If you can't read please download the document
Upload
vannhu
View
283
Download
27
Embed Size (px)
Citation preview
1[ ] MiCOM P14x
MiCOM P14 x
MiCOM P14x , .
, , , , ...
.
. , -.
/ , .
, IEC 61850, SCADA. .
MiCOM P14x , . , , .
(. . 3) , 141 , . , . 143, , , , . .
1 5 A
, EC 61850.
P141, P142 40tE
P143 60tE
2MiCOM P14x[ ]
ANSI IEC 61850 P141 P142 P143
50/51/67 OcpPTOC/RDIR / , / (6 )
50N/51N/67N EfdPTOC/EfmPTOC / , / , .. (4 )
67 N SenEftPTOC (SEF/ I CosI Sin) (4 )
67 W SenEftPTOC
YN
64 SenRefPDIF
51V
46 NgcPTOC
49 ThmPTTR ( 1/2- )
37P / 37N
27 VtpPhsPTUV (2 )
59 VtpPhsPTOV (2 )
59N VtpResPTOV (2 )
47 NgvPTOV
81U PTUF (9 ) -
81O PTOF (9 ) -
81R PFRC (9 ) -
81RF (9 ) -
81RAV (9 ) -
(9 ) .
(2 )
BC
50BF RBRF
VTS ( 1, 2 3 )
CTS
49SR .
79 RREC , 4 -
25 RSYN - -
2nd Harm Block
32R/32L/32O
OptGGIO ()* 8 16 32
RlyGGIO ()* ( / )*
8 15 32
(RS232)
(RS485/Optic/Ethernet)*
(RS232/RS485)*
(IRIG-B)*
InterMiCOM - EIA(RS) 232 19.2 /
* * , , .
3[ ] MiCOM P14x
, , 14 , , , .
, 4
(waveform capture)
Read Only
X 50/51 67N/67W/64
50N/51N
67/67N 51V 46 49
37P/37N
27/59 59N 47 50BF
CTS
VTS 79 25
YN 49SR
Fault records Disturbance Record
Measurements
PSL
Local Communication
2nd Remote comm. port
Remote comm. port
LEDs
Self monitoring
81U/81O/81R
X50/51 67N/67W
/6450N/51N
67/67N
51V 46 4937P/37N
27/59
59N 47 50BF
CTS
VTS 79 25
YN 49SR
Fault records Disturbance Record
Measurements
PSL
Local Communication
2nd Remote comm. port
Remote comm. port
Feeder management P14x
LEDs
BinaryInput / output
always available
optional
Vref
V
I
IE sen
Self monitoring
81U/81O/81R
Y
IEC 61850
2- .
.
61850
14 /
ANSI .
Figure 2a: Typical parallel transformer application
P141
51P51N67P67N
64N274750BF
M
P143
51P51N4946
50BFBC7925
14
MiCOM P14x
4MiCOM P14x[ ]
. , (/). - , ( 10 IEC IEEE).
, . 90- :
0.5V (Vn = 100 - 120V) or 2.0V (Vn = 380 - 480V).
3,2 , .
, . : -
, - 3- .
, .
, . . , .
. .
.. , , I cos , I sin
.. . .. .
, .
.. .
MiCOM P14xProtection Relays 04
Phase OvercurrentSix independent stages are available for each phase overcurrent element. Each stage may be selected as non-directional or directional (forward/ reverse). All stages have definite time delayed characteristics, three of the stages may also be independently set to one of ten IDMT curves (IEC and IEEE).
The IDMT stages have a programmable reset timer for grading electro-mechanical, to reduce autoreclose dead times and to reduce clearance times where intermittent faults occur.
The phase fault directional elements are internally polarised by quadrature phase-phase voltages, and will make a correct directional decision down to:
0.5V (Vn = 100 - 120V) or 2.0V (Vn = 380 - 480V).
A synchronous polarising signal is maintained for 3.2s after voltage collapse to ensure that the instantaneous and time delayed overcurrent elements operate correctly for close-up three phase faults.
Standard Earth FaultThere are two standard earth fault elements, each with four independent stages.
The first element operates from measured quantities:
- Earth fault current which is directly measured using a separate CT, or
- Residual connection of the three line CTs The second standard earth fault element
operates from a residual current that is derived internally from the summation of the three phase currents.
All earth fault elements have the same directionality and IDMT characteristics as the phase overcurrent element. Both earth fault elements may be enabled at the same time providing directional earth fault protection and back-up standby earth fault protection in the same device. The directionality of the earth fault elements is provided by either residual voltageor negative sequence voltage.
Sensitive Earth FaultA core balance CT should be used to drive the sensitive earth fault function. The directionality of the sensitive earth fault element is provided by the residual voltage.
WattmetricAs an alternative to the directional earthfault characteristic a directional I cos j characteristic can be used for Petersen coil earth fault protection using the sensitive earth fault input. A directional I sin j characteristic is also available for protection of insulated feeders.
Blocked Over CurrentEach stage of overcurrent and earth fault protection can be blocked by an optically isolated input. This enables overcurrent and earth fault protection to integrate into a blocked overcurrent busbar protection scheme.
Cold Load Pick-Up LogicCold load pick-up temporarily raises the overcurrent settings following closure of the circuit breaker, allowing the protection settings to be set closer to the load profile.
Restricted Earth FaultThe restricted earth fault protection provided for protection of transformer winding against earth faults may be configured as either high impedance or low impedance biased differential.
Features carefully designed to protect any type of system
DIFFI
BIASIs2I
s1IK1
K2
K1 0% to 20%
K2 0% to 150%
s1I 0.08 to 1. 0I ns2I 0.10 to 1. 5I n
IEC Standard inverse t = TMS x
IEC Very inverse t = TMS x
IEC Extremely inverse t = TMS x
UK Long time inverse t = TMS x
IEEE Moderately inverse
t = TD x
IEEE Very inverse
IEEE Extremely inverse
US CO8 Inverse
US CO2 Short timeinverse
t = TD x
t = TD x
t = TD x
t = TD x
0.14
(I Is -1)0.02
13.5
(I Is -1)
80
(I Is -1)2
120
(I Is -1)
0.0515
(I Is -1)0.02 + 0.114
19.61
(I Is -1)2 + 0.491
28.2
(I Is -1)2 + 0.1217
5.95
(I Is -1)2 + 0.18
0.16758
(I Is -1)0.02 + 0.11858
IEEE/US curvesTD = 7
IEC/UK cur vesTMS = 1
TD 0.5 to 15TMS 0.025 to 1.2
IEEE MIIEEE VI
IEEE EIUS CO8
US CO2
100101
Current (Multiples of Is)
0.1
1
10
10 0
Ope
ratin
gtim
e (s
)
UK LTI
IEC SI
IEC VI
IEC EI
1000
100
10
1
0.1100101
Current (Multiples of Is)O
pera
ting
time
(s)
Rectifier Curve t = TMS x45900
(I Is -1)5.6
RECT
REF biased differential characteristics
Choice of IDMt characteristics
DIFFI
BIASIs2I
s1IK1
K2
K1 0% 20%
K2 0% 150%
s1I 0.08 1.0Ins2I 0.10 1.5In
IEEE MIIEEE VI
IEEE EIUS CO8
US CO2
1001010.1
1
10
10 0
UK LTI
IEC SI
IEC VI
IEC EI
1000
100
10
1
0.1100101
RECT
/ TMS = 1
IEEE/ TD = 7
( Is)
TMS 0.025 - 1.2
( Is)
TD 0.5 - 15
(
)
(
)
5[ ] MiCOM P14x
2 , , , ( ).
, , . .
. , . . , , , . MiCOM S1 Studio PC, .
, . , , .
, .
(/), .. .. -
: . , . , .
/
/ -. , . , , .
. . , .
9 : , , , , .
, . I2 I1.
2 . , . .
6MiCOM P14x[ ]
8 , 32 1 . 50 0,5 . . COMTRADE . MiCOM S1 .
. , :
,
, MiCOM S1
.
:
Ix,
1,0 y x y 2,0
()
, ( ).
( ).
, .
P142 P143 . . .
( ).
P143 / .
P14x .
, 1, . IRIG-B, . . .
. . , , , , , , ... - . MiCOM S1.
, , .
512 .
7[ ] MiCOM P14x
, , . , . , . , , . , .
MiCOM P14x :
- 12 (8 ) IRIG-B RS232 RS485 RS232/RS485/K-Bus Ethernet IEC 61850 () -
+48 1A/5A
P142 P143 , ( ) P141 7 8 . , , .
-.
+48.
. .
; , - .
RS232 MiCOM S1, , , , , , .
RS485. , .
Courier / K-bus Modbus IEC60870-5-103 ( ) DNP 3.0 IEC 61850 ( 100 / Ethernet / )
Ethernet IEC 61850. IEC 61850 , , , .
Ethernet (, RSTP, )
P14x 128 GOOSE.
, RS232, RS485 K-Bus.
,
MODEM MODEM
HMI
PC
COMM 1
COMM 2
SCADA / /
-
MiCOM P14xProtection Relays 04
Phase OvercurrentSix independent stages are available for each phase overcurrent element. Each stage may be selected as non-directional or directional (forward/ reverse). All stages have definite time delayed characteristics, three of the stages may also be independently set to one of ten IDMT curves (IEC and IEEE).
The IDMT stages have a programmable reset timer for grading electro-mechanical, to reduce autoreclose dead times and to reduce clearance times where intermittent faults occur.
The phase fault directional elements are internally polarised by quadrature phase-phase voltages, and will make a correct directional decision down to:
0.5V (Vn = 100 - 120V) or 2.0V (Vn = 380 - 480V).
A synchronous polarising signal is maintained for 3.2s after voltage collapse to ensure that the instantaneous and time delayed overcurrent elements operate correctly for close-up three phase faults.
Standard Earth FaultThere are two standard earth fault elements, each with four independent stages.
The first element operates from measured quantities:
- Earth fault current which is directly measured using a separate CT, or
- Residual connection of the three line CTs The second standard earth fault element
operates from a residual current that is derived internally from the summation of the three phase currents.
All earth fault elements have the same directionality and IDMT characteristics as the phase overcurrent element. Both earth fault elements may be enabled at the same time providing directional earth fault protection and back-up standby earth fault protection in the same device. The directionality of the earth fault elements is provided by either residual voltageor negative sequence voltage.
Sensitive Earth FaultA core balance CT should be used to drive the sensitive earth fault function. The directionality of the sensitive earth fault element is provided by the residual voltage.
WattmetricAs an alternative to the directional earthfault characteristic a directional I cos j characteristic can be used for Petersen coil earth fault protection using the sensitive earth fault input. A directional I sin j characteristic is also available for protection of insulated feeders.
Blocked Over CurrentEach stage of overcurrent and earth fault protection can be blocked by an optically isolated input. This enables overcurrent and earth fault protection to integrate into a blocked overcurrent busbar protection scheme.
Cold Load Pick-Up LogicCold load pick-up temporarily raises the overcurrent settings following closure of the circuit breaker, allowing the protection settings to be set closer to the load profile.
Restricted Earth FaultThe restricted earth fault protection provided for protection of transformer winding against earth faults may be configured as either high impedance or low impedance biased differential.
Features carefully designed to protect any type of system
DIFFI
BIASIs2I
s1IK1
K2
K1 0% to 20%
K2 0% to 150%
s1I 0.08 to 1. 0I ns2I 0.10 to 1. 5I n
IEC Standard inverse t = TMS x
IEC Very inverse t = TMS x
IEC Extremely inverse t = TMS x
UK Long time inverse t = TMS x
IEEE Moderately inverse
t = TD x
IEEE Very inverse
IEEE Extremely inverse
US CO8 Inverse
US CO2 Short timeinverse
t = TD x
t = TD x
t = TD x
t = TD x
0.14
(I Is -1)0.02
13.5
(I Is -1)
80
(I Is -1)2
120
(I Is -1)
0.0515
(I Is -1)0.02 + 0.114
19.61
(I Is -1)2 + 0.491
28.2
(I Is -1)2 + 0.1217
5.95
(I Is -1)2 + 0.18
0.16758
(I Is -1)0.02 + 0.11858
IEEE/US curvesTD = 7
IEC/UK cur vesTMS = 1
TD 0.5 to 15TMS 0.025 to 1.2
IEEE MIIEEE VI
IEEE EIUS CO8
US CO2
100101
Current (Multiples of Is)
0.1
1
10
10 0
Ope
ratin
gtim
e (s
)
UK LTI
IEC SI
IEC VI
IEC EI
1000
100
10
1
0.1100101
Current (Multiples of Is)
Ope
ratin
gtim
e (s
)
Rectifier Curve t = TMS x45900
(I Is -1)5.6
RECT
REF biased differential characteristics
Choice of IDMt characteristics
P14x
8MiCOM P14x[ ]
1998 - MODN. 2 000 .
1999 - P14x MiCOM . 10 000 .
2002 - ( 2) MiCOM P14x.
2004 - UCA2 Ethernet.
2006 IEC 61850
, - , , . , , , - . . - .
Schneider Electric , , 050009, - , 151/115, - , 12, .: (727) 397 04 00, : (727) 397 04 05 , , 010000, . , 31, 216, .: (7172) 58 05 01, : (7172) 58 05 02 , , 400089, . , 15, 12, ./: (8442) 93 08 41 , , 394026, - , 65, 267, .: (4732) 39 06 00, : (4732) 39 06 01 , , 49000, . , 17, 4, .: (380567) 90 08 88, : (380567) 90 09 99 , , 83003, . , 26, .: (062) 206 50 44, : (062) 206 50 45 , , 620014, . , 28, 11, .: (343) 378 47 36, 378 47 37 , , 664047, . 1- , 3 , 312, .: (3952) 29 00 07, : (3952) 29 20 43 , , 420107, . , 6, 7, ./: (843) 526 55 84 / 85 / 86 / 87 , , 236040, ., 15, .: (4012) 53 59 53, : (4012) 57 60 79 , , 03057, . , 20, , .: (044) 538 14 70, : (044) 538 14 71 , , 350063, . , 62 / . , 13 , 224, ./: (861) 214 97 35, 214 97 36 , , 660021, . , 3 , 302, .: (3912) 56 80 95, : (3912) 56 80 96 , , 79015, . , 72, . 1, ./: (032) 298 85 85 , , 220006, . , 15, 9, .: (37517) 327 60 34, 327 60 72 , , 127018, . , 12, . 1, - , .: (495) 777 99 90, : (495) 777 99 92 , , 183038, . , 5/23, - , 739, .: (8152) 28 86 90, : (8152) 28 87 30 , , 603000, . , 10 , 8, ./: (831) 278 97 25 / 26 , , 54030, . , 25, - , 5, .: (0512) 58 24 67, : (0512) 58 24 68 , , 630132, . , 35, , 1309, ./: (383) 227 62 53, 227 62 54 , , 614010, -, 98, 11, ./: (342) 290 26 11 / 13 / 15 --, , 344002, . , 74, 1402, .: (863) 261 83 22, : (863) 261 83 23 , , 443045, . , 150, .: (846) 278 40 86, : (846) 278 40 87 -, , 196158, , 40, . 4, , - , .: (812) 332 03 53, : (812) 332 03 52 , , .: (050) 446 50 90, 383 41 75 , , 354008, . , 20 , 54, .: (8622) 96 06 01, : (8622) 96 06 02 , , 450098, - , 132/3, - , 9, - 3, .: (347) 279 98 29, : (347) 279 98 30 , , 680000, . -, 23, 4, .: (4212) 30 64 70, : (4212) 30 46 66 , , 61070, . . , 1, - Telesens, 204, .: (057) 719 07 49, : (057) 719 07 79
.: 8 (800) 200 64 46 ().: (495) 777 99 88, : (495) 777 99 [email protected] 01/2013