    AB DH485 ProtocolXBT N/R/RT

    03/2009

  • 8/18/2019 Rockwell Dh 485

    2/46

    2 33004016 03/2009

     

     © 2009 Schneider Electric. All rights reserved.

  • 8/18/2019 Rockwell Dh 485

    3/46

    33004016 03/2009 3

    Table of Contents

    Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    Chapter 1 Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    Chapter 2 Operating Principle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11General Information on Bus Communications. . . . . . . . . . . . . . . . . . . . . . 12

    Operating Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    Chapter 3 Software Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 15Vijeo-Designer Lite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    Protocol - AB DH485 Dialog Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    Configuring Equipment Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    Equipment Address Dialog Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    Chapter 4 Variable Types Supported . . . . . . . . . . . . . . . . . . . . . . . . 23Variable Types Supported. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    Chapter 5 Cables and Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . 25Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26SUB-D 25 Pin Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    Chapter 6 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33XBT Detected Error Indication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

    Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37Appendix A RS232/RS485 Recommendations . . . . . . . . . . . . . . . . . . 39

    RS232 Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    RS485 Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

  • 8/18/2019 Rockwell Dh 485

    4/46

    4 33004016 03/2009

  • 8/18/2019 Rockwell Dh 485

    5/46

    33004016 03/2009 5

    §Safety Information

    Important Information

    NOTICE

    Read these instructions carefully, and look at the equipment to become familiar with

    the device before trying to install, operate, or maintain it. The following special

    messages may appear throughout this documentation or on the equipment to warn

    of potential hazards or to call attention to information that clarifies or simplifies a

    procedure.

  • 8/18/2019 Rockwell Dh 485

    6/46

    6 33004016 03/2009

    PLEASE NOTE

    Electrical equipment should be installed, operated, serviced, and maintained only by

    qualified personnel. No responsibility is assumed by Schneider Electric for any

    consequences arising out of the use of this material. © 2008 Schneider Electric. All Rights Reserved.

  • 8/18/2019 Rockwell Dh 485

    7/46

    33004016 03/2009 7

    About the Book 

    At a Glance

    Document Scope

    This document describes communication between automation systems and the

    XBT N/R/RT product range using the AB DH485 protocol.

    Validity Note

    The data and illustrations found in this document are not binding. We reserve the

    right to modify our products in line with our policy of continuous product

    development. The information in this document is subject to change without notice

    and should not be construed as a commitment by Schneider Electric.

    Related Documents

    You can download these technical publications and other technical information from

    our website at www.schneider-electric.com.

    Product Related Information

    Schneider Electric assumes no responsibility for any errors that may appear in this

    document. If you have any suggestions for improvement or amendments or have

    found errors in this publication, please notify us.

    No part of this document may be reproduced in any form or by means, electronic or

    mechanical, including photocopying, without express written permission of

    Schneider Electric.

    Title of Documentation Reference NumberXBT N/R/RT Instruction sheet W916810140111

    A07

    XBT N/R/RT User Manual 33003962

    Vijeo-Designer Lite Online help

  • 8/18/2019 Rockwell Dh 485

    8/46

    8 33004016 03/2009

    All pertinent state, regional and local safety regulations must be observed when

    installing and using this product. For reasons of safety and to ensure compliance

    with documented system data, only the manufacturer should perform repairs to

    components.

    Since the XBT N/R/RT terminals are not designed to pilot safety critical processes,

    no specific instructions apply in this context.

    User Comments

    We welcome your comments about this document. You can reach us by e-mail at

    [email protected].

    Compatibility

  • 8/18/2019 Rockwell Dh 485

    9/46

    33004016 03/2009 9

    1

    33004016 03/2009

    Compatibility

    Compatibility

    Overview

    The DH485 protocol available for XBT terminals can be used to communicate with

    the following Allen Bradley process controllers:

    SLC-5/0X PLCs

    Micrologix

  • 8/18/2019 Rockwell Dh 485

    10/46

    Compatibility

    10 33004016 03/2009

    OperatingPrinciple

    33004016 03/2009

  • 8/18/2019 Rockwell Dh 485

    11/46

    33004016 03/2009 11

    2

    33004016 03/2009

    Operating Principle

    Overview

    This chapter describes the operating principle of XBT terminals in applications using

    the AB DH485 protocol.

    *For additional information, refer to NEMA ICS 1.1 (latest edition), Safety Guidelines

    for the Application, Installation, and Maintenance of Solid State Control  

    What's in this Chapter?

    This chapter contains the following topics:

    WARNINGLOSS OF CONTROL

     

    The designer of any control scheme must consider the potential failure modes

    of control paths and, for certain critical functions, provide a means to achieve a

    safe state during and after a path failure. Examples of critical control functions

    are emergency stop and overtravel stop.

    Separate or redundant control paths must be provided for critical for critical

    control functions.

    System control paths may include communication links. Consideration must be

    given to the implications of unanticipated transmission delays or failures of thelink.*

    Each implementation of a Magelis XBT N/R/RT must be individually and

    thoroughly tested for proper operation before being placed into service.

    Failure to follow these instructions can result in death, serious injury, or

    equipment damage.

    Topic Page

    General Information on Bus Communications 12

    Operating Principle 13

  • 8/18/2019 Rockwell Dh 485

    12/46

    Operating Principle

    12 33004016 03/2009

    General Information on Bus Communications

    OverviewThe XBT terminals can be connected to PLCs using different protocols. This

    document describes the communication using the DH485 protocol with the XBT

    terminal acting as client.

    Roles of XBT Terminals

    The terminals are usually connected to a communication equipment (PLC or other)

    via a field bus. The XBT and the PLCs work autonomously of each other.XBT terminals perform the following functions:

    monitoring function: XBT terminals visualize the processes that are active in the

    PLCs and indicate alarm states

    command function: XBT terminals send information to the PLC upon user request

    Roles of Buses

    A bus system provides the possibility to connect different devices via a uniquecabling.

    Roles of Protocols

    The protocol defines the language that is spoken by all the equipment connected to

    the bus.

  • 8/18/2019 Rockwell Dh 485

    13/46

    Operating Principle

    33004016 03/2009 13

    Operating Principle

    OverviewThe DH485 protocol is an Allen Bradley communication protocol.

    The link between the XBT terminal and the Allen Bradley PLCs is one of the

    following types

    point-to-point

    multidrop

    WARNINGUNINTENDED EQUIPMENT OPERATION

    The protocol must be installed and used by authorized and properly trained

    personnel.

    Failure to follow these instructions can result in death, serious injury, orequipment damage.

  • 8/18/2019 Rockwell Dh 485

    14/46

    Operating Principle

    14 33004016 03/2009

    Software Configuration

    33004016 03/2009

  • 8/18/2019 Rockwell Dh 485

    15/46

    33004016 03/2009 15

    3Software Configuration

    Overview

    This chapter contains the protocol parameters you must configure in the Vijeo-

    Designer Lite software for operating XBT terminals in DH485 applications.

    What's in this Chapter?

    This chapter contains the following topics:

    Topic Page

    Vijeo-Designer Lite 16

    Protocol - AB DH485 Dialog Box 18

    Configuring Equipment Addresses 20

    Equipment Address Dialog Box 22

  • 8/18/2019 Rockwell Dh 485

    16/46

    Software Configuration

    16 33004016 03/2009

    Vijeo-Designer Lite

    OverviewUse the Vijeo-Designer Lite software to configure your XBT terminal for DH485

    protocol applications.

    Opening the Protocol - AB DH485 Dialog Box

    To open the Protocol - AB DH485 dialog box in Vijeo-Designer Lite for setting the

    protocol parameters, proceed as follows:

    WARNINGINCOMPATIBLE SOFTWARE

    Use only Schneider Electric manufactured or approved software to programhardware.

    Failure to follow these instructions can result in death, serious injury, or

    equipment damage.

  • 8/18/2019 Rockwell Dh 485

    17/46

    Software Configuration

    33004016 03/2009 17

    Step Action

    1 Start Vijeo-Designer Lite.

    To create a new application, continue with step 2, if you have already created a DH 485 application, skipsteps 2 and 3 and execute step 4.

    2 From the application browser on the left-hand side of the Vijeo-Designer Lite window select the item

    Configuration→ Terminal & Protocol.

    Result: The following dialog box will be displayed on the right-hand side of the Vijeo-Designer Litewindow.

    3 From the Terminal Protocol list in the lower right corner select the item AB DH485 and click Apply.

    4 Select from the application browser the item Protocol - DH485.

    Result: The dialog box Protocol - AB DH485 will be displayed on the right-hand side of the Vijeo-

    Designer Lite window where you can configure the protocol parameters for DH485 communication.

  • 8/18/2019 Rockwell Dh 485

    18/46

    Software Configuration

    18 33004016 03/2009

    Protocol - AB DH485 Dialog Box

    PurposeUse this dialog box to configure the protocol parameters for DH485 communication.

    Representation

    Elements of the dialog box

    Element Description

    Communication

    Transmission Speed Select the transmission speed (in bit/s) on your

    DH485 bus from the list. Make sure to configure the

    same transmission speed for all devices connectedto the bus.

    Parity Bit You cannot edit this parameter because in DH485

    communications the parity is always even.

    Data Length You cannot edit this parameter because in DH485

    communications the length of user data is always

    8 bits.

    Stop Bits You cannot edit this parameter because in DH485

    communications always 1 stop bit is used.

  • 8/18/2019 Rockwell Dh 485

    19/46

  • 8/18/2019 Rockwell Dh 485

    20/46

    Software Configuration

    20 33004016 03/2009

    Configuring Equipment Addresses

    OverviewUse the Vijeo-Designer Lite software to configure addresses for the equipment your

    XBT terminal should communicate with.

    Opening the Equipment Address Dialog Box

    To open the Equipment Address dialog box in Vijeo-Designer Lite for configuringDH485 equipment addresses, proceed as follows:

  • 8/18/2019 Rockwell Dh 485

    21/46

    Software Configuration

    33004016 03/2009 21

    Step Action

    1 Start Vijeo-Designer Lite.

    2 From the application browser on the left-hand side of the Vijeo-Designer Lite window select the item

    Equipments.

    Result: The following dialog box will be displayed on the right-hand side of the Vijeo-Designer Litewindow.

    3 In the Equipments dialog box select a slave device from the list.

    4 In the Equipment Settings→ Identification box below click the ... button right to the Address text box.

    Result: The Equipment Address dialog box will be displayed where you can configure an address for

    the selected equipment.

  • 8/18/2019 Rockwell Dh 485

    22/46

    Software Configuration

    22 33004016 03/2009

    Equipment Address Dialog Box

    PurposeUse this dialog box to configure the address of equipments connected to the

    network.

    Representation

    DH485 equipment address

    Elements of the dialog

    Element Description

    CPU Number Enter the address (between 0 and 31) for the

    selected equipment.

    OK button Click the OK button to assign the entered address to

    the selected equipment.

    Cancel button Click the Cancel button to discard the changes and

    to close the dialog box.

    Help button Click the Help button to open the Vijeo-Designer Lite

    online help.

  • 8/18/2019 Rockwell Dh 485

    23/46

  • 8/18/2019 Rockwell Dh 485

    24/46

    Variable Types Supported

    24 33004016 03/2009

    Cables and Connectors

    33004016 03/2009

  • 8/18/2019 Rockwell Dh 485

    25/46

    33004016 03/2009 25

    5Cables and Connectors

    OverviewThis chapter specifies the cables and connectors required for XBT terminals in

    DH 485 applications.

    What's in this Chapter?

    This chapter contains the following topics:

    Topic Page

    Cables 26

    SUB-D 25 Pin Connections 30

  • 8/18/2019 Rockwell Dh 485

    26/46

    Cables and Connectors

    26 33004016 03/2009

    Cables

    Technical DataThe following table lists the cables required to connect XBT terminals to the SLC /Micrologix PLCs in multidrop or point-to-point applications.

    * XBT RT 511: you must add a XBT ZG939 cable adapter (SUB-D25 RJ45)

    XBT RT 500: you must add a XBT ZG939 cable adapter (SUB-D25 RJ45)

    and a XBT ZRTPW for power supply.

    ** XBT RT 500: you must add a XBT ZG939 cable adapter for power supply.

    Multidrop Connection Diagram

    Connected Device Terminal Physical Link Cable Reference Length

    SLC/Micrologix, point-

    to-point

    XBT N401/N410

    XBT R410/R411

    RS232 XBT Z9732 2.5 m (8.2 ft.)

    (SUB-D25

    Micrologix 1000)

    XBT RT500/RT511 RS485 XBT Z9734** 2.5 m (8.2 ft.)(RJ45 Micrologix 1000)

    SLC/Micrologix,

    multidrop

    (via 1761-NET-AIC

    provided by Allen

    Bradley)

    XBT N401/N410

    XBT R410/R411

    RS232 XBT Z9730 2.5 m (8.2 ft.)

    (SUB-D25 SUB-D9)

    XBT RT500/RT511 XBT Z9741* 2.5 m (8.2 ft.)

    (SUB-D25 SUB-D9)

    CAUTIONPOWERED CONNECTORS

    Connect the serial link and printer link to the XBT with the power OFF.

    Failure to follow these instructions can result in injury or equipment damage.

  • 8/18/2019 Rockwell Dh 485

    27/46

    Cables and Connectors

    33004016 03/2009 27

    (*) Provided by Allen Bradley

    How to Connect a PC in Point-to-Point Mode to the DH485 Network 

    CAUTIONPOWERED CONNECTORS

    Connect the serial link and printer link to the XBT with the power OFF.

    Failure to follow these instructions can result in injury or equipment damage.

  • 8/18/2019 Rockwell Dh 485

    28/46

  • 8/18/2019 Rockwell Dh 485

    29/46

    Cables and Connectors

    33004016 03/2009 29

  • 8/18/2019 Rockwell Dh 485

    30/46

    Cables and Connectors

    30 33004016 03/2009

    SUB-D 25 Pin Connections

    OverviewThe following XBT terminals provide a SUB-D25 connector on their rear panels:

    XBT N401

    XBT N410

    XBT R410

    XBT R411

    The pin assignment of the SUB-D25 connector is shown in the following figure.

  • 8/18/2019 Rockwell Dh 485

    31/46

    Cables and Connectors

    33004016 03/2009 31

    Wiring

    The illustration below shows the wiring:

    Rt line impedance matching resistor

    NOTE: RP resistors are integrated into the XBT and feature:

    4.7 kΩ for XBT N

    470 Ω for XBT R

    600 Ω for XBT RT

  • 8/18/2019 Rockwell Dh 485

    32/46

    Cables and Connectors

    32 33004016 03/2009

    Diagnostics33004016 03/2009

  • 8/18/2019 Rockwell Dh 485

    33/46

    33004016 03/2009 33

    6Diagnostics

    XBT Detected Error Indication

    Overview

    XBT terminals indicate detected errors in different ways

    by displaying question marks ?????? on alphanumerical fields

    by displaying crosses for graphic objects

    by displaying hash characters in alphanumerical fields

    by blinking alphanumerical fields by issuing system error messages

    The following paragraphs list these three detected errors and their possible reasons.

    Question Marks and Crosses

    When question marks ?????? and crosses XXXXXX are displayed on the display ofyour XBT terminal, a transmission error has occurred. To correct this, check thefollowing:

    If... Then ...

    question marks are displayed verify that all cables are correctly connected.

    question marks are displayed verify that the communication parameters set in the

    Protocol - AB DH485 dialog box are identical for all

    equipment connected to the bus i.e. same transmission

    speed, same use of parity.

    question marks are displayed the XBT terminal may have received no response from thePLC.

  • 8/18/2019 Rockwell Dh 485

    34/46

    Diagnostics

    34 33004016 03/2009

    Hash Characters

    Hash characters displayed in alphanumerical fields on your XBT terminal indicate

    that the value to be displayed is too long for this alphanumerical field and cannot

    completely be displayed. The value 100 can, for example, not be displayed in a 2-

    digit alphanumerical field. To correct this, enter a shorter value or adapt the size of

    the alphanumerical field so that it can display any of the possible values of the PLC

    variable.

    Blinking Alphanumerical Fields

    Blinking alphanumerical fields on your XBT terminal indicate that the value of this

    field has exceeded or fallen below a user-defined threshold.

    System Error Messages

    A variety of system error messages is by default configured for the terminals. All

    these standard system messages are assigned a panel number 200+x. A distinction

    is made between system error messages indicating communication interruptions

    and status messages provoked by inputs at the terminal.

    These 2 message types differ by the numbers they are assigned and by the waythey are displayed at the terminal as shown in the list below:

    System Error

    Message Caused by:

    System Error Message

    Numbers

    Display Mode

    Communication

    Interruptions

    201 – 204 To indicate that a communication

    interruption has occurred, the message

    is displayed in a popup dialog box

    every 10 seconds.

    Input at Terminal 241 – 258 The status message is displayed as a

    response to user input at the terminal.

  • 8/18/2019 Rockwell Dh 485

    35/46

    Diagnostics

    33004016 03/2009 35

    Messages Caused by Communication Interruptions

    Messages 201 to 204 are issued by the terminal to indicate that a communicationinterruption has occurred. They are displayed in a popup dialog every 10 seconds.

    Messages Caused by Input at the Terminal

    Messages 242 to 254 are issued by the XBT as a response to user input at theterminal. These messages are displayed directly after the operator has sent anincorrect command to the terminal and will persist until the user has corrected the

    entered command or value. Messages 255 to 258 are status messages displayedafter the user has initiated an operation at the terminal to indicate that it has (or hasnot) been accepted and is in progress.

    If... Then ...

    message 201: DIALOG TABLE

    AUTHORIZATION INCORRECT is

    displayed

    the authorization word in the dialog table does not

    have the expected value. (Refer to the Vijeo-

    Designer Lite online help for information on how

    this word is working.) To correct this, verify that:

    you are connected to the right PLC

    the memory of your PLC is not corrupted

    the correct value is saved on the PLCmessage 202: DIALOG TABLE

    WRITING IMPOSSIBLE is displayed

    the write cycle to the dialog table of the PLC could

    not be ended. This condition may have the

    following causes:

    too much load on the communication bus

    EMC disturbances on the communication bus

    message 203: DIALOG TABLE

    READING IMPOSSIBLE is displayed

    the read cycle from the dialog table of the PLC

    could not be ended. This condition may have the

    following causes: too much load on the communication bus

    EMC disturbances on the communication bus

    If... Then ...

    message241: IMPOSSIBLE TO READ

    VARIABLE is displayed

    the terminal has attempted to read a variable and

    could not retrieve its value. This condition may

    have the following causes:

    too much load on the communication bus

    EMC disturbances on the communication bus

    message 242: IMPOSSIBLE TO

    WRITE VARIABLE is displayed

    the terminal has attempted to write in a memory

    area of the equipment and has received a

    negative acknowledgement or no

    acknowledgement at all. This condition may have

    the following causes:

    too much load on the communication bus

    EMC disturbances on the communication bus

  • 8/18/2019 Rockwell Dh 485

    36/46

  • 8/18/2019 Rockwell Dh 485

    37/46

  • 8/18/2019 Rockwell Dh 485

    38/46

    38 33004016 03/2009

    RS232/RS485Recommendations

    33004016 03/2009

  • 8/18/2019 Rockwell Dh 485

    39/46

    33004016 03/2009 39

    ARS232/RS485 Recommendations

    OverviewThis chapter decribes the RS232/RS485 recommendations.

    What's in this Chapter?

    This chapter contains the following topics:

    Topic Page

    RS232 Recommendations 40

    RS485 Recommendations 41

  • 8/18/2019 Rockwell Dh 485

    40/46

    RS232/RS485 Recommendations

    40 33004016 03/2009

    RS232 Recommendations

    Diagrams for RS232C Link RS232C link

    Maximum length for the link is 15 m (49.2 ft.).

    Wiring = 3 shielded wires with a minimum cross-section of 0.6 mm2 (AWG22)

    NOTE: The maximum length including the RS232 link is 15 m (49.21 ft.), provided

    that the equipment connected to the XBT terminal is not subject to more stringent

    restrictions (refer to connected devices instruction sheet) and for XBT RT500

    provided that the length of the cable is below 10 m (32.8 ft.) (because power is also

    supplied by this cable).

  • 8/18/2019 Rockwell Dh 485

    41/46

    RS232/RS485 Recommendations

    33004016 03/2009 41

    RS485 Recommendations

    Diagrams for RS485 Link RS485 link

    Maximum length for the link is 1,200 m (3,937 ft.). Wiring = 2 shielded twisted wires with a minimum cross-section of 0.6 mm2 

    (AWG22) and one 0 V wire

    NOTE: The maximum length including the RS485 link is 1,200 m (3,937 ft.),

    provided that the equipment connected to the XBT terminal is not subject to more

    stringent restrictions (refer to connected devices instruction sheet) and for

    XBT RT500 provided that the length of the cable is below 10 m (32.8 ft.) (because

    power is also supplied by this cable).

  • 8/18/2019 Rockwell Dh 485

    42/46

    RS232/RS485 Recommendations

    42 33004016 03/2009

    Glossary

    33004016 03/2009

  • 8/18/2019 Rockwell Dh 485

    43/46

    33004016 03/2009 43

    Glossary

    A

    AWG

    American wire gauge (wire diameter)

    F

    FCS

    frame check sequence

    M

    Magelis

    Generic commercial name of the range of Schneider HMI terminals.

    P

    PLC

    programmable logic controller

  • 8/18/2019 Rockwell Dh 485

    44/46

    Glossary

    44 33004016 03/2009

    R

    RS232

    recommended standard for connecting serial devices = EIA/TIA 232

    RS485

    recommended standard for connecting serial devices = EIA/TIA 485

    V

    Vijeo-Designer Lite

    Configuration software for the low end Magelis range. It replaces the XBT-L1000

    software.

    X

    XBT

    Any HMI terminal (when it is not necessary to make a distinction).

  • 8/18/2019 Rockwell Dh 485

    45/46

  • 8/18/2019 Rockwell Dh 485

    46/46

    Index

    46 33004016 03/2009

    Vvariable types

    DH485 protocol, 23 Vijeo-Designer Lite, 16 

    Wwiring, 31

    XXBT multidrop, 27 

    XBT Z9730, 26 

    XBT Z9732, 26 

    XBT Z9734, 26 