RefLine UM 01

Embed Size (px)

Citation preview

  • 7/29/2019 RefLine UM 01

    1/37

    Genset and

    Reefer

    Container

    Monitoring

  • 7/29/2019 RefLine UM 01

    2/37

    Operators Manual

    Johnson Control s Denmark

    J ens Juuls Vej 28, 8260 Viby J , DenmarkPhone: +45 87 36 35 00 - Fax: +45 87 36 35 01www.yorkref.com - [email protected]

    CopyrightJohnson Contro ls Denmark

    Al l Rights Reserved

    Table of Contents Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 2 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Operators Manual

    Table of Contents

    Introduct ion ...................................................................................................................................3Overview.................................................................................................................................3RefLine Features ....................................................................................................................5

    Instal lat ion .....................................................................................................................................8Mounting the Modules ............................................................................................................8Mounting the Antennas.........................................................................................................12External Sensors...................................................................................................................14Electrical Connections ..........................................................................................................15SIM Card Installation ............................................................................................................17

    Setting RefLine User Options ....................................................................................................18Service Tool Installation........................................................................................................18Connecting to PC..................................................................................................................19Saving and Retrieving Settings.............................................................................................21ID Setting and Info Fields .....................................................................................................22Analog Input Settings............................................................................................................23Digital Input Settings.............................................................................................................25Mobile Phone Settings..........................................................................................................26GPRS Settings......................................................................................................................27Genset Report Settings ........................................................................................................28Reefer Report Settings .........................................................................................................29Other Settings.......................................................................................................................31

    Specifications..............................................................................................................................32

    Appendices ..................................................................................................................................34Pinouts..................................................................................................................................34Status LEDs..........................................................................................................................35Parts and Accessories..........................................................................................................36Document Revision Record..................................................................................................37

  • 7/29/2019 RefLine UM 01

    3/37

    Operators Manual

    Introduction Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 3 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Introduction

    Overview

    About RefLine RefLine is a mobile data telemetry system that provides reefer and genset statusinformation to J CIs Global Monitoring Server, allowing online monitoring of gensetsand refrigerated cargo in overland transit.

    The RefLine system consists of two modules: the Monitoring Module and theTracking Module. The Monitoring Module is a version of the J CI RMM mastermodem that has been adapted for installation on mobile generator sets. It gatherstemperature and other data from reefers equipped with ISO-10368 modems.

    The Tracking Module, which is also available as a stand-alone version calledComPosIT, features an onboard GPS receiver and sensor inputs that report thegenerators location, fuel level, and operating status. It transmits data via the GSMcellular network to J CIs Global Monitoring Server in Denmark.

    Users monitor their cargo and equipment through password-protected accounts tothe Reefers Online website at www.reefers-online.com.

    Continued on next page

  • 7/29/2019 RefLine UM 01

    4/37

    Operators Manual

    Introduction Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 4 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Overview, Continued

    About ReefersOnline

    Reefers Online is the web-based interface for the Global Monitoring Server (GMS),which collects and stores data from J CIs REFCON, RefLine, and RefBox reefermonitoring systems. These effective monitoring solutions for shipping terminals,warehouses, ships, trains, and trucks record data from reefer containers and send it

    to the Global Monitoring Server via Internet connections, satellites, and the GSMmobile phone network.

    Included items The RefLine system is shipped with the following items.

    RefLine Monitoring Module RefLine Tracking Module Tracking Module installation box with module mounting plate GSM antenna with 5 m cable GPS antenna with 5 m cable

  • 7/29/2019 RefLine UM 01

    5/37

    Operators Manual

    Introduction Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 5 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    RefLine Features

    .Introduction The RefLine system is flexible and can be configured with options to add local

    monitoring capabilities. This section describes the standard and optional features.

    GSM datatelemetry

    The RefLine system sends data over the GSM mobile phone network on the 850,900, 1800, and 1900 MHz bands. This requires a data-enabled GSM account and aSIM card (not included).

    Using the GSM network, the system can send

    Status reports and user-defined alarms to the Global Monitoring Server, and User-defined SMS alarms to up to 4 GSM mobile phones.

    This data is transmitted via the GSM networks GPRS mobile data service or Short

    Message Service (SMS) using text messages. GPRS transmission is usually moreeconomical than SMS transmission.

    To obtain GSM service, consult with a local GSM mobile phone provider and select aservice that provides data via GPRS. Note: Tell the GSM provider that you needto disable the SIM cards PIN code request, as not all SIM cards allow you to dothis.

    More information about the GSM system, including coverage maps, is available fromwww.gsmworld.com.

    If you will rely solely on SMS text messages, please verify that the GSM provider youselect supports text messaging through circuit-switched core network services

    rather than packet switched services. You may also want to consider installing anSMS Bridge, available from JCI, that relays SMS messages sent to a domesticnumber.

    Gensetmonitoringinformation

    The standard configuration of the RefLine system provides the following genset datavia Reefers Online:

    Position coordinates (formatted for Google Earth) Location and region (defined by user database) Days stationary at current location Total generator run time, in hours Generator run time since trip start, in hours Fuel level and consumption rate Genset state: running / off / shutdown

    Continued on next page

  • 7/29/2019 RefLine UM 01

    6/37

    Operators Manual

    Introduction Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 6 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    RefLine Features, Continued

    Standard reeferinformation

    In accordance with the ISO 10368 standard for remote condition monitoring offreight thermal containers, the RefLine Monitoring Module provides the followinginformation if it is supported by the reefer controller.

    Container Identification/Operating mode

    Temperatures Alarms

    Container ID Cool max Cool reduced Modulation Fan reduction Heat reduced Heat max

    Alarm shutdown Off Recent Defrost

    Set-point temperature Return air temperature Supply air temperature

    Power Up Sensor failure High Evaporator

    temperature High head Evaporator fan motor Condenser fan motor

    Compressor Defrost termin. on time

    limit Temp. out of range Low pressure Low compressor oil

    pressure Pump down on time

    limit Charge Microprocessor faulty Alarm reset

    Fuse control

    Extended reeferinformation

    RefLine supports the extended alarm codes implemented in controllers from thefollowing manufacturers: Carrier Daikin Thermo King

    GPS receiver The onboard Global Positioning System (GPS) receiver determines the cargos exactlocation. The GPS antenna must be exposed to the sky.

    Analog sensorinputs

    The system has two inputs for connection of analog sensors such as temperature orfuel gauges. In the standard configuration, the genset fuel gauge is connected toanalog input 1. The second input is available for monitoring something else.

    The inputs are compatible with the following sensor types:

    -25 to 30 C NTC temperature sensors 0 to 5 V (0 to 10 V with voltage divider) 4 to 20 mA

    Continued on next page

  • 7/29/2019 RefLine UM 01

    7/37

    Operators Manual

    Introduction Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 7 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    RefLine Features, Continued

    Digital sensorinputs

    Their are two inputs for connection of switches, relays, or digital sensors. TheTracking Module can generate alarms and/or activate auxiliary devices in responseto changes to the sensor input.

    In the standard configuration, the genets run switch and oil pressure sensor areconnected to the digital inputs. Using the following logic, Reefers Online reports thegenerator operating condition.

    Oil pressure detected: genset is running Run switch off: genset is off Run switch on but no oil pressure: genset is shut down

    Low power

    sleep mode

    The Tracking Module has a very low power sleep mode that prevents it from

    draining the generators battery when the generator is not in use.

    When this feature is enabled, the system goes to sleep and consumes little powerwhen the generator is switched off. It wakes up briefly every 5 minutes to check theinputs, and the Tracking Module continues to send status reports as scheduled.

    Sleep mode must be disabled as described on page 31 if the genset run switchis not connected to digital input 1.

    Battery voltagemonitor

    The Tracking Module monitors the battery voltage and can send an alarm if it fallsbelow a specified value.

    Auxi liary devices The Tracking Module has two solid-state 2 A relays (digital outputs) that can controlauxiliary devices in response to user-defined alarms. The relays provide the DCsupply voltage. To prevent draining the battery, the relay outputs open when theTracking Module is in sleep mode.

    If you choose to control devices with the Tracking Module, be sure to consider theeffect of the load on the battery.

  • 7/29/2019 RefLine UM 01

    8/37

    Operators Manual

    Installation Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 8 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Installation

    Mounting the Modules

    Dimensions

    Introduction This section describes two methods for mounting the modules on the genset. Fastening through unthreaded holes Fastening to threaded holes

    Mounting the monitoring module with vibration-damping rubber stud mounts isrecommended.

    Caution! Turn off the generator when mount ing and connecting the devices.

    Continued on next page

  • 7/29/2019 RefLine UM 01

    9/37

    Operators Manual

    Installation Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 9 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Mounting the Modules, Continued

    Tools andmaterials

    required

    You need the following tools: Drill and drill bits Mechanical hand tools including Torx 10 screwdriver 4 mm and 8 mm taps if cutting threads Wire and accessories to connect gauges, sensors, and optional auxiliary devices GSM SIM card

    Fastenersrequired

    To mount the Monitoring Module, you need: 6 pcs 8 mm rubber stud mounts (recommended), or 6 pcs 8 x 20 mm stainless steel bolts 6 pcs 8 mm stainless steel lock nuts (if using unthreaded holes) 6 pcs 8 mm stainless steel lock washers (if using threaded holes)

    To mount the Tracking Module, you need 4 pcs 4 x 20 mm stainless steel screws 4 pcs 4 mm stainless steel lock nuts (if using unthreaded holes) 4 pcs 4 mm stainless steel lock washers

    Module location The RefLine modules are suitable for installation inside or outside the gensethousing. They are provided with extra long cables with lengths as follows:

    Monitoring Module power cable: 2.8 m (9 ft.) Monitoring Module data cable: 2.5 m (8 ft.) GSM antenna cable: 5 m (16 ft)

    GPS antenna cable: 5 m (16 ft)

    MonitoringModuleinstallation

    Mount the Monitoring Module as follows.

    Step Action

    1 Find a location on the genset for the module that will allow the powercable to reach the connection point, which is typically a connection blockat the outlet socket junction.

    2 Using the mounting plate as the guide, carefully mark the location of themounting holes. Note:

    Fastening with rubber stud mounts is recommended. If fastening with nuts and bolts through unthreaded holes, you can use

    either the 10 mm or the 8 mm holes in the mounting plate. If fastening to threaded holes cut in the genset housing, use the 10

    mm holes in the RMM mounting plate. (Fastening through two sets ofthreads is not recommended.)

    3 Make sure that you can drill through the generator housing withoutdamaging anything.

    4 Drill the mounting holes using a 6.8 mm drill bit if you intend to cut threads using an 8 mm tap 8.5 mm drill bit for unthreaded holes

    5 (Optional) Cut the threads in the mounting holes.

    6 Fasten the Monitoring Module securely to the genset with 6 sets oflocking 8 mm hardware.

  • 7/29/2019 RefLine UM 01

    10/37

    Operators Manual

    Installation Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 10 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Mounting the Modules, Continued

    Tracking Modulebox installation

    Mount the installation box for the Tracking Module as follows.

    Step Action

    1 Find the location for the box that provides the best protection fromtampering and moisture. The cable pass-through fittings must pointdown to prevent moisture from creeping into the box.

    2 The box is fastened through the 5 mm holes between the holes for thecover screws. Mark the positions of the holes on the generator set.

    3 Drill the mounting holes using a 3.2 mm drill bit if you intend to cut threads using a 4 mm tap 4.5 mm drill bit for unthreaded holes

    4 (Optional) Cut threads in the mounting holes.5 Install the Tracking Module in the box as described below, then fasten

    the mounting box to the genset with suitable 4 mm hardware.

    Install trackingmodule in box

    Install the Tracking Module in the mounting box as shown and described below.

    Step Action

    1 Place the module on the mounting plate as shown, with the bottom of themodule about 1 cm (3/8 in.) from the bottom of the mounting plate.

    2 Fasten the tracking module to the mounting plate with the 4 sheet metalscrews (included) using a Torx 10 screwdriver.

    3 Insert the assembly into the mounting box and fasten the plate to the boxwith 4 plastic-tap screws (included). Avoid over-tightening.

    Continued on next page

  • 7/29/2019 RefLine UM 01

    11/37

    Operators Manual

    Installation Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 11 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Mounting the Modules, Continued

    Sealing the passthrough fittings

    Some of the cables are too small to form a watertight seal with the pass throughfittings provided with the Tracking Module installation box. If the fitting does notcompress snugly around the cable jacket, it is strongly recommended that you sealthe fitting by other means. This can be accomplished by

    Increasing the diameter of the cable with flexible heat-shrink tubing, cable jacket,tape, etcetera.

    Filling the fitting with sealant.

    Fill unused pass-through fittings with sealant.

  • 7/29/2019 RefLine UM 01

    12/37

    Operators Manual

    Installation Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 12 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Mounting the Antennas

    RefLine antennas

    GPS antennainstallation

    Mount the GPS antenna as follows.

    Step Action

    1 Select a location for the antenna that gives the best exposure to the sky.2 Drill a 13 mm hole.

    3 Clean the mounting surface.4 Remove the nut and washer from the antenna shaft and remove the

    yellow film from the base.5 Insert the antenna into the mounting hole, press down to adhere, and

    fasten securely.

    GPS antennaconnection

    A 5 m length of cable is provided for connection of the GPS antenna. The silver-colored end connects to the antenna lead and the gold-colored end connects to theTracking Module.

    To prevent wear on the antenna lead, protect it with a rubber grommet if it passesthrough a hole that can cause chafe. Place a length of flexible heat shrink tubingover the antenna cable junction to keep it clean and secure.

    Continued on next page

  • 7/29/2019 RefLine UM 01

    13/37

    Operators Manual

    Installation Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 13 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Mounting the Antennas, Continued

    GSM antennainstallation

    The GSM antenna can be installed from above as follows.

    Step Action

    1 Connect the GSM antenna cable to the antenna. Remove the base capand replace the whip to give you something to hold on to. Loosen theround base nut. Select a location for the antenna as high as possible onthe genset and drill a 14 mm hole. Feed the cable through the opening.

    2 Work the antenna into the opening. Position the antenna precisely in thehole so that the raised tab comes through the hole and the top of thebase is flush against the inner surface.

    3 Tighten the base fitting nut.

    4 Remove the whip and replace the base cap. Replace the whip.

    5 Lead the antenna cable to the Tracking module and connect to theGSM Ant. socket. To prevent wear on the cable, protect it with a rubbergrommet if it passes through a hole or opening that can cause chafe.

  • 7/29/2019 RefLine UM 01

    14/37

    Operators Manual

    Installation Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 14 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    External Sensors

    Introduction The RefLine system makes use of the gensets fuel gauge and oil pressure sensor toreport fuel level, consumption rate, and generator operating condition. This sectiondescribes the types of sensors that can be connected to the Tracking Module.

    Oil pressuresensor(digital input)

    Two types of switching devices can be connected to the digital inputs: Electronic switching device (open collector) Standard relay/level switch (switch/contact).

    The standard configuration uses an on/off type oil pressure sensor to sense whenthe generator is running. The oil pressure sensor must be open (no contact) whenthe generator is not running, and it must complete a circuit to ground when thegenerator is running. If an oil pressure sensor is not available, another sensor thatcloses when the genset is running may be used.

    See also the specifications for digital inputs on page 32.

    Fuel gauge(analog input )

    The analog input accepts a 0 to 5 V signal. If the signal output is 0 to 10 V, you willneed a voltage divider in the signal line as shown below.

    The standard configuration uses a fuel gauge connected to analog input 1 to monitorfuel level and consumption rate.

    Configurationrequirements forfuel gauges

    Reefers Online allows you to configure fuel sensors for three genset types but not foreach individual unit. Therefore, to get meaningful readings from multiple gensets of

    the same type, the same type of fuel sensor must be used on each unit and thesensors must be connected to the same analog input.

    Other analogsensors

    The second analog input may be used for custom applications. J CI can provide theNTC temperature sensor for the Tracking Module that is listed on page 36.

    4 to 20 mA sensors may be used as well. See the input specifications on page 32.

  • 7/29/2019 RefLine UM 01

    15/37

    Operators Manual

    Installation Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 15 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Electrical Connections

    Standardconfiguration

    wiring diagram

    Continued on next page

  • 7/29/2019 RefLine UM 01

    16/37

    Operators Manual

    Installation Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 16 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Electrical Connections, Continued

    Reefer pow ersupply

    The heavy yellow cable from the RefLine Monitoring Module contains 4 leads forconnection to the generators 440 V AC output. Connect the leads at the same pointas the leads for the reefer power plugs. The yellow/green striped lead must beconnected to the reefer power ground (earth) terminal. The brown, blue, and greyleads connect to live terminals L1, L2, and L3 in any order.

    Warning! Dangerous voltage present! Verify that power has been removedbefore connecting leads.

    Reefer data The smaller cable from the Monitoring Module contains 3 leads for connection to theTracking Modules RS485 port. Lead the cable into the tracking module mountingbox and connect a 3-pole plug as shown in the table below. Connect the plug to thelast 3 pins (11-13) on connector J 1.

    Lead Function Terminal (J1)

    black RS485 GND 13

    red RS485 TX/RX - 12

    blue RS485 TX/RX + 11

    Tracking modulepower supply

    The Tracking Module requires a DC voltage between 8 and 32V, which is suppliedby the genset starter battery in the standard configuration. Wire the batterys positivepole to terminal 1 and the negative pole to terminal 2 on connector J 1.

    Run switch(digital input 1)

    Connect a lead between the ungrounded side of the run switch and pin 3 on J 1.

    Sleep modejumper(digital input 1)

    The low power sleep mode must be disabled if you chose not to connect thegenset run switch to dig ital input 1. With all new units (from PCB revision E), thiscan be done using the setup utility as described on page 31. Alternatively, you canconnect a jumper between J 1 pins 2 and 3 as shown below.

    Oil pressuresensor(digital input 2)

    Connect the signal lead from the oil pressure sensor to pin 4 of the 10 poleconnector. The oil pressure sensor is described on page 14.

    Fuel gauge(analog inpu t 1)

    Check the fuel gauge output. If it is 0 to 5 V, connect the signal lead to pin 7 and theGND lead to pin 8. If it is 0 to 10 V, a voltage divider is required. See page 14.

    Auxi liary devices

    (digital outputs)To connect optional auxiliary devices (max. 2A), connect the positive supply lead topin 5 (output 1) or pin 6 (output 2). Ground the negative supply lead.

  • 7/29/2019 RefLine UM 01

    17/37

    Operators Manual

    Installation Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 17 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    SIM Card Installation

    Install SIM card Install a SIM card in the Tracking Module as follows.

    Step Action

    1 Slide the lock to the open position.

    2 Tilt the card holder up and slide the SIM card into the holder.

    3 Lower the holder and slide the lock to the closed position.

  • 7/29/2019 RefLine UM 01

    18/37

    Operators Manual

    Setting RefLine User Options Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 18 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Setting RefLine User Options

    Service Tool Installation

    About theService Tool

    The Service Tool is the software used to set RefLine user options with a PC. It isincluded on the Starter Kit CD-ROM.

    Systemrequirements

    The Service Tool runs on personal computers with the Windows 2000 or XPoperating systems.

    The computer must have an RS-232 serial (COM) port with a 9-pin male D-Subsocket. If the computer does not have a built-in serial port, a USB to Serial Portadaptor may be used.

    Installation Follow the steps below to install the Service Tool.

    Step Action

    1 Start by saving anything you are working on and closing all programs.2 Insert the CD-ROM from the starter kit into the CD drive.3 From your Startmenu click My Computer, or, from your desktop,

    double-clickMy Computer.4 Double-click the CD drive containing the CD-ROM.5 Double-click theService Toolfolder.6 Locate and double-click the installation file to start the software

    installation wizard.7 When prompted to select the components to install, select Install

    Refline/Box Service Tool only.

    8 Follow the instructions in the installation wizard to complete the

    installation. The configuration can be changed later by repeating theinstallation procedure.

  • 7/29/2019 RefLine UM 01

    19/37

    Operators Manual

    Setting RefLine User Options Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 19 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Connecting to PC

    Introduction This section describes how to establish a link between RefLine and a PC.

    ConnectTracking Moduleto COM port

    Use the null modem cable supplied with the starter kit to connect the TrackingModule to the PC. Connect one end of the cable to socket P1 on the module.Connect the other end of the cable to the PCs COM port.

    Apply power toTracking Module

    Apply power and verify that LED 1 is lit. If LED 1 is not lit, the module may be insleep mode. Refer to page 16.

    Establish link toService Tool

    Establish a link as follows.

    Step Action

    1 Start the Service Tool. Click the PCs startbutton and select ServiceToolfrom the list of programs.

    2 The Service Tool opens and attempts to establish a link via the COMport selected under Link>Port. Check the bottom left corner of theService Tool window: Connectedis displayed when the link has beenestablished.

    Continued on next page

  • 7/29/2019 RefLine UM 01

    20/37

    Operators Manual

    Setting RefLine User Options Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 20 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Connecting to PC, Continued

    Establish link to Service Tool(continued)

    Step Action3 If the Service Tool does not connect to the Tracking Module, select the

    other port under Link>Port.

    See the troubleshooting tips in the following section if the connectioncannot be established after several tries.

    4 When the link is established, select Link>Receive Setto download thecurrent settings from the Tracking Module.

    The settings can now be viewed and modified.

    Troubleshootingconnection

    problems

    Try the following if the Tracking Module does not connect to the Service Tool.

    Change the data transfer rate under Link>Baud. Check the serial cable connections on both ends. Check LED 1 to verify that the module is powered on and awake. If using a USB to Serial Port adaptor, verify that it is set to COM1 or COM2. To

    check the port number, right-click My Computer, click Manage, click DeviceManager, and double-click Ports (COM & LPT) in the list of devices. The portnumber should be shown in parenthesis after the device name. If set to anotherport, double-click the device name for setting options.

    If other devices or programs are using COM1 and COM2, disable them or reassignthem to another COM port.

  • 7/29/2019 RefLine UM 01

    21/37

    Operators Manual

    Setting RefLine User Options Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 21 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Saving and Retrieving Settings

    Introduction This section describes how to save and retrieve your user settings.

    Note: The settings disp layed on screen do not take effect unt il you selectLink > Transmit Set f rom the main menu.

    Get settings fromTracking Module

    The first step after establishing a link is to transfer the current settings in theTracking Module to the Service Tool. Select Link>Retrieve Setfrom the mainmenu.

    Save settings i nTracking Module

    After settings have been modified in the Service Tool, they must be transferred to theTracking Module. SelectLink>Transmit Setfrom the main menu.

    Delete settings inTracking Module

    To clear all settings from the Tracking Module memory and restore them to factorydefault values, select Link>Clear Settings from the main menu.

    PC file

    operations

    The Service Tool allows you to save settings in a file for backup or convenience

    when configuring multiple installations.

    To save the current settings, selectFile >Save As... from the main menu. Name thefile, select a location, and then click Save in the Save dialog.

    To retrieve a settings file, selectFile >Open from the main menu. Use the Opendialog to locate and select the desired file.

    To clear the current settings from the Service Tool, selectFile >New.

  • 7/29/2019 RefLine UM 01

    22/37

    Operators Manual

    Setting RefLine User Options Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 22 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    ID Setting and Info Fields

    Introduction This section describes the fields at the top of the Service Tool window.

    File When working with a settings file, the file path and name appear in the File field. Ifthe complete path is too long to fit, right-clicking in the field jumps to the end of thename.

    Id The Id field identifies the genset in SMS messages and the Reefers Onlinedatabase. Enter a unique name up to 16 characters in length. The followingcharacters may be used.

    !"#$%&'()*+,-./0123456789:;?@ABCDEFGHIJ KLMNOPQRSTUVWXYZ[\] _abcdefghijklmnopqrstuvwxyz{|}~

    Date/Time The date/time field is not editable. The clock is set automatically to UTC (GMT) time

    by GPS.

    Position The position field displays the latitude and longitude coordinates when the TrackingModule is able to get a valid GPS position fix. No Valid Gps Fix appears if the unitis unable to determine its position, which is usually due to poor reception.

  • 7/29/2019 RefLine UM 01

    23/37

    Operators Manual

    Setting RefLine User Options Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 23 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Analog Input Settings

    About the AnalogInput tab

    The Tracking Module accepts three types of analog input: NTC, V, and mA. You setthe input type and configure analog-based alarms in theAnalog Inputtab. Note:input type must be configured correctly in order to transmit meaningful data to theGlobal Monitoring Server.

    The first column of the table is the analog input number. Input 1 is the fuel gauge inthe standard configuration.

    Sensor reading The Value column displays the sensor reading. The value depends on the Modesetting.

    The range of values for each mode is shown below. The shaded cells are the levelsshown if no input is detected or if the level is out of range.

    Mode Max. Level Min. Level Unit

    NTC 30 -25 C

    Current 20 4 mA

    Voltage 10 0 V

    Signal typeconfiguration

    The signal type is set in theMode column.

    Select Voltage if the analog input is 0 to 5V Select Currentif the analog input is 4 to 20 mA Select NTCif the input is an NTC temperature sensor

    Alarm tr iggerlevels

    Set the sensor values that trigger an alarm in the High Leveland Low Levelfields.If an alarm is not desired, set values above the maximum and below the minimumlevels shown in the table above.

    Continued on next page

  • 7/29/2019 RefLine UM 01

    24/37

    Operators Manual

    Setting RefLine User Options Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 24 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Analog Input Settings, Continued

    Alarm tr iggerdelay

    You can set a trigger delay in the Delay (min) column. A delay prevents alarms dueto brief changes in sensor levels if they return to normal within the selected time.

    Auxi liary devicecontrol

    To activate an auxiliary device in response to an alarm, select the number of itsdigital output in the Outputs column. One or both outputs may be selected.

    SMS alarmmessage

    You can enter an SMS alarm message up to 23 characters long in the MessageTextcolumn. This message is sent to designated mobile phones and the GlobalMonitoring Server when there is an alarm.

    Clearing i nput Double-click the input number to clear all input from a row.

  • 7/29/2019 RefLine UM 01

    25/37

    Operators Manual

    Setting RefLine User Options Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 25 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Digital Input Settings

    About the Digi talInput tab

    The Digital Inputtab is for configuring alarms based on digital inputs. In thestandard configuration, the digital inputs are the genset run switch and the oilpressure sensor. For example, you can set the system to send an SMS message ifthe run switch is turned off.

    When a digital input circuit is open, the value is 0. When closed, the value is 1.

    Alarm tr iggervalues

    You can set alarms based on the digital inputs in theAlarm Levelcolumn. Select 0to trigger an alarm when the switch or sensor is open. Select 1 to trigger an alarm when the switch or sensor is closed. Select Toggle to trigger an alarm when the input circuit changes from one state to

    the other.

    The remaining options, Toggle_Hand Toggle_L are for logging genset hours inapplications without a Monitoring Module. They have no function in the standardconfiguration.

    Trigger delay You can set a trigger delay in the Delay (min) column. A delay prevents alarms dueto brief changes in the digital input if it returns to normal within the selected time.

    Auxi liary devicecontrol

    To activate an auxiliary device in response to an alarm, select the number of itsdigital output in the Outputs column. One or both outputs may be selected.

    SMS alarmmessage

    You can enter an SMS alarm message up to 23 characters long in the MessageTextcolumn. This message is sent to designated mobile phones and the GlobalMonitoring Server when there is an alarm.

    Clearing i nput Double-click the input number to clear all input from a row.

  • 7/29/2019 RefLine UM 01

    26/37

    Operators Manual

    Setting RefLine User Options Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 26 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Mobile Phone Settings

    About the Phonetab

    RefLine can send SMS alarm messages to up to four GSM mobile phones. Youdesignate numbers in the Phone tab. No value is required in the Priorityfield.

    About the SIMcard PIN code

    The SIM card must be unlocked so that no PIN code is required to connect tothe GSM network . If the SIM card is locked, the following dialog appears in thesetup utility when the Tracking Module attempts to connect to the GSM network.

    Enter the PIN code in and click okay. The Tracking Module will unlock the SIM card ifpossible. Note that some SIM cards do not allow you to do this. If you get repeatedrequests to enter the PIN code, the SIM card is not suitable for use.

    Entering phonenumbers

    When entering the phone number, enter the full number starting with the +sign,country code, and city or area code. No international dialing prefix is required.

    Step Action

    1 Click thePhone tab.

    2 Click in the first available line in thePhone column.3 Type +, the country code, and the full phone number with area code.4 Select and click Link>Transmit Setto upload the number.

    Clearing phonenumbers

    To clear a phone number, double click in the Numbercolumn in the row to becleared. Then click Link>Transmit Setto update the Tracking Module.

  • 7/29/2019 RefLine UM 01

    27/37

    Operators Manual

    Setting RefLine User Options Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 27 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    GPRS Settings

    Introduction This section describes how to set up RefLine to send data via GPRS. The defaultsettings are shown below.

    Communicationmode (Bearersetup)

    The Bearer setup option under GPRS connection setup on the GPRS tabdetermines which service, SMS or GPRS, RefLine uses to transmit data to the GMSserver. Your selection will depend on service availability and pricing.

    Select SMS onlyto use text messages as the communication mode. Select GPRS if poss ible to use GPRS as the primary communication mode and

    SMS text messages as a backup mode when GPRS service is not available. Select GPRS onlyto use GPRS as the communication mode.

    Note: When GPRS if possible is selected, RefLine sends alarms by SMS afterattempting to send by GPRS for five minutes. The system waits for a GPRSconnection to send genset and reefer status reports.

    GPRS loginsettings

    To access the GPRS network, enter your GSM networks GPRS access point name(APN), user name, and password in the fields under GPRS connection setup onthe GPRS tab. Some networks do not require a user name or password.

    Contact your GSM service provider for GPRS login information, or search for it

    online using APN and the name of the GSM network.

    Note: You must restart the Tracking Module after changing the GPRS settings.

    GMS address The settings under Global Monitoring Server address determine where RefLine datais sent.

    The default values are for use with J CIs Global Monitoring Server. Do not changethe values unless you are implementing a custom monitoring solution.

  • 7/29/2019 RefLine UM 01

    28/37

    Operators Manual

    Setting RefLine User Options Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 28 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Genset Report Settings

    Introduction This section describes the settings for genset status reports.

    Genset statusreporting interval

    Select the desired genset status reporting interval in the Im Alive statusreporting intervalfield of the Basictab. More frequent reporting provides betterinformation but costs more in SMS or data charges.

    For more economical reporting, use the combined reports option described below.

    Status reporting can be disabled by selecting Offfrom the selectionlist.

    Combined gensetreports(Log settings)

    The options under Log Settings on the Misctab provide an economical way toreport genset data, particularly when sending via SMS. When the Send full logoption is checked, the system combines 14 reports and sends them together. Youset the reporting frequency in the Log Intervallist. For example, you can log dataevery 30 minutes and receive the reports every 7.5 hours.

    Supply voltagealarm settings

    The Tracking Module measures the battery voltage and can be set to generate analarm with the message Supply Voltage: [voltage] if it falls below the specified level.

    Step Action

    1 Click on theMisctab.2 Click in the Enable Low Voltage Alarm check box.3 Enter the desired value in theLowVoltage Alarm Levelfield.4 Select a trigger delay time from the Voltage Alarm Timeout (min) field.

  • 7/29/2019 RefLine UM 01

    29/37

    Operators Manual

    Setting RefLine User Options Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 29 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Reefer Report Settings

    Introduction This section describes the options for reefer status reports.

    Reefer statusreport interval

    The value you enter in the Reefer s tatus reporting interval (hour) field determineshow often reefer status reports (described on page 6) are sent. The timing is alsoinfluenced by the Save reefer status every hour / send wi th GPRS established

    option described below.

    If you use SMS onlyto transmit data, select the reefer status reporting interval thatmeets your reporting requirements. If you use GPRS, see the following section.

    Log reefer datahourly for GPRStransmission

    When the Save reefer status every hour / send with GPRS establishedoption isenabled, RefLine saves reefer status reports every hour and sends them in a bundlewith the next genset status Im alive report (or alarm) to reduce the cost of datatransmission.

    If you schedule Im alive reports (see page 28), you may want to set the Reeferstatus reporting interval (hour) value to Off. If you do not schedule Im alivereports, select the reefer status report interval that meets your monitoring needs.

    When the Save reefer status every hour / send with GPRS establishedoption isdisabled, RefLine sends a reefer status report at the interval selected in the Reeferstatus reporting interval (hour) field.

    Note: This option has no effect if data is transmitted by SMS only.

    Continued on next page

  • 7/29/2019 RefLine UM 01

    30/37

    Operators Manual

    Setting RefLine User Options Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 30 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Reefer Report Settings, Continued

    Reefer locationID

    You can use theLocation of all reefers field on the RefLine tab to identify a groupof gensets in the same location, route, or carrier. For example, if configuring RefLinefor gensets in a specific train, entering the name of the train in the Location of allreefers field will allow you to locate reefers by searching by train name instead of bycontainer or genset ID.

    Lostcommunicationalarm settings

    The lost communication alarm alerts you when the RefLine system is not receivingdata from a reefer container. This alarm is only meaningful when the generator isrunning. Therefore, it is recommended that it be enabled only if a digital input iswired in the standard configuration, i.e., to the run switch or oil pressure sensor.

    Configure the lost communication alarm as follows.

    Step Action1 Click theRefLine tab.2 Select one of the following Lock Reefers on Digital Inputdropdown list.

    Select Off to disable the alarm. Select 1 if the run switch is wired to digital input 1. Select 2 if the oil pressure sensor is wired to digital input 2.

    3 Click theDigital Inputtab.4 In the row for the same digital input, set theAlarm Levelto 1.

    Reefer datadisplay

    The Containertab shows data from connected reefers and is primarily for testingand verification purposes when setting up the system. To test the system and viewthe data, select Link>Receive Containers from the main menu.

    Exp. setpointsettings

    The Exp. Setpointtab is for future use.

  • 7/29/2019 RefLine UM 01

    31/37

    Operators Manual

    Setting RefLine User Options Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 31 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Other Settings

    Server telephonenumber setting

    To use SMS text messages to transmit data, you must enter the telephone numberfor the Global Monitoring Server in the WEB Server Phone numberfield on theBasictab. Unless you use an SMS Bridge (available from J CI), the number to enteris +4540700364. Enter the number exactly as written: no international dialing prefixis required.

    Sleep modesetting

    To enable the low power sleep mode, place a check in theUse Sleep Mode ....check box on the Basictab.

    Sleep mode is recommended in the standard conf iguration to prevent drainingthe battery when the generator is not in use.

    The sleep mode setting works with RefLine Tracking Modules and ComPosIT unitsshipped after November, 2006 (PCB rev. E or later). See also page 7.

  • 7/29/2019 RefLine UM 01

    32/37

    Operators Manual

    Specifications Johnson Cont ro ls DenmarkRevision 1.4 Updated: 081027 Author: Marc Anderson Owner: Robert SvenssonProject 238229.000: RefLine Page 32 of 37File: e:\wordtech\jci\refline\refline manual\refline_um_14.doc

    Specifications

    Size and weight

    Descript ion Value Unit

    Tracking Module in Installation BoxDimensions 225 x 150 x 75 mm

    Weight 0.5 kg

    Monitoring Module

    Dimensions 323 x 226 x 64 mm

    Weight 5 kg

    Environmental

    Descript ion Value Unit

    Operating temperature range -20 +50 C

    Maximum humidity 95 % non-condensingIngress protection 54 IP rating

    Tracking Modulepower

    Descript ion Min. Typ. Max Unit

    Vs Supply voltage, operating 8 32 VDC

    Power consumption, operating 2 W @ 12VDC

    Power consumption, sleeping 5 mW @ 12VDC

    Power consumption, sleep modewith 4 hr. status reporting interval

    100 mW @ 12VDC

    Monitoring Modulepower

    Descript ion Min. Typ. Max Unit

    Vs Supply voltage, operating 340 440 560 VAC (45-70 Hz)

    Power consumption, operating 14 W @ 440VAC

    Digital inputs

    Descript ion Min. Typ. Max Unit

    Logical input low voltage Note 1 -1.4 0.4 V

    Logical input high voltage Note 1 2.1 6.4 V

    Analog inputs

    Descript ion Min. Typ. Max Unit

    Input voltage range Note 3 0 5 V

    Temperature range -25 30 C

    Temperature tolerance Note 4 0.25 C @ -25 < Tamb