Relay Alarm Connection(VMS)

Embed Size (px)

DESCRIPTION

vgood

Citation preview

1

Vietnam VMS Project

Power Relay Alarm Connection

1Relay Alarm Connection in ZXDU68 B201Relay Alarm Connection in ZXDU68 T301BTS Connection and ConfigurationRNC/BSC Connection and Configuration

Agenda 23Relay Alarm Connection in ZXDU68 B201Hardware Location

ZXDU68 B201 DC power supply.We will install this equipment on the rack.4

Relay Alarm Connection in ZXDU68 B201Hardware LocationThe output relay of ZXDU68 B201 is on SIB board of the Monitoring Unit.On SIB board, X16, X17, X18 and X19 are the output relay ports which we can use to connect BTS.5Relay Alarm Connection in ZXDU68 B201SIB Board Interfaces Description

6Relay Alarm Connection in ZXDU68 B201Cable Connection

X16, X17, X18 and X19 are the output relay ports which we can use to connect BTS.7Relay Alarm Connection in ZXDU68 B201Parameter Configuration on Monitoring Unit of ZXDU68 B201

Output relay can be modified as the figure below.8Relay Alarm Connection in ZXDU68 B201Parameter Configuration on Monitoring Unit of ZXDU68 B201

Enter the Alarm Para. We can set the output relay. We can check the meaning of the Parameter as figure below.

9Relay Alarm Connection in ZXDU68 B201Relay Alarm Connection in ZXDU68 T301BTS Connection and ConfigurationRNC/BSC Connection and Configuration

Agenda Relay Alarm Connection in ZXDU68 T30110

The output relay of ZXDU68 T301 is on SIB board of the Monitoring Unit.On SIB board, X15, X16, X17 and X18 are the output relay ports which we can use to connect BTS, RNC and BSC.Hardware Location11Relay Alarm Connection in ZXDU68 T301SIB Board Interfaces Description

Relay Alarm Connection in ZXDU68 T301Use the cable to connect SIB board to BSC and BTS equipment as figure.

12Cable Connection

Relay Alarm Connection in ZXDU68 T30113Parameter Configuration on Monitoring Unit of ZXDU68 T301

14Relay Alarm Connection in ZXDU68 T301Parameter Configuration on Monitoring Unit of ZXDU68 T301

Enter the Alarm Para. We can set the output relay as figure.

15Relay Alarm Connection in ZXDU68 T301Parameter Configuration on Monitoring Unit of ZXDU68 T301Alarm typeAlarm levelrelayAC Aux SW offAC main SW offAC power offMajorA1SMR AlarmMajorA2DC Under-Vol.MajorA3Bat loop breakMajorA4othersdefault0Configure the parameter of output relay as below

16Relay Alarm Connection in ZXDU68 B201Relay Alarm Connection in ZXDU68 T301BTS Connection and ConfigurationRNC/BSC Connection and Configuration

Agenda Relay Cable for BTS and BSC

Relay Cable for BTS and BSC

NoInterface DesignationSignal DescriptionCable Color1DB25_1NODEB_IN1PWhiteDB25_14NODEB_IN1NBlue2DB25_2NODEB_IN2PWhiteDB25_15NODEB_IN2NOrange3DB25_3NODEB_IN3PWhiteDB25_16NODEB_IN3NGreen4DB25_4NODEB_IN4PWhiteDB25_17NODEB_IN4NBrownBTS Connection and Configuration18Relay Connection between ZXG10 B8700 and ZXDU68 B201

19BTS Connection and ConfigurationRelay Connection between ZXG10 B8800 and ZXDU68 B201

20BTS Connection and ConfigurationRelay Connection between ZXG10 B8900 and ZXDU68 B201

21Relay Alarm Connection in ZXDU68 B201Relay Alarm Connection in ZXDU68 T301BTS Connection and ConfigurationRNC/BSC Connection and Configuration

Agenda 22iTC Connection and ConfigurationRelay Connection between iTC and ZXDU68 T301

23BSC Connection and ConfigurationRelay Connection between BSC and ZXDU68 T301

24RNC Connection and ConfigurationRelay Connection between RNC and ZXDU68 T301

Agenda 25