nine curve shapingchoices via switches on the front ofthe unit. Curve shaping flexibility isprovided by dependent long and shortdelay adjustments that are based oncontinuous amperes (Ir) selection.

    Digitrip OPTIM 550 and 1050 tripunits offer programmable curveshaping via 10 curve shaping choicesthat are programmed electronicallyinto the trip unit. OPTIM also offersvirtual infinite settings to allow theuser to optimize coordination for aselectively coordinated distributionsystem. In addition, time-current setpoints can be downloaded via acommunication system from a centralpersonal computer. Digitrip OPTIM isnormally applied to systems wheresystem integrity is very important.

  • 8/20/2019 Mccb Eaton

    10/132

    7.1-6

    For more information, visit: www.eaton.com/consultants  CA08104001E

    December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    Molded-Case Circuit Breakers

    General Description—Trip Units010

    Zone Selective InterlockingZone selective interlocking capabilitiesare available with Digitrip RMS 310+510, 610, 810 and 910 trip units aswell as Digitrip OPTIM 550 and1050 trip units.

    Note: Optional accessory on the OPTIM 550.

    Zone selective interlocking providesincreased system protection and canreduce arc flash risk by allowing thebreaker closest to the fault to tripwithout any preset time delays. This isachieved by setting up the distributionsystem as shown in Figure 27.1-2.The hardwired connection betweenthe trip units sends a restraining  signalupstream, allowing the breaker closestto the fault to act instantaneously. Zoneselective interlocking reduces stresson the distribution system and can

    reduce arc flash risk by isolating faultswithout time delays.

    Figure 27.1-2. Zone Selective Interlocking

    Fault 1

    There are no interlocking signals.The main breaker trip unit will initiatethe trip instantaneously.

    Fault 2

    The feeder breaker trip unit will initiatethe trip instantaneously to clear thefault; and Zone 2 will send an inter-locking signal to the Zone 1 trip unit.The Zone 1 trip unit will begin to timeout, and in the event that the feederbreaker in Zone 2 would not clearthe fault, the main breaker in Zone 1will clear the fault in 0.5 seconds.

    Fault 3

    The branch breaker trip unit will initiatethe trip instantaneously to clear thefault; and Zone 3 will send an interlock-ing signal to the Zone 2 trip unit; andZone 2 will send an interlocking signalto Zone 1.

    Zone 1 and Zone 2 trip units willbegin to time out, and in the eventthat the branch breaker in Zone 3would not clear the fault, the feederbreaker in Zone 2 will clear the fault

    in 0.3 seconds. Similarly, in the eventthat the feeder breaker in Zone 2would not clear the fault, the mainbreaker in Zone 1 will clear the faultin 0.5 seconds.

    Zone 1

    Zone 2

    Zone 3

    Fault 1

    Fault 2

    Fault 3

    Load

    BreakerNumber 1

    BreakerNumber 2

    BreakerNumber 3

    Ground Fault Setting:300A PickupNo Time Delay

    Zone SelectiveInterlocking Wiring

    Ground Fault Setting:600A Pickup0.3 Seconds Time Delay

    Ground Fault Setting:1200A Pickup0.5 Seconds Time Delay

  • 8/20/2019 Mccb Eaton

    11/132

    CA08104001E For more information, visit: www.eaton.com/consultants

    27December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    Molded-Case Circuit Breakers

    Accessories and Modifications011

    Internal AccessoriesNote: For a complete listing of availableexternal accessories, see Volume 4—CircuitProtection Catalog, CA08100005E, Section 25.

    All internal accessories are of the

    plug-in type and are listed for fieldinstallation under UL File E64983.Internal accessories for sealed circuitbreakers are listed under UL File E7819for factory installation only. Theavailable plug-in accessories includethe following:

    ■ Alarm (signal)/lockout switch

    ■ Auxiliary switch

    ■ Shunt trip

    ■ Low energy shunt trip

    ■ Undervoltage release mechanism

    Typical Internal Plug-in Accessory Installedin K-Frame Circuit Breaker 

    Different accessory wiring options areavailable to satisfy most circuit breakermounting applications. The standardwiring configuration is pigtail leadsexiting the rear of the base directlybehind the accessory. Optionalconfigurations include a terminal

    block mounted on the same side of thebase as the accessory, leads exiting theside of the base where the accessoryis mounted, and leads exiting the rearof the base on the side opposite theaccessory. If accessory leads longerthan 18.00 inches (457.2 mm) arerequired, side-mounted terminalblocks should be used.

    Alarm (Signal)/Lockout Switch

    The alarm (signal)/lockout switchmonitors circuit breaker trip status andprovides remote signaling and inter-locking capabilities when the circuitbreaker trips. For two-, three- and

    four-pole circuit breakers, the alarm(signal)/lockout switch consists of oneor two SPDT switches assembled to aplug-in module mounted in retainingslots in the top of the trip unit. TheSPDT switch contacts are identified asmake and break contacts. When thecircuit breaker trips, the make contactcloses and the break contact opens.

    Alarm (Signal)/Lockout Switch 

    Auxiliary Switch

    The auxiliary switch provides circuitbreaker contact status informationby monitoring the position of themolded crossbar containing themoving contact arms. The auxiliaryswitch is used for remote signalingand interlocking purposes, andconsists of one or two SPDT switches

    assembled to a plug-in modulemounted in retaining slots in the topof the trip unit. Each SPDT switch hasone “a” and one “b” contact. Whenthe circuit breaker contacts are open,the ”a“ contact is open and the “b”contact is closed.

    Auxiliary Switch 

    Shunt Trip

    The shunt trip provides remote controlled tripping of the circuit breaker. The shunttrip consists of an intermittent ratedsolenoid with a tripping plunger anda cutoff switch assembled to a plug-in

    module. When required for groundfault protection applications, certainAC rated shunt trips are suitable foroperation at 55% of rated voltage.

    Available in most AC and DC voltages.

    Note: Approximate unlatching time—6 milliseconds. Approximate totalcircuit breaker contact opening time—18 milliseconds. Endurance—4000 electricaloperations plus 1000 mechanical opera-tions. Supply voltages suitable for use withClass 1 GFP devices. Marking label includedwith accessory kits.

    Shunt Trip 

    OPTIM Communications Kit

    Eaton’s OPTIM Communications Kitprovides the option to field installPowerNet communications into a K-, L-

    or N-Frame OPTIM 550 breaker. OPTIM1050 trip units come equipped withcommunications as standard.

    OPTIM Communications Kit 

    Make

    Break

    a

    b

    STa

  • 8/20/2019 Mccb Eaton

    12/132

    7.1-8

    For more information, visit: www.eaton.com/consultants  CA08104001E

    December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    Molded-Case Circuit Breakers

    Accessories and Modifications012

    Low Energy Shunt Trip

    Low energy shunt trip devices aredesigned to operate from low energyoutput signals from dedicated currentsensors typically applied in groundfault protection schemes. However,

    with a proper control voltage source,they may be applied in place ofconventional trip devices for specialapplications. Flux paths surroundingpermanent magnets used in the shunttrip assembly hold a charged springpoised in readiness to operate thecircuit breaker trip mechanism. Whena 100 microfarad capacitor charged to28 Vdc is discharged through the shunttrip coil, the resultant flux opposes thepermanent magnet flux field, whichreleases the stored energy in thespring to trip the circuit breaker. Asthe circuit breaker resets, the resetarm is actuated by the circuit breaker

    handle, resetting the shunt trip. Theplug-in module is mounted in retainingslots in the top of the trip unit. Coil isintermittent-rated only. Cutoff provisionsrequired in control circuit.

    Low Energy Shunt Trip 

    Undervoltage Release MechanismThe undervoltage release mechanismmonitors a voltage (typically a linevoltage) and trips the circuit breakerwhen the voltage falls to between 70and 35% of the solenoid coil rating.

    Note: Undervoltage release mechanismaccessories are not designed for, andshould not be used as, circuit interlocks.

    The undervoltage release mechanismconsists of a continuous ratedsolenoid with a plunger and trippinglever assembled to a plug-in module.

    The tab on the tripping lever resets

    the undervoltage release mechanismwhen normal voltage has beenrestored and the circuit breaker handleis moved to the reset (OFF) position.

    With no voltage applied to the under-voltage release mechanism, the circuitbreaker contacts will not touch when aclosing operation is attempted.

    Undervoltage Release Mechanism 

    External AccessoriesNote: For a complete listing of availableexternal accessories, see Volume 4—CircuitProtection Catalog, CA08100005E, Section 25.

    Non-Padlockable Handle Block

    The nonlockable handle block secures

    the circuit breaker handle in either theON or OFF position. (Trip-free operationallows the circuit breaker to trip whenthe handle block holds the circuitbreaker handle in the ON position.)The device is positioned over the circuitbreaker handle and secured by a set-screw to deter accidental operationof the circuit breaker handle. (Fieldinstallation only.)

    Non-Padlockable Handle Block 

    Padlockable Handle Lock HaspThe padlockable handle lock haspallows the handle to be locked in theON or OFF position. (Trip-free operationallows the circuit breaker to trip whenthe handle lock holds the circuit breakerhandle in the ON position.) The haspmounts on the circuit breaker coverwithin the trimline. The cover ispredrilled on both sides of theoperating handle so that the haspcan be mounted on either side of thehandle. The hasp will accommodateup to three padlocks with 1/4-inch(6.4 mm) shackles. One per circuitbreaker. (Field installation only.)

    Padlockable Handle Lock Hasp 

    Key Interlock Kit (Lock Not Included)

    The key interlock is used to externallylock the circuit breaker handle in theOFF position. When the key interlock islocked, an extended deadbolt blocksmovement of the circuit breaker

    handle. Uniquely coded keys areremovable only with the deadboltextended. Each coded key controls agroup of circuit breakers for a givenspecific customer installation.

    The key interlock assembly consistsof a mounting kit and a purchasersupplied deadbolt lock. The mountingkit comprises a mounting plate, whichis secured to the circuit breaker coverin either the left- or right-pole position;key interlock mounting hardware; anda wire seal. Specific mounting kits arerequired for individual key interlocktypes. (Field installation only.)

    Key Interlock Kit 

    Padlockable Handle Block

    The device is positioned in the coveropening to prevent handle movement.Will accommodate one 5/16-inch(8.0 mm) padlock.

    Padlockable Handle Block 

    ST

    LE

    UV

  • 8/20/2019 Mccb Eaton

    13/132

    CA08104001E For more information visit: www.eaton.com/consultants

    27December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    Special Function Circuit Breakers

    Molded-Case Switches013

    Molded-Case SwitchesEaton molded-case switches (MCS)are UL 489 devices that don’t havethermal protection, but do have a self-protecting high-magnetic trip setting.Molded-case switches are applied

    when a compact high-capacitydisconnect device is necessary.Accessories that can be installed inmolded-case circuit breakers are alsoavailable for molded-case switches.The most common application for amolded-case switch would be as amain disconnect for a panelboardor a loadcenter. Available from 100 to2500A, molded-case switches providea compact high-capacity disconnectdevice along with the added benefitsof a molded-case circuit breakerwithout the thermal protection.

    It provides no overcurrent protection,

    overload or low level fault. The MCSis equipped with a high instantaneousmagnetic fixed trip unit. The fixedmagnetic trip is factory preset tointerrupt high fault currents at orabove its preset level. MCS is selfprotecting within its withstand rating.See Table 27.2-1.

    Motor Circuit Protectors

    Application flexibility of Eaton motorcircuit protectors (Type GMCP/HMCP/ HMCPE) is enhanced by the higherinterrupting ratings and current limitingcharacteristics designed into the line.These devices are available from

    3–1200A in 63, 100, 150, 250, 400, 600,800 and 1200A frame sizes.

    The motor circuit protectors aredesigned for application in individualmotor circuits in combination motorstarter units. Motor circuit protectorsoperate on the magnetic principle witha current sensing element in each poleto provide short-circuit protection.

    The motor circuit protector designpermits the most effective protectionpossible against low-level faults whileoffering circuit breaker convenience,quick-make quick-break action,deadfront safety and preventionof single phasing.

    The GMCP and HMCPE are 480Vdevices rated between 3–100A. TheHMCP is a 600V device available in fiveframes and rated between 3–1200A.The MCP is designed to comply withthe applicable requirements ofUnderwriters Laboratories StandardUL 489, Canadian StandardsAssociation Standard C22.2 No. 5,and International ElectrotechnicalCommission RecommendationsIEC 157-1.

    An innovative design of internalcomponents allows higher MCP-startercombination interrupting ratings.The MCP is marked to permit properelectrical application within theassigned equipment ratings.

    The MCP is a recognized component(UL File E7819) and complies with theapplicable requirements of Underwriters Laboratories Standard UL 489. It is alsodesigned to comply with the applicablerequirements of Canadian StandardsAssociation Standard C22.2 No. 5,and International ElectrotechnicalCommission RecommendationsIEC 157-1. The interrupting ratingis defined on the assembledequipment nameplate.

    Table 27.2-1. Molded-Case Switch Short-Circuit Current Ratings at 60 Hz Only(Maximum Fault Current at Which Device can be Applied in kAIC)

    MCSFrame AmpereRating Short-Circuit Current Rating240V 480V 600V 250 Vdc

    GDEHDFD

      100  100  150

      65  18  65

    221435

    ——18

    101010

    HFDJDHJD

      150  250  250

    100  65100

    653565

    251825

    221022

    DKKDHKD

      400  400  400

      65  65100

    —3565

    —2535

    101022

    LDHLDMDL

      600  600  800

      65100  65

    356550

    253525

    222522

    HMDLNDHND

      80012001200

    100  65100

    655065

    352535

    25——

    RDEGKJGK

    2000  125  250

    125100100

    656565

    50—35

    —4242

    LGKLGKNGKRGK

      400  60012002000

    100100100125

    65656565

    35353550

    4242——

  • 8/20/2019 Mccb Eaton

    14/132

    7.2-2

    For more information visit: www.eaton.com/consultants  CA08104001E

    December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    Special Function Circuit Breakers

    Selection Data—Motor Circuit Protectors014

    Motor ProtectionIn line with 2008 NEC 430.6(A)circuit breaker, HMCP and fuse ratingselections are based on full loadcurrents for induction motors runningat speeds normal for belted motors

    and motors with normal torquecharacteristics using data taken fromNEC Table 430.250 (three-phase).Actual motor nameplate ratings willbe used for selecting motor runningoverload protection. Motors builtspecial for low speeds, high torquecharacteristics, special startingconditions and applications willrequire other considerations asdefined in the application sectionof the NEC.

    These additional considerations mayrequire the use of a higher rated HMCP,or at least one with higher magnetic

    pickup settings.Circuit breaker, HMCP and fuseampere rating selections are inline with maximum rules given inNEC 430.52 and Table 430.250. Basedon known characteristics of Eatontype breakers, specific units arerecommended. The current ratingsare no more than the maximum limitsset by the NEC rules for motors withcode letters F to V or without codeletters. Motors with lower code letterswill require further considerations.

    In general, these selections werebased on:

    1. Ambient—Outside enclosure notmore than 40°C (104°F).

    2. Motor starting—Infrequentstarting, stopping or reversing.

    3. Locked rotor—Maximum 6 timesmotor FLA.

    4. Locked rotor—Maximum 6 timesmotor FLA.

    Type HMCP motor circuit protectormay not be set more than 1300% ofthe motor full-load current to complywith NEC 430.52 (except for NEMADesign B energy efficient motors,

    which can be set up to 1700%).

    Circuit breaker selections are basedon types with standard interruptingratings. Higher interrupting ratingtypes may be required to satisfyspecific system applicationrequirements.

    For motor full load currents of 208Vand 200V, increase the corresponding230V motor values by 10 and 15%respectively.

    Table 27.2-2. Motor Circuit Protector (MCP), Circuit Breaker and Fusible Switch Selection Guide

    Horsepower Full LoadAmperes(NEC) FLA

    Fuse Size NEC 430.52MaximumAmperes

    Recommended Eaton

    CircuitBreaker

    Motor CircuitProtector Type HMCP

    Time Delay Non-Time Delay Amperes Amperes Adj. Range

    230V, Three-Phase

      1  1-1/2  2  3

      3.6  5.2  6.8  9.6

      10  10  15  20

      15  20  25  30

      15  15  15  20

      7  15  15  30

      21–70  45–150  45–150  90–300

      5  7-1/2  10  15

      15.2  22  28  42

      30  40  50  80

      50  70  90  150

      30  50  60  90

      30  50  50  70

      90–300  150–500  150–500  210–700

      20  25  30  40

      54  68  80104

      100  125  150  200

      175  225  250  350

    100125150150

    100150150150

      300–1000  450–1500  450–1500  750–2500

      50  60  75100

    130154192248

      250  300  350  450

      400  500  600  800

    200225300400

    150250400400

      750–25001250–25002000–40002000–4000

    125

    150200

    312

    360480

      600

      7001000

    1000

    12001600

    500

    600700

    600

    600600

    1800–6000

    1800–60001800–6000

    460V, Three-Phase

      1  1-1/2  2  3

      1.8  2.6  3.4  4.8

      6  6  6  10

      6  10  15  15

      15  15  15  15

      7  7  7  15

      21–70  21–70  21–70  45–150

      5  7-1/2  10  15

      7.6  11  14  21

      15  20  25  40

      25  35  45  70

      15  25  35  45

      15  30  30  50

      45–150  90–300  90–300  150–500

      20  25  30  40

      27  34  40  52

      50  60  70  100

      90  110  125  175

      50  70  70100

      50  70100100

      150–500  210–700  300–1000  300–1000

      50  60

      75100

      65  77

      96124

      125  150

      175  225

      200  150

      300  400

    110125

    150175

    150150

    150150

      450–1500  750–2500

      750–2500  750–2500

    125150200

    156180240

      300  350  450

      500  600  800

    225250350

    250400400

    1250–25002000–40002000–4000

    575V, Three-Phase

      1  1-1/2  2  3

      1.4  2.1  2.7  3.9

      3  6  6  10

      6  10  10  15

      15  15  15  15

      3  7  7  7

      9–30  21–70  21–70  21–70

      5  7-1/2  10  15

      6.1  9  11  17

      15  20  20  30

      20  30  35  60

      15  20  25  40

      15  15  30  30

      45–150  45–150  90–300  90–300

      20  25  30 40

      22  27  32 41

      40  50  60 

    80

      70  90  100 125

      50  60  60 80

      50  50  50

    100

      150–500  150–500  150–500 300–1000

      50  60  75100

      52  62  77  99

      100  110  150  175

      175  200  250  300

    100125150175

    100150150150

      300–1000  750–2500  750–2500  750–2500

    125150200

    125144192

      225  300  350

      400  450  600

    200225300

    250250400

    1250–25001250–25002000–4000

  • 8/20/2019 Mccb Eaton

    15/132

    CA08104001E For more information visit: www.eaton.com/consultants

    27December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    Special Function Circuit Breakers

    Selection Data—Current Limiting Circuit Breakers015

    Current Limiting Circuit BreakersEaton offers one of the most completelines of both fusible and non-fusedcurrent limiting breakers, and add-oncurrent limiting modules in theindustry. The industrial breakers are

    available in current limiting versionswith interrupting capacities up to200 kA at 480V without fuses in thesame physical size as standard andhigh interrupting capacity breakers.Eaton also manufactures both fusedand non-fused current limiting deviceswith interrupting capacities up to200 kA at 600 Vac. See Section 27.4 forcomplete selection data for currentlimiting circuit breakers and add-oncurrent limiting modules.

    The current limiting breakers use areverse loop stationary contact. Whencurrent is flowing through the contacts

    of these breakers, the positions of thereverse loop and moving contact arminduce opposing magnetic fields. Theresulting flux lines cause rapid contactblow-apart under these conditions,resulting in very high interruptingcapacities and provide currentlimiting characteristics.

    Current limiting breakers are availablefrom 15–2500A and have an interruptingrating up to 200 kA at 480V. Thesebreakers are most commonly appliedwhen very high fault levels are avail-able and in series rating applicationswhere the current limiting capabilityof these breakers are used upstream

    in series combinations.

    Circuit breakers 600A and below thatare current limiting have frame catalognumbers that end with the letter “C.”For example, the F-Frame model that iscurrent limiting has a catalog numberFDC. In accordance with UL circuitbreaker marking requirements, thenameplate on the breaker is alsolabeled “current limiting.”

    Current Limit-R Breakers—Non-Fused

    FCL Current Limit-R Breaker 

    The Current Limit-R® molded-casecircuit breaker was developed withinterrupting ratings up to 200,000A at480 Vac to provide complete systemprotection against faults, including:

    1. Overloads, by using inverse timecurrent tripping characteristics.

    2. Low-level short-circuits, by usinginstantaneous and/or short-timedelay tripping characteristics.

    3. High-level short-circuits, by usingultra high-speed, blow-apart,current limiting contacts.

    Current Limit-R circuit breakers canbe used in series with Eaton standardmolded-case circuit breakers withlisted interrupting ratings as low as10,000A in systems capable of deliver-ing fault currents as high as 200,000A.The excellent current limiting propertiesof Current Limit-R breakers completelyprotect all Eaton downstream seriescircuit breakers applied within theirvoltage ratings.

    The high level current-limiting action isachieved by the use of special design,blow-apart contacts. The openingspeed of the contacts is amplified bythe repulsion force in the slot motor toeffectively separate the contacts under

    high level fault conditions in less thanone millisecond. The rapid rise of arcvoltage introduces impedance into thesystem, thus limiting the amount of theotherwise available fault current.

    Current Limit-R current limiting circuitbreakers incorporate all the advantagesand features of conventional molded-case circuit breakers. They are availablein two- and three-pole versions intwo physical frame sizes and threecontinuous current frame ratings.

    Type FCL has a maximum continuouscurrent frame rating of 100A. It isequipped with a conventional, non-

    interchangeable, thermal-magnetic-type trip unit with individual ampereratings. The Type LCL is availablewith frames having maximumcontinuous current ratings of either250 or 400A. Overload and low levelshort-circuit protection is provided bya SELTRONIC™ electronic trip unit thatuses the individual rating plug conceptfor determining the continuousrating of the breaker. Rating plugsare available with either fixed oradjustable ampere ratings.

  • 8/20/2019 Mccb Eaton

    16/132

    7.2-4

    For more information visit: www.eaton.com/consultants  CA08104001E

    December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    Special Function Circuit Breakers

    Selection Data—Current Limiting Circuit Breakers016

    TRI-PAC Fused Current Limiting Breakers

    LA TRI-PAC Breaker 

    The increase in demand for electricalpower in modern commercial andindustrial buildings has resulted inelectrical services becoming substan-tially larger. In some low voltage

    distribution systems, available short-circuit currents can exceed 100,000symmetrical rms amperes. Faultcurrents of this intensity may exceedthe interrupting ratings of molded-casebreakers. As a result, larger expensivecircuit interrupting devices that couldwithstand the thermal and magneticstresses associated with currents ofthis value have had to be used. Highinterrupting capacity current limitingdevices have been developed thatwill restrict short-circuit current. Ifapplied correctly, they may be used inconjunction with molded-case circuitbreakers to provide adequate and

    economical protection.The TRI-PAC® breaker was developedfor this application and so namedbecause it affords TRIple-PACkageprotection with (1) time delay thermaltrip, (2) instantaneous magnetic tripand (3) current limiting protection,combined and coordinated in a compactand economical device. These protec-tive actions are so coordinated thatovercurrents and low magnitude faultsare cleared by the thermal action;normal short circuits are cleared bythe magnetic action; and abnormalshort circuits, above an establishedvalue, are cleared by the currentlimiting device. Thus, unless a severeshort-circuit occurs, the current limiteris unaffected and its replacement isheld to a minimum.

    TRI-PAC breakers are available in ratingsfrom 15–1600A and have a UL listedinterrupting capacity of 200,000Aat up to 600 Vac and also have aninterrupting capacity of 100,000Aat up to 250 Vdc.

    The TRI-PAC breaker offers all of theadvantages of the economical molded-case breaker and the current limiteris retained, while the disadvantagesof separately mounted devicesare eliminated.

    Add-on Current Limiting Modules

    Current Limiting Add-On Modules 

    The current limiting breaker modulesuse a reverse loop stationary contactarm. When high short-circuit current isflowing through the contacts of thesemodules, the positions of the reverse

    loop and moving contact arm induceopposing magnetic fields. The resultingflux lines cause rapid contact blow-apartunder fault conditions, resulting invery high interrupting capacities andproviding current limiting characteris-tics. Current limiting breaker modulesin combination with select Series Cand Series G breakers, are availablewith interrupting ratings up to 200 kAat 600 Vac.

    The combination of the current limit-ing breaker or HMCP and the currentlimiter module provides the followingsystem protection:

    ■ Overloads, by using inverse timecurrent tripping characteristics of

    the molded-case circuit breaker■ Low-level short circuits, by using

    instantaneous and/or short-timedelay tripping characteristics of themolded-case circuit breaker

    ■ High-level short circuits, by usingultra-high-speed, blow-apartcontacts of the current limitingmodule in series with the circuitbreaker contacts. The high-levelcurrent limiting action is achievedby the use of special design, blow-apart contacts. The opening speedof the contacts is amplifed by therepulsion force in the slot motor and

    reverse loop stationary contact armto effectively separate the contactsunder high-level fault conditions inless than 1 millisecond. The rapidrise of arc voltage introducesimpedance into the system, thuslimiting the amount of the otherwiseavailable fault current

  • 8/20/2019 Mccb Eaton

    17/132

    CA08104001E For more information visit: www.eaton.com/consultants

    27December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    Special Function Circuit Breakers

    Application Information—100% Rated Circuit Breakers017

    100% Rated Circuit Breakers100% rated circuit breakers are testedinside a minimum size enclosure toUL 489 for application at 100% of thebreaker’s continuous current rating.100% rated circuit breakers are equipped 

    with electronic trip units and appliedwith 90ºC cable rated at 75ºC ampacity.To apply 100% rated breakers inswitchboards and panelboards,additional tests are required to meetUL 67 and UL 891. Eaton molded-casecircuit breaker frames K-, L-, N-, MDLand R-, 70–2000A, can be applied at100% of their rated continuous currentas long as the breaker is installed in itsminimum size enclosure, includingventilation. 100% rated breakers areapplied to distribution system to provideinstallation cost savings. The amountof savings that can be realized isdependent on the application.

    Figure 27.2-1. Breaker Nameplate

    A 100% rated breaker receives its UL listingbased on tests conducted in a minimumsize enclosure with minimum ventilation(if required) and minimum cable sizes,as stated on this nameplate example.

    The amount of protection designedinto a distribution system is often basedon economics. However, each projectshould be furnished with a reliabledistribution system that delivers themost effective protection possible foreach investment dollar.

    Reliable and economic system design

    can be usually achieved with Eaton’scircuit breakers that are UL listed forapplication at 100% of their ratings—instead of standard breakers that inactual use are applied at 80% of theirframe ratings in an enclosure.

    The concept between a system designusing standard breakers and thatusing 100% rated breakers isuncomplicated—but there are noshortcut methods for determining

    which design (and devices) is thebest choice for a given system. Goodengineering practice requires a carefulsystem analysis beginning with thelowest feeder and concluding withthe main device.

    Also included in the system analysismust be all present and futurefactors that could affect the sizeand/or quantity of the breakers andassociated hardware, such as switch-board bus, busway, cable and conduit.Other factors to consider are loads(continuous and noncontinuous) andsystem expansions and transformerswith provisions for forced air cooling.

    The NEC

    The rules and intent of the NationalElectrical Code governing the use ofstandard or 100% rated breakers mustbe understood before recommending

    or applying such devices.

    Section 210.20(A) Continuous andNoncontinuous Loads of the NationalElectrical Code addresses differencesbetween applications of standard ratedbreakers and 100% rated breakers.(Significant sections are in boldface type.)

    Figure 27.2-2. NEC Reference

    Section 210.20(A) covers standardbreakers, and the exception 100%rated breakers. NEC Section 210.20(A)and the Section 210.20(A) exceptioncan be expressed by these formulas:

    Standard 80% Rated Design

    Noncontinuous Load +125% of the Continuous Load= Total Minimum Load

    Special 100% Rated DesignNoncontinuous Load +Continuous Load= Total Minimum Load

    The necessity for these NEC require-ments results from circuit breakertesting procedures.

    A molded-case circuit breaker istested in open air to verify its name-plate ampere rating. The nameplatespecifies a value of current the circuit

    breaker is rated to carry continuouslywithout tripping within specificoperating temperature guidelines.

    In most instances, a breaker is appliedin an enclosure and performance couldbe adversely affected by slow heatdissipation and temperature rise. Thesefactors must be considered regardingthe ability of the breaker to complywith its nameplate ampere rating.

    Testing Conditions and Operating Conditions

    There are distinct differences betweenthese conditions that are addressed inNEC Section 210.20(A) by introducingan overcurrent device and associatedhardware sizing factor. The sizingfactor ensures reliable equipmentperformance under realistic condi-tions. Section 210.20(A) is the key tomaking the best system design choice.

    For feeders, Section 215.2(A)addresses the rating of all overcurrentdevices that have been tested in openair but are applied in an enclosure. Thethermal response of an overcurrentdevice applied in an enclosure willusually be faster than in open air,thus dictating the 125% requirement.

    The exception allows for properly tested

    and listed overcurrent devices to beapplied at 100% of their nameplate rating.

    Breaker

    Nameplate

    Example

    100%

    Application–

    enclosure

    and

    wire ampacity

    requirements.

    “Where a feeder supplies continu-ous loads or any combination ofcontinuous and noncontinuousloads, the rating of the overcur-rent device shall not be less thanthe noncontinuous load plus

    125% of the continuous load.”

    The minimum circuit conductorsize without the application of anyampacity adjustment or correctionfactors shall have an allowableampacity equal to or greater thanthe noncontinuous load plus125% of the continuous load.

    “Exception: Where the assemblyincluding the overcurrent devicesprotecting the feeder(s) are listedfor operation at 100% of theirrating, neither the ampere ratingof the overcurrent device nor theampacity of the feeder conductorsshall be less than the sum ofthe continuous load plus thenoncontinuous load.”

    Note: A continuous load as definedby NEC Article 100 is “a load wherethe maximum current is expected tocontinue for 3 hours or more.”

  • 8/20/2019 Mccb Eaton

    18/132

    7.2-6

    For more information visit: www.eaton.com/consultants  CA08104001E

    December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    Special Function Circuit Breakers

    Application Information—100% Rated Circuit Breakers018

    There is a Difference Between 100% RatedBreakers and 100% Rated Assemblies

    Special attention should be givento the word “assembly” in the NECException. Normally, an assemblyis listed for 100% operation only

    after being successfully tested asan assembly per UL requirements.

    For an assembly to receive a 100%rated UL listing, it must be testedseparately by UL project engineers.Panelboards are tested to UL 67,switchboards tested to UL 891.

    Installing 100% rated breakers inan assembly does not automaticallymake it acceptable for a 100% rating.

    Figure 27.2-3. Conductor Requirements

    Table 27.2-3. The Application—These Examples Illustrate the Cost Savings when the 100% Rated Approach is Used  

    Selection of either a 100% rated design or standard design must result from a system analysis beginning with the lowest feeder and concluding withthe system’s main device. For these system examples, assume that all assembly testing has been successfully completed and either the 100% rateddesign or standard design can be selected. Each system is hypothetical and either approach will meet safety requirements. Loads were arbitrarilyselected. The load table includes the calculations for minimum total loads in conformance with NEC Section 210.20(A).

    Table 27.2-4. Standard 80% Rated Design

    (Noncontinuous Load) + (125%) (Continuous Load) per NEC Section 210.20(A).

    Nearest standard size, not less than calculated value.

    The NEC allowsthe breaker to berated at 100% ofits frame size inan assembly,provided that90°C wire isapplied at the75°C ampacity.

    90°C Wire

    90°C Wire

    A visual comparison of breaker, bus and cable sizes in the Three-Phase Distribution Systemexamples (line diagrams) reveals how a 100% rated system design can provide cost savings.

    Load Feeder #1 Feeder #2 Feeder #3 Main Description

    Continuous 400A 800A 0 1200A Three-phase distributionSystem line diagramsNoncontinuous 200A 0 1000 1200A

    Noncontinuous Load + 125% of the Continuous Load = Total Minimum Load Line Diagram

    Description Feeder No. 1 Feeder No. 2 Feeder No. 3 Main

    Calculationper NECof minimumtotal load

    200 + (1.25) (400)=700A

    0 + (1.25) (800)=1000A

    600 + 0 = 600A 2250A

    Breakerframe (F)trip (T)rating

    (F) (T)800A /700A

    (F) (T)1200A /1000A

    (F) (T)600A/600A

    (F) (T)2500A /2500A

    Bus/cablerating

    800A  1000A 600A 2500A 

    2500A F2500A T

    800A F700A T

    1200A F1000A T

    600A F600A T

    2500A Bus

    Pnlbd. 600A BusMCC 800A Bus

    2–350 kcmil,Cu per phase

    2–500 kcmil,Cu per phase

    3–400 kcmil,Cu per phase

    1000A Busway

    Feeder#1

    Feeder#2

    Feeder#3

  • 8/20/2019 Mccb Eaton

    19/132

    CA08104001E For more information visit: www.eaton.com/consultants

    27December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    Special Function Circuit Breakers

    Application Information—100% Rated Circuit Breakers019

    Table 27.2-5. Standard 100% Rated Design

    (Noncontinuous Load) + (Continuous Load) per NEC Section 210.20(A) Exception. Sum of all NEC calculated minimum feeder loads.

    Table 27.2-6. The Result—Savings in Both Switchboard and Cable Costs

    Table 27.2-7. Available 100% Rated Circuit Breakers

    Thermal-magnetic LG requires venting 7.00 square inches above and 7.00 square inches below on the front face of enclosure. Use with 9.00-inch (228.6 mm) tee connector.

    Noncontinuous Load + Continuous Load = Total Minimum Load Line Diagram

    Description Feeder No. 1 Feeder No. 2 Feeder No. 3 Main

    Calculationper NECof minimum

    total load

    200 + 400 = 600A 0 + 800 = 800A 600 + 0 = 600A 2000A

    Breakerframe (F)trip (T)rating

    (F) (T)600A/600A

    (F) (T)800A/800A

    (F) (T)600A/600A

    (F) (T)2000A/2000A

    Bus/cablerating

    600A 800A 600A 2000A

    Design Minimum Total Load

    (Amperes)

    Potential System

    Savings

    Standard 700 1000 600 2250 100% rated breaker systemscan potentially representsignificant economicadvantages:In lower rated and sizedbreakers, less cable andsignificant reductions inequipment floor and wallspace. These savings can berealized when the results ofa systems analysis favor the100% rated design approach.

    100% rated 600 800 600 2000

    Results The standard designrequires higher rated,more expensive breakerand bus. Although theminimum total load is700A, most breakers andhardware are availableonly in standard sizesrequiring even moreexpensive “neareststandard size” breakersand hardware.

    Dramatic economicadvantages areachieved by usingthe 100% rateddesign. Substantialsavings result fromusing an 800Abusway and signifi-cant savings arealso provided bythe smaller breakerframe and cable size.

    Calculations indicateeither approachresults in the samesize breaker and hard-ware. A 100% ratedbreaker would bemore expensivealthough the finaldecision could reston whether or notfuture load growthis anticipated.

    The 100% approach resultsin the same frame sizebreaker with a savings inconductor material cost.Additionally, Eaton offers a2000A frame 100%-ratedbreaker, which is lessexpensive than the 2500Aframe 80%-rated.

    Frames Ratingat 480V

    TripUnits

    JG-Frame 50/100/250AMinimum enclosure size26.00 x 18.00 x 8.00 in (660.4 x 457.2 x 203.2 mm)

    JGE-C 25 kAJGS-C 35 kAJGH-C 65 kAJGC-C 100 kA

    Thermal-magnetic, Digitrip 310+

    K-Frame 125/250/400AMinimum enclosure size24.00 x 15.00 x 6.00 in (609.6 x 381.0 x 152.4 mm)

    CKD 35 kACHKD 65 kA

    Digitrip 310+ (125A, 250A and 400A)

    LG-Frame  250/400/600AMinimum enclosure size with ventilation28.00 x 19.00 x 8.00 in (711.2 x 482.6 x 203.2 mm)

    LGE-C 35 kALGS-C 50 kALGH-C 65 kA

    Thermal-magnetic, Digitrip 310+

    L-Frame 125/250/400/600AMinimum enclosure size with ventilation24.00 x 15.00 x 6.00 in (609.6 x 381.0 x 152.4 mm)

    CLD 35 kACHLD 65 kACLDC 100 kA

    Digitrip 310, Digitrip OPTIM

    M-Frame 800A

    Minimum enclosure size with ventilation42.00 x 18.00 x 7.50 in (1066.8 x 457.2 x 190.5 mm)

    CMDL 50 kA

    CHMDL 65 kA

    Digitrip 310

    N-Frame 800/1200AMinimum enclosure size with ventilation42.00 x 22.75 x 11.50 in (1066.8 x 577.9 x 292.1 mm)

    CND 50 kACHND 65 kACNDC 100 kA

    Digitrip 310, Digitrip OPTIM

    R-Frame 1600/2000AMinimum enclosure size with ventilation21.50 x 18.00 x 13.00 in (546.1 x 457.2 x 330.2 mm)

    CRD 65 kACRDC 100 kA

    Digitrip 310/510/610/810/910, Digitrip OPTIM

    2000A F

    2 A

    A600A T

    800A FA

    00A FA

    2000A Bus

    Pnlb . A BusM A Bus

    350 kcmil,Cu per phase

    350 kcmil,Cu perphase

    2–600 kcmil,Cu perphase

    800A Busway

    Feeder#1

    Feeder#

    Feeder#

  • 8/20/2019 Mccb Eaton

    20/132

    7.2-8

    For more information visit: www.eaton.com/consultants  CA08104001E

    December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    Special Function Circuit Breakers

    Application Information—Series Rated Systems020

    Series Rated SystemsSeries rating is a short-circuitinterrupting rating assigned to acombination of two or more over-current devices connected in series.The short-circuit interrupting rating

    of the upstream device must be equalto or greater than the available faultcurrent. Downstream breakers,however, are not fully rated for thesystem’s available fault current. Seriescombinations must be tested toUL 489. Series ratings are applied todistribution systems where short-circuit coordination is not required.The Eaton listing of available seriesrating combinations are shown in theapplications section of this document.

    Under most circumstances, selectionof a series rated system will reduceinitial cost and size, because down-

    stream breakers are not fully ratedfor the prospective short-circuit faultcurrent at their point of application.The interrupting rating of theupstream breaker must always beequal to or greater than the availablefault current at its line terminals. Inaddition, downstream breakers musthave been tested in combination withthe upstream breaker and shown to beprotected by the upstream breaker atthe assigned series rated interruptingrating. The net result is that the systemcan be assigned a “series rated” or“integrated” rating higher than therating of the downstream breaker when

    it is tested or applied alone. Design ofthe system and selection of breakers isbased on short-circuit interruption testspecified and witnessed by UL.

    Because of their blow-open design,most molded-case circuit breakers arecurrent limiting to some degree. In aseries rated application and in the eventof a major fault, both upstream anddownstream breakers open, protectingthe lower-rated downstream devicesby limiting the let-through current.

    To develop a series rated protectivesystem, it is suggested that thedesign engineer, after completing

    preliminary steps:■ Define available fault current at

    the line side terminals of theupstream breaker

    ■ Select an upstream breaker with aninterrupting rating equal to or greaterthan the available fault current

    ■ Verify the series tested interruptingratings of the selected combinationof breakers by referring to the tablesin this section

    ■ Confirm, during installation, that thecorrect breakers have been selectedby checking the nameplates appearing on the end-use equipment

    Evaluating the Protection Systems

    Designed properly, series rated andfully rated systems protect electricalequipment with equal effectiveness.But initial cost and continuity of servicecan vary widely depending on theinherent characteristics of the system,and on the design philosophy adopted.

    Fully Rated System

    All breakers are rated for full faultcurrent at their point of application inaccordance with the National ElectricalCode. The continuity of service pro-vided by the system is greater than aseries rated system.

    Series Rated System

    A series rated system is less costlythan a fully rated system. Theupstream breaker is always fully rated,but the interrupting ratings of down-stream breakers are normally lower.Service continuity can be acceptableafter initial startup, because the lower-level arcing faults most likely occurafter that time can be cleared by thedownstream breaker alone. However,under high fault conditions, both theupstream and downstream breakerswould open, eliminating service tothe affected portion of the system.Therefore, it is not possible to achieveselective coordination for all magni-

    tudes of available fault current witha series rated system.

    National Electrical Code Requirements

    Requirements of the National ElectricalCode for short-circuit ratings may nowbe met by equipment that is markedwith ratings adequate for the availablefault current at their point of applicationin the electrical system. Refer to thecurrent NEC for specific requirements.

    General Discussion

    Available Short-Circuit Current. Service equipment must be suitablefor the short-circuit current available

    at its supply terminal.Approval. The conductors and equipment required or permitted by the Code willbe acceptable only if approved. SeeExamination of Equipment for Safetyand Examination, Identification,Installation and Use of Equipment.See definitions of “Approved,”“Identified,” “Labeled” and “Listed.”

    Examination, Identification, Installationand Use of Equipment

    1. Examination: in judging equip-ment, considerations such as thefollowing should be evaluated.

    a. Suitability for installationand use in conformity withthe provisions of this Code.Suitability of equipment usemay be identified by a descrip-tion marked on or providedwith a product to identify thesuitability of the product for aspecific purpose, environmentor application. Suitability ofequipment may be evidencedby listing or labeling.

    b. Mechanical strength anddurability, including, for partsdesigned to enclose and protectother equipment, the adequacy

    of the protection thus provided.c. Wire-ending and

    connection space.

    d. Electrical insulation.

    e. Heating effects under normalconditions of use and alsounder abnormal conditionslikely to arise in service.

    f. Arcing effects.

    g. Classification by type, size,voltage, current capacityand specific use.

    h. Other factors that contribute tothe practical safeguarding of

    persons using or likely to comein contact with the equipment.

    2. Installation and use: listed orlabeled equipment must be usedor installed in accordance withany instructions included in thelisting or labeling.

    Interrupting Rating

    Equipment intended to break current atfault levels must have an interruptingrating sufficient for the system voltageand the current that is available at theterminals of the equipment. Equipmentintended to break current at other thanfault levels must have an interrupting

    rating at system voltage sufficient forthe current that must be interrupted.

  • 8/20/2019 Mccb Eaton

    21/132

    CA08104001E For more information visit: www.eaton.com/consultants

    27December 2013

    Molded-Case Circuit Breakers & Enclosures

    Sheet 27

    Special Function Circuit Breakers

    Application Information—Series Rated System021

    Circuit Impedance and OtherCharacteristics

    The overcurrent protective devices,the total impedance, the componentshort-circuit withstanding ratings, andother characteristics of the circuit to

    be protected should be so selectedand coordinated as to permit thecircuit protective devices used toclear a fault without the occurrenceof extensive damage to the electricalcomponents of the circuit. This faultwill be assumed to be either two ormore of the circuit conductors, orbetween any circuit conductor andthe grounding conductor or enclosingmetal raceway.

    Motor Contribution

    The fault current contribution ofmotors connected between seriesrated breakers must be considered.

    Article 240.86(C) in the 2005 edition ofthe National Electrical Code states thatfor series ratings the sum of the motor,full-load currents cannot exceed 1%of the interrupting rating of the lower-rated circuit breaker. The actual faultcurrent contribution from inductionmotors is about four times their full-load current (impedance value of25%). For example, if the downstreambranch circuit breakers used in a seriesrated combination have an interruptingrating of 14,000A rms symmetrical for a480V system, the maximum full-loadcurrent of motors connected to thatpanel from the branch circuit breakers

    is 140A (1%). For typical inductionmotors, this is equivalent to a totalhorsepower at 480V of approximately115 horsepower.

    Design/Test Considerations for SeriesCoordinated Circuit Breakers

    Test procedures for all Eaton molded-case circuit breakers intended forapplication in series connectedsystems are in full compliance withall applicable paragraphs of th