Uludağ Klima Soğutma Sist.Ltd.Ş. Tel: (224) 243 70 71 Faks: (224) 243 88 96 www.uludagklima.com [email protected] Pano Kliması Enclosure Cabinet Cooler Schaltschrank - Kühlgeräte Montaj ve Kullanım Kılavuzu Device Work Schedule Einbau-und Benutzerhandbuch www.uludagklima.com [email protected] 444 3 780 Tel : +90 224 243 70 71 Faks: +90 224 243 88 96

Pano Kliması Enclosure Cabinet Cooler …en.uludagklima.com/Uploads/files/calisma-kilavuz.pdfUludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 [email protected]

Embed Size (px)

Citation preview

Page 1: Pano Kliması Enclosure Cabinet Cooler …en.uludagklima.com/Uploads/files/calisma-kilavuz.pdfUludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 info@uludagklima.com

Uludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 www.uludagklima.com [email protected]

Pano Kliması

Enclosure Cabinet Cooler

Schaltschrank - Kühlgeräte

Montaj ve Kullanım Kılavuzu

Device Work Schedule

Einbau-und Benutzerhandbuch

www.uludagklima.com [email protected]

444 3 780

Tel : +90 224 243 70 71 Faks: +90 224 243 88 96

Page 2: Pano Kliması Enclosure Cabinet Cooler …en.uludagklima.com/Uploads/files/calisma-kilavuz.pdfUludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 info@uludagklima.com

ULUDAĞ PANO KLİMA

SOLUTION OF PROBLEMS

CAUSED BY HEAT Summer months approaches, temperature rises in enclosures (approximately 45-60 °C) with this increase, unscheduled downtime is inevitable. Against to this expected and said "l'M COMING" danger, precautions to be taken is our enclosure cabinet coolers. Uludag enclosure cabinet cooler devices; put an end to breaks in production..! Uludag enclosure cabinet cooler devices; put an end to breaks in production..! During the guarantee period, what may come per unit the unlimited scope of our device is under warranty.When you send the device to our address (without specifying any excuse) failure shall be removed within the same busi-ness day. if the device can not be resolved within 3 business days then new product will be sent to the user. Delivery time is one day in all our products. All sheet metal parts of our products is stainless steel. You can get the smooth automation solutions with using our products equipped with the components known as class A in the world. Danfoss compressors and EbmPapst fans are used on our products.

Page 3: Pano Kliması Enclosure Cabinet Cooler …en.uludagklima.com/Uploads/files/calisma-kilavuz.pdfUludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 info@uludagklima.com

ULUDAĞ PANO KLİMA

1.ASSEMBLY :

1.1 Fully wired ready for connection, including drilling template, and assembly parts.

1.2 Cut out the sections and drill according to the template.

Page 4: Pano Kliması Enclosure Cabinet Cooler …en.uludagklima.com/Uploads/files/calisma-kilavuz.pdfUludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 info@uludagklima.com

ULUDAĞ PANO KLİMA

1.3 ASSEMBLY WITH SCREWS Screw tapped pins into the blind nuts on the rear of the unit.

1.4. ENERGIZE THE DEVICE WITH THE SENT CABLE (220 V)

Page 5: Pano Kliması Enclosure Cabinet Cooler …en.uludagklima.com/Uploads/files/calisma-kilavuz.pdfUludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 info@uludagklima.com

ULUDAĞ PANO KLİMA

2.Product Details :

DIMENSION

X Y Z A B C D E F G H

Svk500 320 228 470 188 164 130 45 115 230 380 188

Svk1000 350 207 695 270 165 193 60 223 27 550 200

Svk2000 400 237 850 250 250 259 70 243 300 650 250

Svk3000 400 258 950 314 210 357 74 272 330 770 254

Svk4000 500 285 1004 224 224 410 90 228

T 2000 400 700 408 230 60 380 60 100 250 613 230

T 4000 444 780 450 250 75 437 75 100 300 700 250

Page 6: Pano Kliması Enclosure Cabinet Cooler …en.uludagklima.com/Uploads/files/calisma-kilavuz.pdfUludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 info@uludagklima.com

ULUDAĞ PANO KLİMA

Organize Sanayi Bölgesi

Demirciler Sitesi

D Blok No:2

Nilüfer / BURSA / TURKEY

Telefon: +90 (224)23 70 71

Faks: +90 (224) 243 88 96

Tecnic Data Svk-500 Svk-1000 Svk-2000 Svk-3000 T-2000 T-4000

Cooling capacity L35 L35 450 W 1000 W 1700 W 2700 W 1700 W 3700 W

Type of refrigerant R 134a R 134a R 134a R 134a R 134a R134a

Amount of refrigerant 290 gr 410 gr 550 gr 630 gr 630 gr 1150 g

Thermostat setting 34 °C 34 °C 34 °C 34 °C 34 °C 34 °C

Hysteresis 4K 4 K 4 K 4 K 4 K 4 K

External circuit 540 m³/h 540 m³/h 945 m³/h 1175 m3/h 1005 m3/h 1800 m³/h

Internal circuit 290 m³/h 540 m³/h 945 m³/h 945 m³/h 945 m³/h 1175 m³/h

Rated frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz

Standard power supply 198 V-252 V 198 V…252 V 198 V…252 V 198 V…252 V 198 V…252 V 380 V

Running current 1.6 A 3.2 A 4.2 A 6.5 A 4.2 A 6.8 A

Starting current 5.2 A 16.2A 17.2A 21.2A 17.2A 35,7 A

Weight 19 kg 35 kg 40 kg 45 kg 40 kg 62 kg

Height x Width x Depth mm 470*320*215 670*350*207 850*400*230 950*400*255 410*700*400 445*787*450

Ambient air temperature +15 °C 55 °C

Corrosion protection (cover) Stainless / Paslanmaz Çelik

Orientation Wall Mount Top Mount

System of protection IP 54

Fans EbmPapst

Compressor DANFOSS DANFOSS DANFOSS DANFOSS DANFOSS EMBRACO

Page 7: Pano Kliması Enclosure Cabinet Cooler …en.uludagklima.com/Uploads/files/calisma-kilavuz.pdfUludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 info@uludagklima.com

ULUDAĞ PANO KLİMA

3.1.CONDENSER CARE 1. Be sure the energy of the device turned

off before open the front door.

2. Clean the condenser with preassured air

from oil,dust etc.(Dirt on the condenser

may couse insufficient heat transfere,

getting failed rapidly and high

energy consumption. Solvent can be used

if contamination is heavy.)

3. Clean the dirt on fan blades. (Dirt cau-

ses to fan balance and to fail in a short

time).

4. Check the drain hose. Remedy the defects

if there are breaks or obstructions.

(Otherwise condensation water may

splash into the panel.)

5. Check the electrical connection cable.

(Abrasion or dislocation may lead short

circuit and fail of the device.)

6. Check the thermostat settings for the device. Be sure the values are adjusted to the recomen-

dation of the seller. (34 ° C - 38 ° C)

7. Turn on the energy after the lid of the device is closed. (Operating the device while lid is open

may cause injuries or malfunction.)

3.MAINTENANCE :

15-day period of your device in the condenser, evaporator care has to be made in annual periods. Depending on the situation of environment pollution, you must specify the period. (May extend or decrease)

Page 8: Pano Kliması Enclosure Cabinet Cooler …en.uludagklima.com/Uploads/files/calisma-kilavuz.pdfUludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 info@uludagklima.com

ULUDAĞ PANO KLİMA

3.2.Evaporator CARE:

1. Turn off the energy and unscrew

the 8 pcs bolts inside of the device

and remove the fan cover.

2. Clean the oil,dust etc. with preas-

sured air from the evaporator cel-

lular which under the fan engine.

To check the dreinage line’s effici-

ency, pour some water into the

evaporator pan and wach for obst-

ructions.

3. Clean the dirt on fan blades.

4. Check the electrical connection

cable.

5. Replace the fan cover back and

turn the energy on.

6. Check the thermostat settings for

the device. Be sure the values are adjusted to the recomendation of the seller. (34 ° C - 38 ° C)

Page 9: Pano Kliması Enclosure Cabinet Cooler …en.uludagklima.com/Uploads/files/calisma-kilavuz.pdfUludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 info@uludagklima.com

ULUDAĞ PANO KLİMA

3.3. Before the notify service :

The device does not work? Check electrical connections. Device is receiving power but not working? Check the thermostat

value. (Set value should be below ambient temperature) Device is working. but it does not blow cold air / not enough to blow?

Check that the fan is running clogged evaporator. Clean the evaporator, as described above.

Shortly after the device works, but is disabled? Check the thermostat

value. (Operating temperature range from ambient temperature must be below) Make sure the condenser fan is running. Make sure the condenser is clean If not, see above instructions for cleaning condenser (the high pressure circuit protection may be on.

Device is working. but it does not come from the circuit? Check the

thermostat settings for the device. In the heat value of the firm suggests that you pay attention to (34 ° C - 38 ° C). Ambient air from outside is input to the clipboard, you check. The door panels may be left open.

Important Notice!!! The device is running, the cover must be closed. When you open the lid, turn off power. Otherwise, the environment and the dust will block evaporator

Page 10: Pano Kliması Enclosure Cabinet Cooler …en.uludagklima.com/Uploads/files/calisma-kilavuz.pdfUludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 info@uludagklima.com

ULUDAĞ PANO KLİMA

4. The DIGITAL SETTING

ADVANCED PROGRAMMING FOR DIGITAL DATA sent as attachments of the document.

Page 11: Pano Kliması Enclosure Cabinet Cooler …en.uludagklima.com/Uploads/files/calisma-kilavuz.pdfUludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 info@uludagklima.com

ULUDAĞ PANO KLİMA

factory values of parameters

4.3. back to the factory settings for digital:

By holding the up down buttons pressed for 3 seconds when the device is on, then

enter in menu 1 parameters.

1.MENU PARAMETERS DEFAULT

SL1 Set1 value minimum parameter 26

SH1 Set1 value maximum parameter 99

HS1 Hysteresis parameter for compressor 0.1

ASA Waiting mode for elevator application 0

Of1 Off-set parameter for cabin sensor 0

Of2 Off-set parameter for condenser sensor 0

Of3 Off-set parameter for evaporater sensor 0

By holding the reset (R) and SET buttons pressed for 3 seconds, then enter in menu parameters.

2.MENU PARAMETERS DEFAULT

SEn Sensors Active-Cancel parameters 1

HCS Selecting heating/cooling functions 0

Pnt Point position parameter 1

ınt Digital Input Type Selection 0

ıno Digital Input Filter Selection 0

ıPo Digital input polarization 0

CSd Start-Stop Delay Parameters 0

Con Sensor fault ON time 0

CoF Sensor fault OFF time 0

Alo Low alarm fault setting 0.0

Ahı High alarm fault setting 99.9

Cnd Condenser sensor value measured

EuP Evaporater sensor value measured

Page 12: Pano Kliması Enclosure Cabinet Cooler …en.uludagklima.com/Uploads/files/calisma-kilavuz.pdfUludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 info@uludagklima.com
Page 13: Pano Kliması Enclosure Cabinet Cooler …en.uludagklima.com/Uploads/files/calisma-kilavuz.pdfUludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 info@uludagklima.com
Page 14: Pano Kliması Enclosure Cabinet Cooler …en.uludagklima.com/Uploads/files/calisma-kilavuz.pdfUludağ Klima Soğutma Sist.Ltd.Şti. Tel: (224) 243 70 71 Faks: (224) 243 88 96 info@uludagklima.com