FUNGSI
SEBAGAI PENGAMAN UTAMA ATAU CADANGAN
UNTUK GANGGUAN HUBUNG SINGKAT
FASA FASA
FASA TANAH
APLIKASI
PENGAMAN UTAMA
JTM ( DISTRIBUSI )
GENERATOR ( Kapasitas kecil )
TRAFO DAYA ( Kapasitas kecil )MOTOR
SEBAGAI PENGAMAN CADANGAN
5/23/2018 Relai Arus Lebih
3/45
PENGERTIAN
RELAI ARUS LEBIH
SUATU RELAI YANG BEKERJANYA
BERDASARKAN ADANYA KENAIKAN
ARUS YANG MELAMPAUI NILAI
SETTINGNYA .
5/23/2018 Relai Arus Lebih
4/45
JENIS RELAI ARUS LEBIH
NON DIRECTIONAL
DIRECTIONAL
KONTROL TEGANGAN
PENAHAN TEGANGAN
5/23/2018 Relai Arus Lebih
5/45
KARAKTERISTIK
@ ARAH
1. TIDAK BERARAH ( NON DIRECTIONAL )
2. BERARAH ( DIRECTIONAL )
@ ARUS WAKTU
1. TANPA TUNDA ( MOMENT = INSTANT )
2. TUNDA WAKTU ( TIME DELAY )
# DEFINITE ( TERTENTU ) = INDEPENDEN# INVERSE ( I t BERBANDING TERBALIK )
= DEPENDEN
SI / NI = Standard / Normal Iverse
VI = Very Inverse
EI = Exteremely Inverse
LTI = Long Time Invers
5/23/2018 Relai Arus Lebih
6/45
t
IMOMENTISET
SETt
KARAKTERISTIK INSTANT = MOMENT
5/23/2018 Relai Arus Lebih
7/45
t
I
SETt
KARAKTERISTIK TUNDA WAKTUTERTENTU ( DEFINITE TIME )
SETI
5/23/2018 Relai Arus Lebih
8/45
t
I
SETt
KARAKTERISTIK TUNDA WAKTUINVERSE
SETI
5/23/2018 Relai Arus Lebih
9/45
t
I
SETt
KARAKTERISTIK KOMBINASI INSTANTDENGAN TUNDA WAKTU TERTENTU
(DEFINITE TIME )
SETI MOMENTISET
5/23/2018 Relai Arus Lebih
10/45
t
I
KARAKTERISTIK KOMBINASI INSTANTDENGAN TUNDA WAKTU INVERSE
SETI MOMENTISET
5/23/2018 Relai Arus Lebih
11/45
0.6
0.8
1.0
1.2
PEGAS
KONTAK
SETTING
PLUNGER
BELITAN
INTI LUAR
TIPE PLUNGER
Fe = GAYA ELEKTROMEKANIKFp = GAYA PEGAS
Fe < Fp DROP OFF
Fe > Fp PICK UP
5/23/2018 Relai Arus Lebih
12/45
2
L U2
LU
PIRINGAN
KUMPARAN LAGGING
KUMPARAN UTAMA
TIPE KWH
I
Is
5/23/2018 Relai Arus Lebih
13/45
SETTING ARUS DAN WAKTU
TAP / PLUG SETING
KUMPARANUTAMA
TAP SETTING
ARUS DARICT
TIME DIAL SETTING
KONTAK DIAM
KONTAK GERAK
DENGAN MENGATUR
JARAK KONTAK
5/23/2018 Relai Arus Lebih
14/45
R
RECTIFIER
SETTING
I
A CT
LEVEL
DETECTORinV oV
RELAI
BANTU
SUPLAI DC
TIPE RELAI STATIK
)(Re0)(0
setVVVPickupVVV
OINREF
OINREF
5/23/2018 Relai Arus Lebih
15/45
MAX
I
GATE
&
RECT.
F
CS
LD
1T LD
2
RL
1
R F
LD
3 3
RLIs
INSTANT
Is
FILTER
CURVE
SHAPER
LD = LEVEL DETECTOR
T = TIMER
R = REGULATOR
Ia
Ib
Ic
SETTING
INSTANT
BLOK DIAGRAM RELAI ARUS LEBIH STATIK
IBA DOC
5/23/2018 Relai Arus Lebih
16/45
0.2/0.1
0.2/0 0.4/0
0.8/00.4/0
A/D
OUTPUTDRIVER
MICROCOMPUTER
16/0
8//0
4//0
2/0
1/0
0.4/0
0.2/0
0.2/0
0.1/0
0.05/0
0.05/0.025
CURVE SELECT SWITCH
HIGH SET SWITCH
SETTING
TMS SWITCH SETTING
TIMEHS
HS OUTPUT
RELAY
TIME / CURRENT
OUTPUT RELAY
FULLWAVE
RECTIFIERINTERPOSSINGCT
INPUT
CURRENT SETTING
STATIC OVER CURRENT RELAY
MCGG
IBA DOC
5/23/2018 Relai Arus Lebih
17/45
A B C EINST
t
I > Is
INST
t
I > Is
NAME
PLATE
RESET
KARAK
TERISTIK
NS II
xt
IsIINST
IsIINST
xt
NS II
RELAI
OCR / GFRTIPE
MCGG 82
IBA DOC
5/23/2018 Relai Arus Lebih
18/45
PRINSIP SETTING OCR
# Iset Tunda waktu
* Is = k In In = Arus Nominalk = Faktor pabrik ( 1 s/d 2 )
atau 0,05 s/d 2,4 denganstep 0.05
* Plug Setting
IBA DOC
5/23/2018 Relai Arus Lebih
19/45
# Waktu kerja
* Definite ( Langsung atau dengan Tms )* Inverse ( Td atau Tms dan Mps = I / Is )
Tms ( td )
x IsMps = 4 x Is
t
tk
Td = Time dial setting
Tms = Time multiple seting
Mps = Multiple plug setting
. X Is
IBA DOC
5/23/2018 Relai Arus Lebih
20/45
# Is instant ( moment )
* Is instant = k In atauk Is
In = Arus Nominal
Is = Arus setting tunda waktu
k = Faktor pabrik
* Plug setting
IBA DOC
5/23/2018 Relai Arus Lebih
21/45
@ SETTING ARUS OCR /GFR DENGAN TUNDA WAKTU
N
S
NS
I
I
II
ARUS SETTING
ARUS NOMINAL RELAI
FAKTOR PABRIK
0.10.1
0.2
0.4
0.4
0.4
0.8
0.050
00
0
0
0
IBA DOC
5/23/2018 Relai Arus Lebih
22/45
0.1
0.1
0.2
0.4
0.4
0.4
0.8
0.05
000
0
0
0
# MISAL ARUS SETTING Is = 6 A.
Is = 1.2 In
POSISI SAKLAR :
Is = ( 0.1 + 0.1 + 0.2 + 0 + 0 + 0 + 0.8 ) x 5A
= 1,2 x 5A
= 6 A
IBA DOC
5/23/2018 Relai Arus Lebih
23/45
PEMILIHAN KARAKTERISTIK
SI VI EI LTI D2 D4 D8
0 1 0 1 0 1 0
0 0 1 1 0 0 1
0 0 0 0 1 1 1
101
1
1
0
0
0
1
10
0
TRIP TEST : CURVA SI :
IBA DOC
5/23/2018 Relai Arus Lebih
24/45
KURVA / KARAKTERISTIK
@ STANDARD / NORMAL INVERSE ( SI )
tms
I
t
1
14,002,0
@ VERY INVERSE ( VI )
tms
I
t
1
5,13
@ EXTREMELY INVERSE ( EI )
tmsI
t1
802
@ LONG TIME INVERSE ( LTI )
tmsI
t1
120
IBA DOC
5/23/2018 Relai Arus Lebih
25/45
MISAL : KARAKTERISTIK EI
ARUS GANGGUAN 3 x Is ( I = 3 )
WAKTU KERJA = 1 DETIK
PEMILIHAN TMS :
SETTING WAKTU
iktI
tms k det1,0180
13
80
1 22
POSISI SAKLAR 0,025 0,050,05
0,10,20,20,4
0
0
000
IBA DOC
5/23/2018 Relai Arus Lebih
26/45
IBA DOC
SETTING INSTANT
SS
S
S
IinstI
AI
AinstI
36
18
6
18 POSISI SAKLAR
2
4
1
816
00
0000
5/23/2018 Relai Arus Lebih
27/45
R
S
T
E
CT
P1
P2
S1
S2
OCR
OCR
GFROCR
SAMBUNGAN ( WIRING )
3 Buah OCR
1 Buah GFR
PMT
IBA DOC
5/23/2018 Relai Arus Lebih
28/45
R
T
E
PMT
CT
P1
P2
S1
S2
OCR
OCRGFR
SAMBUNGAN ( WIRING )
2 Buah OCR
1 Buah GFR
IBA DOC
5/23/2018 Relai Arus Lebih
29/45
PENGUJIAN RELAI ARUS LEBIH
1. PENGUJIAN INDIVIDUAL
MENGUJI INDIVIDU RELAI ITU SENDIRI , UNTUKMENGETAHUI
APAKAH MASIH DALAM KEADAAN STANDAR ATAU TIDAK
2. PENGUJIAN FUNGSI
MENGUJI FUNGSI DARI SISTEM PROTEKSI
SECARAKESELURUHANAPAKAH MASIH BERFUNGSI ATAU
TIDAK
5/23/2018 Relai Arus Lebih
30/45
PENGUJIAN INDIVIDUAL
HAL HAL YANG PERLU DIPERHATIKAN :
1. CARA SETTING
2. INTERNAL DIAGRAM RELAI
3. ALAT UJI / RANGKAIAN PENGUJIAN
4. ITEM PENGUJIAN5. PROSEDUR PENGUJIAN
6. HASIL UJI DAN KESIMPULAN
5/23/2018 Relai Arus Lebih
31/45
JENIS / ITEM PENGUJIAN
1. ARUS PICK UP DAN ARUS DROP OFF
SERTA
RASIO ARUS PICK UP DENGAN DROP OFF
2. KARAKTERISTIK ARUS WAKTU
3. KARAKTERISTIK INSTANTANEOUS
5/23/2018 Relai Arus Lebih
32/45
1. ARUS PICK UP [ ARUS AWAL / MULA ]
ARUS MINIMUM YANG MENYEBABKAN RELAI BEKERJA
2. ARUS DROP OFF [RESET/ KEMBALI ]
ARUS MAKSIMUM YANG MENYEBABKAN RELAI TIDAK BEKERJA.
3. RASIO ARUS PICK UP DENGAN DROP OFF%100
P
DD
I
IK
I
t
I pick up
I reset
I beban
t gangguan
5/23/2018 Relai Arus Lebih
33/45
PENGUJIAN INDIVIDUAL
RELAI ARUS LEBIH
A
220 Vac
220 Vac
TIMER
START STOP
R
TRAFO ISOLASISLIDE
RANGKAIAN PENGUJIAN
2122
23
24
25
26
27
28
29
30
13
14Vdc
5/23/2018 Relai Arus Lebih
34/45
(+)
(+)
(+)
(-)
(-)
KONTAK
OCR/GFR
RELAI
BANTU
RE 1
RE 2
RELAIBANTU
RE 3
ALARM
TRIP PMT
DIAGRAM
KONTROL DC
5/23/2018 Relai Arus Lebih
35/45
(+)
RESET
TEST LAMP
RELAI BANTU
RE
LAMPU
SIGNAL
KONTAK
RELAI
RANGKAIAN SIGNALISASI
5/23/2018 Relai Arus Lebih
36/45
SETTING OCRGANGGUAN FASA FASA [ TUNDA WAKTU
.max
%80
2,11,1maxminmax
minmaxmin
]2....[min8,0max
]1.....[min
max
2
max
arusbebanI
k
kIIII
IIII
II
k
IkI
D
S
SETSETSETSET
SETSETSETSET
HSSET
D
SSEI
5/23/2018 Relai Arus Lebih
37/45
KOORDINASI OCR
# DEFINITE TIME
A B C
t
I
0,3 det0,8 det
1,3 det
det5,04,0
t
ttt
IIII
ABC
HSSASBSC
5/23/2018 Relai Arus Lebih
38/45
KOORDINASI OCR
# INVERSE TIME
A B C
t
I
TMS ATMS B TMS C
SETING WAKTU DENGAN PEMILIHAN TD / TMS
TD = TIME DIAL
TMA = TIME MULTIPLE SETTING
5/23/2018 Relai Arus Lebih
39/45
SETTING ELEMEN INSTANTANEOUS
DIMAKSUDKAN UNTUK GANGGUAN 3 FASA ,TETAPI HARUS
MEMPERHATIKAN ARUS KETAHANAN KABEL .
abelkemampuankSET
HSSETHS
II
III
2
312 minmin
SETTING INSTANT
212
121
SETSETSETSET
SETSETSETSET
IIII
IIII
5/23/2018 Relai Arus Lebih
40/45
KOORDINASI OCR
# INSTANTANEOUS
A B C
CIBinstI
BIAinstI
HSSET
HSSET
3
3
2,1.
2,1.
5/23/2018 Relai Arus Lebih
41/45
KOORDINASI DARI RELAI KOMBINASI TUNDA WAKTU
DENGAN INSTANT /
A B C
t
I
TMS ATMS B TMS C
t
I
t A
t B
t Ct INSTt INST
t INST t INST
5/23/2018 Relai Arus Lebih
42/45
SETTING GFR[RELAI GANGGUAN TANAH ]
PERLU DIPERHATIKAN ;
1. SISTEM PENTANAHAN TITIK NETRAL
2. BESARNYA ARUS HUBUNG SINGKAT SATU FASAKE TANAH .
3. ARUS KETIDAKSEIMBANGAN BEBAN
4. ARUS KAPASITANSI JARINGAN .
5/23/2018 Relai Arus Lebih
43/45
SISTEM PENTANAHAN DENGAN TAHANAN RENDAH
3 PADA SKTM SPINDEL
BATAS MINIMUM ADALAH RELAI PADA SALURAN
YANG SEHAT TIDAK BOLEH BEKERJA OLEH ARUS
KAPASITANSI ORI3
ORSET IGFRI 33,1
# PADA SUTM
SAMA SEPERTI DI SKTM
5/23/2018 Relai Arus Lebih
44/45
@ SISTEM PENTANAHAN LANGSUNG [ SOLID ]
KARENA ARUS GANGGUAN BESAR , KRITERIA SETTINGNYA
SEPERTI PADA RELAI PENGAMAN ANTAR FASA .
TETAPI BATAS MINIMUMNYA LEBIH KECIL DARI ARUS
BEBAN , TETAPI LEBIH BESAR DARI ARUS KETIDAKSEIMBANGAN
BEBAN .
5/23/2018 Relai Arus Lebih
45/45
@ SISTEM MENGAMBANG
1. RELAI TEGANGAN NOL
RELAI INI TIDAK BOLEH BEKERJA BILA TERJADI
PERGESERAN TEGANGAN NOMINAL
2. RELAI GANGGUAN TANAH BERARAH
[ DIRECTONAL GFR ]
@ SISTEM PENTANAHAN DENGAN TAHANAN TINGGI
RELAI YANG DIGUNAKAN ADALAH DGFR .RELAI OCR SEBAGAI GFR TIDAK DAPAT DIPAKAI .
KARENA ARUS GANGGUAN SATU FASA KETANAH
LEBIH KECIL DARI ARUS KAPASITANSI .
NomO VV 3,03