MOVIDRIVE® Feltbusinterface DFP21APROFIBUS DP (12 Mbaud)
Udgave
03/2001
Manual1051 6182 / DK
SEW-EURODRIVE
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud) 3
Indholdsfortegnelse
1 Indledning .......................................................................................................... 4
2 DFP11A / DFP21A.............................................................................................. 62.1 Forskelle DFP11A / DFP21A .................................................................... 62.2 Omstilling fra DFP11 til DFP21 ................................................................. 7
3 Monterings- / installationsanvisninger ........................................................... 83.1 Understøttede omformertyper................................................................... 83.2 Montering af optionskortet ........................................................................ 83.3 Stikkonfiguration ....................................................................................... 93.4 Skærmning og trækning af buskabler ..................................................... 103.5 Busterminering........................................................................................ 113.6 Indstilling af stationsadressen................................................................. 113.7 Indikeringselementer............................................................................... 123.8 GSD-fil .................................................................................................... 13
4 Projektering og idrifttagning.......................................................................... 144.1 Projektering af DP-master’en.................................................................. 144.2 Ekstern diagnose .................................................................................... 174.3 Idrifttagning af feltomformeren ................................................................ 19
5 Driftsegenskaber på PROFIBUS-DP.............................................................. 225.1 Styring af feltomformeren........................................................................ 225.2 PROFIBUS-DP timeout........................................................................... 245.3 Reaktion feltbus-timeout ......................................................................... 255.4 Parametrering via PROFIBUS-DP .......................................................... 25
6 Svarkoder ved parametreringen .................................................................... 316.1 Elementer................................................................................................ 316.2 Særlige tilfælde ....................................................................................... 32
7 Fejldiagnose .................................................................................................... 357.1 Diagnose-forløb ...................................................................................... 35
8 Tekniske data .................................................................................................. 38
4
Indhold af dennemanual
Denne brugermanual til option beskriver monteringen af PROFIBUS-optionskort DFP i feltomformeren samt idrifttagningen af MOVIDRIVE® på feltbus-systemet PROFIBUS.
Uddybendelitteratur
Med henblik på en enkel og effektiv opkobling af MOVIDRIVE® på feltbussystemetPROFIBUS bør De ud over denne brugermanual til option PROFIBUS rekvirerefølgende uddybende SEW-litteratur om emnet feltbus:
• Manual til feltbus-omformerprofil MOVIDRIVE®
I manualen til "feltbus-omformerprofil" MOVIDRIVE® forklares ud over beskrivelsen affeltbus-parametrene og kodningen af disse de forskellige styringskoncepter ogapplikationsmuligheder ved hjælp af små eksempler.
Manualen "feltbus-omformerprofil" MOVIDRIVE® indeholder en oplistning over alle felt-omformerens parametre, som kan læses og/eller skrives via de forskelligekommunikationsgrænseflader som f.eks. systembus, RS-485 samt også via feltbus-grænsefladen.
Egenskaber Feltomformeren MOVIDRIVE® med option DFP muliggør på grund af dens effektiveuniverselle feltbusgrænseflade en opkobling til overordnede automatiseringssystemervia PROFIBUS.
MOVIDRIVE® ogPROFIBUS
De omformerkarakteristika, den såkaldte omformerprofil, som ligger til grund forPROFIBUS-driften, er feltbusuafhængig og dermed standardiseret. For Dem sombruger åbner dette mulighed for at udvikle feltbusuafhængige drivelementapplikationer.Skift til andre bussystemer som f.eks. INTERBUS (option DFI) er derfor uden videremuligt.
Adgang til alleinformationer
Via PROFIBUS-grænsefladen giver MOVIDRIVE® Dem digital adgang til alle driv-stationsparametre og funktioner. Styringen af feltomformeren sker via de hurtige,cykliske procesdata. Via denne procesdatakanal har De, ud over programmering af set-punkt-værdier som f.eks. omdrejnings-setpunkt, integratortid for acceleration/decelera-tion osv., mulighed for også at udløse forskellige drivstationsfunktioner som f.eks.frikobling, regulatorspærre, normalstop, hurtigstop osv. Samtidig kan De via dennekanal også tilbagelæse aktuelle værdier fra feltomformeren som f.eks. aktueltomdrejningstal, strøm, omformerstatus, fejlnummer eller referencemeddelelser.
Cyklisk og acykliskdataudveksling
Medens udvekslingen af procesdata i reglen foregår cyklisk, kan drivstations-parametrene læses resp. skrives acyklisk via funktioner som READ og WRITE eller viaparameterkanalen. Denne parameterdataudveksling muliggør applikationer, hvor allevigtige drivstationsparametre er lagret i den overordnede automatiseringsenhed,således at der ikke skal foretages nogen manuel, ofte tidskrævende parametrering påselve feltomformeren.
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
Konfiguration afPROFIBUS-optionskortet
Generelt er PROFIBUS-optionskortet konciperet således, at alle feltbusspecifikke ind-stillinger, så som stationsadresser resp. default-busparametre foretages med"hardware"-omskiftere på optionskortet. Ved hjælp af denne manuelle indstilling kanfeltomformeren på et minimum af tid integreres i PROFIBUS-miljøet og indkobles.Parametreringen kan foretages fuldautomatisk fra den overordnede PROFIBUS-master(parameter-download). Denne fremtidsorienterede variant har den fordel, at den ud overat reducere idrifttagningstiden for anlægget også forenkler dokumentationen for Deresapplikationsprogram, fordi nu alle vigtige drivstationsparameterdata kan gemmesdirekte i Deres styringsprogram.
Overvågnings-funktioner
Anvendelsen af et feltbussystem kræver yderligere overvågningsfunktioner til drivsta-tionsteknikken som f.eks. den tidsmæssige overvågning af feltbussen (feltbus time out)eller også specielle hurtigstop-koncepter. De kan tilpasse MOVIDRIVE®’sovervågningsfunktioner specielt til Deres anvendelsesformål. - De kan såledesbestemme, hvilken fejlreaktion feltomformeren skal udløse i tilfælde af fejl på bussen.Til mange applikationer vil et hurtigstop være fornuftigt, men De kan også bestemme, atde sidste setpunkt-værdier skal "fastfryses", således at drivstationen kører videre medde sidste gældende setpunkt-værdier (f.eks. transportbånd). Da styreklemmernesfunktionalitet også er garanteret under feltbusdrift, kan De nu som før via feltbus-omformerens klemmer realisere feltbusuafhængige hurtigstop-koncepter.
Diagnose Med henblik på idrifttagning og service byder feltomformeren MOVIDRIVE® på et utal afdiagnosemuligheder. På den integrerede feltbus-monitor kan De f.eks. både kontrollerede setpunkt-værdier, som er sendt fra den overordnede styring, samt de aktuelleværdier.
Feltbus-monitor Derudover får De utallige yderligere oplysninger om feltbus-optionskortets status.Feltbus-monitorfunktionen byder sammen med PC-sortwaren MOVITOOLS på en enkelog praktisk diagnosemulighed, som ud over indstillingen af samtlige drivstations-parametre (incl. feltbus-parametrene) også muliggør en detaljeret præsentation affeltbus- og omformerstatusinformationer.
01061BXXFig. 1: PROFIBUS med MOVIDRIVE® ([1] = visualisering)
E QE QE Q
Digital I/O Analog I/O
[1]
PROFIBUS Master
PROFIBUS
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
56
2.1 Forskelle DFP11A / DFP21A
Funktionsegenskab DFP11A DFP21A
Maksimal baudrate: 1,5 Mbaud 12 Mbaud
Busafslutningsmodstand: Integreret Via Profibus-stik
Profibus FMS-protokol: JA -
Profibus DP-protokol: JA JA
Ident-nummer: 6000 hex 6003 hex
GSD-filnavn: SEW_6000.GSD SEW_6003.GSD
Modulnavn for projektering: “MOVIDRIVE+DFP11” “MOVIDRIVE+DFP21”
Procesdata-konfigurationer:
(Param) + 1 PD JA JA
(Param) + 2 PD JA JA
(Param) + 3 PD JA JA
(Param) + 6 PD JA JA
(Param) + 10 PD JA JA
Diagnose-informationer forDDLM_Slave_Diag:
DP-standarddiagnose JA JA
Omformerspecifik diagnose (DP) JA JA
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
2.2 Omstilling fra DFP11 til DFP21
Forudsætninger
Fremgangsmåde
Overtagelse af adresseindstillingen fra DIP-switch’ene0 6
Ombytning af optionskort
Ændring af DP-master projekteringen
Genstart af bussystemet
Bus-Fault
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
78
3.1 Understøttede omformertyper
Option DFP til opkobling på PROFIBUS kan arbejde sammen med alle feltomformere iMOVIDRIVE®-familien.
3.2 Montering af optionskortet
Inden Debegynder
• Sørg for at aflade Dem selv for statisk elektricitet, inden De berører optionskortet.Dette gøres ved at træffe egnede forholdsregler (så som at benytte ledende bændel,ledende fodtøj etc.)
• Optionskortet skal altid opbevares i originalemballagen og må først tages ud afdenne, umiddelbart inden kortet skal monteres/udskiftes.
Tag kun på optionskortet langs med kanten - og kun når det er påkrævet. Berør ikkekomponenterne på kortet.
Montering afoptionskortet
• Omformeren skal være spændingsløs. Der skal afbrydes for netforsyningen og evt.for 24 V-forsyningen.
• Den nederste del af beskyttelsesafskærmningen tages af styrehovedet.
• Elektronik-skærmklemmen skrues af.
• Sort frontafskærmningsplade tages af.
• Optionskortet sættes ind i føringsskinnerne til stikplads OPTION1 og skubbes ind.
• Med et moderat tryk på frontpladen trykkes optionskortet på plads. Optionskortet ertrykket rigtigt på plads (låst), når det sidder i plan med styrekortet.
• Elektronik-skærmklemmen skrues på igen.
• Styrehovedets beskyttelsesafskærmning sættes på igen.
• Afhængigt af det anvendte sub-D-stik kan beskyttelsesafskærmningen måske ikkemonteres igen. Omformerens kapslingsklasse (tæthedsgrad) påvirkes ikke heraf.
• Optionskort DFP er nu monteret komplet.
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
Forside ogbestykning afDFP21A
3.3 Stikkonfiguration®
50257AXXFig. 2: Option DFP21A
[1] LED Grøn: RUN [3] Busadresse
[2] LED Rød: BUS FAULT [4] 9polet sub-D-stik (hun)
PROFIBUSDP
RUN
BUSFAULT
2222
0123
222
456
[1]
[2]
[3]
[4]
DFP
X30
ON
ADDRESS
nc
PROFIBUSDP
01222CXXFig. 3: Tilslutning MOVIDRIVE® til PROFIBUS ([1] = 9-polet sub-D-stik; [2] = signalledninger
snoede; [3] = ledende forbindelse mellem stikhus og afskærmning)
384569
RxD/TxD-P (B/ )BRxD/TxD-N (A/ )ACNTR-PDGND (M5V)VP (P5V)DGND (M5V)
E Q
[3]
[1]
[2]
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
910
ForbindelseMOVIDRIVE® /PROFIBUS
®
Baudrater størreend 1,5 Mbaud
3.4 Skærmning og trækning af buskabler
Skærmnings-egenskaber
Pin nr. Signal RS-485 reference
1:2:3:4:5:6:7:8:9:Stikhus
- Ikke anvendt- Ikke anvendtRxD/TxD-P Modtage-/sende-data-PCNTR-P Repeater-styresignal (TTL)DGND Datareferencepotentiale (5 V)VP Forsyningsspænding Plus (P5V)- Ikke anvendtRxD/TxD-N Modtage-/sende-data-NDGND Datareferencepotentiale (5 V)Skærm med parsnoet totrådsledning
B/B’
C/C’
A/A’
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
3.5 Busterminering
3.6 Indstilling af stationsadressen
50232AXXFig. 4: Indstilling af PROFIBUS-stationsadressen / nc = reserveret, stilling OFF
X = on
1: x 0 = +02: x 0 = +04: x 1 = +48: x 0 = +0
16: x 0 = +032: x 0 = +064: x 0 = +0
= 4
1 2 3 41 2 3 4
20
21
22
23
24
25
26
nc
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
1112
P092Feltbus-adresse
3.7 Indikeringselementer
Tabel 1: Eksempel på indstilling af DIP-switch’ene for busadressen 17
Beregning Rest DIP-switch-stilling Valens
17 ÷ 2 = 8 1 X1 = 20 = ON 1
8 ÷ 2 = 4 0 X2 = 21 = OFF 2
4 ÷ 2 = 2 0 X3 = 22 = OFF 4
2 ÷ 2 = 1 0 X4 = 23 = OFF 8
1 ÷ 2 = 0 1 X5 = 24 = ON 16
0 ÷ 2 = 0 0 X6 = 25 = OFF 32
0 ÷ 2 = 0 0 X7 = 26 = OFF 64
Tabel 2: Status for LED RUN (grøn)
RUN Fejlårsag Fejlafhjælpning
ON • PROFIBUS-Hardware OK. -
OFF • Der er hardware-fejl i buselektronikken. • MOVIDRIVE® slukkes og genind-kobles. Optræder fejlen gentagnegange, konsulteres SEW-Service-afdeling.
Blinker • PROFIBUS-adressen er indstillethøjere end 125.
• Kontrollér med P093 Feltbus-adresseden adresse, der er indstillet med DIP-switch’ene.
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
3.8 GSD-fil
Tabel 3: Status for LED BUS-FAULT (rød) ved LED RUN = ON
BUS-FAULT Fejlårsag Fejlafhjælpning
ON • Ingen forbindelse til DP-master’en.• Omformeren detekterer ingen
PROFIBUS-baudrate.• Evt. busafbrydelse.• DP-master’en er ude af drift.
• Kontrollér omformerens PROFIBUS-DP-tilslutning.
• Kontrollér projekteringen i DP-master’en.
• Kontrollér samtlige kabler i DeresPROFIBUS-DP-net.
OFF • Omformeren er i færd med at udveksledata med DP-master’en (status ’Data-Exchange’)
-
Blinker • Omformeren har detekteret baudraten,men adresseres ikke af DP-master’en.
• Omformeren er ikke projekteret ellerforkert projekteret i DP-master’en.
• Kontrollér den indstillede PROFIBUS-adresse på DFP21 og i DP-master’ensprojekterings-software.
• Kontrollér projekteringen af DP-master’en.
• Anvend til projekteringen GSD-filenSEW_6003.GSD med identifikationenMOVIDRIVE-DFP21.
Tabel 4: GSD-fil for DFP21A
Projekterings-tool DP-master Filnavn
Alle DP-projekteringstools efter EN 50170 (V2) for standard DP-master’e
SEW_6003.GSD
Siemens S7 hardware-konfiguration for alle S7 DP-master’e
Siemens S5 COM PROFIBUS for IM 308C m.fl.
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
1314
4.1 Projektering af DP-master’en
Fremgangsmådevedprojekteringen
®
README_GSD6003.PDF
MOVIDRIVE+DFP21
MOVIDRIVE+DFP2
"BUS-FAULT"
DP-konfigurationer
plus®
®
®
00
I
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
UniverselDP-konfiguration
P090 PD-konfiguration
Tabel 5: DP-konfigurationer for DFP21A
Procesdata-konfiguration
Betydning / oplysninger DP-konfigurationer*
0 1
1 PD MOVIDRIVE®-styring via 1 procesdataord 240dec -
2 PD MOVIDRIVE®-styring via 2 procesdataord 241dec -
3 PD MOVIDRIVE®-styring via 3 procesdataord 242dec -
6 PD MOVIDRIVE®-styring via 6 procesdataord(PD4-PD6 kan kun anvendes med IPOSplus®)
0dec 245dec
10 PD MOVIDRIVE®-styring via 10 procesdataord(PD4-PD10 kan kun anvendes med IPOSplus®)
0dec 249dec
Param + 1 PD MOVIDRIVE®-styring via 1 procesdataordParametrering via 8-byte parameterkanal
243dec 240dec
Param + 2 PD MOVIDRIVE®-styring via 2 procesdataordParametrering via 8-byte parameterkanal
243dec 241dec
Param + 3 PD MOVIDRIVE®-styring via 3 procesdataordParametrering via 8-byte parameterkanal
243dec 242dec
Param + 6 PD MOVIDRIVE®-styring via 6 procesdataordParametrering via 8-byte parameterkanal(PD4-PD10 kan kun anvendes med IPOSplus®)
243dec 245dec
Param + 10 PD MOVIDRIVE®-styring via 10 procesdataordParametrering via 8-byte parameterkanal(PD4-PD10 kan kun anvendes med IPOSplus®)
243dec 249dec
Længde Funktion
0 Parameterkanalen er afbrudt
8 I/O-byte resp. 4 I/O-ord Parameterkanalen er i brug
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
00
I
15
16
Længde Funktion
2 I/O-byte resp. 1 I/O-ord 1 procesdataord
4 I/O-byte resp. 2 I/O-ord 2 procesdataord
6 I/O-byte resp. 3 I/O-ord 3 procesdataord
8 I/O-byte resp. 4 I/O-ord 4 procesdataord
10 I/O-byte resp. 5 I/O-ord 5 procesdataord
12 I/O-byte resp. 6 I/O-ord 6 procesdataord
14 I/O-byte resp. 7 I/O-ord 7 procesdataord
16 I/O-byte resp. 8 I/O-ord 8 procesdataord
18 I/O-byte resp. 9 I/O-ord 9 procesdataord
20 I/O-byte resp. 10 I/O-ord 10 procesdataord
Tabel 6: Format af identifikationsbyte Cfg_Data efter EN 50170 (V2)
7 / MSB 6 5 4 3 2 1 0 / LSB
Datalængde0000 = 1 byte/ord1111 = 16 byte/ord
Input/output00 = specielle identifikationsformater01 = input02 = output11 = input/output
Format0 = bytestruktur1 = ordstruktur
Konsistens i0 = byte eller ord1 = hele længden
®
00
I
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
Datakonsistens
4.2 Ekstern diagnose®
Anbefaling ®
Fremgangsmåde
®
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
00
I
17
18
Eksempel påprojektering
Tabel 7: Anvendelsesspecifikke parametreringsdata for MOVIDRIVE® + DFP21
Byte: Tilladt værdi Funktion
0 00 hex Reserveret for DPV1
1 00 hex Reserveret for DPV1
2 00 hex Reserveret for DPV1
3 06 hex Struktureret bruger-parameterblok med længden 6 byte
4 81 hex Strukturtype: Bruger (producentspecifik)
5 00 hex Slot-nummer: 0 = komplet enhed
6 00 hex Reserveret
7 01 hex SEW-bruger-parameter version: 1
8 00 hex DFP21 genererer diagnose-alarm i tilfælde af fejl
01 hex DFP21 genererer ingen diagnose-alarm i tilfælde af fejl (fabriksindstilling)
50256AXXFig. 5: Aktivering af den eksterne diagnose med STEP7
00
I
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
4.3 Idrifttagning af feltomformeren®
®
®
Tabel 8: Hexkode til aktivering af den eksterne diagnosegenerering
Parametreringsdata (hex) Funktion
00, 00 ,00 ,06 ,81 ,00 ,00 ,01 ,00 Diagnose-alarmer genereres i tilfælde af fejl(enabled = on)
00, 00, 00, 06, 81, 00, 00, 01, 01 Diagnose-alarmer genereres ikke i tilfælde af fejl(disabled = off, fabriksindstilling)
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
00
I
19
20
Fremgangsmåde for idrifttagning af feltomformeren MOVIDRIVE®
DI00 = /Regulatorspærre
DI01 = Ingen funktion
ID02 = Ingen funktion
ID03 = Ingen funktion
ID04 = Ingen funktion
ID05 = Ingen funktion
DCOM = Ref. X13:DI00 ... DI05
VO24 = + 24 V
DGND = Ref.-pot. binærsignaler
ST11 = RS-485 +
ST12 = RS-485 -
TF1 = TF-indgang
DGND = Ref.-pot. binærsignaler
DB00 = /Bremse
DO01-C = Relækontakt
DO01-NO = Slutterelæ
DO01-NC = Bryderelæ
DO02 = /Fejl
VO24 = + 24 V
VI24 = + 24 V (ekstern forsyning)
DGND = Ref.-pot. binærsignaler
Frikobling af effekt-udgangstrinnet via jumper [1]
+-
X13:DI00DI01DI02DI03DI04DI05DCOMVO24DGNDST11ST12
24 V ext.
---
TF1DGNDDB00DO01-CDO01-NODO01-NCDO02VO24VI24DGND
X10:
[1]
1234567891011
12345678910
00
I
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
®
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
00
I
21
22
5.1 Styring af feltomformeren
Styrings-eksempel forSimatic S5
®’
50234AXXFig. 6: Afbildning af PROFIBUS-data’ene i PLC-adresseområdet ([1] = parameterkanal /
[2] = PLC-adresseområde)
PW148PW150
PW152PW154PW156PW158PW160 PE 1
PA 1
PE 1
PA 1
PE 2
PA 2
PE 2
PA 2
PE 3
PA 3
PE 3
PA 3
E Q
PW148PW150PW152PW154PW156PW158PW160
[1]
[1][2]
00
I
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
STEP5programeksempel
®
Styrings-eksempel forSimatic S7 SFC 14 DPRD_DAT SFC15 DPWR_DAT
//Konsistent indlæsning af aktuelle værdierL PW 160 //PE1 loades (statusord 1)L PW 158 //PE2 loades (aktuel værdi for omdrejningstal)L PW 156 //PE3 loades (ingen funktion)
//Konsistent udlæsning af setpunkt-værdierL KH 0T PW 160 //0hex skrives til PA3 (har dog ingen funktion)L KF +1500T PW 158 //1500dec skrives til PA2 (omdrejnings-setpunkt = 300 1/min)L KW#16#0006T PW 156 //6hex skrives til PA1 (styreord = frikobling)
Procesdata-konfiguration STEP7-adgang via
1 PD ’Load’- / ’transfer’-kommandoer
2 PD ’Load’- / ’transfer’-kommandoer
3 PD Systemfunktioner SFC14/15 (længde 6 byte)
6 PD Systemfunktioner SFC14/15 (længde 12 byte)
10 PD Systemfunktioner SFC14/15 (længde 20 byte)
Param + 1 PD Parameterkanal: Systemfunktioner SFC14/15 (længde 8 byte)Procesdata: ’Load’- / ’transfer’-kommandoer
Param + 2 PD Parameterkanal: Systemfunktioner SFC14/15 (længde 8 byte)Procesdata: ’Load’- / ’transfer’-kommandoer
Param + 3 PD Parameterkanal: Systemfunktioner SFC14/15 (længde 8 byte)Procesdata: Systemfunktioner SFC14/15 (længde 6 byte)
Param + 6 PD Parameterkanal: Systemfunktioner SFC14/15 (længde 8 byte)Procesdata: Systemfunktioner SFC14/15 (længde 12 byte)
Param + 10 PD Parameterkanal: Systemfunktioner SFC14/15 (længde 8 byte)Procesdata: Systemfunktioner SFC14/15 (længde 20 byte)
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
00
I
23
24
STEP7 program-eksempel
®
5.2 PROFIBUS-DP timeout
®
"BUS-FAULT"® P831 Reaktion feltbus-timeout
P819 Feltbus timeout
®
//Start på den cykliske programbearbejdning i OB1BEGINNETWORKTITLE =Kopiér PE-data fra omformer til DB3, ord 0/2/4CALL SFC 14 (DPRD_DAT) //Read DP Slave Record
LADDR := W#16#240 //Input-adresse 576RET_VAL:= MW 30 //Resultat i markerord 30RECORD := P#DB3.DBX 0.0 BYTE 6 //Cursor
NETWORKTITLE = PLC-program med drivstationsapplikation// PLC-program anvender procesdata i DB3 til// drivstationsstyring
L DB3.DBW 0//PE1 loades (statuswort 1)L DB3.DBW 2 //PE2 loades (aktuel værdi for omdrejningstal)L DB3.DBW 4 //PE3 loades (ingen funktion)
L W#16#0006T DB3.DBW 20//6hex skrives til PA1 (styreord = frikobling)L 1500T DB3.DBW 22//1500dec skrives til PA2 (omdrejnings-setpunkt = 300 1/min)L W#16#0000T DB3.DBW 24//0hex skrives til PA3 (har dog ingen funktion)
//Aslutning på den cykliske programbearbejdning i OB1NETWORKTITLE =Kopiér PA-data fra DB3, ord 20/22/24 til omformerCALL SFC 15 (DPWR_DAT) //Write DP Slave Record
LADDR := W#16#240 //Udgangsadresse 576 = 240hexRECORD := P#DB3.DBX 20.0 BYTE 6 //Cursor på DB/DWRET_VAL:= MW 32 //Resultat i markerord 32
00
I
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
5.3 Reaktion feltbus-timeout
5.4 Parametrering via PROFIBUS-DP®
Opbygning afparameter-kanalen
01065CXXFig. 7: Kommunikation via PROFIBUS-DP med parameterkanal [1] og procesdatakanal [2]
Tabel 9: Opbygning af parameterkanalen
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7
Administra-tion Reserveret
Indeks-high Indeks-low Data MSB Data Data Data LSB
Parameter-indeks 4 byte data
E Q
[1]
[1]
[2]
[2]
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
00
I
25
26
Administration afparameterkanalen
Indeks-adressering
Tabel 10: Opbygning af administrations-byte’n
7 / MSB 6 5 4 3 2 1 0 / LSB
Tjeneste-identifikation0000 = No Service0001 = Read Parameter0010 = Write Parameter0011 = Write Parameter volatile0100 = Read Minimum0101 = Read Maximum0110 = Read Default0111 = Read Scale1000 = Read Attribute
Datalængde00 = 1 byte01 = 2 byte10 = 3 byte11 = 4 byte (skal være indstillet!)
’Handshake’-bitskal ved cyklisk overførsel skiftes ved hver ny opgave
Status-bit0 = ingen fejl ved udførelse af tjenesten1 = fejl ved udførelse af tjenesten
00
I
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
Dataområde
Fejlbehæftettjenesteudførelse
Læsning af enparameter viaPROFIBUS-DP(READ)
Tabel 11: Definition af dataområdet i parameterkanalen
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7
Admini-stration
Reserveret Indeks-high Indeks-low Data MSB Data Data Data LSB
High-byte 1 Low-byte 1 High-byte 2 Low-byte 2
High-ord Low-ord
Dobbeltord
Tabel 12: Opbygning af parameterkanalen ved fejlbehæftet udførelse af tjenesten
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7
Admini-stration
Reserveret Indeks-high Indeks-low Error Class Error Code Add. Codehigh
Add. Codelow
Statusbit = 1: Fejlbehæftet udførelse af tjenesten
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
00
I
27
28
Skrivning af enparameter viaPROFIBUS-DP(WRITE)
Tabel 13: READ-tjeneste-kodning i administrationsbyte’n
7 / MSB 6 5 4 3 2 1 0 / LSB
0 0/1 X X 0 0 0 1
Service-identifikation0001 = ’Read’-parameter
Datalængdeikke relevant for ’Read’-tjeneste
’Handshake’-bitskal ved cyklisk overførsel skiftes ved hver ny opgave
Status-bit0 = ingen fejl ved udførelse af tjenesten1 = fejl ved udførelse af tjenesten
X = ikke relevant0/1 = bitværdi skiftes
00
I
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
Parametrerings-forløb vedPROFIBUS-DP
Tabel 14: "WRITE"-tjeneste-kodning i administrationsbyte’n
7 / MSB 6 5 4 3 2 1 0 / LSB
0 0/1 1 1 0 0 1 0
Service-identifikation0010 = "Write"-parameter
Datalængde11 = 4 byte
’Handshake’-bitskal ved cyklisk overførsel skiftes ved hver ny opgave
Status-bit0 = ingen fejl ved udførelse af tjenesten1 = fejl ved udførelse af tjenesten
0/1 = bitværdi skiftes
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
00
I
29
30
Parameter-dataformat
Parameterfortegnelse MOVIDRIVE®
Tabel 15: Forløb af parametreringen via PROFIBUS-DP
Styring PROFIBUS-DP Feltomformer (slave)
-- 00110010XXX... → Parameterkanal modtages, menevalueres ikke← 00110010XXX... --
Parameterkanalenforberedes til "Write"-tjenesten
’Handshake’-bit’enskiftes og tjenestenovergives til felt-omformeren -- 01110010XXX... →
← 00110010XXX... --
-- 01110010XXX... →
← 00110010XXX... -- "Write"-tjenesten er udført, ’hand-shake’-bit’en skiftes
Tjenestebekræftelsemodtaget, da sende- ogmodtage-’handshake’-bitnu atter stemmeroverens
← 01110010XXX... --
-- 01110010XXX... → Parameterkanal modtages, menevalueres ikke
00
I
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
6.1 Elementer
Ved forkert parametrering sender feltomformeren forskellige svarkoder tilbage til denparametrerende master; disse svarkoder indeholder detaljerede oplysninger om fejl-årsagen. Generelt er disse svarkoder strukturmæssigt opbygget. Der skelnes mellem el-ementerne
• Error-Class
• Error-Code
• Additional-Code
Disse svarkoder er beskrevet entydigt i manualen for feltbus-kommunikationsprofilen ogindgår ikke i denne dokumentation. I forbindelse med PROFIBUS kan der dog optrædefølgende særlige tilfælde:
Error-Class Med elementet "Error-Class" klassificeres fejltypen mere detaljeret. ®
understøtter følgende i henhold til EN 50170 (V2) definerede fejlklasser:
I tilfælde af fejlbehæftet kommunikation genereres "Error-Class" af feltbuskortets kom-munikations-software - med undtagelse af Error-Class 8 = Andre fejl. Svarkoder, somsendes fra feltomformersystemet, hører alle til i kategorien Error-Class 8 = Andre fejl.En mere detaljeret klassificering af fejlen sker med elementet Additional-Code
Error-Code Elementet "Error Code" muliggør en mere detaljeret klassificering af fejlårsagen indenfor "Error-Class" og genereres i tilfælde af fejlbehæftet kommunikation af feltbuskortetskommunikations-software. For Error-Class 8 = Andre fejl er det kun Error-Code = 0(Anden fejlkode), der er defineret. Den detaljerede klassificering sker i dette tilfælde iAdditional Code
Tabel 16: Fejlklasser efter EN 50170 (Error-Class)
Class (hex) Betegnelse Betydning
1 vfd-state Statusfejl i den virtuelle feltenhed
2 application-reference Fejl i anvendelsesprogram
3 definition Definitionsfejl
4 resource Ressource-fejl
5 service Fejl ved tjenesteudførelsen
6 access Adgangsfejl
7 ov Fejl i objektfortegnelsen
8 other Andre fejl (se "Additional-Code")
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
00
I
31
32
Additional Code Additional-Code indeholder de SEW-specifikke svarkoder for forkert parametrering affeltomformeren. De tilbagesendes til master’en under Error-Class 8 = Andre fejl. Neden-stående tabel viser alle mulige kodninger for Additional-Code
6.2 Særlige tilfælde
Særlige svar-koder (særligetilfælde)
Tabel 17: Liste over Additional Codes for Errorclass 8 = Andre fejl
Add.-Codehigh (hex)
Add.-Code low(hex)
Betydning
00 00 Ingen fejl
00 10 Ulovligt parameter-indeks
00 11 Funktion/parameter ikke implementeret
00 12 Kun læseadgang tilladt
00 13 Parameterspærre er aktiv
00 14 Fabriksindstilling er aktiv
00 15 Værdi for parameter for stor
00 16 Værdi for parameter for lille
00 17 Til denne funktion/parameter mangler det nødvendige optionskort
00 18 Fejl i system-software
00 19 Parameteradgang kun via RS485-proces-grænseflade til X13
00 1A Parameteradgang kun via RS485-diagnose-grænseflade
00 1B Parameter er adgangsbeskyttet
00 1C Regulatorspærre nødvendig
00 1D Utilladelig værdi for parameter
00 1E Fabriksindstilling er aktiveret
00 1F Parameter er ikke lagret i EEPROM’en
00 20 Parameter kan ikke ændres med frikoblet udgangstrin
00
I
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
Forkert tjeneste-kodning iparameterkanalen
Forkert længde-angivelse iparameterkanalen
Tabel 18: Svarkode ved forkert kodning af byte 0 og 1 i parameterkanalen
Kode (dec) Betydning
Error-Class: 5 Service
Error-Code: 5 Illegal parameter
Add.-Code high: 0 -
Add.-Code low: 0 -
Tabel 19: Svarkode for forkert længdeangivelse i parameterkanalen (længde ≠ 4)
Kode (dec) Betydning
Error-Class: 6 Access
Error-Code: 8 Type conflict
Add.-Code high: 0 -
Add.-Code low: 0 -
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
00
I
33
34
Intern kommunika-tionsfejl
Svarkoden, som er anført i nedenstående tabel, tilbagesendes, hvis der er opstået enintern kommunikationsfejl. Den parametertjeneste, der er transmitteret via feltbussen, ermuligvis ikke blevet udført og bør gentages. Hvis denne fejl optræder gentagne gange,skal der slukkes helt for feltomformeren, hvorefter den skal genindkobles, således at derkan foretages en ny initialisering.
Gentag "Read"- eller "Write"-tjenesten. Optræder fejlen igen, skal De slukke helt for felt-omformeren og derefter genindkoble den. Hvis fejlen optræder permanent, bedes Dekontakte SEW Elektronik-Service for råd og vejledning.
Tabel 20: Svarkode ved intern kommunikationsfejl
Kode (dec) Betydning
Error-Class: 6 Access
Error-Code: 2 Hardware Fault
Add.-Code high: 0 -
Add.-Code low: 0 -
00
I
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
7.1 Diagnose-forløb
Feltbus-omformerprofil ogparameterfortegnelse MOVIDRIVE®
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
00
I
35
36
↓
→
↓
BUS-FAULT
→
→
↓
Baudrate feltbus
↓
Adresse feltbus
↓
→
↓
↓
↓
"MOVIDRIVE+DFP21"
"Param + 3PD"
↓
PD-konfiguration
↓
Baudrate feltbus
↓
00
I
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
BUS FAULT
↓
↓
↓
→
↓
SETPUNKTKILDE FELTBUSSTYREKILDE FELTBUSFRIKOBLE PA-DATA JA
↓
→
↓
↓
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
00
I
37
38
Sagsnummer PROFIBUS-grænseflade
• 823 618 6
Profibus-protokolvarianter • PROFIBUS-DP efter EN 50170 V2 / DIN E 19245 T3
Automatisk baudrate-detektering fra
• 9,6 kbaud ... 12 Mbaud
Tilslutningsteknik • Via 9-polet sub-D-stik• Stikkonfiguration efter EN 50170 (V2)
Busterminering • Ikke integreret, via PROFIBUS-stik
Stationsadresse • 0-125 indstillelig via DIP-switche
Navn på GSD-fil • SEW_6003.GSD
DP-ident-nummer • 6003hex = 24579dec
Anvendelsesspecifikkeparametreringsdata(Set-Prm-UserData)
• Længde 9 byte• Hex-parametrering 00,00,00,06,81,00,00,01,01 = DP-diagnose-
alarm = OFF• Hex-parametrering 00,00,00,06,81,00,00,01,00 = DP-diagnose-
alarm = ON
DP-konfigurationer forDDLM_Chk_Cfg
• F0hex = 1 procesdataord (1 I/O-ord)• F1hex = 2 procesdataord (2 I/O-ord)• F2hex = 3 procesdataord (3 I/O-ord)• 0hex, F5hex = 6 procesdataord (6 I/O-ord)• 0hex, F9hex = 10 procesdataord (10 I/O-ord)• F3hex, F0hex = parameterkanal + 1 procesdataord (5 I/O-ord)• F3hex, F1hex = parameterkanal + 2 procesdataord (6 I/O-ord)• F3hex, F2hex = parameterkanal + 3 procesdataord (7 I/O-ord)• F3hex, F5hex = parameterkanal + 6 procesdataord (10 I/O-ord)• F3hex, F9hex = parameterkanal + 10 procesdataord (14 I/O-ord)
Diagnose-data • Maks. 8 byte• Standard-diagnose 6 byte
Hjælpeværktøjer tilidrifttagningen
• PC-program MOVITOOLS®
• Betjeningsenhed DBG11
Pi
fkVA
Hz
n
Manual, MOVIDRIVE® Feltbus-interface DFP21A PROFIBUS DP (12 Mbaud)
Installations- og driftsvejledning MOVIDRIVE® compact MCS41A 39
Indeks
AAdditional Code ............................................ 32Administration af parameterkanal ...................... 26
BBaudrate ................................................10, 38Bestykning .....................................................9BUS FAULT ................................................. 12Buskabel ..................................................... 10Busterminering ............................................. 38
DDataformat parameter .................................... 30Dataområde parameterkanal ........................... 27DFP11A / DFP21A ..........................................6Diagnose .......................................................5Diagnosedata ............................................... 38DP-ident-nummer .......................................... 38DP-konfiguration ........................................... 14DP-konfiguration, universel .............................. 15DP-konfigurationer ......................................... 38
EError-Class .................................................. 31Error-Code ................................................... 31
FFejlbehæftet tjenesteudførelse ......................... 27Fejldiganose ................................................. 35Feltbus-monitor ...............................................5Forløb af parametrering .................................. 30Forside ..........................................................9
GGSD-fil ........................................................ 38
IIdent-nummer ............................................... 38Idrifttagning .................................................. 19Indeks-adressering ........................................ 26Indikeringselementer ...................................... 12Intern kommunikationsfejl ................................ 34
KKommunikationsfejl, intern .............................. 34Konfiguration ..................................................5
LLængdeangivelse .......................................... 33Læsning af parameter .................................... 27LEDs .......................................................... 12
OOmformertyper ...............................................8Opbygning af parameterkanal .......................... 25Overvågningsfunktioner ....................................5
PParameter læsning ........................................ 27Parameter skrivning ....................................... 28Parameter-dataformat .................................... 30Parametering, Forløb ..................................... 30Parameterkanal ............................................ 25
Parameterkanal, administration ........................ 26Parameterkanal, opbygning ............................. 25Parametrering via PROFIBUS-DP .................... 25Parametreringsdata ....................................... 38PROFIBUS-DP Timeout ................................. 24Programeksempel STEP5 ............................... 23Programeksempel STEP7 ............................... 24Protokolvarianter ........................................... 38
RREAD ......................................................... 27RUN ........................................................... 12
SSagsnummer ................................................ 38Simatic S5 ................................................... 22Simatic S7 ................................................... 23Skærmning af buskabel .................................. 10Skrivning af parameter ................................... 28Stationsadresse ............................................ 38STEP5 ........................................................ 23STEP7 ........................................................ 24Styring ........................................................ 22Styringseksempel Simatic S5 ........................... 22Styringseksempel Simatic S7 ........................... 23Svarkoder .................................................... 31
TTekniske data ............................................... 38Tilslutningsteknik ........................................... 38Timeout ....................................................... 24Tjeneste-kodning .......................................... 33Tjenesteudførelse, fejlbehæftet ........................ 27Trækning af buskabel ..................................... 10
UUnderstøttede omformertyper ............................8Universel DP-konfiguration .............................. 15
WWRITE ........................................................ 28
SEW-EURODRIVE GmbH & Co · P.O. Box 3023 · D-76642 Bruchsal/Germany · Phone +49-7251-75-0Fax +49-7251-75-1970 · http://www.sew-eurodrive.com · [email protected]