Upload
rulas-santana
View
213
Download
0
Embed Size (px)
Citation preview
8/11/2019 RX-1939_QI_1-0-0
1/36
RX-1939
11990000MMHHZZDDUUAALLMMOODDEE
WWIIRREELLEESSSS
RREEPPEEAATTEERR
USER MANUAL
RX-1939 QI: 1-0-0
Comba Telecom Ltd.
8/11/2019 RX-1939_QI_1-0-0
2/36
USER MANUAL for RD-XXXX
The information contained herein is the responsibility of and is approved by the
follow ing, to whom all enquiries should be directed in the first instance:
This is an unpublished work the copyright in which vests in Comba International
("Comba"). All r ights reserved.
The information contained herein is confidential and the property of Comba and is
supplied without liability for errors or omissions. No part may be reproduced,
disclosed or used except as authorised by contract or other written permission.
The copyright and the foregoing restriction on reproduction and use extend to allmedia in which the information may be embodied.
8/11/2019 RX-1939_QI_1-0-0
3/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 3ENU Status : 1-0-0
0.1 CONTENTS
Section Page
0.2 CONTENTS ........................................................................................................................... 30.3 INDEX TO FIGURES AND TABLES ..................................................................................... 50.4 HISTORY ............................................................................................................................... 60.5 GLOSSARY OF TERMS ....................................................................................................... 70.6 SAFETY NOTICES AND ADMONISHMENTS ...................................................................... 8
1 GENERAL INFORMATION ................................................................................................... 9
2 EQUIPMENT DESCRIPTION .............................................................................................. 102.1 SYSTEM DIAGRAM ............................................................................................................ 102.2 EQUIPMENT LAYOUT ........................................................................................................ 112.3 EQUIPMENT CONSTITUTION ........................................................................................... 11
2.4
KIT OF PARTS .................................................................................................................... 12
3 INSTALLATION ................................................................................................................... 133.1 WARNINGS AND ALERTS ................................................................................................. 133.2 SITE PLANNING CONSIDERATIONS ................................................................................ 143.3 INSTALLATION PROCEDURES ......................................................................................... 153.3.1 GOODS INWARDS INSPECTION ...................................................................................... 153.3.2 TOOLS ................................................................................................................................. 153.3.3 PREPARATION ................................................................................................................... 153.3.4 WALL MOUNTING .............................................................................................................. 163.3.5 POLE MOUNTING OF MOUNTING RACK ......................................................................... 173.3.6 FAN INSTALLATION AND MAINTENANCE ....................................................................... 173.3.7 DRIP-LOOP ......................................................................................................................... 18
3.4
EQUIPMENT CONNECTORS ............................................................................................. 19
3.4.1 CONNECTORS ................................................................................................................... 193.4.2 GROUNDING CONNECTION ............................................................................................. 203.4.3 LI-ION BATTERY CONNECTION ....................................................................................... 203.4.4 RF CONNECTION ............................................................................................................... 203.4.5 EXTERNAL ALARM CONNECTION ................................................................................... 203.4.6 CONNECTION BETWEEN PC AND EQUIPMENT ............................................................ 213.4.7 EXT ALARM CONNCETION ............................................................................................... 21
4 COMMISSIONING ............................................................................................................... 224.1 PRE-COMMISSIONING TASKS ......................................................................................... 224.2 MCU LED INDICATORS ..................................................................................................... 224.3 COMMISSIONING PROCEDURES .................................................................................... 23
5 OMT ..................................................................................................................................... 255.1 LOCAL AND REMOTE CONNECTIONS TO OMT ............................................................. 255.1.1 LOCAL CONNECTION TO OMT......................................................................................... 255.1.2 REMOTE CONNECTION TO OMT ..................................................................................... 265.2 OMT CONFIGURATION ..................................................................................................... 275.3 RF PARAMETER ................................................................................................................. 275.3.1 SWITCH .............................................................................................................................. 285.3.2 CHANNEL NO. .................................................................................................................... 285.3.3 ATT ...................................................................................................................................... 295.3.4 ALARM THRESHOLD ......................................................................................................... 295.3.5 ALARM INFORMATION ...................................................................................................... 295.4 PROPERTIES INFO. ........................................................................................................... 31
5.4.1
EQUIPMENT ID ................................................................................................................... 31
5.4.2 COMM. CONFIG ................................................................................................................. 31
8/11/2019 RX-1939_QI_1-0-0
4/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 4ENU Status : 1-0-0
6 MAINTENANCE ................................................................................................................... 33
7 APPENDICES ...................................................................................................................... 347.1 APPENDIX A: TOOLS FOR INSTALLATION AND MAINTENANCE .................................. 347.2 APPENDIX B: SERVICING POLICY AND RETURN OF EQUIPMENT .............................. 347.3 APPENDIX C: RMA (RETURN MATERIAL AUTHORIZATION) FORM ............................. 35
8/11/2019 RX-1939_QI_1-0-0
5/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 5ENU Status : 1-0-0
0.2 INDEX TO FIGURES AND TABLES
Figure 1: Views of RX-1939 Enclosure .........................................................................................................9Figure 2: RX-1939 System Diagram ...........................................................................................................10Figure 3: RX-1939 Internal Layout ..............................................................................................................11
Figure 4: Mounting Rack Overview .............................................................................................................15Figure 5: Wall Mounting ..............................................................................................................................16
Figure 6: Pole Mounting Overview ..............................................................................................................17Figure 7: Fan Installation .............................................................................................................................18Figure 8: Bottom Panel Interface Diagram ..................................................................................................19Figure 9: The Connection between Equipment and PC ..............................................................................21Figure 10: Connection Type ........................................................................................................................26Figure 11: Serial Port Configuration ............................................................................................................26Figure 12: Remote Connection ...................................................................................................................27Figure 13: OMT Main Window ....................................................................................................................27Figure 14: Switch .........................................................................................................................................28Figure 15: Channel No. ...............................................................................................................................28Figure 16: Frequency Calculator .................................................................................................................28
Figure 17: ATT ............................................................................................................................................29Figure 18: Alarm Threshold .........................................................................................................................29
Figure 19: Master Alarm ..............................................................................................................................30Figure 20: External Alarm............................................................................................................................30Figure 21: Fan Alarm...................................................................................................................................30Figure 22: Equipment ID .............................................................................................................................31Figure 23: Com. Config. ..............................................................................................................................32
Table 1: Equipment Constitution .................................................................................................................11Table 2: Equipment KOP.............................................................................................................................12Table 3: Cable Connection ..........................................................................................................................14Table 4: RX-1939 Connectors .....................................................................................................................19
8/11/2019 RX-1939_QI_1-0-0
6/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 6ENU Status : 1-0-0
0.3 HISTORY
Change No. ENU Details Of Change
1 1-0-0 RX-1939 user manual first created in Dec 2011 and referred to itsChinese manual RX-1939-1001YH.
8/11/2019 RX-1939_QI_1-0-0
7/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 7ENU Status : 1-0-0
0.4 GLOSSARY OF TERMS
ALC Automatic Level Control
ATT Attenuation
AFC Antenna Feedback Cancellation
BTS Base Transceiver Station
CSA Cross Sectional Area
dB Decibel
dBm Decibels relative to 1 milliwatt
DL Downlink
DPX Duplexer
DT Donor Terminal
E/O, O/E Electrical/Optical, Optical/Electrical
FSK Frequency Shift Keying
FOU Fiber Optical Unit
GSM Global Standard for Mobile Communication
Hz Hertz
ID Identification
LNA Low Noise Amplifier
MCU Main Control Unit
MHz Megahertz
MT Mobile Terminal
MTBF Mean Time Between Failures
NF Noise FigureOMC Operation & Maintenance Center
OMT Operation & Maintenance Terminal
OP Optical Fiber
PA Power Amplifier
PLL Phase Locked Loop
PSU Power Supply Unit
RF Radio Frequency
RFU Radio Frequency Unit
RX Receive
SMA Sub-Miniature A ConnectorSIU Slide-In-Unit
TX Transmit
UL Uplink
VAC Volts Alternating Current
VSWR Voltage Standing Wave Ratio
WDM Wavelength Division Multiplexer
8/11/2019 RX-1939_QI_1-0-0
8/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 8ENU Status : 1-0-0
0.5 SAFETY NOTICES AND ADMONISHMENTS
This document contains safety notices in accordance with appropriate standards. In the interests ofconformity with the territory standards for the country concerned, the equivalent territorial admonishments
are also shown.
Any installation, adjustment, maintenance and repair of the equipment must only be carried out by trained,authorized personnel. At all times, personnel must comply with any safety notices and instructions.
Specific hazards are indicated by symbol labels on or near the affected parts of the equipment. The labelsconform to international standards, are triangular in shape, and are coloured black on a yellowbackground. An informative text label may accompany the symbol label.
Hazard labeling is supplemented by safety notices in the appropriate equipment manual. These noticescontain additional information on the nature of the hazard and may also specify precautions.
Warning:
These draw the attention of personnel to hazards that may cause death or injury to the operator or others.Examples of use are cases of high voltage, laser emission, toxic substances, point of high temperature,etc.
Alert:These draw the attention of personnel to hazards that may cause damage to the equipment. An exampleof use is the case of static electricity hazard.
Caution notices may also be used in the handbook to draw attention to matters that do not constitute arisk of causing damage to the equipment but where there is a possibility of seriously impairing itsperformance, e.g. by mishandling or gross maladjustment. Warnings and Cautions within the main text donot incorporate labels and may be in shortened form.
CAUTION: danger of explosion if battery is incorrectly replaced. Replace only with the same or equivalenttype.
End of Section
8/11/2019 RX-1939_QI_1-0-0
9/36
8/11/2019 RX-1939_QI_1-0-0
10/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 10ENU Status : 1-0-0
2 EQUIPMENT DESCRIPTION
2.1 SYSTEM DIAGRAM
DLPA
ULPA
MODEM
DT MT
DT
Duplexer
Li-ion
Battery
PSUAC 100V 240V
Digital
RF
Monitor
ing
Module
MODEM
ANT
LNA
LNA VSWR
Power
ConversionFan
Duplex
Coupling
MT
Duplexer
Figure 2: RX-1939 System Diagram
As shown in the above figure, the downlink BS signals go through DT port to the system and then todownlink by duplexer separation. The DL signals will go through DT duplexer then to digital RF monitoringmodule for digital filtering and self-oscillation elimination. Then the DL signals will be sent to downlink PAto amplify power and filter via duplexer. After amplification, the signals are transmitted at the MT port to
the service antenna.
On the UL, the signals transmitted by the mobile go through MT integration duplexer and digital RFmonitoring module then to uplink PA to power amplify and filter via duplexer, finally get back to BS bydonor antenna.
8/11/2019 RX-1939_QI_1-0-0
11/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 11ENU Status : 1-0-0
2.2 EQUIPMENT LAYOUT
The following figure shows RX-1939 internal layout.
MT DuplexerDT Duplexer
Door Open
Switch
DL PAUL PAPower Supply
Convert Module
Surge
Arrestor
Integrated Module
PSU
Figure 3: RX-1939 Internal Layout
2.3 EQUIPMENT CONSTITUTION
RX-1939 consists of the modules described as below:
Identifier Functional Description
Power Supply Unit (PSU)converts the input voltage into a stable DC toprovide power for the internal functional modulesand to charge the internal Li-ion battery.
Surge Arrestoris assumed that the antenna system will haveample lightning protection.
Integrated Module consists of digital processing unit, RF unit andmonitoring unit.
DT Duplexer realizes UL/DL TX/RX isolation, build-in DL LNA isused to amplify the DL low noise signal.
MT Duplexer realizes UL/DL TX/RX isolation, build-in UL LNA isused to amplify the UL low noise signal while DLVSWR detects DL output power and VSWR.
Table 1: Equipment Constitution
8/11/2019 RX-1939_QI_1-0-0
12/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 12ENU Status : 1-0-0
2.4 KIT OF PARTS
For this system, the following are shipped:
Product Identifier Description Quantity
RX-1939 QI This equipment manual on CD-Rom 1
CPC Connector X14J7P 1
Ground Cable BVR10mm2, 2m 1
Key N/A 2
Ethernet Cable 2m 1
Modem Antenna XD-WCDMA 1
Masonry Bolt M10110 4
U Bolt (with 2 nuts, flat washer,spring washer per bolt)
M10x85x110 2
Power Supply Cable n/a 1
Allen Key 5.5mm 1T-shape Pentagon ScrewWrench
5mm 1
OMT V5.0 or above OMT software on CD-Rom 1
Factory Test Report N/A 1
Table 2: Equipment KOP
End of Section
8/11/2019 RX-1939_QI_1-0-0
13/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 13ENU Status : 1-0-0
3 INSTALLATION
3.1 WARNINGS AND ALERTS
Radio Frequency Energies
There may be situations, particularly for workplace environments near high-powered RF sources, whererecommended limits for safe exposure of human beings to RF energy could be exceeded. In such cases,restrictive measures or actions may be necessary to ensure the safe use of RF energy.
High Voltage
The equipment has been designed and constructed to prevent, as far as reasonably, practicable danger.Any work activity on or near equipment involving installation, operation or maintenance must be, as far asreasonably, free from danger.
Where there is a risk of damage to electrical systems involving adverse weather, extreme temperatures,wet, corrosive or dirty conditions, flammable or explosive atmospheres, the system must be suitablyinstalled to prevent danger.
Protective Earthing
Equipment provided for the purpose of protecting individuals from electrical risk must be suitable for thepurpose and properly maintained and used.
Handling Precautions
This covers a range of activities including lifting, lowering, pushing, pulling, carrying, moving, holding orrestraining an object, animal or person. It also covers activities that require the use of force or effort, suchas pulling a lever, or operating power tools.
Electrostatic Discharge (ESD)
Observe standard precautions for handling ESD-sensitive devices. Assume that all solid-state electronicdevices are ESD-sensitive. Ensure the use of a grounded wrist strap or equivalent while working withESD-sensitive devices. Transport, store, and handle ESD-sensitive devices in static-safe environments.
8/11/2019 RX-1939_QI_1-0-0
14/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 14ENU Status : 1-0-0
3.2 SITE PLANNING CONSIDERATIONS
Site Considerations
The site considerations are listed below:
The distance between the donor antenna and the BS should satisfy line of sight requirements formaximum coverage area. The received spots accept field intensity at least -70dBm.
Make sure that TX and RX antennas isolation should more than the max gain that of -15dB.
Supply power near by the BS and easily access to the grounding spot.
Installation Location
Mounting surface shall be capable of supporting the weight of the equipment.
In order to avoid electromagnetic interference, a proper Mounting location must be selected to minimizeinterference from electromagnetic sources such as large electrical equipment.
Chassis output interface should install higher 1.2m than the ground.
Environmental
Humidity has an adverse effect on the reliability of the equipment. It is recommended to install theequipment in locations having stable temperature and unrestricted air-flow which should under thetemperature that of -40
oC ~+55
oC and relative humidity of maximal 95%.
The installation location for the product should be well ventilated. The equipment has been designed tooperate at the temperature range and humidity level as stated in the product specifications in thedatasheet.
Direct sun light exposure to the equipment should be avoided. Provide additional shelter if necessary.
PoweringThe power supply unit (PSU) provides power to all modules within the equipment. Depending on theproduct variant, it is recommended that the PSU operates on a dedicated circuit breaker or fused circuit.
Grounding Requirement
Verify that the equipment has been well grounded. This includes antennas and all cables connected to thesystem. Ensure lightning protection for the antennas is properly grounded.
Cable Routing
Depending on equipment configuration, a variety of types of cables are required. Where applicable,ensure cables are properly routed and secured so that they are not damaged.
Cable requirements are as follow:
Cable Connection Description
Coaxial Cable N to N Connect BS cable to DT port
Coaxial Cable N to N Connect serve antenna cable toMT port
Local Commissioning Cable RJ45 Connect with PC to realize localcommissioning
Table 3: Cable Connection
Manual Handling
During transportation and installation, take necessary handling precautions to avoid potential physical
injury to the installation personnel and the equipment.
8/11/2019 RX-1939_QI_1-0-0
15/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 15ENU Status : 1-0-0
3.3 INSTALLATION PROCEDURES
3.3.1 GOODS INWARDS INSPECTION
1. Verify the number of packages received against the packing list.
2. Check all packages for external damage; report any external damage to the shipping courier. If thereis damage, a shipping agent should be present before unpacking and inspecting the contentsbecause damage caused during transit is the responsibility of the agent.
3. Open and check each package against the packing list. If any items are missing, please contactComba.
4. Do not remove items from antistatic packing until ready for installation. If damage is discovered at thetime of installation, contact the shipping agent.
3.3.2 TOOLS
See Appendix A for a full list of the recommended tools required for installation and maintenance.
3.3.3 PREPARATION
Wall mounting with the masonry bolts supplied, which make use of the outer holes.
Pole Mounting with the clamp kit supplied, which make use of the inner holes.
200
85
402
Figure 4: Mounting Rack Overview
8/11/2019 RX-1939_QI_1-0-0
16/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 16ENU Status : 1-0-0
3.3.4 WALL MOUNTING
Drill holes on the wall by using the position of the four round holes on the Mounting rack as a guide.
Insert the masonry bolts M10x110 through the round holes and tighten them to take the weight of theentire enclosure.
Hook the enclosure up onto the mounting rack and align the hole positions to that of the mountingrack, then installed the hex bolt (M8 x 20) to complete the installation.
Spring Washer
Plain Washer
M10 Nut
M8x20 Hex Bolt
Masonry Bolt
Figure 5: Wall Mounting
8/11/2019 RX-1939_QI_1-0-0
17/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 17ENU Status : 1-0-0
3.3.5 POLE MOUNTING OF MOUNTING RACK
The equipment can be mounted on a pole of about 60~75mm in diameter.
Insert and tighten the two U bolts to secure the mounting rack onto the pole.
The remaining installation to secure the enclosure to the mounting rack is identical to wall mounting.
M8x20 Hex Bolt
Mounting
Rack
Pole
M10 Nut
Plain
Washer
Spring Washer
U Bolt
Side Bolt
Figure 6: Pole Mounting Overview
3.3.6 FAN INSTALLATION AND MAINTENANCE
The fan is installed pre-hand before delivery. Refer to the following procedure in case of maintenance.
Disconnect the fan from the connector, use T shaped pentagon key wrench to loosen the fourrecessed pentagon socket bolts and then take the old fan unit away.
See the following installation procedure to complete the fan installation.
8/11/2019 RX-1939_QI_1-0-0
18/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 18ENU Status : 1-0-0
M5 Hex Socket Bolt with plain
washer and spring washer
Fan
Figure 7: Fan Installation
3.3.7 DRIP-LOOP
Comba recommends that every horizontal cable entry to the equipment forms a 'U' before its entry to theequipment. Water on the cable will drip down at the bottom of the loop and will not accumulate at the
equipment connectors.
8/11/2019 RX-1939_QI_1-0-0
19/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 19ENU Status : 1-0-0
3.4 EQUIPMENT CONNECTORS
3.4.1 CONNECTORS
.
FAN
POWERLAN MODEM ANT EXT_ALM
DT MT
Figure 8: Bottom Panel Interface Diagram
The connection interfaces are shown below:
Connector Description
MT N-female connector, for external mobile antenna
DT N-female connector, for external donor antenna
Fan 12-pin CPC connector.
EXT_ALM 7-pin CPC connector for external alarm interface.
LAN RJ45 connector, connects with Ethernet cable.
POWER1 Power supply interface
MODEM ANT SMA connector, connects with external antenna.
Table 4:RX-1939 Connectors
1The voltage identification is a variant due to electricity system diversity of global regions. The power cable glandmight be identified for AC 220V, AC 110V, AC 220V/110V, DC -48V, or DC +24V respectively. Please refer tospecific product or contact local sales if any doubt.
8/11/2019 RX-1939_QI_1-0-0
20/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 20ENU Status : 1-0-0
3.4.2 GROUNDING CONNECTION
Ground Connection
To ensure safe operation of the product, a ground (earth) connection is required. For single phase AC
power source, the product must be grounded by connecting the earth wire of the power cord to theground terminal of the AC supply.
3.4.3 LI-ION BATTERY CONNECTION
Li-ion battery which located in the side panel of enclosure is provided with this system to ensure power is
supplied to the system integrated module and MCU and connect the connectors as illustrated below
after system commissioning to ensure the alarm message could be sent to OMC effectively in
case of mains power failure.
Caution: Be careful of the risk of explosion if battery is replaced by an incorrect type. Dispose of usedbatteries according to the instructions.
Figure 9: Li-ion Battery Connection
3.4.4 RF CONNECTION
Donor antenna connection:Connect the cable form donor antenna to DT port
Mobile antenna connection: Connect the cable form mobile antenna to MT port
3.4.5 EXTERNAL ALARM CONNECTION
The external alarm port is used to connect with other external equipment and alarm ports. Connection isnot must in case there is no external alarm port.
8/11/2019 RX-1939_QI_1-0-0
21/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 21ENU Status : 1-0-0
3.4.6 CONNECTION BETWEEN PC AND EQUIPMENT
The below shows the connection:
LAN Port
GSM
Network/PSTN
WirelessBuild-in
GSM
Modern
Realizeremote
monitor
LocalMonitoring
Wire/Wireless
Modem
Monitoring Center
RJ45 Ethernet cable
Figure10: The Connection between Equipment and PC
Note that when connect the RJ45 Ethernet cable with PC, the equipment should be power off and Li-ion
battery output connector is disconnected.
3.4.7 EXT ALARM CONNCETION
The EXT ALARM port is a 7-pin CPC connector. The following figure and table show the pin allocationand definition. Pin numbering are shown looking-into the connector on the enclosure.
21
6 7
3 54
Figure 1: Pins Allocation for EXT_ALM Port
Pin number 1 2 3 4 5 6 7
Alarmdefinition
EXT.Alarm 1
EXT.Alarm 2
EXT.Alarm 3
GNDEXT.
Alarm 4Reserved Reserved
Table 1: Pin Definition of EXT_ALM Port
End of Section
8/11/2019 RX-1939_QI_1-0-0
22/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 22ENU Status : 1-0-0
4 COMMISSIONING
4.1 PRE-COMMISSIONING TASKS
After equipment installation, perform the following steps before equipment powering and commissioning,check that the expected voltage, current, and power levels do not violate any ratings. Double check allconnections including ground before applying power. Do not manipulate circuits or make changes whenpower is applied:
Visually inspect the power connection within the equipment. Ensure that the power cable is correctlyand securely connected, including grounding wire, RF cable and optical cable.
Check grounding connection and verify that the ground resistance is less than 5. Connect the equipment to the PC installed with OMT software.
Check antenna system return loss which working frequency band return loss should less than -14dB(VSWR < 1.5)
The online commissioning can be commenced with following the commissioning steps.
4.2 MCU LED INDICATORS
Three diagnostic LEDs are located on integrated module; each indicates the status of a particularfunction:
LED_ALARM
LED_MODEM
LED_RUN
Figure 2: LEDs
Identifier Colour Indication
LED_RUN GreenOperation indicatorFlashes once every second to indicatenormal system operation.
LED_ALARM Red Alarm indicator. ON = alarm; OFF = no alarm
LED_MODEM RedModem status indicator. Flashes during initiating, and go offafter that. If the indicator is continuous on then the initiatingfails.
Table 2: LED Indicators
8/11/2019 RX-1939_QI_1-0-0
23/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 23ENU Status : 1-0-0
4.3 COMMISSIONING PROCEDURES
Perform the following procedures for system commissioning.
On line& InquiryStatus
ExternalAlarm
Yes
EnableExternalAlarmandConfigure
VoltageappliedtoEXTAlarm
SetChannelNO.
AdjustDownlinkATTandMeasure
DownlinkOutputPower
SignalInput
ExitfromOMT
RemoteConnectiontoOMC
Yes
Configure[EquipmentID]
Comm.Comfig
SelectMonitoringParameters
No
No
Test-Call
DoubleCheckNoInterferencetoBTSand
AntennaIsolationMeetsRequirements
8/11/2019 RX-1939_QI_1-0-0
24/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 24ENU Status : 1-0-0
Commissioning Tasks Observation
1. On-line and Inquiry status
Activate the OMT Main window. The system Initialization willcompleted in about 2 minutes.
Click Connectbutton to enquire the repeaters status. Proceed if
there is no alarm; else check the failure and attend to the alarm.2. Set Channel No. Keep RF switch ON and set the channel number of the repeaters
operating frequency.
3. Adjust Downlink OutputPower and align donorantenna
Observe DL input power from measured value. Align the direction ofdonor antenna until the DL input power reading is maximized.
Note: To ensure that the measured DL input power is accurate, oneshould set the DL ATT to 0 before performing the check.
4. Configure [Equipment ID] Go to [Properties Info] and set [Equipment ID].
5. Comm. Config Enable the power supply by selecting Onin [RF] -> [Switch]; go to
[Properties Info.] -> [Comm. Config.] and set OMC Phones No. , theservice No. of SMSC, Report Mode.
6. Select MonitoringParameters
Select the equipment controlled and monitored parameters. If the external devices are connected to the equipment for
management, please enable in the [External Alarm Info.] Interface.
7. Test coverage area fieldintensity and adjustservice antenna.
Use test-handset to verify field intensity within the coverage area. Ifneeded, realign the service antenna to achieve the desiredcoverage.
Note: If during operation, the equipment gain could not be set tomaximum or the output power is not high enough due to insufficientdonor and service antennas isolation, then the antennas positionshould be changed to increase isolation. If the output power is toohigh and ALC is activated, then adjust the DL ATT to achieveoptimal DL Gain.
8. Verify UL gain and ensuretest call produces goodvoice quality and there isno interfering BTS
Adjust UL gain and perform test calls. Typically, the UL gain is setaround 5dB less than DL gain. Perform test calls in the coveragearea while adjusting UL gain if required.
Note: If the repeater is near the BTS and the test call performanceis poor, this may be due to UL noise interference to the BTS. Userscan calculate and determine if the repeater UL noise will interferewith the BTS.
Verify again that there is no unacceptable interference to BTS.
Table 3: Commissioning
End of Section
8/11/2019 RX-1939_QI_1-0-0
25/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 25ENU Status : 1-0-0
5 OMT
The equipment can be monitored and controlled by OMT software running on a local PC with localcommissioning cable, remote connection to the equipment via wireless GSM / CDMA network.
OMT software running on a local PC with serial connection to the equipment. OMC (optional) software with remote connection to the equipment over wireless GSM / CDMA
network.
This chapter is to introduce how to apply local and remote connection to OMT for the first installation, forthe detailed OMT information, please refer to OMT user manual and other references.
Notice: The OMC software with remote connection to the equipment over wireless GSM / CDMA networkis optional for customers.
5.1 LOCAL AND REMOTE CONNECTIONS TO OMT
After installing OMT software on the PC, connection to the equipment can be done locally or remotely.
Double click the OMT explorer icon, the OMT Explorer main screen window will appear.
5.1.1 CONNECTION VIA ETHERNET (UDP)
In order to access to equipment via Ethernet (UDP), the PC must be set with proper IP address andsubnet mask in advance.
Figure 3: PC Protocol Setting
The default IP address of repeater is 195.60.16.254. To access the repeater for the first time, the PCmust be set with proper IP address: 195.60.16.X (X=1~253), subnet mask: 255.255.255.0.
After the PC protocol has been properly set, please connect the RJ45 cable to PC and equipment
Ethernet port.
Choose Connection via Ethernet (UDP) and click ONLINE.
8/11/2019 RX-1939_QI_1-0-0
26/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 26ENU Status : 1-0-0
After database configuration is done successfully, the following window will pop up and select [Connectionvia Ethernet (UDP)] for connection.
Figure 4: Connection Type
After clicking ONLINE, a window will pop up for user configuring IP Address and Port No.
Items Default Value
PC IP Address 195.60.16.X (X=1~253)
Device IP Site Port NO. 7025 (defaults)
PC Subnet Mask 255.255.255.0
Repeater IP Address 195.60.16.254
Table 4: IP Setting Quick Look-up Table
5.1.1 REMOTE CONNECTION TO OMT
If remote connection is needed, users can select [Remote connection via modem] in connection typewindow. Select desired serial port and click OKin [Serial Port Configuration] window to go to OMT mainwindow and start modem initialization. Click connectand the [Remote Connection] window will show up.
8/11/2019 RX-1939_QI_1-0-0
27/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 27ENU Status : 1-0-0
Figure 11: Remote Connection
Config: Enter the correct phone number (Users don't have to enter the password) and click connect, itwill be connected remotely.
Notice: Please enable the SIM card to support Circuit Switch Data.
5.2 OMT CONFIGURATION
After entering the OMT main screen, click the Connectbutton on the toolbar, to connect the equipmentto the OMT. Successful connection will be indicated by a message Online Okand equipmentparameters can be read and/or set.
Users can configure the parameters, and then offset the parameters according to desired coverage leveland interference to other BTS signals.
OMT parameters include: Common Information, RF Information, Alarm Information, and PropertiesInformation.
Figure 12: OMT Main Window
5.3 RF PARAMETER
It is recommended to configure the following RF parameters for the first installation.
8/11/2019 RX-1939_QI_1-0-0
28/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 28ENU Status : 1-0-0
5.3.1 SWITCH
Switch is to enable/disable power for internal modules. When user checks and sets non-RF parameters,such as checking physical antenna connection, switching off will disable equipment power temporarily toprotect PA in operation.
Figure 13: Switch
RF Switch: Turn off DL PA and UL PA.
Config:Select the required state in setting columns of RF information window for RF switch, then press [Enter] or[Config] button to finish the configuration operation.
5.3.2 CHANNEL NO.
Channel No. includes Low Edge Channel No. and High Edge Channel No. The value in [MaxValue]column is the upper limit of the range, while the value in [MinValue] column is the lower limit of the range.
Figure 14: Channel No.
Here takes the GSM channel NO. setting as an example. In case setting WCDMA, please follow the stepsbelow.
Config:Enter the required value in setting columns and click [Config] button to finish the configuration operation.There are two methods to insert the channel number: Insert the desired channel number (within the setting range) into the [Setting] column directly Right click the [Setting] column, the [Frequency Calculator] dialogue window seen as below will pop-
up, insert the desired channel number. Then the corresponding frequency will turn up automatically.This function makes it easier for user to configure.
Figure 15: Frequency Calculator
8/11/2019 RX-1939_QI_1-0-0
29/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 29ENU Status : 1-0-0
5.3.3 ATT
ATT adjustment includes UL/DL ATT adjustment. The purpose of adjusting the ATT is to adjust systemgain.
DL/UL ATT setting range: 0~30dB
Figure 16: ATT
Config:Select the required value in setting columns of RF information window for ATT, and press [Enter] or[Config] button to finish the configuration operation.
5.3.4 ALARM THRESHOLD
Alarm Threshold includes Power threshold, Temperature threshold and VSWR threshold.Users can set alarm threshold according to the specific situation. If the measured value is lower than thethreshold lower limit or more than the threshold upper limit, the appropriate alarm will be generated.
Figure 17: Alarm Threshold
Config:Enter the required value in setting columns of RF information window for Alarm threshold, and press[Enter] or [Config] button to finish the configuration operation.
5.3.5 ALARM INFORMATION
Alarm information operation is to select alarm parameters for monitoring. Alarm parameters includeMaster Alarm, Channel Alarm, External Alarm and Fan Alarm.
Click any tree node in [Alarm Info] group, [Alarm Parameter Information] window will appear in the rightside. The picture below shows the master alarm information.
8/11/2019 RX-1939_QI_1-0-0
30/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 30ENU Status : 1-0-0
Figure 18: Master Alarm
Figure 19: Channel Alarm
Figure 20: External Alarm
Figure 21: Fan Alarm
Config:Tick the check box of [Item select] and [Enable] of the desired parameters and click [config] button tofinish configuration operation.
Notice: [Enable] box is to enable the alarm monitoring for system. Only if users enable the alarm byticking the [Enable] box, the alarms can be monitored by the OMT/OMC.
On the MCU, if any alarm is generated and this alarm is also enabled in [Enable] box, LED H2 turns RED;while it is OFF when normal working. On the OMT/OMC window, [Alarm Status] indicator keeps GREEN ifno alarm and turns RED if an alarm is generated.
8/11/2019 RX-1939_QI_1-0-0
31/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 31ENU Status : 1-0-0
5.4 PROPERTIES INFO.
5.4.1 EQUIPMENT ID
Equipment ID is to be configured after local commission has been completed, which includes Site ID, and
Site Sub ID.
Figure 22: Equipment ID
See the table below for configuration details of each parameter.
Item Description
Site ID Site ID is the unique equipment identification. It is a hexadecimal string of eightcharacters in the range of [00000000~FFFFFFFF]. e.g. 00000000
Site Sub ID Site Sub ID is used for Master-Slave System. It is the unique identification ofeach Master/ Slave Unit and is a hexadecimal string of two characters in therange of [00~FF].For the system located with single equipment, the Site Sub ID should be FF.For Master-Slave system, the Site Sub ID for Master Unit is 00, and the Site SubID for each Slave Unit is represented in the range of [01~FE] in ascending order.
e.g. Master Site ID: 00, Slave Site ID: 01
5.4.2 COMM. CONFIG
If the equipment is to be monitored by OMC software over wireless GSM / CDMA network, users mustfinish the [Comm. Config.] in the next step.
The Comm. Config information requires to be manually entered by users after successful connection tothe equipment.
8/11/2019 RX-1939_QI_1-0-0
32/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 32ENU Status : 1-0-0
Figure 23: Com. Config.
See the table below for configuration details of each parameter.
Item Description
Checking Control Select Enableor Disablefrom the drop down menu as shown to enable or
disable the Phone Number Authentication feature. Refer to [Phone No.] indetails.
OMC Server IP Based on the current network conditions, users can enter the IP addressinformation of the equipment, which is connected to the OMT/OMC viaEthernet. This connection via Ethernet is not available at this stage.
Phone No. This is designed for authentication purpose when remote connection viamodem is required. It is the phone number to dial the equipment. Only thephone number pre-defined in this field, will it be allowed to dial theequipment. It is required to manually enter the phone number. Up to 5 phonenumbers are allowed. The use of phone number authentication can avoidunauthorized use of the OMT. In addition, it can prevent the equipmentreceiving piles of spam short messages, thus help the operator greatly
reduce the cost.
Report Config The Report No. is the SIM card number of the modem built into the OMCServer computer. The equipment will send alarm SMS to this number.If remote communication is needed via modem, users have to enable SMSmode and set the report phone No. by entering the SIM card number of theequipment built-in modem.
SMSC No. It specifies the SMS center. Users have to set the service No. of SMSC forthe first installation, so that the alarms can be sent to OMC.
End of Section
8/11/2019 RX-1939_QI_1-0-0
33/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 33ENU Status : 1-0-0
6 MAINTENANCE
The RX-1939 repeater is designed for trouble-free operation and generally does not need maintenance.Maintenance activities should only be carried out by trained personnel.
The equipment operation status can be observed remotely through OMC.
Periodic inspection of the repeater equipment(s) is recommended, the recommended tasks includes:
Inspect and record operation status and output power of the repeater from OMC or OMT. Verify the direction and position of antennas. Re-align if necessary. Make sure the cable gland and sealing on the RF cable connectors are not damaged. Verify lightning and grounding protection is in good condition.
End of Section
8/11/2019 RX-1939_QI_1-0-0
34/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 34ENU Status : 1-0-0
7 APPENDICES
7.1 APPENDIX A: TOOLS FOR INSTALLATION AND MAINTENANCE
The following are the recommended list of tools new installation and routine maintenance:
Slotted screwdriver
Philips screwdriver
Ring spanner (Assorted size: 12~20mm)
Electrically operated drill and masonry drill bits 10mm
Anti-static wrist strap
Allen key (M5.5)
Side cutter
Frequency counter (e.g. FLUKE PM6685R)
RF Power Meter (e.g. Bird 5000)
T-shaped Pentagon Key Wrench
8/11/2019 RX-1939_QI_1-0-0
35/36
USER MANUAL FOR RX-1939
RX-1939 QI Copyright - refer to title page Page 35ENU Status : 1-0-0
7.2 APPENDIX B: RMA (RETURN MATERIAL AUTHORIZATION) FORM
End of Section
End of Document
8/11/2019 RX-1939_QI_1-0-0
36/36
USER MANUAL for RD-XXXX