Page 2: Medium Voltage Cable Testing Technologies - Neta … Voltage Cable Testing Technologies . Energization Sources: ... standard for MV Cables Note 2 – there is no IEEE DC field testing

Energization Sources:

• DC and DC Leakage Methods (Insulation

Resistance)

• Damped AC (20-300 Hz)

• AC – Power Frequency

• AC – Low Frequency (VLF – 0.1 Hz)

Most Commonly Used Cable Testing

Methods

Page 3: Medium Voltage Cable Testing Technologies - Neta … Voltage Cable Testing Technologies . Energization Sources: ... standard for MV Cables Note 2 – there is no IEEE DC field testing

Cable Diagnostic Technique:

• Withstand

• Tan Delta / Dissipation Factor

• Partial Discharge (Online and Offline)

• TDR (Time Domain Reflectometry)

• Thermal Imaging

• Others

• Combination of the Above - Smart

Most Commonly Used MV Cable Testing

Methods

Page 4: Medium Voltage Cable Testing Technologies - Neta … Voltage Cable Testing Technologies . Energization Sources: ... standard for MV Cables Note 2 – there is no IEEE DC field testing
Page 5: Medium Voltage Cable Testing Technologies - Neta … Voltage Cable Testing Technologies . Energization Sources: ... standard for MV Cables Note 2 – there is no IEEE DC field testing

Online versus Offline • Online testing is generally easier to

carry out, and is so called “non-destructive” its effectiveness is also limited..

• Offline testing, while requiring more preparation and setup, provides more insight into the cables true condition.

Page 6: Medium Voltage Cable Testing Technologies - Neta … Voltage Cable Testing Technologies . Energization Sources: ... standard for MV Cables Note 2 – there is no IEEE DC field testing

IEEE MV Cable Field Testing Chart

IEEE 400 (OmniBus) - 2012 Guide for Field Testing & Evaluation of the Insulation of Shielded Power Cable Systems Rated 5kV and above

IEEE 400.1 Field Testing of Laminated Cables Rated 5kV and above using DC.

IEEE 400.2 – 2013 Field Testing of Shielded Power Cables using Very Low Frequency VLF

IEEE 400.3 PD Testing of Shielded Power Cables in the Field Environment

Note 1 – there is no IEEE 60Hz field withstand testing

standard for MV Cables

Note 2 – there is no IEEE DC field testing standard for any

extruded cables.

Page 7: Medium Voltage Cable Testing Technologies - Neta … Voltage Cable Testing Technologies . Energization Sources: ... standard for MV Cables Note 2 – there is no IEEE DC field testing

• Potential Negative Impact on the Service

Reliability of Extruded Cables

• Ineffectiveness to Detect Serious Defects in

Cable Insulation

The Demise of the DC Hipot for Testing

MV Cables

Ref: IEEE400-2012

Page 8: Medium Voltage Cable Testing Technologies - Neta … Voltage Cable Testing Technologies . Energization Sources: ... standard for MV Cables Note 2 – there is no IEEE DC field testing

Concentric Neutral Design Vs. Tape Shielded

Cable Design Can Impact the Effectiveness and Usability

of Certain Diagnostic Techniques That are Rich in

Frequencies.

Page 9: Medium Voltage Cable Testing Technologies - Neta … Voltage Cable Testing Technologies . Energization Sources: ... standard for MV Cables Note 2 – there is no IEEE DC field testing
Page 10: Medium Voltage Cable Testing Technologies - Neta … Voltage Cable Testing Technologies . Energization Sources: ... standard for MV Cables Note 2 – there is no IEEE DC field testing

Which Energization Source and

Diagnostic Method/s to use and

when……….

Page 11: Medium Voltage Cable Testing Technologies - Neta … Voltage Cable Testing Technologies . Energization Sources: ... standard for MV Cables Note 2 – there is no IEEE DC field testing

IEEE 400 has an Informative Table in the

Appendix on the Applicability of Various Testing

Methods.

Comments

• Some Methods Were Not Analyzed Due to

Lack of Information / Data.

• Some Methods were shown to be useful and

some were Not.

• Table Does Not Address Tape Shielded

Cables and Mainly Focuses on Utility Style

CN Type.

Applicability Of Testing Methods

Page 12: Medium Voltage Cable Testing Technologies - Neta … Voltage Cable Testing Technologies . Energization Sources: ... standard for MV Cables Note 2 – there is no IEEE DC field testing

Test and Diagnostic Selection Matrix:

Expanded from IEEE 400 - 2012

Method New Extruded

Acceptance

Old Extruded

Maintenance

PILC

Laminat

ed

Old

Hybrid

Combo

Unjacket

ed

Accessories

(Splice &

Term)

Shield Type Tape CN Tape CN Mixed Mixed CN Mixed

DC Withstand

Testing

X X X X X X Limited

VLF AC Withstand

Test

Tan Delta /

Dissipation Factor

Test

Partial Discharge

Test – Offline

Limited

Limited Limited

Partial Discharge

Test – Online Limite

d Limited Limited Limited

Limited Limited

Smart VLF W/S Test

- combination with

TD

Smart VLF W/S Test

- combination with

PD

Limited

Limited Limited

TDR (Time Domain

Reflectometry) Useful Useful Not

Useful Useful Useful Limited Useful

Page 13: Medium Voltage Cable Testing Technologies - Neta … Voltage Cable Testing Technologies . Energization Sources: ... standard for MV Cables Note 2 – there is no IEEE DC field testing

• Testing Organizations Need to Be Aware of the

Changes in Standards and Guides

• A Need to Inform and Educate Customers / End

Users

• Careful Consideration When DC is Requested

• Choice of Test Method Often Determined By Age

and Type of Cable and the Intended Defect

Diagnosis

• Often, a Testing Strategy Involving a Combination

of Tests is Most Appropriate.

Conclusions