1 ELABORACION DEL ESTUDIO DEFINITO Y EXPEDIENTE TECNICO DEL PROYECTO: "ESQUEMA CARAPONGO - AMPLIACION DE LOS SISTEMAS DE AGUA POTABLE Y ALCANTARILLADO DE LOS SECTORES 136 Y 137 DEL DISTRITO DE LURIGANCHO" RESERVORIO APOYADO RAP-01 V = 200 m3 DISEÑO DEL MURO CILINDRICO (SECCION CONSTANTE) MATERIALES f´c (kg/cm2) Ec (kg/cm2) fy (kg/cm2) Es (kg/cm2) 280.00 250,998.01 4,200.00 2,000,000.00 PROPIEDADES DEL SUELO DE FUNDACION γs (T/m3) φ σt (kg/cm2) Df (m) 1.90 35.00 5.00 1.00 GEOMETRIA DEL TANQUE Di (m) Dm (m) ri (m) rm (m) 7.60 7.90 3.800 3.950 t (m) Hm (m) Ha (m) 0.30 4.90 4.40 V (m3) 199.60 MOMENTOS MAXIMOS EN SERVICIO DEBIDO A PRESIONES HIDROSTATICAS Cara humeda Cara seca COMB. DESCRIPCION -M22s (T-m) +M22s (T-m) 1 PRESION HIDROSTATICA 6.32 2.72 ESFUERZOS ADMISIBLES CONCRETO Y ACERO fcadm (kg/cm2) fsadm (kg/cm2) 126.00 1,680.00 DIMENSIONAMIENTO DE LA PARED CILINDRICA n k j K (kg/cm2) 7.97 0.37 0.88 20.63 b (cm) rec (cm) db (cm) 100.00 5.00 1.91

Memoria de Cálculo Estructural Reservorios

Embed Size (px)

DESCRIPTION

Cálculo de Estructuras de Reservorio

Citation preview

1

ELABORACION DEL ESTUDIO DEFINITO Y EXPEDIENTE TECNICO DEL PROYECTO: "ESQUEMA CARAPONGO - AMPLIACION DE LOS SISTEMAS DE AGUA POTABLE Y ALCANTARILLADO DE LOS

SECTORES 136 Y 137 DEL DISTRITO DE LURIGANCHO"

RESERVORIO APOYADO RAP-01 V = 200 m3

DISEÑO DEL MURO CILINDRICO (SECCION CONSTANTE)

MATERIALES

f´c (kg/cm2) Ec (kg/cm2) fy (kg/cm2) Es (kg/cm2) 280.00 250,998.01 4,200.00 2,000,000.00

PROPIEDADES DEL SUELO DE FUNDACION

γγγγs (T/m3) φφφφ σσσσt (kg/cm2) Df (m) 1.90 35.00 5.00 1.00

GEOMETRIA DEL TANQUE

Di (m) Dm (m) ri (m) rm (m) 7.60 7.90 3.800 3.950

t (m) Hm (m) Ha (m) 0.30 4.90 4.40

V (m3) 199.60

MOMENTOS MAXIMOS EN SERVICIO DEBIDO A PRESIONES HIDROSTATICAS

Cara humeda Cara seca

COMB. DESCRIPCION -M22s (T-m) +M22s (T-m) 1 PRESION HIDROSTATICA 6.32 2.72

ESFUERZOS ADMISIBLES CONCRETO Y ACERO

fcadm (kg/cm2) fsadm (kg/cm2) 126.00 1,680.00

DIMENSIONAMIENTO DE LA PARED CILINDRICA

n k j K (kg/cm2) 7.97 0.37 0.88 20.63

b (cm) rec (cm) db (cm) 100.00 5.00 1.91

2

SECCION NEGATIVA (BASE DEL MURO)

-Ms (T-m) dmin (cm) hmin (cm) t (cm) d (cm) 6.32 17.50 23.46 30.00 24.05

SECCION POSITIVA

+Ms (T-m) t (cm) d (cm) 2.72 30.00 25.05

DISEÑO POR RESISTENCIA ACI 350-06

FACTORES DE AMPLIFICACION DE CARGA

F.C.V. F.C.V. (SISMO) F.C.S. 1.70 1.20 1.00

MOMENTOS MAXIMOS ULTIMOS PARA LOS DIFERENTES ESTADOS DE CARGA

Cara humeda Cara seca

COMB. DESCRIPCION -M22u (T-m) +M22u (T-m) 1 PRESION HIDROSTATICA * 1.70 10.74 4.62

2 P. HIDROSTATICA * 1.20 + P. HIDRODINAMICA 10.20 4.47

DISEÑO DEL REFUERZO VERTICAL DEL MURO

SECCION DE MOMENTO POSITIVO (CARA SECA)

FACTOR DE DURABILIDAD (SIN SISMO) Y REDUCCION DE RESISTENCIA

F.D. φφφφ

1.30 0.90

MOMENTO ULTIMO DE DISEÑO Y AREA DE REFUERZO

+Mu (T-m) b (cm) t (cm) d (cm)

6.01 100.00 30.00 25.05

As (cm2) ρρρρ 6.50 0.00217

ρρρρmin Asmin (cm2/cara)

0.0030 4.50

DIAMETRO Y ESPACIAMIENTO DEL REFUERZO

Ab (cm2) s (m) 1.27 0.28

3

s (m) # varillas 0.25 102

SECCION DE MOMENTO NEGATIVO (CARA HUMEDA)

FACTOR DE DURABILIDAD (SIN SISMO) Y REDUCCION DE RESISTENCIA

F.D. φφφφ

1.30 0.90

MOMENTO ULTIMO DE DISEÑO Y AREA DE REFUERZO

-Mu (T-m) b (cm) t (cm) d (cm)

13.97 100.00 30.00 24.05

As (cm2) ρρρρ

16.35 0.00545

ρρρρmin Asmin (cm2/cara)

0.0030 4.50

DIAMETRO Y ESPACIAMIENTO DEL REFUERZO

Ab (cm2) s (m) 1.63 0.10

s (m) # varillas 0.100 242

CORTE DEL REFUERZO NEGATIVO A Hm/4

Hc (m) 1.23

As (cm2) s (m) As (cm2)/m d (cm) a (cm) -Mur (T-m) 1.98 0.20 9.90 24.05 1.75 -8.67

# VARILLAS COMPLETAS EN PARED VERTICAL

s (m) # varillas 0.20 121

DISEÑO DEL REFUERZO CIRCULAR DEL MURO

FACTORES DE AMPLIFICACION, DURABILIDAD Y REDUCCION DE RESISTENCIA

F.C.V. F.D. φφφφ

1.70 1.65 0.90

4

PRESIONES, TENSIONES CIRCUNFERENCIALES ULTIMAS Y ACERO REQUERIDO

h (m) Ts (T) Tu (T) As (cm2) φ φ φ φ (c/cara) s (m) 4.90 16.71 46.86 12.40 1.27 0.20 4.60 15.29 42.89 11.35 1.27 0.22 4.30 13.88 38.94 10.30 1.27 0.25 4.00 12.63 35.42 9.37 1.27 0.27 3.70 11.42 32.04 8.48 1.27 0.30 3.40 10.23 28.71 7.59 1.27 0.33 3.10 9.05 25.39 6.72 1.27 0.38 2.80 7.87 22.08 5.84 1.27 0.43 2.50 6.69 18.76 4.96 0.71 0.29 2.20 5.51 15.45 4.09 0.71 0.35 1.90 4.33 12.13 3.21 0.71 0.44 1.60 3.14 8.80 2.33 0.71 0.61 1.30 1.94 5.43 1.44 0.71 0.99

USAR: 5 φφφφ 1/2" @ 0.20, Rto. φ φ φ φ 1/2" @ 0.25 c/cara

REFUERZO MINIMO

ρρρρmin Asmin (cm2/cara) Ab (cm2) s (m) 0.0030 4.50 1.27 0.28

DISEÑO DE LA CUPULA

MATERIALES

f´c (kg/cm2) Ec (kg/cm2) fy (kg/cm2) Es (kg/cm2) 245.00 234,787.14 4,200.00 2,000,000.00

GEOMETRIA DEL TANQUE

Di (m) Dm (m) ri (m) rm (m) 7.60 7.90 3.80 3.95

t (m) 0.30

GEOMETRIA DE LA CUPULA

fmin (m) fmax (m) f (m) r (m) φ φ φ φ (rad) 0.76 0.95 0.90 8.47 0.47

ESPESORES DE LA CUPULA

emin (m) emax (m) 0.07 0.15

5

CARGAS EN SERVICIO

p.p. (kg/m2) p.acab. (kg/m2) s/c (kg/m2) w (kg/m2) 185 50 50 285

CARGA TOTAL (P) Y CARGA POR METRO LINEAL (V)

P (kg) V (kg/m) 13,645 571

COMPONENTE HORIZONTAL (H) y RESULTANTE "R"

H (kg/m) R (kg/m) 1,139 1,274

VERIFICACION DEL ESPESOR MINIMO DE LA CUPULA

fcadm (kg/cm2) emin (cm) OBS. 10.00 1.27 OK

REFUERZO RADIAL Y CIRCUNFERENCIAL

REFUERZO RADIAL

fs (kg/cm2) As (cm2)/m

1,000.00 0.57

REFUERZOS MINIMOS

ρρρρmin

0.0020

ZONA DE ENSANCHE EN APOYO

Asmin (cm2)/m φ φ φ φ (ref. superior) s (m) s (m) # varillas 3.00 0.71 0.24 0.20 130

EN ZONA DE ESPESOR CONSTANTE

Asmin (cm2)/m φ φ φ φ (ref. central) s (m) s (m) # varillas 1.40 0.32 0.23 0.20 130

REFUERZO CIRCUNFERENCIAL

ZONA DE ENSANCHE EN APOYO

Asmin (cm2)/m φ φ φ φ (ref. c/cara) s (m) s (m) 3.00 0.32 0.21 0.20

EN ZONA DE ESPESOR CONSTANTE

6

Asmin (cm2)/m φ φ φ φ (ref. central) s (m) s (m) 1.40 0.32 0.23 0.20

DISEÑO DE LA VIGA ANULAR DE APOYO

TRACCION MAXIMA

Tmax (kg) 4,327

AREA MINIMA DE CONCRETO

fcadm (kg/cm2) Ac (cm2) 10.00 433

SECCION TRANSVERSAL DE LA VIGA ANULAR

bmin (cm) b (cm) hmin (cm) h (cm) 40.00 40.00 10.82 30.00

REFUERZO LONGITUDINAL

fs (kg/cm2) As (cm2) 1,000.00 4.33

ρρρρmin Asmin (cm2) 0.0050 6.00

Av (cm2) # varillas

1.27 4.7 USAR: 4 φφφφ 1/2" + 2 φφφφ 3/8"

REFUERZO TRANSVERSAL DE MONTAJE

φφφφestribo s (m) # estribos 3/8" 0.25 101

DISEÑO DE LA CIMENTACION

ANILLO DE CIMENTACION

CARGA POR METRO LINEAL (P)

P (kg) 5,704

ANCHO Y PERALTE DE LA ZAPATA ANULAR (B)

Bmin (m) B (m) hzmin (m) hz (m) rz (m) 0.90 1.00 0.60 0.60 4.40

7

ESFUERZOS EN EL TERRENO

σσσσact (kg/cm2) σσσσt (kg/cm2) OBS. 0.57 5.00 OK

REFUERZO RADIAL

ρρρρmin Asmin (cm2) 0.0030 18.00

φ φ φ φ (ref. c/cara) s (m) s (m) # varillas 1.98 0.22 0.20 137

REFUERZO CIRCUNFERENCIAL

ρρρρmin Asmin (cm2) 0.0030 18.00

Ab (cm2) # total varillas 1.27 14

LOSA DE FONDO

ESFUERZO DE COMPRESION EN LA LOSA (FRANJA DE 1 METRO)

tmin (m) t (m) q (T/m) σσσσact (kg/cm2) 0.14 0.25 5.00 0.50 << 0.40 f´c

REFUERZO

ρρρρmin Asmin (cm2) 0.0030 7.50

φ φ φ φ (ref.) c/cara s (m) s (cm) 0.71 0.19 0.20

8

RESERVORIO APOYADO RAP-02 V = 250 m3

RESERVORIO APOYADO RAP-05 V = 250 m3

DISEÑO DEL MURO CILINDRICO (SECCION CONSTANTE)

MATERIALES

f´c (kg/cm2) Ec (kg/cm2) fy (kg/cm2) Es (kg/cm2) 280.00 250,998.01 4,200.00 2,000,000.00

PROPIEDADES DEL SUELO DE FUNDACION

γγγγs (T/m3) φφφφ σσσσt (kg/cm2) Df (m) 1.90 35.00 5.00 1.00

GEOMETRIA DEL TANQUE

Di (m) Dm (m) ri (m) rm (m) 9.60 9.85 4.800 4.925

t (m) Hm (m) Ha (m) 0.25 4.00 3.50

V (m3) 253.34

MOMENTOS MAXIMOS EN SERVICIO DEBIDO A PRESIONES HIDROSTATICAS

Cara humeda Cara seca

COMB. DESCRIPCION -M22s (T-m) +M22s (T-m) 1 PRESION HIDROSTATICA 3.26 1.38

ESFUERZOS ADMISIBLES CONCRETO Y ACERO

fcadm (kg/cm2) fsadm (kg/cm2) 126.00 1,680.00

DIMENSIONAMIENTO DE LA PARED CILINDRICA

n k j K (kg/cm2) 7.97 0.37 0.88 20.63

b (cm) rec (cm) db (cm) 100.00 5.00 1.91

SECCION NEGATIVA (BASE DEL MURO)

-Ms (T-m) dmin (cm) hmin (cm) t (cm) d (cm) 3.26 12.57 18.53 25.00 19.05

9

SECCION POSITIVA

+Ms (T-m) t (cm) d (cm) 1.38 25.00 20.05

DISEÑO POR RESISTENCIA ACI 350-06

FACTORES DE AMPLIFICACION DE CARGA

F.C.V. F.C.V. (SISMO) F.C.S. 1.70 1.20 1.00

MOMENTOS MAXIMOS ULTIMOS PARA LOS DIFERENTES ESTADOS DE CARGA

Cara humeda Cara seca

COMB. DESCRIPCION -M22u (T-m) +M22u (T-m) 1 PRESION HIDROSTATICA * 1.70 5.54 2.35

2 P. HIDROSTATICA * 1.20 + P. HIDRODINAMICA 6.49 2.98

DISEÑO DEL REFUERZO VERTICAL DEL MURO

SECCION DE MOMENTO POSITIVO (CARA SECA)

FACTOR DE DURABILIDAD (SIN SISMO) Y REDUCCION DE RESISTENCIA

F.D. φφφφ

1.30 0.90

MOMENTO ULTIMO DE DISEÑO Y AREA DE REFUERZO

+Mu (T-m) b (cm) t (cm) d (cm)

3.05 100.00 25.00 20.05

As (cm2) ρρρρ 4.10 0.00164

ρρρρmin Asmin (cm2/cara)

0.0030 3.75

DIAMETRO Y ESPACIAMIENTO DEL REFUERZO

Ab (cm2) s (m) 1.27 0.31

s (m) # varillas 0.30 105

10

SECCION DE MOMENTO NEGATIVO (CARA HUMEDA)

FACTOR DE DURABILIDAD (SIN SISMO) Y REDUCCION DE RESISTENCIA

F.D. φφφφ

1.30 0.90

MOMENTO ULTIMO DE DISEÑO Y AREA DE REFUERZO

-Mu (T-m) b (cm) t (cm) d (cm)

7.20 100.00 25.00 19.05

As (cm2) ρρρρ 10.52 0.00421

ρρρρmin Asmin (cm2/cara)

0.0030 3.75

DIAMETRO Y ESPACIAMIENTO DEL REFUERZO

Ab (cm2) s (m) 1.63 0.15

s (m) # varillas 0.150 203

CORTE DEL REFUERZO NEGATIVO A Hm/4

Hc (m) 1.00

As (cm2) s (m) As (cm2)/m d (cm) a (cm) -Mur (T-m) 1.98 0.30 6.60 19.05 1.16 -4.61

# VARILLAS COMPLETAS EN PARED VERTICAL

s (m) # varillas 0.30 102

DISEÑO DEL REFUERZO CIRCULAR DEL MURO

FACTORES DE AMPLIFICACION, DURABILIDAD Y REDUCCION DE RESISTENCIA

F.C.V. F.D. φφφφ

1.70 1.65 0.90

11

PRESIONES, TENSIONES CIRCUNFERENCIALES ULTIMAS Y ACERO REQUERIDO

h (m) Ts (T) Tu (T) As (cm2) φ φ φ φ (c/cara) s (m) 4.00 12.20 34.23 9.06 1.27 0.28 3.80 14.92 41.85 11.07 1.27 0.23 3.60 14.74 41.35 10.94 1.27 0.23 3.40 13.78 38.64 10.22 0.71 0.14 3.20 12.60 35.35 9.35 0.71 0.15 3.00 11.18 31.35 8.29 0.71 0.17 2.75 9.89 27.73 7.34 0.71 0.19 2.50 8.64 24.22 6.41 0.71 0.22 2.25 7.39 20.74 5.49 0.71 0.26 2.00 6.15 17.26 4.57 0.71 0.31 1.75 4.91 13.76 3.64 0.71 0.39 1.50 3.65 10.23 2.71 0.71 0.52 1.25 2.38 6.66 1.76 0.71 0.81

USAR: 5 φφφφ 1/2" @ 0.20, 6 φφφφ 3/8" @ 0.15, Rto. φ φ φ φ 3/8" @ 0.20 c/cara

REFUERZO MINIMO

ρρρρmin Asmin (cm2/cara) Ab (cm2) s (m) 0.0030 3.75 0.71 0.19

DISEÑO DE LA CUPULA

MATERIALES

f´c (kg/cm2) Ec (kg/cm2) fy (kg/cm2) Es (kg/cm2) 245.00 234,787.14 4,200.00 2,000,000.00

GEOMETRIA DEL TANQUE

Di (m) Dm (m) ri (m) rm (m) 9.60 9.85 4.80 4.93

t (m) 0.25

GEOMETRIA DE LA CUPULA

fmin (m) fmax (m) f (m) r (m) φ φ φ φ (rad) 0.96 1.20 1.20 10.20 0.49

ESPESORES DE LA CUPULA

emin (m) emax (m) 0.07 0.15

12

CARGAS EN SERVICIO

p.p. (kg/m2) p.acab. (kg/m2) s/c (kg/m2) w (kg/m2) 185 50 50 285

CARGA TOTAL (P) Y CARGA POR METRO LINEAL (V)

P (kg) V (kg/m) 21,903 726

COMPONENTE HORIZONTAL (H) y RESULTANTE "R"

H (kg/m) R (kg/m) 1,362 1,543

VERIFICACION DEL ESPESOR MINIMO DE LA CUPULA

fcadm (kg/cm2) emin (cm) OBS. 10.00 1.54 OK

REFUERZO RADIAL Y CIRCUNFERENCIAL

REFUERZO RADIAL

fs (kg/cm2) As (cm2)/m

1,000.00 0.73

REFUERZOS MINIMOS

ρρρρmin

0.0020

ZONA DE ENSANCHE EN APOYO

Asmin (cm2)/m φ φ φ φ (ref. superior) s (m) s (m) # varillas 3.00 0.71 0.24 0.20 159

EN ZONA DE ESPESOR CONSTANTE

Asmin (cm2)/m φ φ φ φ (ref. central) s (m) s (m) # varillas 1.40 0.32 0.23 0.20 159

REFUERZO CIRCUNFERENCIAL

ZONA DE ENSANCHE EN APOYO

Asmin (cm2)/m φ φ φ φ (ref. c/cara) s (m) s (m) 3.00 0.32 0.21 0.20

13

EN ZONA DE ESPESOR CONSTANTE

Asmin (cm2)/m φ φ φ φ (ref. central) s (m) s (m) 1.40 0.32 0.23 0.20

DISEÑO DE LA VIGA ANULAR DE APOYO

TRACCION MAXIMA

Tmax (kg) 6,536

AREA MINIMA DE CONCRETO

fcadm (kg/cm2) Ac (cm2) 10.00 654

SECCION TRANSVERSAL DE LA VIGA ANULAR

bmin (cm) b (cm) hmin (cm) h (cm) 35.00 35.00 18.67 35.00

REFUERZO LONGITUDINAL

fs (kg/cm2) As (cm2) 1,000.00 6.54

ρρρρmin Asmin (cm2) 0.0050 6.13

Av (cm2) # varillas

1.27 5.1 USAR: 6 φφφφ 1/2"

REFUERZO TRANSVERSAL DE MONTAJE

φφφφestribo s (m) # estribos 3/8" 0.25 125

DISEÑO DE LA CIMENTACION

ANILLO DE CIMENTACION

CARGA POR METRO LINEAL (P)

P (kg) 4,446

ANCHO Y PERALTE DE LA ZAPATA ANULAR (B)

14

Bmin (m) B (m) hzmin (m) hz (m) rz (m) 0.85 1.00 0.60 0.60 5.35

ESFUERZOS EN EL TERRENO

σσσσact (kg/cm2) σσσσt (kg/cm2) OBS. 0.44 5.00 OK

REFUERZO RADIAL

ρρρρmin Asmin (cm2) 0.0030 18.00

φ φ φ φ (ref. c/cara) s (m) s (m) # varillas 1.98 0.22 0.20 167

REFUERZO CIRCUNFERENCIAL

ρρρρmin Asmin (cm2) 0.0030 18.00

Ab (cm2) # total varillas 1.27 14

LOSA DE FONDO

ESFUERZO DE COMPRESION EN LA LOSA (FRANJA DE 1 METRO)

tmin (m) t (m) q (T/m) σσσσact (kg/cm2) 0.17 0.25 4.10 0.41 << 0.40 f´c

REFUERZO

ρρρρmin Asmin (cm2) 0.0030 7.50

φ φ φ φ (ref.) c/cara s (m) s (cm) 0.71 0.19 0.20

15

RESERVORIO APOYADO RAP-03 V = 150 m3

RESERVORIO APOYADO RAP-06 V = 150 m3

DISEÑO DEL MURO CILINDRICO (SECCION CONSTANTE)

MATERIALES

f´c (kg/cm2) Ec (kg/cm2) fy (kg/cm2) Es (kg/cm2) 280.00 250,998.01 4,200.00 2,000,000.00

PROPIEDADES DEL SUELO DE FUNDACION

γγγγs (T/m3) φφφφ σσσσt (kg/cm2) Df (m) 1.90 35.00 5.00 1.00

GEOMETRIA DEL TANQUE

Di (m) Dm (m) ri (m) rm (m) 7.60 7.85 3.800 3.925

t (m) Hm (m) Ha (m) 0.25 3.85 3.35

V (m3) 151.97

MOMENTOS MAXIMOS EN SERVICIO DEBIDO A PRESIONES HIDROSTATICAS

Cara humeda Cara seca

COMB. DESCRIPCION -M22s (T-m) +M22s (T-m) 1 PRESION HIDROSTATICA 2.88 1.22

ESFUERZOS ADMISIBLES CONCRETO Y ACERO

fcadm (kg/cm2) fsadm (kg/cm2) 126.00 1,680.00

DIMENSIONAMIENTO DE LA PARED CILINDRICA

n k j K (kg/cm2) 7.97 0.37 0.88 20.63

b (cm) rec (cm) db (cm) 100.00 5.00 1.91

SECCION NEGATIVA (BASE DEL MURO)

-Ms (T-m) dmin (cm) hmin (cm) t (cm) d (cm) 2.88 11.82 17.77 25.00 19.05

16

SECCION POSITIVA

+Ms (T-m) t (cm) d (cm) 1.22 25.00 20.05

DISEÑO POR RESISTENCIA ACI 350-06

FACTORES DE AMPLIFICACION DE CARGA

F.C.V. F.C.V. (SISMO) F.C.S. 1.70 1.20 1.00

MOMENTOS MAXIMOS ULTIMOS PARA LOS DIFERENTES ESTADOS DE CARGA

Cara humeda Cara seca

COMB. DESCRIPCION -M22u (T-m) +M22u (T-m) 1 PRESION HIDROSTATICA * 1.70 4.90 2.07

2 P. HIDROSTATICA * 1.20 + P. HIDRODINAMICA 5.19 2.33

DISEÑO DEL REFUERZO VERTICAL DEL MURO

SECCION DE MOMENTO POSITIVO (CARA SECA)

FACTOR DE DURABILIDAD (SIN SISMO) Y REDUCCION DE RESISTENCIA

F.D. φφφφ

1.30 0.90

MOMENTO ULTIMO DE DISEÑO Y AREA DE REFUERZO

+Mu (T-m) b (cm) t (cm) d (cm)

2.70 100.00 25.00 20.05

As (cm2) ρρρρ 3.62 0.00145

ρρρρmin Asmin (cm2/cara)

0.0030 3.75

DIAMETRO Y ESPACIAMIENTO DEL REFUERZO

Ab (cm2) s (m) 0.99 0.26

s (m) # varillas 0.25 101

17

SECCION DE MOMENTO NEGATIVO (CARA HUMEDA)

FACTOR DE DURABILIDAD (SIN SISMO) Y REDUCCION DE RESISTENCIA

F.D. φφφφ

1.30 0.90

MOMENTO ULTIMO DE DISEÑO Y AREA DE REFUERZO

-Mu (T-m) b (cm) t (cm) d (cm)

6.36 100.00 25.00 19.05

As (cm2) ρρρρ 9.24 0.00369

ρρρρmin Asmin (cm2/cara)

0.0030 3.75

DIAMETRO Y ESPACIAMIENTO DEL REFUERZO

Ab (cm2) s (m) 1.98 0.21

s (m) # varillas 0.200 121

CORTE DEL REFUERZO NEGATIVO A Hm/4

Hc (m) 0.96

As (cm2) s (m) As (cm2)/m d (cm) a (cm) -Mur (T-m) 1.98 0.40 4.95 19.05 0.87 -3.48

# VARILLAS COMPLETAS EN PARED VERTICAL

s (m) # varillas 0.40 60

DISEÑO DEL REFUERZO CIRCULAR DEL MURO

FACTORES DE AMPLIFICACION, DURABILIDAD Y REDUCCION DE RESISTENCIA

F.C.V. F.D. φφφφ

1.70 1.65 0.90

18

PRESIONES, TENSIONES CIRCUNFERENCIALES ULTIMAS Y ACERO REQUERIDO

h (m) Ts (T) Tu (T) As (cm2) φ φ φ φ (c/cara) s (m) 3.85 10.59 29.70 7.86 0.71 0.18 3.65 11.79 33.07 8.75 0.71 0.16 3.45 11.14 31.24 8.27 0.71 0.17 3.25 10.23 28.70 7.59 0.71 0.19 3.05 9.35 26.23 6.94 0.71 0.20 2.85 8.51 23.87 6.32 0.71 0.22 2.65 7.70 21.61 5.72 0.71 0.25 2.45 6.91 19.39 5.13 0.71 0.28 2.25 6.14 17.21 4.55 0.71 0.31 2.05 5.36 15.03 3.98 0.71 0.36 1.85 4.51 12.64 3.34 0.71 0.42 1.65 3.27 9.17 2.43 0.71 0.59 1.35 2.12 5.94 1.57 0.71 0.90

USAR: 6 φφφφ 3/8" @ 0.15, Rto. φ φ φ φ 3/8" @ 0.20 c/cara

REFUERZO MINIMO

ρρρρmin Asmin (cm2/cara) Ab (cm2) s (m) 0.0030 3.75 0.71 0.19

DISEÑO DE LA CUPULA

MATERIALES

f´c (kg/cm2) Ec (kg/cm2) fy (kg/cm2) Es (kg/cm2) 245.00 234,787.14 4,200.00 2,000,000.00

GEOMETRIA DEL TANQUE

Di (m) Dm (m) ri (m) rm (m) 7.60 7.85 3.80 3.93

t (m) 0.25

GEOMETRIA DE LA CUPULA

fmin (m) fmax (m) f (m) r (m) φ φ φ φ (rad) 0.76 0.95 0.90 8.47 0.47

ESPESORES DE LA CUPULA

emin (m) emax (m) 0.07 0.15

CARGAS EN SERVICIO

19

p.p. (kg/m2) p.acab. (kg/m2) s/c (kg/m2) w (kg/m2) 185 50 50 285

CARGA TOTAL (P) Y CARGA POR METRO LINEAL (V)

P (kg) V (kg/m) 13,645 571

COMPONENTE HORIZONTAL (H) y RESULTANTE "R"

H (kg/m) R (kg/m) 1,139 1,274

VERIFICACION DEL ESPESOR MINIMO DE LA CUPULA

fcadm (kg/cm2) emin (cm) OBS. 10.00 1.27 OK

REFUERZO RADIAL Y CIRCUNFERENCIAL

REFUERZO RADIAL

fs (kg/cm2) As (cm2)/m

1,000.00 0.57

REFUERZOS MINIMOS

ρρρρmin

0.0020

ZONA DE ENSANCHE EN APOYO

Asmin (cm2)/m φ φ φ φ (ref. superior) s (m) s (m) # varillas 3.00 0.71 0.24 0.20 128

EN ZONA DE ESPESOR CONSTANTE

Asmin (cm2)/m φ φ φ φ (ref. central) s (m) s (m) # varillas 1.40 0.32 0.23 0.20 128

REFUERZO CIRCUNFERENCIAL

ZONA DE ENSANCHE EN APOYO

Asmin (cm2)/m φ φ φ φ (ref. c/cara) s (m) s (m) 3.00 0.32 0.21 0.20

EN ZONA DE ESPESOR CONSTANTE

Asmin (cm2)/m φ φ φ φ (ref. central) s (m) s (m) 1.40 0.32 0.23 0.20

20

DISEÑO DE LA VIGA ANULAR DE APOYO

TRACCION MAXIMA

Tmax (kg) 4,327

AREA MINIMA DE CONCRETO

fcadm (kg/cm2) Ac (cm2) 10.00 433

SECCION TRANSVERSAL DE LA VIGA ANULAR

bmin (cm) b (cm) hmin (cm) h (cm) 35.00 35.00 12.36 30.00

REFUERZO LONGITUDINAL

fs (kg/cm2) As (cm2) 1,000.00 4.33

ρρρρmin Asmin (cm2) 0.0050 5.25

Av (cm2) # varillas

1.27 4.1 USAR: 4 φφφφ 1/2" + 2 φφφφ 3/8"

REFUERZO TRANSVERSAL DE MONTAJE

φφφφestribo s (m) # estribos 3/8" 0.25 100

DISEÑO DE LA CIMENTACION

ANILLO DE CIMENTACION

CARGA POR METRO LINEAL (P)

P (kg) 4,074

ANCHO Y PERALTE DE LA ZAPATA ANULAR (B)

Bmin (m) B (m) hzmin (m) hz (m) rz (m) 0.85 1.00 0.60 0.60 4.35

21

ESFUERZOS EN EL TERRENO

σσσσact (kg/cm2) σσσσt (kg/cm2) OBS. 0.41 5.00 OK

REFUERZO RADIAL

ρρρρmin Asmin (cm2) 0.0030 18.00

φ φ φ φ (ref. c/cara) s (m) s (m) # varillas 1.98 0.22 0.20 135

REFUERZO CIRCUNFERENCIAL

ρρρρmin Asmin (cm2) 0.0030 18.00

Ab (cm2) # total varillas 1.27 14

LOSA DE FONDO

ESFUERZO DE COMPRESION EN LA LOSA (FRANJA DE 1 METRO)

tmin (m) t (m) q (T/m) σσσσact (kg/cm2) 0.13 0.25 3.95 0.40 << 0.40 f´c

REFUERZO

ρρρρmin Asmin (cm2) 0.0030 7.50

φ φ φ φ (ref.) c/cara s (m) s (cm) 0.71 0.19 0.20

22

RESERVORIO APOYADO RAP-04 V = 950 m3

DISEÑO DEL MURO CILINDRICO (SECCION CONSTANTE)

MATERIALES

f´c (kg/cm2) Ec (kg/cm2) fy (kg/cm2) Es (kg/cm2) 280.00 250,998.01 4,200.00 2,000,000.00

PROPIEDADES DEL SUELO DE FUNDACION

γγγγs (T/m3) φφφφ σσσσt (kg/cm2) Df (m) 1.90 35.00 5.00 1.00

GEOMETRIA DEL TANQUE

Di (m) Dm (m) ri (m) rm (m) 15.00 15.35 7.500 7.675

t (m) Hm (m) Ha (m) 0.35 5.90 5.40

V (m3) 954.26

MOMENTOS MAXIMOS EN SERVICIO DEBIDO A PRESIONES HIDROSTATICAS

Cara humeda Cara seca

COMB. DESCRIPCION -M22s (T-m) +M22s (T-m) 1 PRESION HIDROSTATICA 11.50 4.95

ESFUERZOS ADMISIBLES CONCRETO Y ACERO

fcadm (kg/cm2) fsadm (kg/cm2) 126.00 1,680.00

DIMENSIONAMIENTO DE LA PARED CILINDRICA

n k j K (kg/cm2) 7.97 0.37 0.88 20.63

b (cm) rec (cm) db (cm) 100.00 5.00 1.91

SECCION NEGATIVA (BASE DEL MURO)

-Ms (T-m) dmin (cm) hmin (cm) t (cm) d (cm) 11.50 23.61 29.57 35.00 29.05

23

SECCION POSITIVA

+Ms (T-m) t (cm) d (cm) 4.95 35.00 30.05

DISEÑO POR RESISTENCIA ACI 350-06

FACTORES DE AMPLIFICACION DE CARGA

F.C.V. F.C.V. (SISMO) F.C.S. 1.70 1.20 1.00

MOMENTOS MAXIMOS ULTIMOS PARA LOS DIFERENTES ESTADOS DE CARGA

Cara humeda Cara seca

COMB. DESCRIPCION -M22u (T-m) +M22u (T-m) 1 PRESION HIDROSTATICA * 1.70 19.55 8.42

2 P. HIDROSTATICA * 1.20 + P. HIDRODINAMICA 22.70 10.60

DISEÑO DEL REFUERZO VERTICAL DEL MURO

SECCION DE MOMENTO POSITIVO (CARA SECA)

FACTOR DE DURABILIDAD (SIN SISMO) Y REDUCCION DE RESISTENCIA

F.D. φφφφ

1.30 0.90

MOMENTO ULTIMO DE DISEÑO Y AREA DE REFUERZO

+Mu (T-m) b (cm) t (cm) d (cm)

10.94 100.00 35.00 30.05

As (cm2) ρρρρ 9.92 0.00283

ρρρρmin Asmin (cm2/cara)

0.0030 5.25

DIAMETRO Y ESPACIAMIENTO DEL REFUERZO

Ab (cm2) s (m) 1.98 0.20

s (m) # varillas 0.20 245

24

SECCION DE MOMENTO NEGATIVO (CARA HUMEDA)

FACTOR DE DURABILIDAD (SIN SISMO) Y REDUCCION DE RESISTENCIA

F.D. φφφφ

1.30 0.90

MOMENTO ULTIMO DE DISEÑO Y AREA DE REFUERZO

-Mu (T-m) b (cm) t (cm) d (cm)

25.42 100.00 35.00 29.05

As (cm2) ρρρρ 25.06 0.00716

ρρρρmin Asmin (cm2/cara)

0.0030 5.25

DIAMETRO Y ESPACIAMIENTO DEL REFUERZO

Ab (cm2) s (m) 2.85 0.11

s (m) # varillas 0.100 474

CORTE DEL REFUERZO NEGATIVO A Hm/4

Hc (m) 1.48

As (cm2) s (m) As (cm2)/m d (cm) a (cm) -Mur (T-m) 2.85 0.20 14.25 29.05 2.51 -14.97

# VARILLAS COMPLETAS EN PARED VERTICAL

s (m) # varillas 0.20 237

DISEÑO DEL REFUERZO CIRCULAR DEL MURO

FACTORES DE AMPLIFICACION, DURABILIDAD Y REDUCCION DE RESISTENCIA

F.C.V. F.D. φφφφ

1.70 1.65 0.90

25

PRESIONES, TENSIONES CIRCUNFERENCIALES ULTIMAS Y ACERO REQUERIDO

h (m) Ts (T) Tu (T) As (cm2) φ φ φ φ (c/cara) s (m) 5.90 28.63 80.31 21.25 1.98 0.19 5.60 35.49 99.55 26.34 1.98 0.15 5.30 35.38 99.24 26.25 1.98 0.15 5.00 33.27 93.31 24.68 1.98 0.16 4.70 30.69 86.08 22.77 1.98 0.17 4.40 27.95 78.39 20.74 1.98 0.19 4.10 24.49 68.69 18.17 1.27 0.14 3.70 21.38 59.97 15.86 1.27 0.16 3.30 18.32 51.39 13.60 1.27 0.19 2.90 15.26 42.80 11.32 1.27 0.22 2.50 12.18 34.17 9.04 1.27 0.28 2.10 9.07 25.45 6.73 1.27 0.38 1.70 5.93 16.65 4.40 1.27 0.58

USAR: 14 φφφφ 5/8" @ 0.15, 6 φφφφ 1/2" @ 0.15, Rto. φ φ φ φ 1/2" @ 0.20 c/cara

REFUERZO MINIMO

ρρρρmin Asmin (cm2/cara) Ab (cm2) s (m) 0.0030 5.25 1.27 0.24

DISEÑO DE LA CUPULA

MATERIALES

f´c (kg/cm2) Ec (kg/cm2) fy (kg/cm2) Es (kg/cm2) 245.00 234,787.14 4,200.00 2,000,000.00

GEOMETRIA DEL TANQUE

Di (m) Dm (m) ri (m) rm (m) 15.00 15.35 7.50 7.68

t (m) 0.35

GEOMETRIA DE LA CUPULA

fmin (m) fmax (m) f (m) r (m) φ φ φ φ (rad) 1.50 1.88 1.80 16.53 0.47

ESPESORES DE LA CUPULA

emin (m) emax (m) 0.07 0.15

CARGAS EN SERVICIO

26

p.p. (kg/m2) p.acab. (kg/m2) s/c (kg/m2) w (kg/m2) 185 50 50 285

CARGA TOTAL (P) Y CARGA POR METRO LINEAL (V)

P (kg) V (kg/m) 53,227 1,130

COMPONENTE HORIZONTAL (H) y RESULTANTE "R"

H (kg/m) R (kg/m) 2,218 2,489

VERIFICACION DEL ESPESOR MINIMO DE LA CUPULA

fcadm (kg/cm2) emin (cm) OBS. 10.00 2.49 OK

REFUERZO RADIAL Y CIRCUNFERENCIAL

REFUERZO RADIAL

fs (kg/cm2) As (cm2)/m

1,000.00 1.13

REFUERZOS MINIMOS

ρρρρmin

0.0020

ZONA DE ENSANCHE EN APOYO

Asmin (cm2)/m φ φ φ φ (ref. superior) s (m) s (m) # varillas 3.00 0.71 0.24 0.20 247

EN ZONA DE ESPESOR CONSTANTE

Asmin (cm2)/m φ φ φ φ (ref. central) s (m) s (m) # varillas 1.40 0.32 0.23 0.20 247

REFUERZO CIRCUNFERENCIAL

ZONA DE ENSANCHE EN APOYO

Asmin (cm2)/m φ φ φ φ (ref. c/cara) s (m) s (m) 3.00 0.32 0.21 0.20

EN ZONA DE ESPESOR CONSTANTE

Asmin (cm2)/m φ φ φ φ (ref. central) s (m) s (m) 1.40 0.32 0.23 0.20

27

DISEÑO DE LA VIGA ANULAR DE APOYO

TRACCION MAXIMA

Tmax (kg) 16,632

AREA MINIMA DE CONCRETO

fcadm (kg/cm2) Ac (cm2) 10.00 1,663

SECCION TRANSVERSAL DE LA VIGA ANULAR

bmin (cm) b (cm) hmin (cm) h (cm) 45.00 45.00 36.96 40.00

REFUERZO LONGITUDINAL

fs (kg/cm2) As (cm2) 1,000.00 16.63

ρρρρmin Asmin (cm2) 0.0050 9.00

Av (cm2) # varillas

2.85 5.8 USAR: 6 φφφφ 3/4"

REFUERZO TRANSVERSAL DE MONTAJE

φφφφestribo s (m) # estribos 3/8" 0.25 194

DISEÑO DE LA CIMENTACION

ANILLO DE CIMENTACION

CARGA POR METRO LINEAL (P)

P (kg) 8,473

ANCHO Y PERALTE DE LA ZAPATA ANULAR (B)

Bmin (m) B (m) hzmin (m) hz (m) rz (m) 0.95 1.20 0.60 0.60 8.15

28

ESFUERZOS EN EL TERRENO

σσσσact (kg/cm2) σσσσt (kg/cm2) OBS. 0.71 5.00 OK

REFUERZO RADIAL

ρρρρmin Asmin (cm2) 0.0030 18.00

φ φ φ φ (ref. c/cara) s (m) s (m) # varillas 1.98 0.22 0.20 254

REFUERZO CIRCUNFERENCIAL

ρρρρmin Asmin (cm2) 0.0030 21.60

Ab (cm2) # total varillas 1.27 17

LOSA DE FONDO

ESFUERZO DE COMPRESION EN LA LOSA (FRANJA DE 1 METRO)

tmin (m) t (m) q (T/m) σσσσact (kg/cm2) 0.28 0.30 6.12 0.61 << 0.40 f´c

REFUERZO

ρρρρmin Asmin (cm2) 0.0030 9.00

φ φ φ φ (ref.) c/cara s (m) s (cm) 1.27 0.28 0.25

29

RESERVORIO APOYADO RRP-01 V = 550 m3

DISEÑO DEL MURO CILINDRICO (SECCION CONSTANTE)

MATERIALES

f´c (kg/cm2) Ec (kg/cm2) fy (kg/cm2) Es (kg/cm2) 280.00 250,998.01 4,200.00 2,000,000.00

PROPIEDADES DEL SUELO DE FUNDACION

γγγγs (T/m3) φφφφ σσσσt (kg/cm2) Df (m) 1.90 35.00 5.00 1.00

GEOMETRIA DEL TANQUE

Di (m) Dm (m) ri (m) rm (m) 12.60 12.90 6.300 6.450

t (m) Hm (m) Ha (m) 0.30 4.95 4.45

V (m3) 554.87

MOMENTOS MAXIMOS EN SERVICIO DEBIDO A PRESIONES HIDROSTATICAS

Cara humeda Cara seca

COMB. DESCRIPCION -M22s (T-m) +M22s (T-m) 1 PRESION HIDROSTATICA 6.53 2.81

ESFUERZOS ADMISIBLES CONCRETO Y ACERO

fcadm (kg/cm2) fsadm (kg/cm2) 126.00 1,680.00

DIMENSIONAMIENTO DE LA PARED CILINDRICA

n k j K (kg/cm2) 7.97 0.37 0.88 20.63

b (cm) rec (cm) db (cm) 100.00 5.00 1.91

SECCION NEGATIVA (BASE DEL MURO)

-Ms (T-m) dmin (cm) hmin (cm) t (cm) d (cm) 6.53 17.79 23.75 30.00 24.05

30

SECCION POSITIVA

+Ms (T-m) t (cm) d (cm) 2.81 30.00 25.05

DISEÑO POR RESISTENCIA ACI 350-06

FACTORES DE AMPLIFICACION DE CARGA

F.C.V. F.C.V. (SISMO) F.C.S. 1.70 1.20 1.00

MOMENTOS MAXIMOS ULTIMOS PARA LOS DIFERENTES ESTADOS DE CARGA

Cara humeda Cara seca

COMB. DESCRIPCION -M22u (T-m) +M22u (T-m) 1 PRESION HIDROSTATICA * 1.70 11.10 4.78

2 P. HIDROSTATICA * 1.20 + P. HIDRODINAMICA 13.10 6.09

DISEÑO DEL REFUERZO VERTICAL DEL MURO

SECCION DE MOMENTO POSITIVO (CARA SECA)

FACTOR DE DURABILIDAD (SIN SISMO) Y REDUCCION DE RESISTENCIA

F.D. φφφφ

1.30 0.90

MOMENTO ULTIMO DE DISEÑO Y AREA DE REFUERZO

+Mu (T-m) b (cm) t (cm) d (cm)

6.21 100.00 30.00 25.05

As (cm2) ρρρρ 6.72 0.00224

ρρρρmin Asmin (cm2/cara)

0.0030 4.50

DIAMETRO Y ESPACIAMIENTO DEL REFUERZO

Ab (cm2) s (m) 1.98 0.29

s (m) # varillas 0.25 165

31

SECCION DE MOMENTO NEGATIVO (CARA HUMEDA)

FACTOR DE DURABILIDAD (SIN SISMO) Y REDUCCION DE RESISTENCIA

F.D. φφφφ

1.30 0.90

MOMENTO ULTIMO DE DISEÑO Y AREA DE REFUERZO

-Mu (T-m) b (cm) t (cm) d (cm)

14.43 100.00 30.00 24.05

As (cm2) ρρρρ 16.93 0.00564

ρρρρmin Asmin (cm2/cara)

0.0030 4.50

DIAMETRO Y ESPACIAMIENTO DEL REFUERZO

Ab (cm2) s (m) 2.85 0.17

s (m) # varillas 0.150 266

CORTE DEL REFUERZO NEGATIVO A Hm/4

Hc (m) 1.24

As (cm2) s (m) As (cm2)/m d (cm) a (cm) -Mur (T-m) 2.85 0.30 9.50 24.05 1.68 -8.33

# VARILLAS COMPLETAS EN PARED VERTICAL

s (m) # varillas 0.30 133

DISEÑO DEL REFUERZO CIRCULAR DEL MURO

FACTORES DE AMPLIFICACION, DURABILIDAD Y REDUCCION DE RESISTENCIA

F.C.V. F.D. φφφφ

1.70 1.65 0.90

32

PRESIONES, TENSIONES CIRCUNFERENCIALES ULTIMAS Y ACERO REQUERIDO

h (m) Ts (T) Tu (T) As (cm2) φ φ φ φ (c/cara) s (m) 4.95 21.74 60.98 16.13 1.98 0.25 4.65 24.87 69.75 18.45 1.98 0.21 4.35 23.57 66.10 17.49 1.98 0.23 4.05 21.43 60.12 15.91 1.27 0.16 3.75 19.27 54.05 14.30 1.27 0.18 3.45 17.19 48.21 12.75 1.27 0.20 3.15 15.18 42.57 11.26 1.27 0.23 2.85 13.20 37.04 9.80 1.27 0.26 2.55 11.25 31.55 8.35 1.27 0.30 2.25 9.30 26.07 6.90 1.27 0.37 1.95 7.33 20.57 5.44 1.27 0.47 1.65 5.36 15.02 3.97 1.27 0.64 1.35 3.37 9.45 2.50 1.27 1.02

USAR: 5 φ φ φ φ 5/8" @ 0.20, 4 φφφφ 1/2" @ 0.15, 4 φφφφ 1/2" @ 0.20, Rto. φ φ φ φ 1/2" @ 0.25 c/cara

REFUERZO MINIMO

ρρρρmin Asmin (cm2/cara) Ab (cm2) s (m) 0.0030 4.50 1.27 0.28

DISEÑO DE LA CUPULA

MATERIALES

f´c (kg/cm2) Ec (kg/cm2) fy (kg/cm2) Es (kg/cm2) 245.00 234,787.14 4,200.00 2,000,000.00

GEOMETRIA DEL TANQUE

Di (m) Dm (m) ri (m) rm (m) 12.60 12.90 6.30 6.45

t (m) 0.30

GEOMETRIA DE LA CUPULA

fmin (m) fmax (m) f (m) r (m) φ φ φ φ (rad) 1.26 1.58 1.50 13.98 0.47

ESPESORES DE LA CUPULA

emin (m) emax (m) 0.07 0.15

CARGAS EN SERVICIO

33

p.p. (kg/m2) p.acab. (kg/m2) s/c (kg/m2) w (kg/m2) 185 50 50 285

CARGA TOTAL (P) Y CARGA POR METRO LINEAL (V)

P (kg) V (kg/m) 37,525 948

COMPONENTE HORIZONTAL (H) y RESULTANTE "R"

H (kg/m) R (kg/m) 1,878 2,104

VERIFICACION DEL ESPESOR MINIMO DE LA CUPULA

fcadm (kg/cm2) emin (cm) OBS. 10.00 2.10 OK

REFUERZO RADIAL Y CIRCUNFERENCIAL

REFUERZO RADIAL

fs (kg/cm2) As (cm2)/m

1,000.00 0.95

REFUERZOS MINIMOS

ρρρρmin

0.0020

ZONA DE ENSANCHE EN APOYO

Asmin (cm2)/m φ φ φ φ (ref. superior) s (m) s (m) # varillas 3.00 0.71 0.24 0.20 208

EN ZONA DE ESPESOR CONSTANTE

Asmin (cm2)/m φ φ φ φ (ref. central) s (m) s (m) # varillas 1.40 0.32 0.23 0.20 208

REFUERZO CIRCUNFERENCIAL

ZONA DE ENSANCHE EN APOYO

Asmin (cm2)/m φ φ φ φ (ref. c/cara) s (m) s (m) 3.00 0.32 0.21 0.20

EN ZONA DE ESPESOR CONSTANTE

Asmin (cm2)/m φ φ φ φ (ref. central) s (m) s (m) 1.40 0.32 0.23 0.20

34

DISEÑO DE LA VIGA ANULAR DE APOYO

TRACCION MAXIMA

Tmax (kg) 11,831

AREA MINIMA DE CONCRETO

fcadm (kg/cm2) Ac (cm2) 10.00 1,183

SECCION TRANSVERSAL DE LA VIGA ANULAR

bmin (cm) b (cm) hmin (cm) h (cm) 40.00 40.00 29.58 35.00

REFUERZO LONGITUDINAL

fs (kg/cm2) As (cm2) 1,000.00 11.83

ρρρρmin Asmin (cm2) 0.0050 7.00

Av (cm2) # varillas

1.98 6.0 USAR: 6 φφφφ 5/8"

REFUERZO TRANSVERSAL DE MONTAJE

φφφφestribo s (m) # estribos 3/8" 0.25 163

DISEÑO DE LA CIMENTACION

ANILLO DE CIMENTACION

CARGA POR METRO LINEAL (P)

P (kg) 6,302

ANCHO Y PERALTE DE LA ZAPATA ANULAR (B)

Bmin (m) B (m) hzmin (m) hz (m) rz (m) 0.90 1.20 0.60 0.60 6.90

35

ESFUERZOS EN EL TERRENO

σσσσact (kg/cm2) σσσσt (kg/cm2) OBS. 0.53 5.00 OK

REFUERZO RADIAL

ρρρρmin Asmin (cm2) 0.0030 18.00

φ φ φ φ (ref. c/cara) s (m) s (m) # varillas 1.98 0.22 0.20 215

REFUERZO CIRCUNFERENCIAL

ρρρρmin Asmin (cm2) 0.0030 21.60

Ab (cm2) # total varillas 1.27 17

LOSA DE FONDO

ESFUERZO DE COMPRESION EN LA LOSA (FRANJA DE 1 METRO)

tmin (m) t (m) q (T/m) σσσσact (kg/cm2) 0.23 0.30 5.17 0.52 << 0.40 f´c

REFUERZO

ρρρρmin Asmin (cm2) 0.0030 9.00

φ φ φ φ (ref.) c/cara s (m) s (cm) 1.27 0.28 0.25

36

RESERVORIO APOYADO RRP-02 V = 650 m3

DISEÑO DEL MURO CILINDRICO (SECCION CONSTANTE)

MATERIALES

f´c (kg/cm2) Ec (kg/cm2) fy (kg/cm2) Es (kg/cm2) 280.00 250,998.01 4,200.00 2,000,000.00

PROPIEDADES DEL SUELO DE FUNDACION

γγγγs (T/m3) φφφφ σσσσt (kg/cm2) Df (m) 1.90 35.00 5.00 1.00

GEOMETRIA DEL TANQUE

Di (m) Dm (m) ri (m) rm (m) 13.50 13.80 6.750 6.900

t (m) Hm (m) Ha (m) 0.30 5.10 4.60

V (m3) 658.44

MOMENTOS MAXIMOS EN SERVICIO DEBIDO A PRESIONES HIDROSTATICAS

Cara humeda Cara seca

COMB. DESCRIPCION -M22s (T-m) +M22s (T-m) 1 PRESION HIDROSTATICA 7.20 3.11

ESFUERZOS ADMISIBLES CONCRETO Y ACERO

fcadm (kg/cm2) fsadm (kg/cm2) 126.00 1,680.00

DIMENSIONAMIENTO DE LA PARED CILINDRICA

n k j K (kg/cm2) 7.97 0.37 0.88 20.63

b (cm) rec (cm) db (cm) 100.00 5.00 1.91

SECCION NEGATIVA (BASE DEL MURO)

-Ms (T-m) dmin (cm) hmin (cm) t (cm) d (cm) 7.20 18.68 24.64 30.00 24.05

37

SECCION POSITIVA

+Ms (T-m) t (cm) d (cm) 3.11 30.00 25.05

DISEÑO POR RESISTENCIA ACI 350-06

FACTORES DE AMPLIFICACION DE CARGA

F.C.V. F.C.V. (SISMO) F.C.S. 1.70 1.20 1.00

MOMENTOS MAXIMOS ULTIMOS PARA LOS DIFERENTES ESTADOS DE CARGA

Cara humeda Cara seca

COMB. DESCRIPCION -M22u (T-m) +M22u (T-m) 1 PRESION HIDROSTATICA * 1.70 12.24 5.29

2 P. HIDROSTATICA * 1.20 + P. HIDRODINAMICA 14.80 6.87

DISEÑO DEL REFUERZO VERTICAL DEL MURO

SECCION DE MOMENTO POSITIVO (CARA SECA)

FACTOR DE DURABILIDAD (SIN SISMO) Y REDUCCION DE RESISTENCIA

F.D. φφφφ

1.30 0.90

MOMENTO ULTIMO DE DISEÑO Y AREA DE REFUERZO

+Mu (T-m) b (cm) t (cm) d (cm)

6.87 100.00 30.00 25.05

As (cm2) ρρρρ 7.46 0.00249

ρρρρmin Asmin (cm2/cara)

0.0030 4.50

DIAMETRO Y ESPACIAMIENTO DEL REFUERZO

Ab (cm2) s (m) 1.98 0.27

s (m) # varillas 0.25 176

38

SECCION DE MOMENTO NEGATIVO (CARA HUMEDA)

FACTOR DE DURABILIDAD (SIN SISMO) Y REDUCCION DE RESISTENCIA

F.D. φφφφ

1.30 0.90

MOMENTO ULTIMO DE DISEÑO Y AREA DE REFUERZO

-Mu (T-m) b (cm) t (cm) d (cm)

15.91 100.00 30.00 24.05

As (cm2) ρρρρ 18.80 0.00627

ρρρρmin Asmin (cm2/cara)

0.0030 4.50

DIAMETRO Y ESPACIAMIENTO DEL REFUERZO

Ab (cm2) s (m) 2.85 0.15

s (m) # varillas 0.150 285

CORTE DEL REFUERZO NEGATIVO A Hm/4

Hc (m) 1.28

As (cm2) s (m) As (cm2)/m d (cm) a (cm) -Mur (T-m) 2.85 0.30 9.50 24.05 1.68 -8.33

# VARILLAS COMPLETAS EN PARED VERTICAL

s (m) # varillas 0.30 142

DISEÑO DEL REFUERZO CIRCULAR DEL MURO

FACTORES DE AMPLIFICACION, DURABILIDAD Y REDUCCION DE RESISTENCIA

F.C.V. F.D. φφφφ

1.70 1.65 0.90

39

PRESIONES, TENSIONES CIRCUNFERENCIALES ULTIMAS Y ACERO REQUERIDO

h (m) Ts (T) Tu (T) As (cm2) φ φ φ φ (c/cara) s (m) 5.10 23.16 64.96 17.19 1.98 0.23 4.80 27.28 76.52 20.24 1.98 0.20 4.50 26.26 73.66 19.49 1.98 0.20 4.20 24.07 67.52 17.86 1.98 0.22 3.90 21.75 60.99 16.14 1.27 0.16 3.60 19.49 54.66 14.46 1.27 0.18 3.30 17.31 48.55 12.84 1.27 0.20 3.00 15.18 42.58 11.26 1.27 0.23 2.70 13.08 36.68 9.70 1.27 0.26 2.40 10.98 30.81 8.15 1.27 0.31 2.10 8.89 24.93 6.59 1.27 0.39 1.80 6.77 19.00 5.03 1.27 0.51 1.50 4.64 13.02 3.45 1.27 0.74

USAR: 6 φ φ φ φ 5/8" @ 0.20, 4 φφφφ 1/2" @ 0.15, 4 φφφφ 1/2" @ 0.20, Rto. φ φ φ φ 1/2" @ 0.25 c/cara

REFUERZO MINIMO

ρρρρmin Asmin (cm2/cara) Ab (cm2) s (m) 0.0030 4.50 1.27 0.28

DISEÑO DE LA CUPULA

MATERIALES

f´c (kg/cm2) Ec (kg/cm2) fy (kg/cm2) Es (kg/cm2) 245.00 234,787.14 4,200.00 2,000,000.00

GEOMETRIA DEL TANQUE

Di (m) Dm (m) ri (m) rm (m) 13.50 13.80 6.75 6.90

t (m) 0.30

GEOMETRIA DE LA CUPULA

fmin (m) fmax (m) f (m) r (m) φ φ φ φ (rad) 1.35 1.69 1.60 15.04 0.47

ESPESORES DE LA CUPULA

emin (m) emax (m) 0.07 0.15

CARGAS EN SERVICIO

40

p.p. (kg/m2) p.acab. (kg/m2) s/c (kg/m2) w (kg/m2) 185 50 50 285

CARGA TOTAL (P) Y CARGA POR METRO LINEAL (V)

P (kg) V (kg/m) 43,056 1,015

COMPONENTE HORIZONTAL (H) y RESULTANTE "R"

H (kg/m) R (kg/m) 2,021 2,262

VERIFICACION DEL ESPESOR MINIMO DE LA CUPULA

fcadm (kg/cm2) emin (cm) OBS. 10.00 2.26 OK

REFUERZO RADIAL Y CIRCUNFERENCIAL

REFUERZO RADIAL

fs (kg/cm2) As (cm2)/m

1,000.00 1.02

REFUERZOS MINIMOS

ρρρρmin

0.0020

ZONA DE ENSANCHE EN APOYO

Asmin (cm2)/m φ φ φ φ (ref. superior) s (m) s (m) # varillas 3.00 0.71 0.24 0.20 222

EN ZONA DE ESPESOR CONSTANTE

Asmin (cm2)/m φ φ φ φ (ref. central) s (m) s (m) # varillas 1.40 0.32 0.23 0.20 222

REFUERZO CIRCUNFERENCIAL

ZONA DE ENSANCHE EN APOYO

Asmin (cm2)/m φ φ φ φ (ref. c/cara) s (m) s (m) 3.00 0.32 0.21 0.20

EN ZONA DE ESPESOR CONSTANTE

Asmin (cm2)/m φ φ φ φ (ref. central) s (m) s (m) 1.40 0.32 0.23 0.20

41

DISEÑO DE LA VIGA ANULAR DE APOYO

TRACCION MAXIMA

Tmax (kg) 13,643

AREA MINIMA DE CONCRETO

fcadm (kg/cm2) Ac (cm2) 10.00 1,364

SECCION TRANSVERSAL DE LA VIGA ANULAR

bmin (cm) b (cm) hmin (cm) h (cm) 40.00 40.00 34.11 40.00

REFUERZO LONGITUDINAL

fs (kg/cm2) As (cm2) 1,000.00 13.64

ρρρρmin Asmin (cm2) 0.0050 8.00

Av (cm2) # varillas

1.98 6.9 USAR: 8 φφφφ 5/8"

REFUERZO TRANSVERSAL DE MONTAJE

φφφφestribo s (m) # estribos 3/8" 0.25 175

DISEÑO DE LA CIMENTACION

ANILLO DE CIMENTACION

CARGA POR METRO LINEAL (P)

P (kg) 6,593

ANCHO Y PERALTE DE LA ZAPATA ANULAR (B)

Bmin (m) B (m) hzmin (m) hz (m) rz (m) 0.90 1.20 0.60 0.60 7.35

42

ESFUERZOS EN EL TERRENO

σσσσact (kg/cm2) σσσσt (kg/cm2) OBS. 0.55 5.00 OK

REFUERZO RADIAL

ρρρρmin Asmin (cm2) 0.0030 18.00

φ φ φ φ (ref. c/cara) s (m) s (m) # varillas 1.98 0.22 0.20 229

REFUERZO CIRCUNFERENCIAL

ρρρρmin Asmin (cm2) 0.0030 21.60

Ab (cm2) # total varillas 1.27 17

LOSA DE FONDO

ESFUERZO DE COMPRESION EN LA LOSA (FRANJA DE 1 METRO)

tmin (m) t (m) q (T/m) σσσσact (kg/cm2) 0.25 0.30 5.32 0.53 << 0.40 f´c

REFUERZO

ρρρρmin Asmin (cm2) 0.0030 9.00

φ φ φ φ (ref.) c/cara s (m) s (cm) 1.27 0.28 0.25

43

RESERVORIO APOYADO RRP-03 V = 1400 m3

DISEÑO DEL MURO CILINDRICO (SECCION CONSTANTE)

MATERIALES

f´c (kg/cm2) Ec (kg/cm2) fy (kg/cm2) Es (kg/cm2) 280.00 250,998.01 4,200.00 2,000,000.00

PROPIEDADES DEL SUELO DE FUNDACION

γγγγs (T/m3) φφφφ σσσσt (kg/cm2) Df (m) 1.90 35.00 5.00 1.00

GEOMETRIA DEL TANQUE

Di (m) Dm (m) ri (m) rm (m) 16.60 17.00 8.300 8.500

t (m) Hm (m) Ha (m) 0.40 7.00 6.50

V (m3) 1,406.76

MOMENTOS MAXIMOS EN SERVICIO DEBIDO A PRESIONES HIDROSTATICAS

Cara humeda Cara seca

COMB. DESCRIPCION -M22s (T-m) +M22s (T-m) 1 PRESION HIDROSTATICA 19.70 8.59

ESFUERZOS ADMISIBLES CONCRETO Y ACERO

fcadm (kg/cm2) fsadm (kg/cm2) 126.00 1,680.00

DIMENSIONAMIENTO DE LA PARED CILINDRICA

n k j K (kg/cm2) 7.97 0.37 0.88 20.63

b (cm) rec (cm) db (cm) 100.00 5.00 1.91

SECCION NEGATIVA (BASE DEL MURO)

-Ms (T-m) dmin (cm) hmin (cm) t (cm) d (cm) 19.70 30.90 36.86 40.00 34.05

44

SECCION POSITIVA

+Ms (T-m) t (cm) d (cm) 8.59 40.00 35.05

DISEÑO POR RESISTENCIA ACI 350-06

FACTORES DE AMPLIFICACION DE CARGA

F.C.V. F.C.V. (SISMO) F.C.S. 1.70 1.20 1.00

MOMENTOS MAXIMOS ULTIMOS PARA LOS DIFERENTES ESTADOS DE CARGA

Cara humeda Cara seca

COMB. DESCRIPCION -M22u (T-m) +M22u (T-m) 1 PRESION HIDROSTATICA * 1.70 33.49 14.60

2 P. HIDROSTATICA * 1.20 + P. HIDRODINAMICA 37.20 17.30

DISEÑO DEL REFUERZO VERTICAL DEL MURO

SECCION DE MOMENTO POSITIVO (CARA SECA)

FACTOR DE DURABILIDAD (SIN SISMO) Y REDUCCION DE RESISTENCIA

F.D. φφφφ

1.30 0.90

MOMENTO ULTIMO DE DISEÑO Y AREA DE REFUERZO

+Mu (T-m) b (cm) t (cm) d (cm)

18.98 100.00 40.00 35.05

As (cm2) ρρρρ 14.89 0.00372

ρρρρmin Asmin (cm2/cara)

0.0030 6.00

DIAMETRO Y ESPACIAMIENTO DEL REFUERZO

Ab (cm2) s (m) 2.42 0.16

s (m) # varillas 0.15 363

45

SECCION DE MOMENTO NEGATIVO (CARA HUMEDA)

FACTOR DE DURABILIDAD (SIN SISMO) Y REDUCCION DE RESISTENCIA

F.D. φφφφ

1.30 0.90

MOMENTO ULTIMO DE DISEÑO Y AREA DE REFUERZO

-Mu (T-m) b (cm) t (cm) d (cm)

43.54 100.00 40.00 34.05

As (cm2) ρρρρ 37.47 0.00937

ρρρρmin Asmin (cm2/cara)

0.0030 6.00

DIAMETRO Y ESPACIAMIENTO DEL REFUERZO

Ab (cm2) s (m) 3.96 0.11

s (m) # varillas 0.100 525

CORTE DEL REFUERZO NEGATIVO A Hm/4

Hc (m) 1.75

As (cm2) s (m) As (cm2)/m d (cm) a (cm) -Mur (T-m) 5.07 0.20 25.35 34.05 4.47 -30.48

# VARILLAS COMPLETAS EN PARED VERTICAL

s (m) # varillas 0.20 262

DISEÑO DEL REFUERZO CIRCULAR DEL MURO

FACTORES DE AMPLIFICACION, DURABILIDAD Y REDUCCION DE RESISTENCIA

F.C.V. F.D. φφφφ

1.70 1.65 0.90

46

PRESIONES, TENSIONES CIRCUNFERENCIALES ULTIMAS Y ACERO REQUERIDO

h (m) Ts (T) Tu (T) As (cm2) φ φ φ φ (c/cara) s (m) 7.00 42.37 118.86 31.44 2.85 0.18 6.60 48.54 136.16 36.02 2.85 0.16 6.20 46.29 129.85 34.35 2.85 0.17 5.80 42.51 119.24 31.55 2.85 0.18 5.40 38.68 108.51 28.71 1.98 0.14 5.00 35.03 98.25 25.99 1.98 0.15 4.60 31.51 88.39 23.38 1.98 0.17 4.20 28.08 78.75 20.83 1.98 0.19 3.80 24.67 69.19 18.30 1.98 0.22 3.40 21.13 59.26 15.68 1.27 0.16 3.00 16.75 46.99 12.43 1.27 0.20 2.50 12.54 35.18 9.31 1.27 0.27 2.00 8.26 23.17 6.13 1.27 0.41

USAR: 14 φφφφ 3/4" @ 0.15, 13 φφφφ 5/8" @ 0.15, Rto. φ φ φ φ 1/2" @ 0.20 c/cara

REFUERZO MINIMO

ρρρρmin Asmin (cm2/cara) Ab (cm2) s (m) 0.0030 6.00 1.27 0.21

DISEÑO DE LA CUPULA

MATERIALES

f´c (kg/cm2) Ec (kg/cm2) fy (kg/cm2) Es (kg/cm2) 245.00 234,787.14 4,200.00 2,000,000.00

GEOMETRIA DEL TANQUE

Di (m) Dm (m) ri (m) rm (m) 16.60 17.00 8.30 8.50

t (m) 0.40

GEOMETRIA DE LA CUPULA

fmin (m) fmax (m) f (m) r (m) φ φ φ φ (rad) 1.66 2.08 2.00 18.22 0.47

ESPESORES DE LA CUPULA

emin (m) emax (m) 0.07 0.15

CARGAS EN SERVICIO

47

p.p. (kg/m2) p.acab. (kg/m2) s/c (kg/m2) w (kg/m2) 185 50 50 285

CARGA TOTAL (P) Y CARGA POR METRO LINEAL (V)

P (kg) V (kg/m) 65,217 1,251

COMPONENTE HORIZONTAL (H) y RESULTANTE "R"

H (kg/m) R (kg/m) 2,444 2,746

VERIFICACION DEL ESPESOR MINIMO DE LA CUPULA

fcadm (kg/cm2) emin (cm) OBS. 10.00 2.75 OK

REFUERZO RADIAL Y CIRCUNFERENCIAL

REFUERZO RADIAL

fs (kg/cm2) As (cm2)/m

1,000.00 1.25

REFUERZOS MINIMOS

ρρρρmin

0.0020

ZONA DE ENSANCHE EN APOYO

Asmin (cm2)/m φ φ φ φ (ref. superior) s (m) s (m) # varillas 3.00 0.71 0.24 0.20 274

EN ZONA DE ESPESOR CONSTANTE

Asmin (cm2)/m φ φ φ φ (ref. central) s (m) s (m) # varillas 1.40 0.32 0.23 0.20 274

REFUERZO CIRCUNFERENCIAL

ZONA DE ENSANCHE EN APOYO

Asmin (cm2)/m φ φ φ φ (ref. c/cara) s (m) s (m) 3.00 0.32 0.21 0.20

EN ZONA DE ESPESOR CONSTANTE

Asmin (cm2)/m φ φ φ φ (ref. central) s (m) s (m) 1.40 0.32 0.23 0.20

48

DISEÑO DE LA VIGA ANULAR DE APOYO

TRACCION MAXIMA

Tmax (kg) 20,287

AREA MINIMA DE CONCRETO

fcadm (kg/cm2) Ac (cm2) 10.00 2,029

SECCION TRANSVERSAL DE LA VIGA ANULAR

bmin (cm) b (cm) hmin (cm) h (cm) 50.00 50.00 40.57 45.00

REFUERZO LONGITUDINAL

fs (kg/cm2) As (cm2) 1,000.00 20.29

ρρρρmin Asmin (cm2) 0.0050 11.25

Av (cm2) # varillas

2.85 7.1 USAR: 8 φφφφ 3/4"

REFUERZO TRANSVERSAL DE MONTAJE

φφφφestribo s (m) # estribos 3/8" 0.25 215

DISEÑO DE LA CIMENTACION

ANILLO DE CIMENTACION

CARGA POR METRO LINEAL (P)

P (kg) 11,064

ANCHO Y PERALTE DE LA ZAPATA ANULAR (B)

Bmin (m) B (m) hzmin (m) hz (m) rz (m) 1.00 1.50 0.60 0.80 9.00

49

ESFUERZOS EN EL TERRENO

σσσσact (kg/cm2) σσσσt (kg/cm2) OBS. 0.74 5.00 OK

REFUERZO RADIAL

ρρρρmin Asmin (cm2) 0.0030 24.00

φ φ φ φ (ref. c/cara) s (m) s (m) # varillas 2.85 0.24 0.20 281

REFUERZO CIRCUNFERENCIAL

ρρρρmin Asmin (cm2) 0.0030 36.00

Ab (cm2) # total varillas 1.98 18

LOSA DE FONDO

ESFUERZO DE COMPRESION EN LA LOSA (FRANJA DE 1 METRO)

tmin (m) t (m) q (T/m) σσσσact (kg/cm2) 0.30 0.35 7.34 0.73 << 0.40 f´c

REFUERZO

ρρρρmin Asmin (cm2) 0.0030 10.50

φ φ φ φ (ref.) c/cara s (m) s (cm) 1.27 0.24 0.20

ING. CARLOS IRALA CANDIOTTI REG. CIP No. 31113

Lima, 19 de Enero del 2015