R&T 2004 - VFD Condensers - Reindl

Embed Size (px)

Citation preview

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    1/23

    Douglas T. Reindl

    Director, IRC

    University of Wisconsin-Madison

    University of Wisconsin-Madison

    Emerging Technologies:

     VFDs for Condensers

    Emerging Technologies:Emerging Technologies:

     VFDs VFDs for Condensersfor Condensers

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    2/23

    We’ve looked at VFDs on

    Evaporators and compressors, what is thepotential for application on condensers?

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    3/23

    Head Pressure Control

    Our heat rejection system controls headpressure

    Evaporative condenser fan controls

    on/off (single speed fans)

    two-speed fans

    variable speed fans

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    4/23

    Floating Head Pressure Control

    Consequences of lowering head pressure

    increased evaporative condenser energy use

    decreased compressor energy use

    reduced high stage compression (on average)

    Does the decrease in compressor energy

    use outweigh the increase in condenserfan energy use???

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    5/23

    Optimum Head Pressure

    82 84 86 88 90 92 94 960

    20

    40

    60

    80

    100

    120

    140

    160

    Saturated Condensing Temperature (F)

       P  o  w  e  r   (   k   W   )

    Compressor 

    Compressor+Condenser 

    Condenser 

     Axial Fan

    Tcond,opt = 87.1 F

    Toa,wb=78°F

     

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    6/23

    Optimum Head Pressure

    82 84 86 88 90 92 94 960

    50

    100

    150

    200

    250

    300

    Saturated Condensing Temperature (F)

       P  o  w  e  r   (   k   W   )

    Centrifugal Fan

    Compressor 

    Compressor+Condenser 

    Condenser 

    Tcond,opt = 89.9 F

    Toa,wb=78°F

     

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    7/23

    Optimum Head Pressure

    Depends on:

    Condenser fan type (axial vs. centrifugal)

    Fan control strategy

    Condenser sizing strategy

    95°F saturated condensing (historic)

    90°F saturated condensing (recommended)

    85°F saturated condensing (possible not practical)

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    8/23

    Case Study:Cold Storage Warehouse

    Size34°F 39,000 (ft²)

    0°F 52,000 (ft²)

    600,000 (lbs/day, food)

    Type

    ammonia, single-stagecompression, liquidoverfeed evaporators

    Operating Costs

    9,000 ($/month)

    4 Compressors Available

    Instrumentation

    Temp, Pressure,

    Mass Flow!

    Defrost Strategies

    Head Pressure Control

    The refrigeration system examined as part of this case study is a cold storage warehouse

    facility located near Milwaukee, WI. The facility contains four types of refrigerated spaces – low temperature freezer (0°F), cooler (34°F), docks (45°F), and ripening rooms (45-64°F).

    From a thermal mass perspective, the warehouse construction type can be considered

    “lightweight” for all spaces. There is mostly insulation and very little mass in the walls and

    roofs.

    The freezer and cooler with its loading dock are separate buildings located adjacent to each

    other. The banana and tomato ripening rooms are located in a heated space adjacent to the

    cooler. The refrigerant used throughout this system is ammonia (R-717). Evaporators in the

    freezer are top fed, pumped liquid overfeed. Cooler, and cooler dock evaporators are all

    bottom feed pumped liquid overfeed where as the evaporators in the banana and tomato

    ripening rooms are direct expansion controlled by thermal expansion valves and back

    pressure regulators.

    (NOTE: This case study was conducted by Manske, K. A. in partial fulfi llment of the

    requirements for a MS degree in Mechanical Engineering under the direction of

    Professor’s Reindl , D. T., and Klein, S.A. during 1998-1999. Portions of the thesisprepared by Mankse titled “ Performance Optimization of Industrial Refrigeration

    Systems” , 1999 have been excerpted for this section. A complete copy of the Manske

    thesis is available for download at: http://www.irc.wisc.edu/publications

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    9/23

    Case Study:Cold Storage Warehouse

    Condenser 

    Qreject

    Evap

    Qspace

    Evap

    Qspace

    23°F

    -10°F

    Evap

    Qspace

    45-55°F

    BPR 

    D

    X

    PLO

    PLO

    Design Loads Yearly Average Loads

    Fruit Ripening = 90 tons

    Cooler = 107 tons

    Freezer = 106 tons

    Fruit Ripening = 43 tons

    Cooler = 58 tons

    Freezer = 71 tons

    HPR 

    There are three main vessels in the system as shown above. The first is the high pressure

    receiver where liquid refrigerant draining from the condenser is stored. Liquid refrigerant from

    the high pressure receiver is then throttled to either the intermediate pressure receiver or to

    the direct expansion evaporators in the banana and tomato ripening rooms. The temperature

    of the refrigerant in the banana/tomato room evaporators is regulated at a desired level by use

    of a back-pressure regulator. The back-pressure regulator then throttles the refrigerant gas tothe intermediate pressure receiver which is at a lower temperature/pressure. Liquid in the

    intermediate pressure receiver is then either pumped to the cooler and cooler dock

    evaporators or throttled again to the low pressure receiver. Liquid refrigerant from the low

    pressure receiver is pumped to freezer evaporators with a mechanical liquid recirculating

    pump. Liquid levels in the intermediate and low pressure receivers are maintained at a near

    constant level by a pilot operated, modulating expansion valve controlled by a float switch

    located on the receiver tank.

     A single-screw (Vilter model# VSS 451 connected to the low temperature vessel) and

    reciprocating compressor (Vilter model# VMC 4412 connected to the high temperature vessel)

    operate in parallel, each compressing to a common discharge header and a singleevaporative condenser. The suction line from the low pressure receiver leads to the screw

    compressor. The suction line from the intermediate pressure receiver leads to the

    reciprocating compressor. Additional compressors, in parallel piping arrangements to the

    primary compressors, can be brought on-line if the load exceeds the capacity of the primary

    compressors.

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    10/23

    Control Options

    Single speed fan with on/off control

    most common head pressure control method

    set cut-in (e.g. 150 psig) & cut-out pressures(e.g. 140 psig)

    simple control method but results in

    higher energy consumption vs. two-speed or VFD

    higher maintenance (fan motors & belts)

    liquid management problems w/multiple condensers

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    11/23

    Control Options – Cont.

    2-Speed fan control set high speed cut-in (e.g. 160 psig)

    low-speed cut-in pressure (e.g. 150 psig), andlow-speed cut-out pressure (e.g. 140 psig)

    relatively simple control method but results in

    higher capital cost compared to single speed fan option

    lower energy consumption vs. single-speed but slightly higherenergy consumption compared to variable speed

    yields less system transients compared to single speed

    sequencing speed controls requires attention

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    12/23

    Control Options – Cont.

     Variable speed fan (VFD) set a target head pressure modulate fan speed

    to maintain head pressure

    a very simple principle & method to implement

    highest capital cost alternative

    lowest energy consumption control alternative

    modulate all condensers the same in systems withmultiple evaporative condensers

    results in smoother system operation with minimaltransients

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    13/23

    Condenser Fan Control Map

    Strategy Mode 1 Mode 2 Mode 3 Mode 4 Mode 5

    Small Motor off on off on

    Large Motor off off on on

    Small Motor off off on

    Large Motor off on on

    Small Motor off on on on

    Large Motor off off half-speed on

    Small Motor off half-speed half-speed on on

    Large Motor off off half-speed half-speed on

    Small Motor off  

    Large Motor off  5

    variable speed

    variable speed

    1

    2

    3

    4

    The above map provides five different strategies that could be used for an evaporative

    condenser that is equipped with twin motors, two-speed fans, or variable speed fans. The

    “modes” are indicative of changes in head pressure (either increasing as one moves from left

    to right or decreasing as one moves from right to left).

    For example, strategy 3 would work as follows. In mode 1 all fans are off. As the head

    pressure rises, the system responds by energizing a small fan motor in attempts to maintain

    system head pressure. If the head pressure continues to rise and the setpoint is not satisfied,

    mode three is initiated by the start of the larger fan motor to half-speed. As the head pressure

    rises further, mode 4 dictates that the larger fan motor is tripped to run at high speed. The

    exact opposite sequence occurs as the head pressure falls.

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    14/23

    Condenser Fan Control Options

    The above figure illustrates the required fan energy (expressed as a percentage of full-load

    fan power) as a function of the evaporative condenser capacity for the five strategies listed

    previously. The least efficient option is the on/off control (strategy 1) while the most efficient

    option is the variable speed drive option. The two-speed fan option yields nearly all of the

    part-load power and capacity benefits of the variable speed option but with much less costly

    equipment.

    Notice that at zero fan power for all options, the capacity of the evaporative condenser is not

    zero. This is due to the fact that natural convection will occur drawing air through the

    condenser coils and rejecting heat yielding about 10% of the condenser’s heat rejection

    capacity while the fans are idle. This assumes that the condenser coils are running wet i.e.

    water continues to flow over the condenser coils.

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    15/23

    Condenser Fan Controls

    Source: Manske, K., 2000

    May

    Of course we do not want to just minimize the power of the evaporative condenser at the

    expense of the system; consequently, we must look at the impacts or tradeoffs associated

    with spending more energy on evaporative condenser fans vs. the reduction in compressor

    power that accrues due to the lower head pressure.

    The case study system had an oversized evaporative condenser. As a result, it was possible

    to drive head pressures extremely low in the system. So low in fact that the incremental

    expenditure of fan energy was not compensated for by an incremental reduction in

    compressor energy demand.

    The above plot shows the comparison between heat rejection system control strategies. The

    point furthest to the left on the curves in the figure represents the system balance point head

    pressure at which the condenser is operating at 100 percent capacity (for a given outdoor air

    wet bulb and system load during a peak hour on a average day in May). Any further decrease

    in condensing pressure would prevent the condenser from rejecting the required amount of

    energy from the system. The figure shows that VFD fan control could save the system nearly

    8% in combined compressor and condenser energy requirements if the head pressure were

    raised to 125 psia. VFD fan control looses its advantages at low head pressures because thefans must run at near full speed most of the time anyway. At high head pressures the fans in

    on/off control don’t stay on long because of the high rate of heat transfer that occurs.

    However, at high head pressure an on/off control strategy would cycle the fans on and off

    frequently which would cause excessive wear on the motors and fan belts. The figure also

    shows that there is a different optimum head pressure for each type of condenser fan control.

    It is also interesting to note that half-speed fan motors have energy requirements that are only

    approximately one percent above the VFD motors at elevated head pressures. Since this

    system has a minimum allowed head pressure of 130 psia, VFD and half-speed motors may

    have very similar energy requirements for most of the year.

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    16/23

    Optimum Head Pressure Control

    Source: Manske, K., 2000

    This plot illustrates the preferred control head pressure control strategy for two different

    evaporative condenser sizes. With an evaporative condenser sized for 95 F saturated

    condensing temperature on a design day, the optimum head pressure is the lowest head

    pressure achievable by running the evap condenser fans “full out”. If the condenser is

    oversized (i.e. an oversized evap condenser is defined as one that yields a saturated

    condensing temperature of 85 F on the design day), there is an optimum head pressure (i.e. ahead pressure greater than the minimum achievable that will minimize the combined power of

    the compressor and condenser). In this case, the optimum head pressure is likely a function

    of the outside air wetbulb temperature.

    The dark set of lines is for the condenser that is currently installed in the system. The current

    condenser is large enough to allow the system to balance out with a saturated condensingtemperature of 85°F on the design day. The compressor/condenser power with a smaller

    condenser is given by the lighter colored line. The point furthest to the left on each line

    represents the pressure at which the evaporative condenser has reached 100 percent

    capacity. Given that the load is constant, it would be physically impossible to achieve a lower

    head pressure without adding additional condensing capacity. Note, the above case assumesthat the refrigeration load is progressively decreasing during the winter months; however,

    refrigeration load has little influence on the optimum head pressure.

    Because of the presence of high temperature direct-expansion coils in the case study system,

    the head pressure is not allowed to go below 130 psia. Therefore, the system cannot possibly

    be operated at its ideal head pressure except for the months of June through September. It

    must be operated above its optimum head pressure resulting in a slight excess of compressor

    power.

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    17/23

    50 55 60 65 70 75 80120

    130

    140

    150

    160

    170

    180

    190

    200

    210

    220

    230

    1.5x106

    1.7x106

    1.9x106

    2.1x106

    2.3x106

    2.5x106

    2.6x106

    2.8x106

    3.0x106

    3.2x106

    3.4x106

    Outside Air Wet Bulb Temperature [°F]

       O  p   t   i  m  u  m   H  e  a   d   P  r  e  s  s  u  r  e   [  p  s   i  a   ]

    Calculated Ideal Head Pressure (Variable Evaporator Load)Calculated Ideal Head Pressure (Variable Evaporator Load)

    Curve Fit (Variable Evaporator Load)Curve Fit (Variable Evaporator Load)

    minimum head pressure    T

      o   t  a   l   S  y  s   t  e  m   H  e  a   t   R  e   j  e  c   t   i  o  n   [   B   t  u   /   h  r   ]

    Calculated Condenser Heat Rejection (Variable Evaporator Load)Calculated Condenser Heat Rejection (Variable Evaporator Load)

    Calculated Ideal Head Pressure (Constant Evaporator Load)Calculated Ideal Head Pressure (Constant Evaporator Load)

    Calculated Condenser Heat Rejection (Constant Evaporator Load)Calculated Condenser Heat Rejection (Constant Evaporator Load)

    as required by dx txv

    Optimum Head Pressure

    Source: Manske, K., 2000

    When performing the calculations to identify the optimum condensing pressure for the year,

    we discovered that the optimum condensing pressure had a near linear relationship with the

    outside air wet bulb temperature. The above curve illustrates the relationship between

    optimum head pressure and outside air wetbulb temperature (lower curve) over a range of

    evaporator load conditions (corresponding variability in heat rejection is shown by the points

    above). In the case of this system, a very simple linear relationship was developed thatallows a supervisory reset on the system head pressure given the prevailing outside air wet

    bulb temperature according to the following:

    Phead,opt = -27.6 + 2.55 * Twb

    where Phead,opt is the head pressure corresponding to minimum system power in psia and Twbis the outside air wet bulb temperature in F. This relationship assumes that the condensers

    have variable speed drives. Keep in mind that the above relationship needs to have a lower

    bound as dictated by the characteristics of each given system.

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    18/23

    Optimizing Head Pressure

    1. Measure the outdoor air wet bulb temperature2. Note the current condensing pressure and system electrical demand

    3. Reset the condensing pressure down 5 psig & allow system to equilibrate

    4. Note the new system electrical demand

    5. Continue steps 3 and 4 until the lower condensing pressure limit setpoint isreached

    6. Plot the system electrical demand vs. the condensing pressure and note thecondensing pressure corresponding to point of minimum system electricaldemand

    7. Plot that single “optimum” condensing pressure point on a optimumcondensing pressure vs. outdoor air wet bulb temperature curve

    8. Repeat the procedure from 1-7 to more fully develop a curve analogous to

    the figure given on the previous page.

    Procedure for Determining Optimum Relation Between Condensing Pressure and Outdoor

    Wetbulb

    The trajectory of optimum condensing pressures for corresponding outside air wet bulb

    temperatures as shown on the previous page is specific to the existing ammonia system.

    Each system will have its own unique trajectory. However, the following procedure can be

    used to empirically develop the trajectory of optimum condensing pressures. Note, this

    procedure needs to be executed during off-design periods of the year (during relatively lower

    outside air wet bulb conditions). The procedure also requires the ability to continuously

    monitor the outdoor air wet bulb temperature, condensing pressure, and the engine room total

    electrical demand. We also recommend that other system state variables (such as suction

    pressures, superheat – if applicable, etc.) be monitored to ensure reliable system operation

    during the procedure.

    1. Measure the outdoor air wet bulb temperature

    2. Note the current condensing pressure and system electrical demand

    3. Reset the condensing pressure down 5 psig (35 kPa) and allow the system to equilibrate4. Note the new system electrical demand

    5. Continue steps 3 and 4 until the lower limit in condensing pressure setpoint is reached

    6. Plot the system electrical demand vs. the condensing pressure and note the condensing

    pressure that corresponds to the point of minimum system electrical demand

    7. Plot that single “optimum” condensing pressure point on a optimum condensing pressure

    vs. outdoor air wet bulb temperature curve

    8. Repeat the procedure from 1-7 to more fully develop a curve analogous to the figure given

    on the previous page.

    Once the optimum condensing pressure trajectory curve is developed, it can be programmed

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    19/23

    Economic Benefits of Drive

     Annual savings for warehouse

    13 kW (peak) reduction

    97,140 kWh reduction (~5%)

    $3,856 per year in electrical operatingcosts (~5%)

    Drive cost = $6,900

    Simple payback of 1.8 yrs

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    20/232

    Final Thoughts

     VFDs on condensers can provideeconomic and operating cost benefitson the high-side

    Take advantage of lowering headpressure

    Consider barriers to lowering headpressure

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    21/232

    Floating Head Pressure Control

    Head pressure limits dictated by: hot gas defrost requirements

    setting of defrost relief valves

    sizing of hot gas main

    condensate management in hot gas main

    DX evaporators

    most thermostatic expansion valves need at least75 psig differential pressure to function properly

    liquid injection oil cooling check manufacturer’s requirements for TXV

    pressure differential

     As with most things, there are limits to lowering system head pressure. We do not want to

    create problems by trying to improve the efficiency of our systems. The above items are

    some of the more common factors constraining or limiting our ability to lower system head

    pressure. Keep in mind that these items may not necessarily be unmovable barriers;

    however, changes in components or system arrangements may be required to overcome their

    limiting effects on the system.

    Hot Gas Defrost:

    Many industrial refrigeration systems utilize hot gaseous refrigerant to defrost evaporators. In

    cases where defrost relief valves are installed, a sufficient pressure differential (e.g. 75 psig)

    across the valve must be created to open the valve. Sizing of the hot gas main may also

    impose constraints. If a hot gas main is undersized, hot gas (at a sufficient rate) will not be

    delivered to the evaporator without a high differential pressure. For larger size hot gas mains,

    a much lower differential pressure will allow adequate flow of hot gas to defrosting

    evaporator(s). Finally, if condensate is not properly managed in hot gas mains, hydraulic

    shock can cause catastrophic failures of hot gas piping on a call for defrost. Also, the

    condensate effectively decreases the pipe size causing similar symptoms as an undersizedline with regard to head pressure requirements. All of these deficiencies can be overcome in

    the long run; however, they do create real barriers to lowering head pressure in the short run.

    DX Evaporators:

    In systems that utilize direct-expansion evaporators, a minimum differential pressure is

    required across the thermostatic expansion valves (TXV). The minimum pressure differential

    is dependent on the specific valve selection but is routinely on the order of 75 psig. When we

    drop the pressure differential across the TXV below the minimum, we lose controllability of the

    valve (control engineers call this “control authority”). What results is an inability to properly

    modulate refrigerant to the evaporator. Since our evaporator pressure i.e. downstream of the

    TXV the pressure is fixed (to satisfy our temperature requirements for meeting load), the head

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    22/232

    Floating Head Pressure Control

    Head pressure limits dictated by: evaporative condenser selection

    oversized evaporative condensers results in anoptimum head pressure that depends on outdoorair wet bulb temperature

    evaporative condenser fan controls

     VFD fans are preferred but 2-speed fans yieldconsiderable benefits

    thermosiphon oil coolers

    Evaporative Condenser Selection:

    If an evaporative condenser is too small, the system head pressure will rise until its heat

    rejection capacity is sufficient to reject the needed heat from the system.

    Fan Controls:

     Although fan controls themselves do not necessarily limit head pressure, there are methods of

    fan controls that lead to more stable and efficient system operation. Two speed condenser

    fans or variable frequency drive (VFD) fans have better capacity modulating capability and

    result in more stable head pressures – leading to more stable system operation. In addition to

    their stability, two-speed and VFD controlled fans will result in improved energy due to their

    better part-load performance as compared to single speed fans.

    Thermosiphon Oil Cooling (TSOC):

    TSOC improves compressor efficiency by using a thermosiphon effect coupled with thesystem’s evaporative condenser to reject heat from the compressor’s oil.

  • 8/18/2019 R&T 2004 - VFD Condensers - Reindl

    23/23

    Floating Head Pressure Control

    Head pressure limits dictated by: hand expansion valve settings

    significantly lowering head pressure will likely requireseasonal HEV adjustments

    this constraint can be overcome by the use of motorizedvalves or pulse width valves

    oil separator sizing

    gas driven systems (transfer systems & gas pumpers)

    controlled-pressure receiver setpoints

    heat recovery engineering and operations (knowledge & willingness)