74
MODBUS PROTOCOL & MEMORY MAP DOCUMENT K-PAM F3000, DG3000, M3000, T3000 Rev Date : 2009-05-04 Version : 1.70

MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

MODBUS PROTOCOL &MEMORY MAP DOCUMENT

K-PAM F3000, DG3000, M3000, T3000

Rev Date : 2009-05-04 Version : 1.70

Page 2: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 2 / 31

Information in this document is subject to change without notice. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose without the express written permission of Kyong Bo Co., Ltd.

For further information, contact:

Kyong Bo Co, Ltd. Tel:+82-2-465-1138

5, Seongsuil-ro 12ga-gil, Fax:+82-2-465-1333

Sungdong Gu, Seoul, 04792, Korea http://www.kyongbo.co.kr

Page 3: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 3 / 31

TABLE OF CONTENTS

1.2.3.4.5.6.7.8.9.10.11.

Scope ··············································································· Applicable Document ·····························································Register Types ·····································································Functions and message parsing ··················································Exception Responses ·····························································Data Formats ······································································Communication Configuration ···················································Register Map ········································································Register Formats ····································································Event Recording File Format ·····················································Waveform Recording File Format ················································

44455556

607474

Page 4: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 4 / 31

1. ScopeThis document describes the Modbus RTU register map for the Relay

2. Applicable DocumentModicon Modbus Protocol Reference GuideDWG#:PI-MBUS-300 Rev.E

This document describes the Modicon Modbus RTU communication protocol used by the Relay

The device configuration parameters, such as baud rate, is only accessible via debug port on the device.Because MODBUS is a multidrop network, the operator is responsible to make sure no 2 devices have the

same ID on the network, The device ID can range from 1 ~ 254 only.

3. Register Types The registers are mapped in order listed below.

Register Type CategoryFunction

CodeStart

AddressUse/Contents Access

Input Registers Fixed Value Registers 0x03(03) 0000Fixed data reported by

the deviceR/O

Input RegistersDynamic Value

Registers

0x04(04)

1000 Metering data

R/O

1600 Status data

Set-point Registers Setting Registers 2000 Counter

Report Registers Fault Registers2100 Logic Operand data5000 Float Metering data

Coil Registers Coil Command Registers 0x05(05) 0500Command coils used for

activationW/O

Set-point Registers Setting Registers0x06(06)0x10(16)

2500 Device Setting** R/W2800 Device Configuration R/W*

* Debug Port Only ** Master Device Setting Write Operation 1. Write Setting Data to Appropriate Register(2510~...) 2. Set Setting Flag Register(2500) 3. Control Set Update(0506)

Page 5: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 5 / 31

4. Functions and message parsing The Relay supports a subset of Modbus commands. All the supported commands are listed below.

Function Code Modbus Definition KyongBo Definition Register Groups

0x03 03 Read Holding Registers Read Actual Values of Set-pointsSet-point & Control registers and

fixed values

0x04 04 Read Input RegistersRead Actual Values of Set-points,

values of Multiple Set-pointsDynamic values, events,

Set-point registers fault and reports

0x05 05 Force Single Coil Execute Operation Coil registers

0x06 06 Preset Single Register Program Set-points Set-point registers

0x10 16 Preset Multiple Register Program Multiple Set-points Set-point registers

5. Exception ResponsesWhen a system host command received by a Relay cannot be performed,

it replies with an error code.01- illegal function02- illegal register address03- illegal data value04- slave device failure05- acknowledge long duration command06- busy servicing another long duration command07- negative acknowledge08- invalid report index

6. Data FormatsFormat Description Etc.ASCII 16bits assigned ASCII Ex) '1' ⇒ 0x0031

INT16U 0 ~ 65535 H-L OrderEx) 0x1234 ⇒ 0x1234INT16S -32768 ~ 32767

INT32U 0 ~ 4294967295 LL-HH OrderEx) 0x1234-0x5678 ⇒ 0x56781234INT32S -2147483648 ~ 2147483647

Bit Struct 16bits Bit Structure

FLOAT IEEE Floating point(32bits)

Page 6: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 6 / 31

7. Communication Configuration

Operation Half-Duplex (2-wire)

Interface RS-232, RS-485

BaudRS-232 19200

RS-485 300, 1200, 2400, 4800, 9600, 19200, 38400

Protocol Modbus RTU

Data Bit 8 bit

Stop Bit 1 bit

Parity Bit None(0)

Page 7: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 7 / 74

8. Register MapAddress

(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Device Inform0000 0x04 Unit Address 1 ~ 254 -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠

0001~ 0012 0x04 Device Type

12 ASCII characters "DG3000 ""M3000 ""F3000 ""T3000 "

-- R/O F602 -- ⊠ ⊠ ⊠ ⊠

0013~ 0024 0x04 Device ID 12 ASCII characters -- R/O F602 -- ⊠ ⊠ ⊠ ⊠0025~ 0028 0x04 MPU S/W Version 4 characters -- R/O F601 -- ⊠ ⊠ ⊠ ⊠0029~ 0032 0x04 DSP S/W Version 4 characters -- R/O F601 -- ⊠ ⊠ ⊠ ⊠0033 ~ ReservedControl (BO)0500 0x06 Open/Close Breaker1 On(H'FF00)/Off(0000) -- W/O -- -- ⊠ ⊠ ⊠ ⊠0501 0x06 Open/Close Breaker2 On(H'FF00)/Off(0000) -- W/O -- -- ⊠ ⊠ ⊠ ⊠0502 0x06 Reset Annunciator FF00 only (65280) -- W/O -- -- ⊠ ⊠ ⊠ ⊠0503 0x06 Clear Event Data FF00 only (65280) -- W/O -- -- ⊠ ⊠ ⊠ ⊠0504 0x06 Clear Waveform Data FF00 only (65280) -- W/O -- -- ⊠ ⊠ ⊠ ⊠0505 0x06 Clear Energy Data FF00 only (65280) -- W/O -- -- ⊠ ⊠ ⊠0506 0x06 Setting(Group) Update FF00 only (65280) -- W/O -- -- ⊠ ⊠ ⊠ ⊠0507 0x06 Setting Group 1 Active FF00 only (65280) -- W/O -- -- ⊠ ⊠ ⊠ ⊠0508 0x06 Setting Group 2 Active FF00 only (65280) -- W/O -- -- ⊠ ⊠ ⊠ ⊠0509 0x06 Setting Group 3 Active FF00 only (65280) -- W/O -- -- ⊠ ⊠ ⊠ ⊠0510 0x06 Setting Group 4 Active FF00 only (65280) -- W/O -- -- ⊠ ⊠ ⊠ ⊠0511 0x06 Clear Thermal FF00 only (65280) -- W/O -- -- ⊠ ⊠0512 0x06 Min/Max Reset FF00 only (65280) -- W/O -- -- ⊠ ⊠ ⊠0513 ~ ReservedMeasurement (AI)

Phase Voltage1000 0x04 Phase A Voltage Magnitude 0.00 ~ 655.35 -- R/O INT16U kV ⊠ ⊠ ⊠ ⊠1001 0x04 Phase A Voltage Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠

Page 8: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 8 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

1002 0x04 Phase B Voltage Magnitude 0.00 ~ 655.35 -- R/O INT16U kV ⊠ ⊠ ⊠1003 0x04 Phase B Voltage Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠1004 0x04 Phase C Voltage Magnitude 0.00 ~ 655.35 -- R/O INT16U kV ⊠ ⊠ ⊠1005 0x04 Phase C Voltage Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠1006 0x04 Phase N Voltage Magnitude

(Phase Aa Voltage Magnitude) 0.00 ~ 655.35 -- R/O INT16U kV ⊠ ⊠ ⊠1007 0x04 Phase N Voltage Angle

(Phase Aa Voltage Angle) 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠1008 0x04 3-Phase Average Voltage

Magnitude 0.00~ 655.35 -- R/O INT16U kV ⊠ ⊠ ⊠Line to Line Voltage

1009 0x04 Line AB Voltage Magnitude 0.00 ~ 655.35 -- R/O INT16U kV ⊠ ⊠ ⊠1010 0x04 Line AB Voltage Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠1011 0x04 Line BC Voltage Magnitude 0.00 ~ 655.35 -- R/O INT16U kV ⊠ ⊠ ⊠1012 0x04 Line BC Voltage Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠1013 0x04 Line CA Voltage Magnitude 0.00 ~ 655.35 -- R/O INT16U kV ⊠ ⊠ ⊠1014 0x04 Line CA Voltage Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠1015 ~ Reserved

Fundamental CurrentWinding 1

1021 0x04 Phase A Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠ ⊠ ⊠ ⊠1022 0x04 Phase A Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠1023 0x04 Phase B Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠ ⊠ ⊠ ⊠1024 0x04 Phase B Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠1025 0x04 Phase C Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠ ⊠ ⊠ ⊠1026 0x04 Phase C Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠1027 0x04 Phase N Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠ ⊠ ⊠ ⊠1028 0x04 Phase N Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠1029 0x04 3-Phase Average Current

Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠ ⊠ ⊠1030 0x04 Sensitive Ground Current

Magnitude 0.0 ~ 6553.5 -- R/O INT16U mA ⊠ ⊠1031 0x04 Sensitive Ground Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠

Page 9: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 9 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Winding 21032 0x04 Phase A Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠1033 0x04 Phase A Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠1034 0x04 Phase B Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠1035 0x04 Phase B Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠1036 0x04 Phase C Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠1037 0x04 Phase C Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠1038 0x04 Phase N Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠1039 0x04 Phase N Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠1040 Reserved

Winding 31041 0x04 Phase A Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠1042 0x04 Phase A Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠1043 0x04 Phase B Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠1044 0x04 Phase B Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠1045 0x04 Phase C Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠1046 0x04 Phase C Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠1047 0x04 Phase N Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠1048 0x04 Phase N Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠1049 Reserved

Power1050 0x04 Phase A Watt -327.67 ~ 327.67 -- R/O INT16S MW ⊠ ⊠ ⊠1051 0x04 Phase B Watt -327.67 ~ 327.67 -- R/O INT16S MW ⊠ ⊠ ⊠1052 0x04 Phase C Watt -327.67 ~ 327.67 -- R/O INT16S MW ⊠ ⊠ ⊠1053 0x04 3 Phase Watt -327.67 ~ 327.67 -- R/O INT16S MW ⊠ ⊠ ⊠1054 0x04 Phase A Var -327.67 ~ 327.67 -- R/O INT16S MVar ⊠ ⊠ ⊠1055 0x04 Phase B Var -327.67 ~ 327.67 -- R/O INT16S MVar ⊠ ⊠ ⊠1056 0x04 Phase C Var -327.67 ~ 327.67 -- R/O INT16S MVar ⊠ ⊠ ⊠1057 0x04 3 Phase Var -327.67 ~ 327.67 -- R/O INT16S MVar ⊠ ⊠ ⊠1058 0x04 Phase A VA 0.00 ~ 655.35 -- R/O INT16U MVA ⊠ ⊠ ⊠1059 0x04 Phase B VA 0.00 ~ 655.35 -- R/O INT16U MVA ⊠ ⊠ ⊠1060 0x04 Phase C VA 0.00 ~ 655.35 -- R/O INT16U MVA ⊠ ⊠ ⊠1061 0x04 3 Phase VA 0.00 ~ 655.35 -- R/O INT16U MVA ⊠ ⊠ ⊠

Page 10: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 10 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Power Factor1062 0x04 Phase A Power Factor -99.99 ~99.99 -- R/O INT16S % ⊠ ⊠ ⊠1063 0x04 Phase B Power Factor -99.99 ~99.99 -- R/O INT16S % ⊠ ⊠ ⊠1064 0x04 Phase C Power Factor -99.99 ~99.99 -- R/O INT16S % ⊠ ⊠ ⊠1065 0x04 3 Phase Power Factor -99.99 ~99.99 -- R/O INT16S % ⊠ ⊠ ⊠

Energy1066~ 1067 0x04 kW-Hour Import 0 ~ 4294967295 -- R/O INT32U kWh ⊠ ⊠ ⊠1068~ 1069 0x04 kW-Hour Export 0 ~ 4294967295 -- R/O INT32U kWh ⊠ ⊠ ⊠1070~ 1071 0x04 kVar-Hours Import 0 ~ 4294967295 -- R/O INT32U kVAR

h ⊠ ⊠ ⊠1072~ 1073 0x04 kVar-Hours Export 0 ~ 4294967295 -- R/O INT32U kVAR

h ⊠ ⊠ ⊠1074~ 1075 0x04 kVA-Hour 0 ~ 4294967295 -- R/O INT32U kVAh ⊠ ⊠ ⊠

Sequence Voltage

1076 0x04 Positive Sequence VoltageMagnitude 0.00 ~ 655.35 -- R/O INT16U kV ⊠ ⊠ ⊠

1077 0x04 Positive Sequence VoltageAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠

1078 0x04 Negative Sequence VoltageMagnitude 0.00 ~ 655.35 -- R/O INT16U kV ⊠ ⊠ ⊠

1079 0x04 Negative Sequence VoltageAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠

1080 0x04 Zero Sequence VoltageMagnitude 0.00 ~ 655.35 -- R/O INT16U kV ⊠ ⊠ ⊠

1081 0x04 Zero Sequence VoltageAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠Sequence CurrentWinding 1

1082 0x04 Positive Sequence CurrentMagnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠ ⊠ ⊠ ⊠

1083 0x04 Positive Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠

Page 11: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 11 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

1084 0x04 Negative Sequence CurrentMagnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠ ⊠ ⊠ ⊠

1085 0x04 Negative Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠

1086 0x04 Zero Sequence CurrentMagnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠ ⊠ ⊠ ⊠

1087 0x04 Zero Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠Winding 2

1088 0x04 Positive Sequence CurrentMagnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠

1089 0x04 Positive Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1090 0x04 Negative Sequence CurrentMagnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠

1091 0x04 Negative Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1092 0x04 Zero Sequence CurrentMagnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠

1093 0x04 Zero Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠Winding 3

1094 0x04 Positive Sequence CurrentMagnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠

1095 0x04 Positive Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1096 0x04 Negative Sequence CurrentMagnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠

1097 0x04 Negative Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1098 0x04 Zero Sequence CurrentMagnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠

1099 0x04 Zero Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

Page 12: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 12 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Compensate Fundamental Current (for CT Secondary)Winding 1

1100 0x04 Compensate FundamentalPhase A Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠

1101 0x04 Compensate FundamentalPhase A Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1102 0x04 Compensate FundamentalPhase B Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠

1103 0x04 Compensate FundamentalPhase B Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1104 0x04 Compensate FundamentalPhase C Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠

1105 0x04 Compensate FundamentalPhase C Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠Winding 2

1106 0x04 Compensate FundamentalPhase A Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠

1107 0x04 Compensate FundamentalPhase A Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1108 0x04 Compensate FundamentalPhase B Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠

1109 0x04 Compensate FundamentalPhase B Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1110 0x04 Compensate FundamentalPhase C Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠

1111 0x04 Compensate FundamentalPhase C Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠Winding 3

1112 0x04 Compensate FundamentalPhase A Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠

1113 0x04 Compensate FundamentalPhase A Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1114 0x04 Compensate FundamentalPhase B Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠

Page 13: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 13 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

1115 0x04 Compensate FundamentalPhase B Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1116 0x04 Compensate FundamentalPhase C Current Magnitude 0.000 ~ 65.535 -- R/O INT16U kA ⊠

1117 0x04 Compensate FundamentalPhase C Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠Differential Current

1118 0x04 Phase A Differential Current 0.00 ~ 655.35 -- R/O INT16U A ⊠1119 0x04 Phase B Differential Current 0.00 ~ 655.35 -- R/O INT16U A ⊠1120 0x04 Phase C Differential Current 0.00 ~ 655.35 -- R/O INT16U A ⊠

Restraint Current1121 0x04 Phase A Restraint Current 0.00 ~ 655.35 -- R/O INT16U A ⊠1122 0x04 Phase B Restraint Current 0.00 ~ 655.35 -- R/O INT16U A ⊠1123 0x04 Phase C Restraint Current 0.00 ~ 655.35 -- R/O INT16U A ⊠

Differential Harmonic Current

1124 0x04 Phase A Differential 2nd

Harmonic Current 0.00 ~ 655.35 -- R/O INT16U A ⊠1125 0x04 Phase B Differential 2nd

Harmonic Current 0.00 ~ 655.35 -- R/O INT16U A ⊠1126 0x04 Phase C Differential 2nd

Harmonic Current 0.00 ~ 655.35 -- R/O INT16U A ⊠1127 0x04 Phase A Differential 5th

Harmonic Current 0.00 ~ 655.35 -- R/O INT16U A ⊠1128 0x04 Phase B Differential 5th

Harmonic Current 0.00 ~ 655.35 -- R/O INT16U A ⊠1129 0x04 Phase C Differential 5th

Harmonic Current 0.00 ~ 655.35 -- R/O INT16U A ⊠Reference Winding

1130 0x04 Reference Winding 1 ~ 3 -- R/O INT16U A ⊠Magnitude compensation factor

1131 0x04 Winding1 Mag Compens factor 1.00 ~ 999.99 -- R/O INT16U A ⊠1132 0x04 Winding2 Mag Compens factor 1.00 ~ 999.99 -- R/O INT16U A ⊠1133 0x04 Winding3 Mag Compens factor 1.00 ~ 999.99 -- R/O INT16U A ⊠

Frequency1134 0x04 Frequency (VA) 0.00 ~ 327.67 R/O INT16U Hz ⊠ ⊠ ⊠ ⊠

Page 14: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 14 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Demand Phase Current1135 0x04 Phase A Demand Current 0.000 ~ 65.535 -- R/O INT16U kA ⊠ ⊠ ⊠1136 0x04 Phase B Demand Current 0.000 ~ 65.535 -- R/O INT16U kA ⊠ ⊠ ⊠1137 0x04 Phase C Demand Current 0.000 ~ 65.535 -- R/O INT16U kA ⊠ ⊠ ⊠

Demand 3 Phase Power1138 0x04 3 Phase Demand Watt -327.67 ~ 327.67 -- R/O INT16S MW ⊠ ⊠ ⊠1139 0x04 3 Phase Demand Var -327.67 ~ 327.67 -- R/O INT16S MVar ⊠ ⊠ ⊠1140 0x04 3 Phase Demand VA 0.00 ~ 655.35 -- R/O INT16U MVA ⊠ ⊠ ⊠1141 0x04 Frequency (VAa) 0.00 ~ 327.67 -- R/O INT16U Hz ⊠1142 ~ Reserved

Voltage THD1150 0x04 Phase A Voltage THD 0.0 ~ 100.0 -- R/O INT16U % ⊠ ⊠ ⊠1151 0x04 Phase B Voltage THD 0.0 ~ 100.0 -- R/O INT16U % ⊠ ⊠ ⊠1152 0x04 Phase C Voltage THD 0.0 ~ 100.0 -- R/O INT16U % ⊠ ⊠ ⊠

Current THD1153 0x04 Phase A Current THD 0.0 ~ 100.0 -- R/O INT16U % ⊠ ⊠ ⊠1154 0x04 Phase B Current THD 0.0 ~ 100.0 -- R/O INT16U % ⊠ ⊠ ⊠1155 0x04 Phase C Current THD 0.0 ~ 100.0 -- R/O INT16U % ⊠ ⊠ ⊠1156 ~ Reserved

Voltage Harmonics1160~ 1190 0x04 Phase A Voltage 1st ~ 31th

Harmonics 0.0 ~ 100.0 -- R/O INT16U % ⊠ ⊠ ⊠1191~ 1221 0x04 Phase B Voltage 1st ~ 31th

Harmonics 0.0 ~ 100.0 -- R/O INT16U % ⊠ ⊠ ⊠1222~ 1252 0x04 Phase C Voltage 1st ~ 31th

Harmonics 0.0 ~ 100.0 -- R/O INT16U % ⊠ ⊠ ⊠Current Harmonics

1253~ 1283 0x04 Phase A Current 1st ~ 31th

Harmonics 0.0 ~ 100.0 -- R/O INT16U % ⊠ ⊠ ⊠1284~ 1314 0x04 Phase B Current 1st ~ 31th

Harmonics 0.0 ~ 100.0 -- R/O INT16U % ⊠ ⊠ ⊠1315~ 1345 0x04 Phase C Current 1st ~ 31th

Harmonics 0.0 ~ 100.0 -- R/O INT16U % ⊠ ⊠ ⊠

Page 15: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 15 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Thermal Overload1346 0x04 Thermal Overload 0.0 ~ 250.0 -- R/O INT16U % ⊠ ⊠1347 ~ Reserved

Secondary Phase Voltage1400 0x04 Sec Phase A Voltage Magnitude 0.00 ~ 655.35 -- R/O INT16U V ⊠ ⊠ ⊠ ⊠1401 0x04 Sec Phase A Voltage Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠1402 0x04 Sec Phase B Voltage Magnitude 0.00 ~ 655.35 -- R/O INT16U V ⊠ ⊠ ⊠1403 0x04 Sec Phase B Voltage Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠1404 0x04 Sec Phase C Voltage Magnitude 0.00 ~ 655.35 -- R/O INT16U V ⊠ ⊠ ⊠1405 0x04 Sec Phase C Voltage Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠1406 0x04 Sec Phase N Voltage Magnitude 0.00 ~ 655.35 -- R/O INT16U V ⊠ ⊠ ⊠1407 0x04 Sec Phase N Voltage Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠1408 0x04 Sec 3 Phase Average Voltage

Magnitude 0.00 ~ 655.35 -- R/O INT16U V ⊠ ⊠ ⊠Secondary Line to Line Voltage

1409 0x04 Sec Line AB Voltage Magnitude 0.00 ~ 655.35 -- R/O INT16U V ⊠ ⊠ ⊠1410 0x04 Sec Line AB Voltage Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠1411 0x04 Sec Line BC Voltage Magnitude 0.00 ~ 655.35 -- R/O INT16U V ⊠ ⊠ ⊠1412 0x04 Sec Line BC Voltage Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠1413 0x04 Sec Line CA Voltage Magnitude 0.00 ~ 655.35 -- R/O INT16U V ⊠ ⊠ ⊠1414 0x04 Sec Line CA Voltage Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠

Secondary Fundamental CurrentWinding 1

1415 0x04 Sec Phase A Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠ ⊠ ⊠ ⊠1416 0x04 Sec Phase A Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠1417 0x04 Sec Phase B Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠ ⊠ ⊠ ⊠1418 0x04 Sec Phase B Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠1419 0x04 Sec Phase C Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠ ⊠ ⊠ ⊠1420 0x04 Sec Phase C Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠1421 0x04 Sec Phase N Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠ ⊠ ⊠ ⊠1422 0x04 Sec Phase N Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠1423 0x04 Sec 3 Phase Average Current

Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠ ⊠ ⊠Winding 2

1424 0x04 Sec Phase A Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

Page 16: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 16 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

1425 0x04 Sec Phase A Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠1426 0x04 Sec Phase B Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠1427 0x04 Sec Phase B Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠1428 0x04 Sec Phase C Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠1429 0x04 Sec Phase C Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠1430 0x04 Sec Phase N Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠1431 0x04 Sec Phase N Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

Winding 31432 0x04 Sec Phase A Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠1433 0x04 Sec Phase A Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠1434 0x04 Sec Phase B Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠1435 0x04 Sec Phase B Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠1436 0x04 Sec Phase C Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠1437 0x04 Sec Phase C Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠1438 0x04 Sec Phase N Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠1439 0x04 Sec Phase N Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

Secondary Power1440 0x04 Sec Phase A Watt -32.767 ~ 32.767 -- R/O INT16S kW ⊠ ⊠ ⊠1441 0x04 Sec Phase B Watt -32.767 ~ 32.767 -- R/O INT16S kW ⊠ ⊠ ⊠1442 0x04 Sec Phase C Watt -32.767 ~ 32.767 -- R/O INT16S kW ⊠ ⊠ ⊠1443 0x04 Sec 3 Phase Watt -32.767 ~ 32.767 -- R/O INT16S kW ⊠ ⊠ ⊠1444 0x04 Sec Phase A Var -32.767 ~ 32.767 -- R/O INT16S kVar ⊠ ⊠ ⊠1445 0x04 Sec Phase B Var -32.767 ~ 32.767 -- R/O INT16S kVar ⊠ ⊠ ⊠1446 0x04 Sec Phase C Var -32.767 ~ 32.767 -- R/O INT16S kVar ⊠ ⊠ ⊠1447 0x04 Sec 3 Phase Var -32.767 ~ 32.767 -- R/O INT16S kVar ⊠ ⊠ ⊠1448 0x04 Sec Phase A VA 0.000 ~ 65.535 -- R/O INT16U kVA ⊠ ⊠ ⊠1449 0x04 Sec Phase B VA 0.000 ~ 65.535 -- R/O INT16U kVA ⊠ ⊠ ⊠1450 0x04 Sec Phase C VA 0.000 ~ 65.535 -- R/O INT16U kVA ⊠ ⊠ ⊠1451 0x04 Sec 3 Phase VA 0.000 ~ 65.535 -- R/O INT16U kVA ⊠ ⊠ ⊠

Secondary Energy1452~ 1453 0x04 Sec kW-Hour Import 0 ~ 4294967295 -- R/O INT32U kWh ⊠ ⊠ ⊠1454~ 1455 0x04 Sec kW-Hour Export 0 ~ 4294967295 -- R/O INT32U kWh ⊠ ⊠ ⊠

Page 17: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 17 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

1456~ 1457 0x04 kVar-Hours Import 0 ~ 4294967295 -- R/O INT32U kVAR

h ⊠ ⊠ ⊠1458~ 1459 0x04 kVar-Hours Export 0 ~ 4294967295 -- R/O INT32U kVAR

h ⊠ ⊠ ⊠1460~ 1461 0x04 kVA-Hour 0 ~ 4294967295 -- R/O INT32U kVAh ⊠ ⊠ ⊠

Secondary Sequence Voltage

1462 0x04 Sec Positive Sequence VoltageMagnitude 0.00 ~ 655.35 -- R/O INT16U V ⊠ ⊠ ⊠

1463 0x04 Sec Positive Sequence VoltageAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠

1464 0x04 Sec Negative Sequence VoltageMagnitude 0.00 ~ 655.35 -- R/O INT16U V ⊠ ⊠ ⊠

1465 0x04 Sec Negative Sequence VoltageAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠

1466 0x04 Sec Zero Sequence VoltageMagnitude 0.00 ~ 655.35 -- R/O INT16U V ⊠ ⊠ ⊠

1467 0x04 Sec Zero Sequence VoltageAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠Secondary Sequence CurrentWinding 1

1468 0x04 Sec Positive Sequence CurrentMagnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠ ⊠ ⊠ ⊠

1469 0x04 Sec Positive Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠

1470 0x04 Sec Negative Sequence CurrentMagnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠ ⊠ ⊠ ⊠

1471 0x04 Sec Negative Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠

1472 0x04 Sec Zero Sequence CurrentMagnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠ ⊠ ⊠ ⊠

1473 0x04 Sec Zero Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠ ⊠ ⊠ ⊠Winding 2

1474 0x04 Sec Positive Sequence CurrentMagnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

Page 18: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 18 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

1475 0x04 Sec Positive Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1476 0x04 Sec Negative Sequence CurrentMagnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

1477 0x04 Sec Negative Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1478 0x04 Sec Zero Sequence CurrentMagnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

1479 0x04 Sec Zero Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠Winding 3

1480 0x04 Sec Positive Sequence CurrentMagnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

1481 0x04 Sec Positive Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1482 0x04 Sec Negative Sequence CurrentMagnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

1483 0x04 Sec Negative Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1484 0x04 Sec Zero Sequence CurrentMagnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

1485 0x04 Sec Zero Sequence CurrentAngle 0.0 ~ 359.9 -- R/O INT16U deg ⊠Compensate Fundamental Current (for CT Secondary)Winding 1

1486 0x04 Compensate FundamentalPhase A Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

1487 0x04 Compensate FundamentalPhase A Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1488 0x04 Compensate FundamentalPhase B Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

1489 0x04 Compensate FundamentalPhase B Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1490 0x04 Compensate FundamentalPhase C Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

Page 19: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 19 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

1491 0x04 Compensate FundamentalPhase C Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠Winding 2

1492 0x04 Compensate FundamentalPhase A Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

1493 0x04 Compensate FundamentalPhase A Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1494 0x04 Compensate FundamentalPhase B Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

1495 0x04 Compensate FundamentalPhase B Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1496 0x04 Compensate FundamentalPhase C Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

1497 0x04 Compensate FundamentalPhase C Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠Winding 3

1498 0x04 Compensate FundamentalPhase A Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

1499 0x04 Compensate FundamentalPhase A Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1500 0x04 Compensate FundamentalPhase B Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

1501 0x04 Compensate FundamentalPhase B Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠

1502 0x04 Compensate FundamentalPhase C Current Magnitude 0.00 ~ 655.35 -- R/O INT16U A ⊠

1503 0x04 Compensate FundamentalPhase C Current Angle 0.0 ~ 359.9 -- R/O INT16U deg ⊠Secondary Demand Phase Current

1504 0x04 Sec Phase A Demand Current 0.00 ~ 655.35 -- R/O INT16U A ⊠ ⊠ ⊠1505 0x04 Sec Phase B Demand Current 0.00 ~ 655.35 -- R/O INT16U A ⊠ ⊠ ⊠1506 0x04 Sec Phase C Demand Current 0.00 ~ 655.35 -- R/O INT16U A ⊠ ⊠ ⊠

Demand 3 Phase Power1507 0x04 3 Phase Demand Watt -32.767 ~ 32.767 -- R/O INT16S kW ⊠ ⊠ ⊠1508 0x04 3 Phase Demand Var -32.767 ~ 32.767 -- R/O INT16S kVar ⊠ ⊠ ⊠

Page 20: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 20 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

1509 0x04 3 Phase Demand VA 0.00 ~ 65.535 -- R/O INT16U kVA ⊠ ⊠ ⊠Remain Start Monitoring Time

1510 0x04 Remain Start Monitoring Time 0.0 ~ 120.0 -- R/O INT16U min ⊠1511 0x04 Motor Cold Start Counter 0 ~ 5 -- R/O INT16U -- ⊠1512 0x04 Motor Hot Start Counter 1 ~ 5 -- R/O INT16U -- ⊠1513 0x04 Current Reclosing Counter 0 ~ 4 -- R/O INT16U -- ⊠1514 ~ Reserved

Page 21: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 21 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Status (BI)Self-Diagnosis

1600 0x04 Memory Fail OK(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1601 0x04 Setting Fail OK(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1602 0x04 A/D Converter Fail OK(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1603 0x04 Calibration Fail OK(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1604 0x04 DC Power Failure NOP(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1605 0x04 CPU Except NOP(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1606 0x04 DSP Failure NOP(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1607 0x04 AI Circuit Failure NOP(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1608 0x04 EasyLogic Failure NOP(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1609 0x04 DI Circuit Failure NOP(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1610 0x04 DO Circuit Failure NOP(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1611 0x04 PT Fuse Failure NOP(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠1612 0x04 Current Sum NOP(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠1613 0x04 Voltage Balance NOP(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠1614 0x04 Current Balance NOP(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠1615 0x04 Trip Circuit Supervision NOP(0), Fail(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1616 ~ Reserved

ProtectionPhase Overcurrent (50/51)Winding 1

1620 0x04 50/51 Phase A Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1621 0x04 50/51 Phase B Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1622 0x04 50/51 Phase C Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1623 0x04 50_1 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1624 0x04 50_1 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1625 0x04 50_1 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1626 0x04 50_2 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1627 0x04 50_2 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1628 0x04 50_2 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1629 0x04 51 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1630 0x04 51 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1631 0x04 51 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠

Page 22: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 22 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Winding 21632 0x04 50/51 Phase A Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠1633 0x04 50/51 Phase B Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠1634 0x04 50/51 Phase C Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠1635 0x04 50_1 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠1636 0x04 50_1 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠1637 0x04 50_1 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠1638 0x04 50_2 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠1639 0x04 50_2 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠1640 0x04 50_2 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠1641 0x04 51 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠1642 0x04 51 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠1643 0x04 51 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠

Winding 31644 0x04 50/51 Phase A Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1645 0x04 50/51 Phase B Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1646 0x04 50/51 Phase C Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1647 0x04 50_1 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1648 0x04 50_1 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1649 0x04 50_1 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1650 0x04 50_2 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1651 0x04 50_2 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1652 0x04 50_2 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1653 0x04 51 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1654 0x04 51 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1655 0x04 51 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠

Ground/Neutral Overcurrent (50N/51N)Winding 1

1656 0x04 50/51N Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1657 0x04 50N_1 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1658 0x04 50N_2 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠

Page 23: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 23 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

1659 0x04 51N Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠Winding 2

1660 0x04 50/51N Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠1661 0x04 50N_1 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠1662 0x04 50N_2 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠1663 0x04 51N Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠

Winding 31664 0x04 50/51N Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1665 0x04 50N_1 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1666 0x04 50N_2 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1667 0x04 51N Operate NOP(0), OP(1) -- R/O INT16U -- ⊠

Sensitive Directional Ground Overcurrent (67Ns)1668 0x04 67Ns Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠1669 0x04 67Ns Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠

Thermal Overload (49)1670 0x04 49 Alarm NOP(0), Alarm(1) -- R/O INT16U -- ⊠ ⊠1671 0x04 49 Trip NOP(0), Trip(1) -- R/O INT16U -- ⊠ ⊠1672 ~ Reserved

Undercurrent (37)1680 0x04 37 Phase A Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠1681 0x04 37 Phase B Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠1682 0x04 37 Phase C Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠1683 0x04 37 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠1684 0x04 37 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠1685 0x04 37 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠

Negative Phase Sequence Overcurrent (46/46T)Winding 1

1686 0x04 46 Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1687 0x04 46_1 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1688 0x04 46_2 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1689 0x04 46T Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠

Page 24: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 24 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Winding 21690 0x04 46 Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1691 0x04 46_1 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1692 0x04 46_2 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1693 0x04 46T Operate NOP(0), OP(1) -- R/O INT16U -- ⊠

Winding 31694 0x04 46 Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1695 0x04 46_1 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1696 0x04 46_2 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1697 0x04 46T Operate NOP(0), OP(1) -- R/O INT16U -- ⊠

Phase Unbalance Protection (46U)1698 0x04 46U Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠ ⊠1699 0x04 46U Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠

Phase Overvoltage (59)1700 0x04 59 Phase A Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1701 0x04 59 Phase B Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠ ⊠1702 0x04 59 Phase C Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠ ⊠1703 0x04 59_1 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1704 0x04 59_1 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠1705 0x04 59_1 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠1706 0x04 59_2 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1707 0x04 59_2 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠1708 0x04 59_2 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠

Phase Undervoltage (27)1709 0x04 27 Phase A Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1710 0x04 27 Phase B Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠ ⊠1711 0x04 27 Phase C Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠ ⊠1712 0x04 27_1 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1713 0x04 27_1 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠1714 0x04 27_1 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠1715 0x04 27_2 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠

Page 25: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 25 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

1716 0x04 27_2 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠1717 0x04 27_2 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠

Residual/Ground Overvoltage (59G)1718 0x04 59G Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠1719 0x04 59G_1 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠1720 0x04 59G_2 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠

Negative Phase Sequence Overvoltage (47)1721 0x04 47 Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠ ⊠1722 0x04 47 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠

Under/Over Frequency (81U/O)1723 0x04 81U/O_1 Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠1724 0x04 81U/O_1 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠1725 0x04 81U/O_2 Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠1726 0x04 81U/O_2 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠1727 0x04 81U/O_3 Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠1728 0x04 81U/O_3 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠

Auto-Reclosing (79)1729 0x04 Auto Reclose Ready NOP(0), Ready(1) -- R/O INT16U -- ⊠1730 0x04 Auto Reclose in Progressing NOP(0), Prog(1) -- R/O INT16U -- ⊠1731 0x04 Auto Reclose Failed NOP(0), Fail(1) -- R/O INT16U -- ⊠1732 0x04 Auto Reclose Success NOP(0), Success(1) -- R/O INT16U -- ⊠

Circuit Breaker Failure (50BF)1733 0x04 50BF Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠

Cold Load Pickup1734 0x04 Cold Load Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1735 0x04 Cold Load Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠

Inrush Detection1736 0x04 Inrush detect NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠

Start-up Monitoring/Stall Protection for Motor (48/51L)1737 0x04 Start-up Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1738 0x04 Start-up Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1739 0x04 Rotor locked NOP(0), Lock(1) -- R/O INT16U -- ⊠

Page 26: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 26 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Start inhibit for Motor (66/68)1740 0x04 Start inhibit Progress NOP(0), Prog(1) -- R/O INT16U -- ⊠1741 0x04 Start inhibit Operation NOP(0), OP(1) -- R/O INT16U -- ⊠

HOC (50/87)1742 0x04 50/87 Phase A Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1743 0x04 50/87 Phase B Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1744 0x04 50/87 Phase C Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1745 0x04 50/87 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1746 0x04 50/87 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1747 0x04 50/87 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠

Phase Differential (87T)1748 0x04 87T Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1749 0x04 87T Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1750 0x04 87T Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠

Ground Differential (87G)Winding 1

1751 0x04 87G Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1752 0x04 87G Operate NOP(0), OP(1) -- R/O INT16U -- ⊠

Winding 21753 0x04 87G Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1754 0x04 87G Operate NOP(0), OP(1) -- R/O INT16U -- ⊠

Winding 31755 0x04 87G Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1756 0x04 87G Operate NOP(0), OP(1) -- R/O INT16U -- ⊠

V/Hz (24)1757 0x04 24 Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1758 0x04 24_1 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1759 0x04 24_2 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠

Phase Direction (67)1760 0x04 67 Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠1761 0x04 67 Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠1762 0x04 67 Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠

Ground Direction (67N)1763 0x04 67N Operate NOP(0), OP(1) -- R/O INT16U -- ⊠ ⊠ ⊠

Page 27: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 27 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

dF/dT (81R)1764 0x04 81R Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1765 0x04 81R_1 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1766 0x04 81R_2 Operate NOP(0), OP(1) -- R/O INT16U -- ⊠

Over Power (32P)1767 0x04 32P Phase A Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1768 0x04 32P Phase B Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1769 0x04 32P Phase C Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1770 0x04 32P Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1771 0x04 32P Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1772 0x04 32P Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠

Under Power (32U)1773 0x04 32U Phase A Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1774 0x04 32U Phase B Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1775 0x04 32U Phase C Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1776 0x04 32U Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1777 0x04 32U Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1778 0x04 32U Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠

Reactive Power (32Q)1779 0x04 32Q Phase A Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1780 0x04 32Q Phase B Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1781 0x04 32Q Phase C Pickup NOP(0), Pickup(1) -- R/O INT16U -- ⊠1782 0x04 32Q Phase A Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1783 0x04 32Q Phase B Operate NOP(0), OP(1) -- R/O INT16U -- ⊠1784 0x04 32Q Phase C Operate NOP(0), OP(1) -- R/O INT16U -- ⊠

Synchro Check (25)1785 0x04 25 Dead Source NOP(0), OP(1) -- R/O INT16U -- ⊠1786 0x04 25 SYNC OK NOP(0), OP(1) -- R/O INT16U -- ⊠1787 0x04 25 Dead Source or SYNC OK NOP(0), OP(1) -- R/O INT16U -- ⊠1788 ~ Reserved

Contact Input1800~ 1815 0x04 Contact Input#1 ~ #16 Off(0), ON(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1816 ~ Reserved

Page 28: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 28 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Contact Output1820~ 1835 0x04 Contact Output#1 ~ #16 DeEnergized(0),

Enegized(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1836 ~ Reserved

LED1840 System Error LED Off(0), On(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1841 Trip LED Off(0), On(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1842 Breaker Local/Remote Status Remote(0), Local(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1843 Breaker1 Status

Close(0), Open(1),Trouble(2),Setting error(3)

-- R/O INT16U -- ⊠ ⊠ ⊠ ⊠

1844 Breaker2 StatusClose(0), Open(1),Trouble(2),Setting error(3)

-- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1845~ 1852 LED#1 ~ #8 Off(0), On(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1853 ~ Reserved

Logic Component1860~ 1907 Logic Component#1 ~ #48 Off(0), On(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠1908 ~ Reserved

Counter(CNT)2000 Event Counter 0 ~ 1024 -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠2001 Waveform Counter 0 ~ 8 -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠2002 CB1 Trip Counter 0 ~ 65535 -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠2003 CB2 Trip Counter 0 ~ 65535 -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠2004 ~ Reserved

Logic Operand Easy-Logic Monitoring2100 ~ Logic Operand Status Data Off(0), On(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠~2499 Reserved

Page 29: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 29 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

System Setting2500~ 2503 0x06/0x10 Setting Flag -- -- W/O F700 -- ⊠ ⊠ ⊠ ⊠2504 0x06/0x10 Setting Group 1 ~ 4 1 W/O INT16U -- ⊠ ⊠ ⊠ ⊠

PasswordPassword

2505~ 2506 0x04 Setting Password 4 number character

"0000" ~ "9999" -- R/O F601 -- ⊠ ⊠ ⊠ ⊠2507~ 2508 0x04 Control Password 4 number character

"0000" ~ "9999" -- R/O F601 -- ⊠ ⊠ ⊠ ⊠Power SystemPower System

2509 0x04/0x06/0x10 Frequency 0 ~1 1 R/W F200 Hz ⊠ ⊠ ⊠ ⊠2510 0x04/0x06/0x10 PT Connection 0 ~2 1 R/W F203 -- ⊠ ⊠ ⊠2511 Reserved2512 0x04/0x06/0x10 Phase PT Primary 0.01 ~ 600.00 0.01 R/W INT16U kV ⊠ ⊠ ⊠ ⊠2513 0x04/0x06/0x10 Phase PT Secondary 50.0 ~ 250.0 0.1 R/W INT16U V ⊠ ⊠ ⊠ ⊠2514 Reserved2515 0x04/0x06/0x10 Ground PT Primary 0.01 ~ 600.00 0.01 R/W INT16U kV ⊠ ⊠ ⊠2516 0x04/0x06/0x10 Ground PT Secondary 50.0 ~ 250.0 0.1 R/W INT16U V ⊠ ⊠ ⊠2517 0x04/0x06/0x10 Phase CT Ratio 5 ~ 50000

1 ~ 5000051 R/W INT16U :5

:1 ⊠ ⊠ ⊠2518 0x04/0x06/0x10 Ground CT Ratio 5 ~ 50000

1 ~ 5000051 R/W INT16U :5

:1 ⊠ ⊠ ⊠2519 0x04/0x06/0x10 Setting Group 0 ~ 3 1 R/W F209 -- ⊠ ⊠ ⊠ ⊠

Motor2520 0x04/0x06/0x10 Start Current 1.00 ~ 50.00 0.01 R/W INT16U A ⊠2521 0x04/0x06/0x10 Stop Current 0.10 ~ 1.00 0.01 R/W INT16U A ⊠

Transformer2522 0x04/0x06/0x10 Type 0 ~ 11 1 R/W F260 -- ⊠2523 0x04/0x06/0x10 Phase Compensation 0 ~ 1 1 R/W F202 -- ⊠2524 0x04/0x06/0x10 W1-W2 Phase 0 ~ 11 1 R/W F261 ° lag ⊠2525 0x04/0x06/0x10 W1-W3 Phase 0 ~ 11 1 R/W F261 ° lag ⊠

Winding #12526 0x04/0x06/0x10 Nominal Voltage 0.01 ~ 600.00 0.01 R/W INT16U kV ⊠

Page 30: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 30 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

2527 0x04/0x06/0x10 Rated Load 0.01 ~ 600.00 0.01 R/W INT16U MVA ⊠2528 0x04/0x06/0x10 Phase CT Ratio 5 ~ 10000 5 R/W INT16U :5 ⊠2529 0x04/0x06/0x10 Ground CT Ratio 5 ~ 10000 5 R/W INT16U :5 ⊠2530 0x04/0x06/0x10 Grounding 0 ~ 1 1 F101 -- ⊠

Winding #22531 0x04/0x06/0x10 Nominal Voltage 0.01 ~ 600.00 0.01 R/W INT16U kV ⊠2532 0x04/0x06/0x10 Rated Load 0.01 ~ 600.00 0.01 R/W INT16U MVA ⊠2533 0x04/0x06/0x10 Phase CT Ratio 5 ~ 10000 5 R/W INT16U :5 ⊠2534 0x04/0x06/0x10 Ground CT Ratio 5 ~ 10000 5 R/W INT16U :5 ⊠2535 0x04/0x06/0x10 Grounding 0 ~ 1 1 F101 -- ⊠

Winding #32536 0x04/0x06/0x10 Nominal Voltage 0.01 ~ 600.00 0.01 R/W INT16U kV ⊠2537 0x04/0x06/0x10 Rated Load 0.01 ~ 600.00 0.01 R/W INT16U MVA ⊠2538 0x04/0x06/0x10 Phase CT Ratio 5 ~ 10000 5 R/W INT16U :5 ⊠2539 0x04/0x06/0x10 Ground CT Ratio 5 ~ 10000 5 R/W INT16U :5 ⊠2540 0x04/0x06/0x10 Grounding 0 ~ 1 1 R/W F101 -- ⊠2541 ~ Reserved

RTCRTC

2550 0x04/0x06/0x10 Year 2000 ~ 2100 1 R/W INT16U -- ⊠ ⊠ ⊠ ⊠2551 0x04/0x06/0x10 Month 1 ~ 12 1 R/W INT16U -- ⊠ ⊠ ⊠ ⊠2552 0x04/0x06/0x10 Day 1 ~ 31 1 R/W INT16U -- ⊠ ⊠ ⊠ ⊠2553 0x04/0x06/0x10 Hour 0 ~ 23 1 R/W INT16U -- ⊠ ⊠ ⊠ ⊠2554 0x04/0x06/0x10 Minute 0 ~ 59 1 R/W INT16U -- ⊠ ⊠ ⊠ ⊠2555 0x04/0x06/0x10 Second 0 ~ 59 1 R/W INT16U -- ⊠ ⊠ ⊠ ⊠2556 0x04/0x06/0x10 Millisecond 0 ~ 999 1 R/W INT16U -- ⊠ ⊠ ⊠ ⊠

Waveform RecordWaveform Record

2557 0x04/0x06/0x10 Type 0 ~ 2 1 R/WF214

Cycle⊠ ⊠

F215 ⊠F216 ⊠

2558 0x04/0x06/0x10 Trigger Source F410 1 R/W INT16U -- ⊠ ⊠ ⊠ ⊠2559 0x04/0x06/0x10 Trigger Position 0 ~ 99 1 R/W INT16U % ⊠ ⊠ ⊠ ⊠

Page 31: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 31 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

BreakerBreaker #1

2560 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠2561 ~ 2566 0x04/0x06/0x10 ID 12 ASCII characters -- R/W F600 -- ⊠ ⊠ ⊠ ⊠2567 0x04/0x06/0x10 Trip Pulse Time 0.1 ~ 5.0 0.1 R/W INT16U sec ⊠ ⊠ ⊠ ⊠2568 0x04/0x06/0x10 Close Pulse Time 0.1 ~ 5.0 0.1 R/W INT16U sec ⊠ ⊠ ⊠ ⊠2569 0x04/0x06/0x10 52a Input 0 ~ 16 1 R/W F220 -- ⊠ ⊠ ⊠ ⊠2570 0x04/0x06/0x10 52b Input 0 ~ 16 1 R/W F220 -- ⊠ ⊠ ⊠ ⊠2571 0x04/0x06/0x10 Key Control 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Breaker #22572 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠2573~ 2578 0x04/0x06/0x10 ID 12 ASCII characters -- R/W F600 -- ⊠ ⊠ ⊠ ⊠2579 0x04/0x06/0x10 Trip Pulse Time 0.1 ~ 5.0 0.1 R/W INT16U sec ⊠ ⊠ ⊠ ⊠2580 0x04/0x06/0x10 Close Pulse Time 0.1 ~ 5.0 0.1 R/W INT16U sec ⊠ ⊠ ⊠ ⊠2581 0x04/0x06/0x10 52a Input 0 ~ 16 1 R/W F220 -- ⊠ ⊠ ⊠ ⊠2582 0x04/0x06/0x10 52b Input 0 ~ 16 1 R/W F220 -- ⊠ ⊠ ⊠ ⊠2583 0x04/0x06/0x10 Key Control 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

CommunicationCOM #1

2584 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠2585 0x04/0x06/0x10 BPS 0 ~6 1 R/W F230 -- ⊠ ⊠ ⊠ ⊠2586 0x04/0x06/0x10 Slave Address Modbus (1 ~ 254)

DNP3.0 (1 ~ 65534) 1 R/W INT16U -- ⊠ ⊠ ⊠ ⊠2587 0x04/0x06/0x10 Protocol 0 ~ 1 1 R/W F231 -- ⊠ ⊠ ⊠ ⊠

COM #22588 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠2589 0x04/0x06/0x10 BPS 0 ~6 1 R/W F230 -- ⊠ ⊠ ⊠ ⊠2590 0x04/0x06/0x10 Slave Address Modbus : 1 ~ 254 1 R/W INT16U -- ⊠ ⊠ ⊠ ⊠2591 0x04/0x06/0x10 Protocol Fixed (1) 고정

[Modbus] 1 R/W INT16U -- ⊠ ⊠ ⊠ ⊠DNP3.0

2592 0x04/0x06/0x10 Tx Delay 0 ~ 65000 1 R/W INT16U msec ⊠ ⊠ ⊠ ⊠2593 0x04/0x06/0x10 Link Confirm 0 ~ 2 1 R/W F232 -- ⊠ ⊠ ⊠ ⊠

Page 32: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 32 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

2594 0x04/0x06/0x10 Link Retry 0 ~ 5 1 R/W INT16U -- ⊠ ⊠ ⊠ ⊠2595 0x04/0x06/0x10 Link Timeout 1 ~ 65000 1 R/W INT16U msec ⊠ ⊠ ⊠ ⊠2596 0x04/0x06/0x10 SBO Timeout 1 ~ 65000 1 R/W INT16U msec ⊠ ⊠ ⊠ ⊠2597 0x04/0x06/0x10 Write Time Interval 0 ~ 65000 1 R/W INT16U min ⊠ ⊠ ⊠ ⊠2598 0x04/0x06/0x10 Cold Restart 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

MonitoringPT Fuse Failure

2599 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠2600 0x04/0x06/0x10 Zero Sequence Voltage Pickup 10 ~ 190 1 R/W INT16U V ⊠ ⊠ ⊠2601 0x04/0x06/0x10 Zero Sequence Current Pickup 0.10 ~ 5.00 0.01 R/W INT16U A ⊠ ⊠ ⊠2602 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠

Current Sum2603 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠2604 0x04/0x06/0x10 Current Sum Threshold 0.10 ~ 10.00 0.01 R/W INT16U A ⊠ ⊠ ⊠2605 0x04/0x06/0x10 Current Sum Factor 0.10 ~ 0.90 0.01 R/W INT16U -- ⊠ ⊠ ⊠2606 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠

Voltage Balance2607 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠2608 0x04/0x06/0x10 Voltage Balance Threshold 10 ~ 150 1 R/W INT16U V ⊠ ⊠ ⊠2609 0x04/0x06/0x10 Voltage Balance Factor 0.10 ~ 0.90 0.01 R/W INT16U -- ⊠ ⊠ ⊠2610 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠

Current Balance2611 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠2612 0x04/0x06/0x10 Current Balance Threshold 0.10 ~ 10.00 0.01 R/W INT16U A ⊠ ⊠ ⊠2613 0x04/0x06/0x10 Current Balance Factor 0.10 ~ 0.90 0.01 R/W INT16U -- ⊠ ⊠ ⊠2614 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠

Trip Circuit Supervision2615 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠2616 0x04/0x06/0x10 Trip Relay Feedback Input 0 ~ 15 1 R/W F222 -- ⊠ ⊠ ⊠ ⊠

DemandDemand

2617 0x04/0x06/0x10 Demand Interval 0 ~ 2 1 R/W F205 -- ⊠ ⊠ ⊠2618 0x04/0x06/0x10 Demand Update Number 1 ~ 15 1 R/W INT16U -- ⊠ ⊠ ⊠2619 0x04/0x06/0x10 Demand Sync. Time 0 ~ 3 1 R/W F206 -- ⊠ ⊠ ⊠2620 ~ Reserved

Page 33: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 33 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Protection SettingDirection DetectionPhase Direction Detection (67)

2700 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠2701 0x04/0x06/0x10 Direction 0 ~ 2 1 R/W F305 -- ⊠ ⊠ ⊠2702 0x04/0x06/0x10 Maximum Torque Angle -90 ~ +90

Data -> 0 ~ 180 1 R/W INT16U deg ⊠ ⊠ ⊠2703 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠2704 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠

Ground Direction Detection (67N)2705 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠2706 0x04/0x06/0x10 Direction 0 ~ 2 1 R/W F305 -- ⊠ ⊠ ⊠2707 0x04/0x06/0x10 Polarizing 0 ~ 2 1 R/W F303 -- ⊠ ⊠ ⊠2708 0x04/0x06/0x10 Voltage Source 0 ~ 1 1 R/W F306 -- ⊠ ⊠ ⊠2709 0x04/0x06/0x10 Minimum Voltage 5 ~ 170 1 R/W INT16U V ⊠ ⊠ ⊠2710 0x04/0x06/0x10 Maximum Torque Angle -90 ~ +90

Data -> 0 ~ 180 1 R/W INT16U deg ⊠ ⊠ ⊠2711 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠2712 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠2713 ~ Reserved

Phase OvercurrentWinding 1Instantaneous Phase Overcurrent (50_1)

2720 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠2721 0x04/0x06/0x10 Pickup 1A : 0.10 ~ 20.00

5A : 0.50 ~ 100.00 0.01 R/W INT16U A ⊠ ⊠ ⊠ ⊠2722 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠ ⊠2723 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠2724 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Instantaneous Phase Overcurrent (50_2)2725 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Page 34: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 34 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

2726 0x04/0x06/0x10 Pickup 1A : 0.10 ~ 20.005A : 0.50 ~ 100.00 0.01 R/W INT16U A ⊠ ⊠ ⊠ ⊠

2727 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠ ⊠2728 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠2729 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Inverse Time Phase Overcurrent (51)2730 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠2731 0x04/0x06/0x10 Curve 0 ~ 13 1 R/W F307 -- ⊠ ⊠ ⊠ ⊠2732 0x04/0x06/0x10 Pickup 1A : 0.10 ~ 20.00

5A : 0.50 ~ 100.00 0.01 R/W INT16U A ⊠ ⊠ ⊠ ⊠2733 0x04/0x06/0x10 Multiplier 0.01 ~ 10.00 0.01 R/W INT16U -- ⊠ ⊠ ⊠ ⊠2734 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠2735 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Winding 2Instantaneous Phase Overcurrent (50_1)

2736 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠2737 0x04/0x06/0x10 Pickup 0.50 ~ 100.00 0.01 R/W INT16U A ⊠ ⊠2738 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠2739 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠2740 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠

Instantaneous Phase Overcurrent (50_2)2741 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠2742 0x04/0x06/0x10 Pickup 0.50 ~ 100.00 0.01 R/W INT16U A ⊠ ⊠2743 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠2744 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠2745 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠

Inverse Time Phase Overcurrent (51)2746 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠2747 0x04/0x06/0x10 Curve 0 ~ 13 1 R/W F307 -- ⊠ ⊠2748 0x04/0x06/0x10 Pickup 0.50 ~ 100.00 0.01 R/W INT16U A ⊠ ⊠

Page 35: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 35 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

2749 0x04/0x06/0x10 Multiplier 0.01 ~ 10.00 0.01 R/W INT16U -- ⊠ ⊠2750 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠2751 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠

Winding 3Instantaneous Phase Overcurrent (50_1)

2752 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠2753 0x04/0x06/0x10 Pickup 0.50 ~ 100.00 0.01 R/W INT16U A ⊠2754 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠2755 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠2756 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Instantaneous Phase Overcurrent (50_2)2757 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠2758 0x04/0x06/0x10 Pickup 0.50 ~ 100.00 0.01 R/W INT16U A ⊠2759 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠2760 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠2761 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Inverse Time Phase Overcurrent (51)2762 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠2763 0x04/0x06/0x10 Curve 0 ~ 13 1 R/W F307 -- ⊠2764 0x04/0x06/0x10 Pickup 0.50 ~ 100.00 0.01 R/W INT16U A ⊠2765 0x04/0x06/0x10 Multiplier 0.01 ~ 10.00 0.01 R/W INT16U -- ⊠2766 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠2767 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠2768 ~ Reserved

Ground OvercurrentWinding 1Instantaneous Ground Overcurrent (50N_1)

2780 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠2781 0x04/0x06/0x10 Pickup 1A : 0.02 ~ 20.00

5A : 0.10 ~ 100.00 0.01 R/W INT16U A ⊠ ⊠ ⊠ ⊠2782 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠ ⊠

Page 36: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 36 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

2783 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠2784 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Instantaneous Ground Overcurrent (50N_2)2785 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠2786 0x04/0x06/0x10 Pickup 1A : 0.02 ~ 20.00

5A : 0.10 ~ 100.00 0.01 R/W INT16U A ⊠ ⊠ ⊠ ⊠2787 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠ ⊠2788 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠2789 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Inverse Time Ground Overcurrent (51N)2790 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠2791 0x04/0x06/0x10 Curve 0 ~ 13 1 R/W F307 -- ⊠ ⊠ ⊠ ⊠2792 0x04/0x06/0x10 Pickup 1A : 0.02 ~ 20.00

5A : 0.10 ~ 100.00 0.01 R/W INT16U A ⊠ ⊠ ⊠ ⊠2793 0x04/0x06/0x10 Multiplier 0.01 ~ 10.00 0.01 R/W INT16U -- ⊠ ⊠ ⊠ ⊠2794 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠2795 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Winding 2Instantaneous Ground Overcurrent (50N_1)

2796 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠2797 0x04/0x06/0x10 Pickup 0.10 ~ 100.00 0.01 R/W INT16U A ⊠ ⊠2798 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠2799 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠2800 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠

Instantaneous Ground Overcurrent (50N_2)2801 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠2802 0x04/0x06/0x10 Pickup 0.10 ~ 100.00 0.01 R/W INT16U A ⊠ ⊠2803 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠2804 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠2805 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠

Page 37: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 37 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Inverse Time Ground Overcurrent (51N)2806 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠2807 0x04/0x06/0x10 Curve 0 ~ 13 1 R/W F307 -- ⊠ ⊠2808 0x04/0x06/0x10 Pickup 0.10 ~ 100.00 0.01 R/W INT16U A ⊠ ⊠2809 0x04/0x06/0x10 Multiplier 0.01 ~ 10.00 0.01 R/W INT16U -- ⊠ ⊠2810 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠2811 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠

Winding 3Instantaneous Ground Overcurrent (50N_1)

2812 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠2813 0x04/0x06/0x10 Pickup 0.10 ~ 100.00 0.01 R/W INT16U A ⊠2814 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠2815 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠2816 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Instantaneous Ground Overcurrent (50N_2)2817 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠2818 0x04/0x06/0x10 Pickup 0.10 ~ 100.00 0.01 R/W INT16U A ⊠2819 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠2820 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠2821 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Inverse Time Ground Overcurrent (51N)2822 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠2823 0x04/0x06/0x10 Curve 0 ~ 13 1 R/W F307 -- ⊠2824 0x04/0x06/0x10 Pickup 0.10 ~ 100.00 0.01 R/W INT16U A ⊠2825 0x04/0x06/0x10 Multiplier 0.01 ~ 10.00 0.01 R/W INT16U -- ⊠2826 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠2827 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠2828 ~ Reserved

Sensitive Directional Ground Overcurrent (67Ns)2840 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠

Page 38: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 38 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

2841 0x04/0x06/0x10 Direction 0 ~ 2 1 R/W F300 -- ⊠ ⊠2842 0x04/0x06/0x10 Polarizing Voltage Source 0 ~ 1 1 R/W F304 -- ⊠ ⊠2843 0x04/0x06/0x10 Voltage Pickup 5 ~ 170 1 R/W INT16U V ⊠ ⊠2844 0x04/0x06/0x10 Current Pickup 1 ~ 100 1 R/W INT16U mA ⊠ ⊠2845 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠2846 0x04/0x06/0x10 Maximum Torque Angle -90 ~ +90

Data -> 0 ~ 180 1 R/W INT16U deg ⊠ ⊠2847 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠2848 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠

Thermal ProtectionThermal Overload (49)

2849 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠2850 0x04/0x06/0x10 K-Factor 0.10 ~ 4.00 0.01 R/W INT16U -- ⊠ ⊠2851 0x04/0x06/0x10 Time Constant 1.0 ~ 999.9 0.1 R/W INT16U min ⊠ ⊠2852 0x04/0x06/0x10 Cooling Time Factor 1.0 ~10.0 0.1 R/W INT16U -- ⊠2853 0x04/0x06/0x10 Thermal Alarm 50 ~ 100 1 R/W INT16U % ⊠ ⊠2854 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠2855 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠2856 ~ Reserved

Under Current (37)2888 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠2889 0x04/0x06/0x10 Pickup 1A : 0.02 ~ 1.00

5A : 0.10 ~ 5.00 0.01 R/W INT16U A ⊠ ⊠2890 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 180.00 0.01 R/W INT16U sec ⊠ ⊠2891 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠2892 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠2893 ~ Reserved

Negative Phase SequenceWinding 1Definite Time 1 (46_1)

2900 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠2901 0x04/0x06/0x10 Pickup Current of Ineg 1A : 0.10 ~ 20.00

5A : 0.50 ~ 100.00 0.01 R/W INT16U A ⊠ ⊠ ⊠ ⊠2902 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠ ⊠2903 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠

Page 39: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 39 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

2904 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠Definite Time 2 (46_2)

2905 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠2906 0x04/0x06/0x10 Pickup Current of Ineg 1A : 0.10 ~ 20.00

5A : 0.50 ~ 100.00 0.01 R/W INT16U A ⊠ ⊠ ⊠ ⊠2907 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠ ⊠2908 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠2909 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Inverse Time (46T)2910 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠2911 0x04/0x06/0x10 Curve 0 ~ 13 1 R/W F307 -- ⊠ ⊠ ⊠ ⊠2912 0x04/0x06/0x10 Pickup Current of Ineg 1A : 0.10 ~ 20.00

5A : 0.50 ~ 100.00 0.01 R/W INT16U A ⊠ ⊠ ⊠ ⊠2913 0x04/0x06/0x10 Time Multiplier 0.01 ~ 10.00 0.01 R/W INT16U -- ⊠ ⊠ ⊠ ⊠2914 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠2915 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Winding 2Definite Time 1 (46_1)

2916 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠2917 0x04/0x06/0x10 Pickup Current of Ineg 0.50 ~ 100.00 0.01 R/W INT16U A ⊠2918 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠2919 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠2920 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Definite Time 2 (46_2)2921 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠2922 0x04/0x06/0x10 Pickup Current of Ineg 0.50 ~ 100.00 0.01 R/W INT16U A ⊠2923 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠2924 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠2925 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Inverse Time (46T)2926 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠2927 0x04/0x06/0x10 Curve 0 ~ 13 1 R/W F307 -- ⊠2928 0x04/0x06/0x10 Pickup Current of Ineg 0.50 ~ 100.00 0.01 R/W INT16U A ⊠2929 0x04/0x06/0x10 Time Multiplier 0.01 ~ 10.00 0.01 R/W INT16U -- ⊠2930 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠

Page 40: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 40 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

2931 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠Winding 3Definite Time 1 (46_1)

2932 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠2933 0x04/0x06/0x10 Pickup Current of Ineg 0.50 ~ 100.00 0.01 R/W INT16U A ⊠2934 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠2935 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠2936 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Definite Time 2 (46_2)2937 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠2938 0x04/0x06/0x10 Pickup Current of Ineg 0.50 ~ 100.00 0.01 R/W INT16U A ⊠2939 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠2940 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠2941 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Inverse Time (46T)2942 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠2943 0x04/0x06/0x10 Curve 0 ~ 13 1 R/W F307 -- ⊠2944 0x04/0x06/0x10 Pickup Current of Ineg 0.50 ~ 100.00 0.01 R/W INT16U A ⊠2945 0x04/0x06/0x10 Time Multiplier 0.01 ~ 10.00 0.01 R/W INT16U -- ⊠2946 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠2947 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Phase Unbalance Protection (46U)2948 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠2949 0x04/0x06/0x10 Pickup Current of Ineg/Ipos 2 ~ 80 1 R/W INT16U % ⊠ ⊠ ⊠2950 0x04/0x06/0x10 Minimum Current of Ipos 1A : 0.10 ~ 1.00

5A : 0.50 ~ 5.00 0.01 R/W INT16U A ⊠ ⊠ ⊠2951 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠2952 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠2953 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠2954 ~ Reserved

Phase OvervoltagePhase Overvoltage1 (59_1)

3000 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠3001 0x04/0x06/0x10 Pickup Voltage 5 ~ 170 1 R/W INT16U V ⊠ ⊠ ⊠ ⊠

Page 41: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 41 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

3002 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠ ⊠3003 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠3004 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Phase Overvoltage2 (59_2)3005 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠3006 0x04/0x06/0x10 Mode 0 ~ 1 1 R/W F310 -- ⊠ ⊠ ⊠ ⊠3007 0x04/0x06/0x10 Pickup Voltage 5 ~ 170 1 R/W INT16U V ⊠ ⊠ ⊠ ⊠3008 0x04/0x06/0x10 Time Multiplier 0.01 ~ 10.00 0.01 R/W INT16U -- ⊠ ⊠ ⊠ ⊠3009 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠ ⊠3010 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠3011 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Phase UndervoltagePhase Undervoltage1 (27_1)

3012 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠3013 0x04/0x06/0x10 Pickup Voltage 5 ~ 170 1 R/W INT16U V ⊠ ⊠ ⊠ ⊠3014 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠ ⊠3015 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠3016 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Phase Undervoltage2 (27_2)3017 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠3018 0x04/0x06/0x10 Mode 0 ~ 1 1 R/W F310 -- ⊠ ⊠ ⊠ ⊠3019 0x04/0x06/0x10 Pickup Voltage 5 ~ 170 1 R/W INT16U V ⊠ ⊠ ⊠ ⊠3020 0x04/0x06/0x10 Time Multiplier 0.01 ~ 10.00 0.01 R/W INT16U -- ⊠ ⊠ ⊠ ⊠3021 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠ ⊠3022 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠3023 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Residual / Ground OvervoltageResidual / Ground Overvoltage1 (59G_1)

3024 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠3025 0x04/0x06/0x10 Voltage Source 0 ~ 1 1 R/W F306 -- ⊠ ⊠3026 0x04/0x06/0x10 Pickup Voltage 5 ~ 170 1 R/W INT16U V ⊠ ⊠3027 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠3028 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠3029 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠

Page 42: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 42 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Residual / Ground Overvoltage2 (59G_2)3030 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠3031 0x04/0x06/0x10 Voltage Source 0 ~ 1 1 R/W F306 -- ⊠ ⊠3032 0x04/0x06/0x10 Mode 0 ~ 1 1 R/W F312 -- ⊠ ⊠3033 0x04/0x06/0x10 Pickup Voltage 5 ~ 170 1 R/W INT16U V ⊠ ⊠3034 0x04/0x06/0x10 Time Multiplier 0.01 ~ 10.00 0.01 R/W INT16U -- ⊠ ⊠3035 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠3036 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠3037 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠

Negative Phase Sequence Overvoltage (47)3038 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠3039 0x04/0x06/0x10 Pickup Voltage 5 ~ 170 1 R/W INT16U V ⊠ ⊠ ⊠3040 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠3041 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠3042 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠3043 ~ Reserved

Under / Over FrequencyUnder/Over Frequency1 (81U/O_1)

3050 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠3051 0x04/0x06/0x10 Mode 0 ~ 1 1 R/W F330 -- ⊠ ⊠3052 0x04/0x06/0x10 Pickup Frequency 45.00 ~ 65.00 0.01 R/W INT16U Hz ⊠ ⊠3053 0x04/0x06/0x10 Pickup Undervoltage 5 ~ 170 1 R/W INT16U V ⊠ ⊠3054 0x04/0x06/0x10 dF/dT Pickup -10.0 ~ +10.0

Data -> 0.0 ~ 20.0 0.1 R/W INT16U Hz/s ⊠ ⊠3055 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 180.00 0.01 R/W INT16U sec ⊠ ⊠3056 0x04/0x06/0x10 Undervoltage Block 0 ~ 1 1 R/W F101 -- ⊠ ⊠3057 0x04/0x06/0x10 dF/dT Block 0 ~ 1 1 R/W F101 -- ⊠ ⊠3058 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠3059 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠

Under/Over Frequency2 (81U/O_2)3060 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠

Page 43: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 43 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

3061 0x04/0x06/0x10 Mode 0 ~ 1 1 R/W F330 -- ⊠ ⊠3062 0x04/0x06/0x10 Pickup Frequency 45.00 ~ 65.00 0.01 R/W INT16U Hz ⊠ ⊠3063 0x04/0x06/0x10 Pickup Undervoltage 5 ~ 170 1 R/W INT16U V ⊠ ⊠3064 0x04/0x06/0x10 dF/dT Pickup -10.0 ~ +10.0

Data -> 0.0 ~ 20.0 0.1 R/W INT16U Hz/s ⊠ ⊠3065 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 180.00 0.01 R/W INT16U sec ⊠ ⊠3066 0x04/0x06/0x10 Undervoltage Block 0 ~ 1 1 R/W F101 -- ⊠ ⊠3067 0x04/0x06/0x10 dF/dT Block 0 ~ 1 1 R/W F101 -- ⊠ ⊠3068 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠3069 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠

Under/Over Frequency3 (81U/O_3)3070 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠3071 0x04/0x06/0x10 Mode 0 ~ 1 1 R/W F330 -- ⊠ ⊠3072 0x04/0x06/0x10 Pickup Frequency 45.00 ~ 65.00 0.01 R/W INT16U Hz ⊠ ⊠3073 0x04/0x06/0x10 Pickup Undervoltage 5 ~ 170 1 R/W INT16U V ⊠ ⊠3074 0x04/0x06/0x10 dF/dT Pickup -10.0 ~ +10.0

Data -> 0.0 ~ 20.0 0.1 R/W INT16U Hz/s ⊠ ⊠3075 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 180.00 0.01 R/W INT16U sec ⊠ ⊠3076 0x04/0x06/0x10 Undervoltage Block 0 ~ 1 1 R/W F101 -- ⊠ ⊠3077 0x04/0x06/0x10 dF/dT Block 0 ~ 1 1 R/W F101 -- ⊠ ⊠3078 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠3079 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠

Auto - Reclosing 3080 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3081 0x04/0x06/0x10 Shot Number 1 ~ 4 1 R/W INT16U -- ⊠3082 0x04/0x06/0x10 Prepare Condition 0 ~ ? 1 R/W F410 -- ⊠3083 0x04/0x06/0x10 Cycle Start Condition 0 ~ ? 1 R/W F410 -- ⊠3084 0x04/0x06/0x10 Cycle Stop Condition 0 ~ ? 1 R/W F410 -- ⊠3085 0x04/0x06/0x10 Prepare Time 0.05 ~ 200.00 0.01 R/W INT16U sec ⊠3086 0x04/0x06/0x10 Discrimination Time 0.01 ~ 5.00 0.01 R/W INT16U sec ⊠3087 0x04/0x06/0x10 Reclaim Time 0.01 ~ 350.00 0.01 R/W INT16U sec ⊠3088 0x04/0x06/0x10 1st Shot Time 0.01 ~ 300.00 0.01 R/W INT16U sec ⊠3089 0x04/0x06/0x10 2nd Shot Time 0.01 ~ 300.00 0.01 R/W INT16U sec ⊠3090 0x04/0x06/0x10 3rd Shot Time 0.01 ~ 300.00 0.01 R/W INT16U sec ⊠

Page 44: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 44 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

3091 0x04/0x06/0x10 4th Shot Time 0.01 ~ 300.00 0.01 R/W INT16U sec ⊠3092 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3093 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠3094 ~ Reserved

Circuit Break Failure(50BF)3100 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠3101 0x04/0x06/0x10 Trip Relay Input 0 ~ 21 1 R/W F224 -- ⊠ ⊠ ⊠ ⊠3102 0x04/0x06/0x10 Pickup Current 1A : 0.04 ~ 1.00

5A : 0.20 ~ 5.00 0.01 R/W INT16U A ⊠ ⊠ ⊠ ⊠3103 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 6.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠ ⊠3104 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠3105 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Cold Load Pick-up3106 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠3107 0x04/0x06/0x10 Pickup Current 1A : 0.02 ~ 1.00

5A : 0.10 ~ 5.00 0.01 R/W INT16U A ⊠ ⊠ ⊠ ⊠3108 0x04/0x06/0x10 Operating Delay Time 0 ~ 1000 1 R/W INT16U sec ⊠ ⊠ ⊠ ⊠3109 0x04/0x06/0x10 Reset Delay Time 0 ~ 1000 1 R/W INT16U sec ⊠ ⊠ ⊠ ⊠3110 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠3111 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠

Inrush Detection (I2f/I1f)3112 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠3113 0x04/0x06/0x10 2nd Harmonic of I2f/I1f 10 ~ 100 1 R/W INT16U % ⊠ ⊠ ⊠ ⊠3114 0x04/0x06/0x10 Pickup Current 1A : 0.02 ~ 0.50

5A : 0.10 ~ 2.50 0.01 R/W INT16U A ⊠ ⊠ ⊠ ⊠3115 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 6.00 0.01 R/W INT16U sec ⊠ ⊠ ⊠ ⊠3116 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠ ⊠ ⊠ ⊠3117 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠ ⊠ ⊠ ⊠3118 ~ Reserved

Motor ProtectionStart-up Monitoring / Stall Protection for Motor (48)

3130 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3131 0x04/0x06/0x10 Start-up Current 5.00 ~ 90.00 0.01 R/W INT16U A ⊠3132 0x04/0x06/0x10 Start-up Time 1.0 ~ 180.0 0.1 R/W INT16U sec ⊠

Page 45: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 45 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

3133 0x04/0x06/0x10 Locked Rotor Time 0.5 ~ 180.0 0.1 R/W INT16U sec ⊠3134 0x04/0x06/0x10 Speed Switch Input 0 ~ 16 1 R/W F220 -- ⊠3135 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3136 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Start Inhibit for Motor (66/68)3137 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3138 0x04/0x06/0x10 Start Monitoring Time 5 ~ 120 1 R/W INT16U min ⊠3139 0x04/0x06/0x10 Cold Start Number 1 ~ 5 1 R/W INT16U -- ⊠3140 0x04/0x06/0x10 Hot Start Number 0 ~ 5 1 R/W INT16U -- ⊠3141 0x04/0x06/0x10 Consecutive Start Interval 1 ~ 120 1 R/W INT16U min ⊠3142 0x04/0x06/0x10 Emergency Start Switch Input 0 ~ 16 1 R/W F220 -- ⊠3143 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3144 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠3145 ~ Reserved

Phase DifferentialInstantaneous Differential (50/87)

3150 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3151 0x04/0x06/0x10 Differential Current Pickup 10 ~ 150 1 R/W INT16U A ⊠3152 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠3153 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3154 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Phase Differential (87T)3155 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3156 0x04/0x06/0x10 Minimum Differential Current 0.20 ~ 2.50 0.01 R/W INT16U A ⊠3157 0x04/0x06/0x10 Slope 1 5 ~ 100 1 R/W INT16U % ⊠3158 0x04/0x06/0x10 Slope 2 20 ~ 200 1 R/W INT16U % ⊠3159 0x04/0x06/0x10 Knee Point 5.0 ~ 100.0 0.1 R/W INT16U A ⊠3160 0x04/0x06/0x10 Harmonic Restraint 0 ~ 3 1 R/W F262 -- ⊠3161 0x04/0x06/0x10 2nd Harmonics of I2f/I1f 5.0 ~ 40.0 0.1 R/W INT16U % ⊠3162 0x04/0x06/0x10 5th Harmonics of I5f/I1f 5.0 ~ 40.0 0.1 R/W INT16U % ⊠3163 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠3164 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3165 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Page 46: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 46 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Ground DifferentialWinding 1Ground Differential (W1_87G)

3166 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3167 0x04/0x06/0x10 Minimum Differential Current 0.20 ~ 2.50 0.01 R/W INT16U A ⊠3168 0x04/0x06/0x10 Slope 5 ~ 100 1 R/W INT16U % ⊠3169 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠3170 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3171 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Winding 2Ground Differential (W2_87G)

3172 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3173 0x04/0x06/0x10 Minimum Differential Current 0.20 ~ 2.50 0.01 R/W INT16U A ⊠3174 0x04/0x06/0x10 Slope 5 ~ 100 1 R/W INT16U % ⊠3175 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠3176 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3177 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Winding 3Ground Differential (W3_87G)

3178 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3179 0x04/0x06/0x10 Minimum Differential Current 0.20 ~ 2.50 0.01 R/W INT16U A ⊠3180 0x04/0x06/0x10 Slope 5 ~ 100 1 R/W INT16U % ⊠3181 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠3182 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3183 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠3184 ~ Reserved

Overexcitation ProtectionVolts Per Herts 1 (24_1)

3200 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3201 0x04/0x06/0x10 V/Hz Pickup 1.00 ~ 4.00 0.01 R/W INT16U V/Hz ⊠3202 0x04/0x06/0x10 Minimum Voltage 5 ~ 50 1 R/W INT16U V ⊠3203 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 180.00 0.01 R/W INT16U sec ⊠3204 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3205 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Page 47: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 47 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Volts Per Herts 1 (24_2)3206 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3207 0x04/0x06/0x10 V/Hz Pickup 1.00 ~ 4.00 0.01 R/W INT16U V/Hz ⊠3208 0x04/0x06/0x10 Minimum Voltage 5 ~ 50 1 R/W INT16U V ⊠3209 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 180.00 0.01 R/W INT16U Cycle ⊠3210 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3211 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Rate of Change of FrequencyRate of Change of Frequency (81R_1)

3212 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3213 0x04/0x06/0x10 dF/dT Pickup -10.0 ~ +10.0

Data -> 0.0 ~ 20.0 0.1 R/W INT16U Hz/s ⊠3214 0x04/0x06/0x10 Minimum Voltage 5 ~ 170 1 R/W INT16U V ⊠3215 0x04/0x06/0x10 Operating Delay Time 3 ~ 60 1 R/W INT16U Cycle ⊠3216 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3217 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Rate of Change of Frequency (81R_2)3218 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3219 0x04/0x06/0x10 dF/dT Pickup -10.0 ~ +10.0

Data -> 0.0 ~ 20.0 0.1 R/W INT16U Hz/s ⊠3220 0x04/0x06/0x10 Minimum Voltage 5 ~ 170 1 R/W INT16U V ⊠3221 0x04/0x06/0x10 Operating Delay Time 3 ~ 60 1 R/W INT16U Cycle ⊠3222 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3223 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Over PowerOver Power (32P)

3224 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3225 0x04/0x06/0x10 Mode 0 ~ 1 1 R/W F322 -- ⊠3226 0x04/0x06/0x10 Polarity 0 ~ 1 1 R/W F320 -- ⊠3227 0x04/0x06/0x10 Curve 0 ~ 2 1 R/W F321 -- ⊠3228 0x04/0x06/0x10 Pickup Power 3 ~ 1500 1 R/W INT16U W ⊠3229 0x04/0x06/0x10 Time Multiplier 0.01 ~ 10.00 0.01 R/W INT16U -- ⊠3230 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠

Page 48: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 48 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

3231 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3232 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Under PowerUnder Power (32U)

3233 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3234 0x04/0x06/0x10 Mode 0 ~ 1 1 R/W F322 -- ⊠3235 0x04/0x06/0x10 Polarity 0 ~ 1 1 R/W F320 -- ⊠3236 0x04/0x06/0x10 Curve 0 ~ 2 1 R/W F321 -- ⊠3237 0x04/0x06/0x10 Pickup Power 3 ~ 900 1 R/W INT16U W ⊠3238 0x04/0x06/0x10 Time Multiplier 0.01 ~ 10.00 0.01 R/W INT16U -- ⊠3239 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠3240 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3241 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Reactive PowerReactive Power (32Q)

3242 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3243 0x04/0x06/0x10 Polarity 0 ~ 1 1 R/W F320 -- ⊠3244 0x04/0x06/0x10 Curve 0 ~ 2 1 R/W F321 -- ⊠3245 0x04/0x06/0x10 Pickup Power 3 ~ 1500 1 R/W INT16U Var ⊠3246 0x04/0x06/0x10 Time Multiplier 0.01 ~ 10.00 0.01 R/W INT16U -- ⊠3247 0x04/0x06/0x10 Operating Delay Time 0.00 ~ 60.00 0.01 R/W INT16U sec ⊠3248 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3249 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠

Synchro CheckSynchro Check (25)

3250 0x04/0x06/0x10 Function 0 ~ 1 1 R/W F100 -- ⊠3251 0x04/0x06/0x10 Dead Source Condition 0 ~ 4 1 R/W F370 -- ⊠3252 0x04/0x06/0x10 Angle Difference 0 ~ 99 1 R/W INT16U deg ⊠3253 0x04/0x06/0x10 Voltage Difference 0 ~ 50 1 R/W INT16U V ⊠3254 0x04/0x06/0x10 Frequency Slip 0.00 ~ 2.00 0.01 R/W INT16U Hz ⊠3255 0x04/0x06/0x10 Dead Voltage 5 ~ 170 1 R/W INT16U V ⊠3256 0x04/0x06/0x10 Live Voltage 5 ~ 170 1 R/W INT16U V ⊠3257 0x04/0x06/0x10 Block 0 ~ ? 1 R/W F410 -- ⊠3258 0x04/0x06/0x10 Event 0 ~ 1 1 R/W F100 -- ⊠3259 ~ Reserved

Page 49: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 49 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Float measurement (AI)M-3000 / F-3000 Magnitude(Float)Phase Voltage magnitude

5000 0x04 Phase A Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠ ⊠5002 0x04 Phase B Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠ ⊠5004 0x04 Phase C Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠ ⊠5006 0x04 Phase N Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠ ⊠5008 0x04 3-Phase Average Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠ ⊠

Line to Line Voltage magnitude5010 0x04 Phase AB Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠ ⊠5012 0x04 Phase BC Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠ ⊠5014 0x04 Phase CA Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠ ⊠

Phase Current magnitude5016 0x04 Phase A Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠ ⊠5018 0x04 Phase B Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠ ⊠5020 0x04 Phase C Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠ ⊠5022 0x04 Phase N Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠ ⊠5024 0x04 3-Phase Average Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠ ⊠5026 0x04 Sensitive Ground Current 0.0 ~ 999999.9 -- R/O FLOAT mA ⊠ ⊠

Power 5028 0x04 Phase A Watt -1012 ~ 1012 -- R/O FLOAT W ⊠ ⊠5030 0x04 Phase B Watt -1012 ~ 1012 -- R/O FLOAT W ⊠ ⊠5032 0x04 Phase C Watt -1012 ~ 1012 -- R/O FLOAT W ⊠ ⊠5034 0x04 3 Phase Watt -1012 ~ 1012 -- R/O FLOAT W ⊠ ⊠5036 0x04 Phase A Var -1012 ~ 1012 -- R/O FLOAT Var ⊠ ⊠5038 0x04 Phase B Var -1012 ~ 1012 -- R/O FLOAT Var ⊠ ⊠5040 0x04 Phase C Var -1012 ~ 1012 -- R/O FLOAT Var ⊠ ⊠5042 0x04 3 Phase Var -1012 ~ 1012 -- R/O FLOAT Var ⊠ ⊠5044 0x04 Phase A VA 0 ~ 1012 -- R/O FLOAT VA ⊠ ⊠5046 0x04 Phase B VA 0 ~ 1012 -- R/O FLOAT VA ⊠ ⊠5048 0x04 Phase C VA 0 ~ 1012 -- R/O FLOAT VA ⊠ ⊠5050 0x04 3 Phase VA 0 ~ 1012 -- R/O FLOAT VA ⊠ ⊠

Power Factor5052 0x04 Phase A Power Factor -1.00 ~ 1.00 -- R/O FLOAT -- ⊠ ⊠5054 0x04 Phase B Power Factor -1.00 ~ 1.00 -- R/O FLOAT -- ⊠ ⊠

Page 50: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 50 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

5056 0x04 Phase C Power Factor -1.00 ~ 1.00 -- R/O FLOAT -- ⊠ ⊠5058 0x04 3 Phase Power Factor -1.00 ~ 1.00 -- R/O FLOAT -- ⊠ ⊠

Energy5060 0x04 kW-Hour Import 0 ~ 4294967295 -- R/O FLOAT kWh ⊠ ⊠5062 0x04 kW-Hour Export 0 ~ 4294967295 -- R/O FLOAT kWh ⊠ ⊠5064 0x04 kVar-Hour Import 0 ~ 4294967295 -- R/O FLOAT kVARh ⊠ ⊠5066 0x04 kVar-Hour Export 0 ~ 4294967295 -- R/O FLOAT kVARh ⊠ ⊠5068 0x04 kVA-Hour 0 ~ 4294967295 -- R/O FLOAT kVAh ⊠ ⊠

Sequence Voltage magnitude5070 0x04 Positive Sequence Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠ ⊠5072 0x04 Negative Sequence Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠ ⊠5074 0x04 Zero Sequence Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠ ⊠

Sequence Current magnitude5076 0x04 Positive Sequence Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠ ⊠5078 0x04 Negative Sequence Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠ ⊠5080 0x04 Zero Sequence Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠ ⊠

Frequency5082 0x04 Frequency(VA) 0.00 ~ 80.00 -- R/O FLOAT Hz ⊠ ⊠

Demand Phase Current magnitude5084 0x04 Phase A Demand Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠ ⊠5086 0x04 Phase B Demand Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠ ⊠5088 0x04 Phase C Demand Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠ ⊠

Demand 3 Phase Power5090 0x04 3 Phase Demand Watt -1012 ~ 1012 -- R/O FLOAT W ⊠ ⊠5092 0x04 3 Phase Demand Var -1012 ~ 1012 -- R/O FLOAT VAR ⊠ ⊠5094 0x04 3 Phase Demand VA 0 ~ 1012 -- R/O FLOAT VA ⊠ ⊠

Voltage THD5096 0x04 Phase A Voltage THD 0.0 ~ 100.0 -- R/O FLOAT % ⊠ ⊠5098 0x04 Phase B Voltage THD 0.0 ~ 100.0 -- R/O FLOAT % ⊠ ⊠5100 0x04 Phase C Voltage THD 0.0 ~ 100.0 -- R/O FLOAT % ⊠ ⊠

Current THD5102 0x04 Phase A Current THD 0.0 ~ 100.0 -- R/O FLOAT % ⊠ ⊠5104 0x04 Phase B Current THD 0.0 ~ 100.0 -- R/O FLOAT % ⊠ ⊠5106 0x04 Phase C Current THD 0.0 ~ 100.0 -- R/O FLOAT % ⊠ ⊠

Page 51: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 51 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Thermal Overload5108 0x04 Thermal Overload 0.0 ~ 250.0 -- R/O FLOAT % ⊠ ⊠

M-3000 / F-3000 Angle(Float)Phase Voltage angle

5110 0x04 Phase A Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠5112 0x04 Phase B Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠5114 0x04 Phase C Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠5116 0x04 Phase N Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠

Line to Line Voltage angle5118 0x04 Phase AB Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠5120 0x04 Phase BC Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠5122 0x04 Phase CA Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠

Phase Current angle5124 0x04 Phase A Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠5126 0x04 Phase B Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠5128 0x04 Phase C Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠5130 0x04 Phase N Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠5132 0x04 Sensitive Ground Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠

Sequence Voltage angle5134 0x04 Positive Sequence Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠5136 0x04 Negative Sequence Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠5138 0x04 Zero Sequence Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠

Sequence Current angle5140 0x04 Positive Sequence Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠5142 0x04 Negative Sequence Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠5144 0x04 Zero Sequence Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠ ⊠5146 ~ Reserved

Page 52: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 52 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

DG-3000 Magnitude(Float)Phase Voltage magnitude

5200 0x04 Phase A Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠5202 0x04 Phase B Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠5204 0x04 Phase C Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠5206 0x04 Phase Aa Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠5208 0x04 3-Phase Average Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠

Line to Line Voltage magnitude5210 0x04 Phase AB Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠5212 0x04 Phase BC Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠5214 0x04 Phase CA Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠

Phase Current magnitude5216 0x04 Phase A Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5218 0x04 Phase B Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5220 0x04 Phase C Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5222 0x04 Phase N Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5224 0x04 3-Phase Average Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠

Power 5226 0x04 Phase A Watt -1012 ~ 1012 -- R/O FLOAT W ⊠5228 0x04 Phase B Watt -1012 ~ 1012 -- R/O FLOAT W ⊠5230 0x04 Phase C Watt -1012 ~ 1012 -- R/O FLOAT W ⊠5232 0x04 3 Phase Watt -1012 ~ 1012 -- R/O FLOAT W ⊠5234 0x04 Phase A Var -1012 ~ 1012 -- R/O FLOAT Var ⊠5236 0x04 Phase B Var -1012 ~ 1012 -- R/O FLOAT Var ⊠5238 0x04 Phase C Var -1012 ~ 1012 -- R/O FLOAT Var ⊠5240 0x04 3 Phase Var -1012 ~ 1012 -- R/O FLOAT Var ⊠5242 0x04 Phase A VA 0 ~ 1012 -- R/O FLOAT VA ⊠5244 0x04 Phase B VA 0 ~ 1012 -- R/O FLOAT VA ⊠5246 0x04 Phase C VA 0 ~ 1012 -- R/O FLOAT VA ⊠5248 0x04 3 Phase VA 0 ~ 1012 -- R/O FLOAT VA ⊠

Power Factor5250 0x04 Phase A Power Factor -1.00 ~ 1.00 -- R/O FLOAT -- ⊠5252 0x04 Phase B Power Factor -1.00 ~ 1.00 -- R/O FLOAT -- ⊠5254 0x04 Phase C Power Factor -1.00 ~ 1.00 -- R/O FLOAT -- ⊠5256 0x04 3 Phase Power Factor -1.00 ~ 1.00 -- R/O FLOAT -- ⊠

Page 53: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 53 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Energy5258 0x04 kW-Hour Import 0 ~ 4294967295 -- R/O FLOAT kWh ⊠5260 0x04 kW-Hour Export 0 ~ 4294967295 -- R/O FLOAT kWh ⊠5262 0x04 kVar-Hour Import 0 ~ 4294967295 -- R/O FLOAT kVARh ⊠5264 0x04 kVar-Hour Export 0 ~ 4294967295 -- R/O FLOAT kVARh ⊠5266 0x04 kVA-Hour 0 ~ 4294967295 -- R/O FLOAT kVAh ⊠

Sequence Voltage magnitude5268 0x04 Positive Sequence Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠5270 0x04 Negative Sequence Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠5272 0x04 Zero Sequence Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠

Sequence Current magnitude5274 0x04 Positive Sequence Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5276 0x04 Negative Sequence Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5278 0x04 Zero Sequence Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠

Frequency5280 0x04 Frequency(VA) 0.00 ~ 80.00 -- R/O FLOAT Hz ⊠5282 0x04 Frequency(VAa) 0.00 ~ 80.00 -- R/O FLOAT Hz ⊠

Demand Phase Current magnitude5284 0x04 Phase A Demand Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5286 0x04 Phase B Demand Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5288 0x04 Phase C Demand Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠

Demand 3 Phase Power5290 0x04 3 Phase Demand Watt -1012 ~ 1012 -- R/O FLOAT W ⊠5292 0x04 3 Phase Demand Var -1012 ~ 1012 -- R/O FLOAT VAR ⊠5294 0x04 3 Phase Demand VA 0 ~ 1012 -- R/O FLOAT VA ⊠

Voltage THD5296 0x04 Phase A Voltage THD 0.0 ~ 100.0 -- R/O FLOAT % ⊠5298 0x04 Phase B Voltage THD 0.0 ~ 100.0 -- R/O FLOAT % ⊠5300 0x04 Phase C Voltage THD 0.0 ~ 100.0 -- R/O FLOAT % ⊠

Current THD5302 0x04 Phase A Current THD 0.0 ~ 100.0 -- R/O FLOAT % ⊠5304 0x04 Phase B Current THD 0.0 ~ 100.0 -- R/O FLOAT % ⊠5306 0x04 Phase C Current THD 0.0 ~ 100.0 -- R/O FLOAT % ⊠

Page 54: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 54 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

DG-3000 Angle(Float)Phase Voltage angle

5308 0x04 Phase A Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5310 0x04 Phase B Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5312 0x04 Phase C Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5314 0x04 Phase Aa Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠

Line to Line Voltage angle5316 0x04 Phase AB Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5318 0x04 Phase BC Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5320 0x04 Phase CA Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠

Phase Current angle5322 0x04 Phase A Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5324 0x04 Phase B Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5326 0x04 Phase C Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5328 0x04 Phase N Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠

Sequence Voltage angle5330 0x04 Positive Sequence Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5332 0x04 Negative Sequence Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5334 0x04 Zero Sequence Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠

Sequence Current angle5336 0x04 Positive Sequence Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5338 0x04 Negative Sequence Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5340 0x04 Zero Sequence Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5342 ~ Reserved

Page 55: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 55 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

T-3000 Magnitude(Float)Phase Voltage magnitude

5400 0x04 Phase A Voltage 0.00 ~ 999999.99 -- R/O FLOAT V ⊠Phase Current magnitudeWinding 1

5402 0x04 Phase A Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5404 0x04 Phase B Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5406 0x04 Phase C Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5408 0x04 Phase N Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠

Winding 25410 0x04 Phase A Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5412 0x04 Phase B Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5414 0x04 Phase C Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5416 0x04 Phase N Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠

Winding 35418 0x04 Phase A Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5420 0x04 Phase B Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5422 0x04 Phase C Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5424 0x04 Phase N Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠

Sequence Current magnitudeWinding 1

5426 0x04 Positive Sequence Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5428 0x04 Negative Sequence Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5430 0x04 Zero Sequence Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠

Winding 25432 0x04 Positive Sequence Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5434 0x04 Negative Sequence Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5436 0x04 Zero Sequence Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠

Winding 35438 0x04 Positive Sequence Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5440 0x04 Negative Sequence Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5442 0x04 Zero Sequence Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠

Compensate Fundamental Current magnitudeWinding 1

5444 0x04 Compensate Phase A Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠

Page 56: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 56 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

5446 0x04 Compensate Phase B Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5448 0x04 Compensate Phase C Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠

Winding 25450 0x04 Compensate Phase A Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5452 0x04 Compensate Phase B Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5454 0x04 Compensate Phase C Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠

Winding 35456 0x04 Compensate Phase A Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5458 0x04 Compensate Phase B Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5460 0x04 Compensate Phase C Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠

Differential Current magnitude5462 0x04 Phase A Differential Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5464 0x04 Phase B Differential Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5466 0x04 Phase C Differential Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠

Restraint Current magnitude5468 0x04 Phase A Restrain Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5470 0x04 Phase B Restrain Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5472 0x04 Phase C Restrain Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠

Differential Harmonic Current magnitude

5474 0x04 Phase A Differential 2nd

Harmonic Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5476 0x04 Phase B Differential 2nd

Harmonic Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5478 0x04 Phase C Differential 2nd

Harmonic Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5480 0x04 Phase A Differential 5th

Harmonic Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5482 0x04 Phase B Differential 5th

Harmonic Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠5484 0x04 Phase C Differential 5th

Harmonic Current 0.00 ~ 999999.99 -- R/O FLOAT A ⊠Magnitude compensation magnitude

5486 0x04 Winding 1 Mag Compens factor 1.00 ~ 999.99 -- R/O FLOAT -- ⊠5488 0x04 Winding 2 Mag Compens factor 1.00 ~ 999.99 -- R/O FLOAT -- ⊠5490 0x04 Winding 3 Mag Compens factor 1.00 ~ 999.99 -- R/O FLOAT -- ⊠

Page 57: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 57 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Frequency5492 0x04 Frequency(VA) 0.00 ~ 80.00 -- R/O FLOAT Hz ⊠

T-3000 Angle(Float)Phase Voltage angle

5494 0x04 Phase A Voltage 0.0 ~ 359.9 -- R/O FLOAT deg ⊠Phase Current angleWinding 1

5496 0x04 Phase A Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5498 0x04 Phase B Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5500 0x04 Phase C Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5502 0x04 Phase N Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠

Winding 25504 0x04 Phase A Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5506 0x04 Phase B Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5508 0x04 Phase C Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5510 0x04 Phase N Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠

Winding 35512 0x04 Phase A Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5514 0x04 Phase B Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5516 0x04 Phase C Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5518 0x04 Phase N Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠

Sequence Current angleWinding 1

5520 0x04 Positive Sequence Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5522 0x04 Negative Sequence Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5524 0x04 Zero Sequence Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠

Winding 25526 0x04 Positive Sequence Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5528 0x04 Negative Sequence Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5530 0x04 Zero Sequence Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠

Winding 35532 0x04 Positive Sequence Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5534 0x04 Negative Sequence Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5536 0x04 Zero Sequence Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠

Page 58: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 58 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

Compensate Fundamental Current angleWinding 1

5538 0x04 Compensate Phase A Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5540 0x04 Compensate Phase B Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5542 0x04 Compensate Phase C Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠

Winding 25544 0x04 Compensate Phase A Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5546 0x04 Compensate Phase B Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5548 0x04 Compensate Phase C Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠

Winding 35550 0x04 Compensate Phase A Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5552 0x04 Compensate Phase B Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5554 0x04 Compensate Phase C Current 0.0 ~ 359.9 -- R/O FLOAT deg ⊠5556 ~ Reserved

Page 59: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 59 / 74

Address(dec) Function Code Description Range Step Access Format Units M 3000 DG 3000 F 3000 T 3000

File ( Event, Wave Recording, EasyLogic File, MinMax Value)

60500~60519 0x06/0x10

File OpenOperation

File Name(ID) -- W/O FN0 -- ⊠ ⊠ ⊠ ⊠

60520 0x06/0x10 File Open Operation RD(0), WR(1),RW(2), AP(3) 1 W/O INT16U -- ⊠ ⊠ ⊠ ⊠

60521 0x06/0x10 File Close Operation RD(0), WR(1),RW(2), AP(3) 1 W/O INT16U -- ⊠ ⊠ ⊠ ⊠

60522 0x04 File Status OK(0), EOF(1) -- R/O INT16U -- ⊠ ⊠ ⊠ ⊠60523 ~ 60524 Reserved

60525 0x06/0x10 File rewind 1 W/O INT16U -- ⊠ ⊠ ⊠ ⊠60526~ 60527 0x04/0x06/0x10 File size 0 ~ 4294967295 1 R/W INT32U Byte ⊠ ⊠ ⊠ ⊠60528 0x04/0x06/0x10 File Attribute FN6 1 R/W INT16U -- ⊠ ⊠ ⊠ ⊠60529 ~ 60599 Reserved

60600 0x04/0x06/0x10 Buff Valid Byte Length 1 R/W INT16U Byte ⊠ ⊠ ⊠ ⊠60601 0x04/0x06/0x10 File buffer[0] 1 R/W FN9 -- ⊠ ⊠ ⊠ ⊠… … … … … … … … ⊠ ⊠ ⊠ ⊠60724 0x04/0x06/0x10 File butter[123] 1 R/W FN9 -- ⊠ ⊠ ⊠ ⊠60725 ~ Reserved

Page 60: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 60 / 74

9. Register Formats

No. Format Name Description

FN0

File ID

Address ID 60500 60501 60502 60503 60504

60505 ~ 60519

ASCII 분석

내용

Event log File 0x7665 0x6E65 0x2E74 0x6F6C 0x0067

NULL

event.log

Waveform recording log File 0x6177 0x6576 0x315F 0x6C2E 0x7473 wave_1.lst

Waveform recording #1 *.cfg(config)file 0x6177 0x6576 0x315F 0x632E 0x6766 wave_1.cfg

Waveform recording #1 *.dat(data)file 0x6177 0x6576 0x315F 0x642E 0x7461 wave_1.dat

Waveform recording #2 *.cfg(config)file 0x6177 0x6576 0x325F 0x632E 0x6766 wave_2.cfg

Waveform recording #2 *.dat(data)file 0x6177 0x6576 0x325F 0x642E 0x7461 wave_2.dat

Waveform recording #3 *.cfg(config)file 0x6177 0x6576 0x335F 0x632E 0x6766 wave_3.cfg

Waveform recording #3 *.dat(data)file 0x6177 0x6576 0x335F 0x642E 0x7461 wave_3.dat

Waveform recording #4 *.cfg(config)file 0x6177 0x6576 0x345F 0x632E 0x6766 wave_4.cfg

Waveform recording #4 *.dat(data)file 0x6177 0x6576 0x345F 0x642E 0x7461 wave_4.dat

Waveform recording #5 *.cfg(config)file 0x6177 0x6576 0x355F 0x632E 0x6766 wave_5.cfg

Waveform recording #5 *.dat(data)file 0x6177 0x6576 0x355F 0x642E 0x7461 wave_5.dat

Waveform recording #6 *.cfg(config)file 0x6177 0x6576 0x365F 0x632E 0x6766 wave_6.cfg

Waveform recording #6 *.dat(data)file 0x6177 0x6576 0x365F 0x642E 0x7461 wave_6.dat

Waveform recording #7 *.cfg(config)file 0x6177 0x6576 0x375F 0x632E 0x6766 wave_7.cfg

Waveform recording #7 *.dat(data)file 0x6177 0x6576 0x375F 0x642E 0x7461 wave_7.dat

Waveform recording #8 *.cfg(config)file 0x6177 0x6576 0x385F 0x632E 0x6766 wave_8.cfg

Waveform recording #8*.dat(data)file 0x6177 0x6576 0x385F 0x642E 0x7461 wave_8.dat

데이터 읽기 순서

1. Event log File에서 Data 순서 읽기

- 1 ~ FileSize 순서대로 최근 등록 순서

2. Waveform recording log File 순서 읽기

- 1 ~ FileSize 순서대로 최근 등록 순서

3. Waveform recording *.cfg, Waveform recording *.dat 순서 읽기

- ID #1 ~ ID #8 순서대로 최근 등록 순서

FN3 DNP Data & TimeFormat

A most significant number holds the number of minutes since 1/1/70A least significant number holds the number of mill-seconds in the current minute.1st word : Most significant(high word)2nd word : Most significant(low word)3rd word : Least significant

FN6 File Attributes Bit Description0: Read1: Write

Page 61: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 61 / 74

No. Format Name Description

FN7 File Mode Open mode0: Read Only1: Write Only2: Read/Write3: Append

FN8 File Error Codes 0: No errors : 에러 아니다

1: Not Exist : 존재 하지 않다

2: No Permission : 허가 되지 않은 요구 시 에러, ID입력 에러

3: Already Opened : 이미 열려 있는 상태, 데이터 전송 완료 상태, 보낼 파일 없는 상태

파일 닫기 후 파일 열기부터 요망

4: Not Opened : 열리지 않은 상태, 강제 종료, ID입력 에러, 파일 닫기 후 파일 열기 요망

FN9 File Buffer 2Byte assemble into a wordL-H order0x12-0x34 ->0x3412

FN10 File Status 0: OK - Buff File is Not End of File1: EOF(1) - Buff File is End of File

F001 INT8U UNSIGNED 8 BIT INTEGER (0 ~ 255)

F002 INT8S SIGNED 8 BIT INTEGER (-128 ~ +128)

F003 INT16U UNSIGNED 16 BIT INTEGER (0 ~ 65535)

F004 INT16S SIGNED 16 BIT INTEGER (-32767 ~ +32767)

F005 INT32U UNSIGNED 32 BIT INTEGER (0 ~ +4294967295)

F006 INT32S SIGNED 32 BIT INTEGER (-2147483647 ~ +2147483647)

F100 Disabled/Enabled ENUMERATION0: Disabled1: Enabled

F101 Confirm No/Yes ENUMERATION0: No1: Yes

F200 Frequency ENUMERATION0: 60Hz1: 50Hz

F201 CT SecondaryENUMERATION0: 1A1: 5A

F202 Phase CompensationENUMERATION0: INTERNAL1: EXTERNAL

F203 PT Connection ENUMERATION0: NONE1: WYE2: DEL

F205 Demand Interval ENUMERATION0: 15 min1: 30 min2: 60 min

F206 Demand Sync Time ENUMERATION0: 0 min1: 15 min2: 30 min3: 45 min

Page 62: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 62 / 74

No. Format Name Description

F207 Trip Relay Selection ENUMERATION0: CONT OUT#11: CONT OUT#22: CONT OUT#33: CONT OUT#4

F208 Motor Start Detection ENUMERATION0: CURR1: CB ST2: CURR OR CB ST

F209 Setting Group ENUMERATION0: GROUP#11: GROUP#22: GROUP#33: GROUP#4

F210 Wave RecordingType

ENUMERATION0: 2*2401: 4*1202: 8*60

F211 Wave RecordingType

ENUMERATION0: 10*121: 20*6

F212 Trigger Source ENUMERATION0: TRIP1: EXT_L_H2: EXT_H_L

F213 Wave RecordingType

ENUMERATION0: 2*4001: 4*2002: 8*100

F214 Wave RecordingType

ENUMERATION0: 2*2001: 4*1002: 8*50

F215 Wave RecordingType

ENUMERATION0: 2*3201: 4*1602: 8*80

F216 Wave RecordingType

ENUMERATION0: 2*1801: 4*902: 8*45

Page 63: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 63 / 74

No. Format Name Description

F220F221

Breaker Open/CloseInput

Speed Switch

ENUMERATION0: NONE1: CONT IN#12: CONT IN#23: CONT IN#34: CONT IN#45: CONT IN#56: CONT IN#67: CONT IN#78: CONT IN#89: CONT IN#910: CONT IN#1011: CONT IN#1112: CONT IN#1213: CONT IN#1314: CONT IN#1415: CONT IN#1516: CONT IN#16

F222 TCS Input

ENUMERATION******0 은 없음 ******1: CONT IN#12: CONT IN#23: CONT IN#34: CONT IN#45: CONT IN#56: CONT IN#67: CONT IN#78: CONT IN#89: CONT IN#910: CONT IN#1011: CONT IN#1112: CONT IN#1213: CONT IN#1314: CONT IN#1415: CONT IN#1516: CONT IN#16

F223 CBF Trip Input

ENUMERATION0: CONT OUT#11: CONT OUT#22: CONT OUT#33: CONT OUT#44: CONT OUT#55: CONT OUT#6

F224 CBF Trip Input

ENUMERATION

0: CONT OUT#11: CONT OUT#22: CONT OUT#33: CONT OUT#44: CONT OUT#55: CONT OUT#66: CONT IN#17: CONT IN#28: CONT IN#39: CONT IN#410: CONT IN#5

11: CONT IN#612: CONT IN#713: CONT IN#814: CONT IN#915: CONT IN#1016: CONT IN#1117: CONT IN#1218: CONT IN#1319: CONT IN#1420: CONT IN#1521: CONT IN#16

Page 64: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 64 / 74

No. Format Name Description

F230 BPS

ENUMERATION0: 3001: 12002: 24003: 48004: 96005: 192006: 38400

F231 Protocol ENUMERATION0: DNP3.01: Modbus

F232 DNP Link Confirm

ENUMERATION0: Never1: Always2: Sometimes

F240 CONT IN connection

ENUMERATION0: NOT CONNECTED1: CB OPENED2: CB CLOSED3: ANNUN RESET4: PROT BLOCK5: GENERAL INPUT

F260 Transformer Type

ENUMERATION0: Y-Y1: Y-D2: D-Y3: D-D4: Y-Y-Y5: Y-Y-D6: Y-D-Y7: Y-D-D8: D-Y-Y9: D-Y-D10: D-D-Y11: D-D-D

F261 Phase Lag

ENUMERATION0: 01: 302: 603: 904: 1205: 1506: 1807: 2108: 2409: 27010: 30011: 330

F262 Harmonic Restrain

ENUMERATION0: NONE1: 2nd

2: 5th

3: 2nd + 5th

F300 Direction

ENUMERATION0: NONE1: FORWARD2: REVERSE

Page 65: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 65 / 74

No. Format Name Description

F301 Inverse Time Overcurrent Curve

ENUMERATION0: IEC_NI ----- (IEC Normal Inverse)1: IEC_VI ----- (IEC Very Inverse)2: IEC_EI ----- (IEC Extremely Inverse)3: IEC_LI ----- (IEC Long Inverse)4: ANSI_I ----- (ANSI Inverse)5: ANSI_SI ---- (ANSI Short Inverse)6: ANSI_LI ---- (ANSI Long Inverse)7: ANSI_MI ---- (ANSI Moderately Inverse)8: ANSI_VI ---- (ANSI Very Inverse)9: ANSI_EI ---- (ANSI Extremely Inverse)10: ANSI_DI ---- (ANSI Definite Inverse)11: KNI ----- (KEPCO Normal Inverse)12: KVI ----- (KEPCO Very Inverse)

F302 Protection Reset Type

ENUMERATION0: INST1: TIMED

F303 PolarizingENUMERATION0: VOLT1: CURR2: VOLT or CURR

F304 Polarizing Voltage Source

ENUMERATION0: -3V01: VG

F305 DirectionENUMERATION0: NONE1: FORWARD2: REVERSE

F306 Polarizing VoltageSource

ENUMERATION0: 3V01: VG

F307 Inverse Time Overcurrent Curve

ENUMERATION0: IEC_NI ----- (IEC Normal Inverse)1: IEC_VI ----- (IEC Very Inverse)2: IEC_EI ----- (IEC Extremely Inverse)3: IEC_LI ----- (IEC Long Inverse)4: ANSI_I ----- (ANSI Inverse)5: ANSI_SI ---- (ANSI Short Inverse)6: ANSI_LI ---- (ANSI Long Inverse)7: ANSI_MI ---- (ANSI Moderately Inverse)8: ANSI_VI ---- (ANSI Very Inverse)9: ANSI_EI ---- (ANSI Extremely Inverse)10: ANSI_DI ---- (ANSI Definite Inverse)11: KNI ----- (KEPCO Normal Inverse)12: KVI ----- (KEPCO Very Inverse)13: KDNI ----- (KEPCO Definite Normal Inverse)

F310 Voltage ModeENUMERATION0: DT1: INV

F311 OVGR ModeENUMERATION0: INST1: TIMED

Page 66: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 66 / 74

No. Format Name Description

F312 Ground OvervoltageMode

ENUMERATION0: DT1: INV TRIP2: INV ALARM

F320 Power Polarity

ENUMERATION0: DISABLED1: POSITIVE2: NEGATIVE

F321 OPR Curve

ENUMERATION0: DT1: INV12: INV2

F322 OPR/UPR ModeENUMERATION0: 1 PHASE1: 3 PHASE

F323 UPR/RPR ModeENUMERATION0: DT1: INV1

F330 Frequency TypeENUMERATION0: UNDER1: OVER

F350 RTD Type Setting

ENUMERATION0: PT1001: NI1002: NI120

F360 Trip Relay Selection

ENUMERATION0: CONT OUT#11: CONT OUT#22: CONT OUT#33: CONT OUT#44: CONT OUT#55: CONT OUT#66: CONT OUT#77: CONT OUT#88: CONT OUT#99: CONT OUT#1010: CONT OUT#1111: CONT OUT#1212: CONT OUT#1313: CONT OUT#1414: CONT OUT#1515: CONT OUT#16

F370 SynchroCheck DeadSource Condition

ENUMERATION0: NONE1: LVA_AND_DVAa2: DVA_AND_LVAa3: DVA_XOR_DVAa4: DVA_AND_DVAa

F400 E3R CO, LEDInput gate

ENUMERATION0: OR8 :L_OFF all1: HALF-OR8 : 1 ~4 : L_OFF, 5~8: L_ON2: AND8 : L_OFF all3: HALF-AND8 : 1 ~4 : L_OFF, 5~8: L_ON

Page 67: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 67 / 74

No. Format Name Description

F401 EasyLogic Operator

ENUMERATION0: NOP1: AND22: AND33: AND44: AND55: AND66: AND77: AND88: OR29: OR310: OR411: OR512: OR613: OR714: OR815: NAND216: NAND317: NAND418: NAND519: NAND620: NAND721: NAND822: NOR223: NOR324: NOR425: NOR526: NOR627: NOR728: NOR829: NOT30: LATCH31: ON_DLY_TIMER32: OFF_DLY_TIMER33: PULSE_TIMER

F402 Reset Type ENUMERATION0: Self1: Manual

F410 EasyLogic Operand ** 표1 참조

F600 TEXT12,12ASCII characters

12 ASCII characters(6words Address Allocation)2 Bytes assemble into a wordex) "Breaker#1 " (12Bytes) -> "rB" , "ae" , "ek“ , "#r" , " 1" , " " (6Words) order

F601 CH4 4 ASCII characters(4 Address Allocation, Low Byte Only)

F602 CH12 12 ASCII characters(12 Address Allocation, Low Byte Only)

F700 Setting Flag, 64bitsBITFIELD: HH-HL-LH-LL(Bit63 … Bit0) order

** 표2 참조

Page 68: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 68 / 74

[표1] EasyLogic Operand

Operand Group Operand DG3000 F3000 M3000 T3000

Logic L_OFF 0 0 0 0 L_ON 1 1 1 1

Contact Inputs CONT_IN_1 2 2 2 2 … … … … …

CONT_IN_16 17 17 17 17

Logic Components LOGIC_CMP_1 18 18 18 18 … … … … …

LOGIC_CMP_48 65 65 65 65

Monitoring

SYSTEM_ERR 66 66 66 66 PT_FUSE_FAIL 67 67 67 -- PT_BAL_FAIL 68 68 68 -- CT_SUM 69 69 69 -- CT_BAL_FAIL 70 70 70 -- TCS_FAIL 71 71 71 67

Control

ANN RESET 72 72 72 68 LO_RE_SW_LO 73 73 73 69 CB1_OPN_CTRL 74 74 74 70 CB1_CLS_CTRL 75 75 75 71 CB2_OPN_CTRL 76 76 76 72 CB2_CLS_CTRL 77 77 77 73

Protection

ALL PROT_OP_OR 78 78 78 74 PROT_PKP_OR 79 79 79 75

50_1(W1_50_1), 50_2(W1_50_2), 51(W1_51)

(W1_)50/51_PKP 80 80 80 76 (W1_)50/51_PKP_A 81 81 81 77 (W1_)50/51_PKP_B 82 82 82 78 (W1_)50/51_PKP_C 83 83 83 79 (W1_)50_1_OP 84 84 84 80 (W1_)50_1_OP_A 85 85 85 81 (W1_)50_1_OP_B 86 86 86 82 (W1_)50_1_OP_C 87 87 87 83 (W1_)50_2_OP 88 88 88 84 (W1_)50_2_OP_A 89 89 89 85 (W1_)50_2_OP_B 90 90 90 86 (W1_)50_2_OP_C 91 91 91 87 (W1_)51_OP 92 92 92 88 (W1_)51_OP_A 93 93 93 89 (W1_)51_OP_B 94 94 94 90 (W1_)51_OP_C 95 95 95 91

W2_50_1, W2_50_2, W2_51

W2_50/51_PKP 96 -- -- 92 … … -- -- …

W2_51_OP_C 111 -- -- 107

W3_50_1, W3_50_2, W3_51

W3_50/51_PKP -- -- -- 108 … -- -- -- …

W3_51_OP_C -- -- -- 123

50N_1(W1_50N_1), 50N_2(W1_50N_2), 51N(W1_51N)

(W1_)50/51N_PKP 112 96 96 124 (W1_)50N_1_OP 113 97 97 125 (W1_)50N_2_OP 114 98 98 126 (W1_)51N_OP 115 99 99 127

W2_50N_1, W2_50N_2, W2_51N

W2_50/51N_PKP 116 -- -- 128 … … -- -- …

W2_51N_OP_C 119 -- -- 131

Page 69: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 69 / 74

Operand Group Operand DG3000 F3000 M3000 T3000

Protection

W3_50N_1, W3_50N_2, W3_51N

W3_50/51N_PKP -- -- -- 132

… -- -- -- …

W3_51N_OP_C -- -- -- 135

67Ns 67Ns_PKP -- 100 100 --

67Ns_OP -- 101 101 --

49 49_ALARM -- 102 102 --

49_TRIP -- 103 103 --

49R_1, 49R_2, 49R_3, 49R_4

49R_1_ARM -- -- 104 --

49R_1_TRIP -- -- 105 --

49R_2_ARM -- -- 106 --

49R_2_TRIP -- -- 107 --

49R_3_ARM -- -- 108 --

49R_3_TRIP -- -- 109 --

49R_4_ARM -- -- 110 --

49R_4_TRIP -- -- 111 --

37

37_PKP -- 104 112 --

37_PKP_A -- 105 113 --

37_PKP_B -- 106 114 --

37_PKP_C -- 107 115 --

37_OP -- 108 116 --

37_OP_A -- 109 117 --

37_OP_B -- 110 118 --

37_OP_C -- 111 119 --

46_1(W1_46_1), 46_2(W1_46_2), 46T(W1_46T)

(W1_)46_PKP 120 112 120 136

(W1)46_1_OP 121 113 121 137

(W1)46_2_OP 122 114 122 138

(W1)46T_OP 123 115 123 139

W2_46_1, W2_46_2, W2_46T

W2_46_PKP -- -- -- 140

… -- -- -- …

W2_46T_OP -- -- -- 143

W3_46_1, W3_46_2, W3_46T

W3_46_PKP -- -- -- 144

… -- -- -- …

W3_46T_OP -- -- -- 147

46U 46U_PKP 124 116 124 --

46U_OP 125 117 125 --

59_1, 59_2

59_PKP 126 118 126 148

59_PKP_A 127 119 127 --

59_PKP_B 128 120 128 --

59_PKP_C 129 121 129 --

59_1_OP 130 122 130 149

59_1_OP_A 131 123 131 --

59_1_OP_B 132 124 132 --

59_1_OP_C 133 125 133 --

59_2_OP 134 126 134 150

59_2_OP_A 135 127 135 --

59_2_OP_B 136 128 136 --

59_2_OP_C 137 129 137 --

Page 70: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 70 / 74

Operand Group Operand DG3000 F3000 M3000 T3000

Protection

27_1, 27_2

27_PKP 138 130 138 151 27_PKP_A 139 131 139 -- 27_PKP_B 140 132 140 -- 27_PKP_C 141 133 141 -- 27_1_OP 142 134 142 152 27_1_OP_A 143 135 143 -- 27_1_OP_B 144 136 144 -- 27_1_OP_C 145 137 145 -- 27_2_OP 146 138 146 153 27_2_OP_A 147 139 147 -- 27_2_OP_B 148 140 148 -- 27_2_OP_C 149 141 149 --

59G_1, 59G_2

59G_PKP -- 142 150 -- 59G_1_OP -- 143 151 -- 59G_2_OP -- 144 152 --

47 47_PKP 150 145 153 -- 47_OP 151 146 154 --

81U/O_1, 81U/O_2, 81U/O_3

81U/O_1_PKP 152 147 -- -- 81U/O_1_OP 153 148 -- -- 81U/O_2_PKP 154 149 -- -- 81U/O_2_OP 155 150 -- -- 81U/O_3_PKP 156 151 -- -- 81U/O_3_OP 157 152 -- --

79

79_READY -- 153 -- -- 79_IN_PROG -- 154 -- -- 79_FAIL -- 155 -- -- 79_SUCCESS -- 156 -- --

50BF 50BF_OP 158 157 155 154

48/51L

48/51L_ING -- -- -- -- 48/51L_PKP -- -- 156 -- 48/51L_OP -- -- 157 -- ROTOR_LOCK -- -- 158 --

66/68 66/68_IN_PROG -- -- 159 -- 66/68_IN_OP -- -- 160 --

50/87, 87T

50/87_PKP -- -- -- 155 50/87_PKP_A -- -- -- 156 50/87_PKP_B -- -- -- 157 50/87_PKP_C -- -- -- 158 50/87_OP -- -- -- 159 50/87_OP_A -- -- -- 160 50/87_OP_B -- -- -- 161 50/87_OP_C -- -- -- 162 87T_OP -- -- -- 163 87T_OP_A -- -- -- 164 87T_OP_B -- -- -- 165 87T_OP_C -- -- -- 166

W1_87G, W2_87G, W3_87G

W1_87G_PKP -- -- -- 167 W1_87G_OP -- -- -- 168 W2_87G_PKP -- -- -- 169 W2_87G_OP -- -- -- 170 W3_87G_PKP -- -- -- 171 W3_87G_OP -- -- -- 172

Page 71: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 71 / 74

Operand Group Operand DG3000 F3000 M3000 T3000

Protection

24_1, 24_2

24_PKP -- -- -- 173

24_1_OP -- -- -- 174

24_2_OP -- -- -- 175

67

67_OP_A 159 158 161 --

67_OP_B 160 159 162 --

67_OP_C 161 160 163 --

67N 67N_OP 162 161 164 --

COLD_LD COLD_LD_PKP 163 162 165 176

COLD_LD_OP 164 163 166 177

I2f/I1f I2f/I1f_OP 165 164 167 178

81R_1, 81R_2

81R_PKP 166

81R_1_OP 167

81R_2_OP 168

32P

32P_PKP 169

32P_PKP_A 170

32P_PKP_B 171

32P_PKP_C 172

32P_OP 173

32P_OP_A 174

32P_OP_B 175

32P_OP_C 176

32U

32U_PKP 177

32U_PKP_A 178

32U_PKP_B 179

32U_PKP_C 180

32U_OP 181

32U_OP_A 182

32U_OP_B 183

32U_OP_C 184

32Q

32Q_PKP 185

32Q_PKP_A 186

32Q_PKP_B 187

32Q_PKP_C 188

32Q_OP 189

32Q_OP_A 190

32Q_OP_B 191

32Q_OP_C 192

25

25_DEAD 193

25_SYNC 194

25_DEAD_SYNC 195

Page 72: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 72 / 74

[표2] Setting Flag [BITFIED : HH-HL-LH-LL(Bit63 … Bit0) order]

LONG bit Flag Description DG3000 F3000 M3000 T3000

0(2500 ~ 2501)

0 SET_PASSWORD_FLAG Setting/Control Passwor √ √ √ √

1 SET_POWER_SYSTEM_FLAG Motor포함(M3000), Transformer/winding#1~3(T3000) √ √ √ √

2 SET_RTC_FLAG √ √ √ √

3 SET_WAVEFORM_FLAG √ √ √ √

4 SET_BREAKER_FLAG Breaker#1~# √ √ √ √

5 SET_COM_FLAG COM1/COM2/DNP3.0포함 √ √ √ √

6 SET_SUPERVISION_FLAG

PT Fuse Failure √ √ √

Voltage Balance √ √ √

Current Sum √ √ √

Current Balance √ √ √

Trip Circuit Supervision √ √ √ √

7 SET_DEMAND_FLAG √ √ √

8 SET_67_FLAG √ √ √

9 SET_67N_FLAG √ √ √

10 SET_50_51_FLAG(W1_)50_1/(W1_)50_2/(W1_)51, D1_50_1,(for DG3000)

√ √ √ √

11 SET_W2_50_51_FLAGW2_50_1/W2_50_2/W2_51 , T3000 OnlyD2_50_1,(for DG3000)

√ √

12 SET_W3_50_51_FLAG W3_50_1/W3_50_2/W3_51, T3000 Only √

13 SET_50N_51N_FLAG(W1_)50N_1/(W1_)50N_2/(W1_)51ND1_50N_1(for DG3000)

√ √ √ √

14 SET_W2_50N_51N_FLAGW2_50N_1/W2_50N_2/W2_51ND2_50N_1,(for DG3000)

√ √

15 SET_W3_50N_51N_FLAG W3_50N_1/W3_50N_2/W3_51N, √

16 SET_67Ns_FLAG √ √

17 SET_49_FLAG 49 √ √ √

18 SET_RTD_FLAG RTD1~RTD4 √

19 SET_37_FLAG 37 √ √

20 SET_46_FLAG (W1_)46_1/(W1_)46_2/(W1_)46 √ √ √ √

21 SET_W2_46_FLAG W2_46_1/W2_46_2/W2_46T , T3000 Only √

22 SET_W3_46_FLAG W3_46_1/W3_46_2/W3_46T, T3000 Only √

23 SET_46U_FLAG 46 √ √ √

24 SET_59_FLAG 59_1,59_2 √ √ √ √

25 SET_27_FLAG 27_1,27_2 √ √ √ √

26 SET_59G_FLAG 59G_1,59G_2 √ √

27 SET_47_FLAG 47 √ √ √

28 SET_81OU_1_FLAG 81O/U_1 √ √

29 SET_81OU_2_FLAG 81O/U_2 √ √

30 SET_81OU_3_FLAG 81O/U_3 √ √

31 Reserve

Page 73: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 73 / 74

LONG bit Flag Description DG3000 F3000 M3000 T3000

1(2502 ~ 2503)

0 SET_79_FLAG 79 √

1 SET_50BF_FLAG 50BF √ √ √ √

2 SET_COLD_LD_FLAG COLD_LD √ √ √ √

3 SET_I2f_I1f_FLAG I2f/I1f √ √ √ √

4 SET_STALL_48_FLAG √

5 SET_66_68_FLAG √

6 SET_50_87_FLAG √

7 SET_87T_FLAG √

8 SET_W1_87G_FLAG √

9 SET_W2_87G_FLAG √

10 SET_W3_87G_FLAG √

11 SET_24_1_FLAG √

12 SET_24_2_FLAG √

13 SET_CONT_IN_FLAG √ √ √ √

14 SET_CONT_OUT_FLAG √ √ √ √

15 SET_LED_FLAG √ √ √ √

16 SET_LOGIC_COMP_FLAG √ √ √ √

17 SET_CAL_FLAG Internal Use √ √ √ √

18 SET_GRP_CHG_FLAG √ √ √ √

19 SET_81R_1_FLAG √

20 SET_81R_2_FLAG √

21 SET_32P_FLAG √

22 SET_32U_FLAG √

23 SET_32Q_FLAG √

24 SET_25_FLAG √

25~30 Reserve

31 SET_REMOTE_FLAG √ √ √ √

Page 74: MODBUS PROTOCOL & MEMORY MAP DOCUMENTkyongbo.co.kr/admin/fileDown6.jsp?filename=K-PAM 3000... · modbus protocol & memory map document k-pam f3000, dg3000, m3000, t3000 rev date :

K-PAM 3000 Series Modbus V1.70

경보전기[주] 74 / 74

10. Event Recording File FormatType 0 Event Format<TYPE>,<DATE/TIME>,<EVENT ID>,<CR/LF>ex) 0,2001/05/08,20:16:24.999,System Reset-Power On<CR,LF> -> 52 characters

Type 1 Event Format<TYPE>,<DATE/TIME>,<EVENT ID>,<Field#1>,<Field#2>,...,<Field#n><CR/LF>ex) 1,2001/05/08,20:16:24.999,IOCR Start-(A / / ) Ia:5.00A,0.0,Ib:1.00A,0.0,Ic:0.00A,0.0,In:12.00A,0.0 ->Max.52*4 characters

11. Waveform Recording File FormatCOMTRADE File FormatConfiguration and Data File supported

1) *.cfg File Format L-H Order 2Byte ASCII ex) 3,2A,1D<CR/LF> File Buff: 0x2C 0x33 0x41 0x32 0x31 0x2C 0x0D 0x44 0x0A ASCII : ',' '3' 'A' '2' '1' ',' <CR> 'D' <LF> Read : 3,2A,1D<CR/LF>

2) *.dat File Format L-H Order 2Byte assemble into a word ex) File Buff: 0x12 0x34 Read : 0x3412