RX-1939_QI_1-0-0

Embed Size (px)

Citation preview

  • 8/11/2019 RX-1939_QI_1-0-0

    1/36

    RX-1939

    11990000MMHHZZDDUUAALLMMOODDEE

    WWIIRREELLEESSSS

    RREEPPEEAATTEERR

    USER MANUAL

    RX-1939 QI: 1-0-0

    Comba Telecom Ltd.

  • 8/11/2019 RX-1939_QI_1-0-0

    2/36

    USER MANUAL for RD-XXXX

    The information contained herein is the responsibility of and is approved by the

    follow ing, to whom all enquiries should be directed in the first instance:

    This is an unpublished work the copyright in which vests in Comba International

    ("Comba"). All r ights reserved.

    The information contained herein is confidential and the property of Comba and is

    supplied without liability for errors or omissions. No part may be reproduced,

    disclosed or used except as authorised by contract or other written permission.

    The copyright and the foregoing restriction on reproduction and use extend to allmedia in which the information may be embodied.

  • 8/11/2019 RX-1939_QI_1-0-0

    3/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 3ENU Status : 1-0-0

    0.1 CONTENTS

    Section Page

    0.2 CONTENTS ........................................................................................................................... 30.3 INDEX TO FIGURES AND TABLES ..................................................................................... 50.4 HISTORY ............................................................................................................................... 60.5 GLOSSARY OF TERMS ....................................................................................................... 70.6 SAFETY NOTICES AND ADMONISHMENTS ...................................................................... 8

    1 GENERAL INFORMATION ................................................................................................... 9

    2 EQUIPMENT DESCRIPTION .............................................................................................. 102.1 SYSTEM DIAGRAM ............................................................................................................ 102.2 EQUIPMENT LAYOUT ........................................................................................................ 112.3 EQUIPMENT CONSTITUTION ........................................................................................... 11

    2.4

    KIT OF PARTS .................................................................................................................... 12

    3 INSTALLATION ................................................................................................................... 133.1 WARNINGS AND ALERTS ................................................................................................. 133.2 SITE PLANNING CONSIDERATIONS ................................................................................ 143.3 INSTALLATION PROCEDURES ......................................................................................... 153.3.1 GOODS INWARDS INSPECTION ...................................................................................... 153.3.2 TOOLS ................................................................................................................................. 153.3.3 PREPARATION ................................................................................................................... 153.3.4 WALL MOUNTING .............................................................................................................. 163.3.5 POLE MOUNTING OF MOUNTING RACK ......................................................................... 173.3.6 FAN INSTALLATION AND MAINTENANCE ....................................................................... 173.3.7 DRIP-LOOP ......................................................................................................................... 18

    3.4

    EQUIPMENT CONNECTORS ............................................................................................. 19

    3.4.1 CONNECTORS ................................................................................................................... 193.4.2 GROUNDING CONNECTION ............................................................................................. 203.4.3 LI-ION BATTERY CONNECTION ....................................................................................... 203.4.4 RF CONNECTION ............................................................................................................... 203.4.5 EXTERNAL ALARM CONNECTION ................................................................................... 203.4.6 CONNECTION BETWEEN PC AND EQUIPMENT ............................................................ 213.4.7 EXT ALARM CONNCETION ............................................................................................... 21

    4 COMMISSIONING ............................................................................................................... 224.1 PRE-COMMISSIONING TASKS ......................................................................................... 224.2 MCU LED INDICATORS ..................................................................................................... 224.3 COMMISSIONING PROCEDURES .................................................................................... 23

    5 OMT ..................................................................................................................................... 255.1 LOCAL AND REMOTE CONNECTIONS TO OMT ............................................................. 255.1.1 LOCAL CONNECTION TO OMT......................................................................................... 255.1.2 REMOTE CONNECTION TO OMT ..................................................................................... 265.2 OMT CONFIGURATION ..................................................................................................... 275.3 RF PARAMETER ................................................................................................................. 275.3.1 SWITCH .............................................................................................................................. 285.3.2 CHANNEL NO. .................................................................................................................... 285.3.3 ATT ...................................................................................................................................... 295.3.4 ALARM THRESHOLD ......................................................................................................... 295.3.5 ALARM INFORMATION ...................................................................................................... 295.4 PROPERTIES INFO. ........................................................................................................... 31

    5.4.1

    EQUIPMENT ID ................................................................................................................... 31

    5.4.2 COMM. CONFIG ................................................................................................................. 31

  • 8/11/2019 RX-1939_QI_1-0-0

    4/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 4ENU Status : 1-0-0

    6 MAINTENANCE ................................................................................................................... 33

    7 APPENDICES ...................................................................................................................... 347.1 APPENDIX A: TOOLS FOR INSTALLATION AND MAINTENANCE .................................. 347.2 APPENDIX B: SERVICING POLICY AND RETURN OF EQUIPMENT .............................. 347.3 APPENDIX C: RMA (RETURN MATERIAL AUTHORIZATION) FORM ............................. 35

  • 8/11/2019 RX-1939_QI_1-0-0

    5/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 5ENU Status : 1-0-0

    0.2 INDEX TO FIGURES AND TABLES

    Figure 1: Views of RX-1939 Enclosure .........................................................................................................9Figure 2: RX-1939 System Diagram ...........................................................................................................10Figure 3: RX-1939 Internal Layout ..............................................................................................................11

    Figure 4: Mounting Rack Overview .............................................................................................................15Figure 5: Wall Mounting ..............................................................................................................................16

    Figure 6: Pole Mounting Overview ..............................................................................................................17Figure 7: Fan Installation .............................................................................................................................18Figure 8: Bottom Panel Interface Diagram ..................................................................................................19Figure 9: The Connection between Equipment and PC ..............................................................................21Figure 10: Connection Type ........................................................................................................................26Figure 11: Serial Port Configuration ............................................................................................................26Figure 12: Remote Connection ...................................................................................................................27Figure 13: OMT Main Window ....................................................................................................................27Figure 14: Switch .........................................................................................................................................28Figure 15: Channel No. ...............................................................................................................................28Figure 16: Frequency Calculator .................................................................................................................28

    Figure 17: ATT ............................................................................................................................................29Figure 18: Alarm Threshold .........................................................................................................................29

    Figure 19: Master Alarm ..............................................................................................................................30Figure 20: External Alarm............................................................................................................................30Figure 21: Fan Alarm...................................................................................................................................30Figure 22: Equipment ID .............................................................................................................................31Figure 23: Com. Config. ..............................................................................................................................32

    Table 1: Equipment Constitution .................................................................................................................11Table 2: Equipment KOP.............................................................................................................................12Table 3: Cable Connection ..........................................................................................................................14Table 4: RX-1939 Connectors .....................................................................................................................19

  • 8/11/2019 RX-1939_QI_1-0-0

    6/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 6ENU Status : 1-0-0

    0.3 HISTORY

    Change No. ENU Details Of Change

    1 1-0-0 RX-1939 user manual first created in Dec 2011 and referred to itsChinese manual RX-1939-1001YH.

  • 8/11/2019 RX-1939_QI_1-0-0

    7/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 7ENU Status : 1-0-0

    0.4 GLOSSARY OF TERMS

    ALC Automatic Level Control

    ATT Attenuation

    AFC Antenna Feedback Cancellation

    BTS Base Transceiver Station

    CSA Cross Sectional Area

    dB Decibel

    dBm Decibels relative to 1 milliwatt

    DL Downlink

    DPX Duplexer

    DT Donor Terminal

    E/O, O/E Electrical/Optical, Optical/Electrical

    FSK Frequency Shift Keying

    FOU Fiber Optical Unit

    GSM Global Standard for Mobile Communication

    Hz Hertz

    ID Identification

    LNA Low Noise Amplifier

    MCU Main Control Unit

    MHz Megahertz

    MT Mobile Terminal

    MTBF Mean Time Between Failures

    NF Noise FigureOMC Operation & Maintenance Center

    OMT Operation & Maintenance Terminal

    OP Optical Fiber

    PA Power Amplifier

    PLL Phase Locked Loop

    PSU Power Supply Unit

    RF Radio Frequency

    RFU Radio Frequency Unit

    RX Receive

    SMA Sub-Miniature A ConnectorSIU Slide-In-Unit

    TX Transmit

    UL Uplink

    VAC Volts Alternating Current

    VSWR Voltage Standing Wave Ratio

    WDM Wavelength Division Multiplexer

  • 8/11/2019 RX-1939_QI_1-0-0

    8/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 8ENU Status : 1-0-0

    0.5 SAFETY NOTICES AND ADMONISHMENTS

    This document contains safety notices in accordance with appropriate standards. In the interests ofconformity with the territory standards for the country concerned, the equivalent territorial admonishments

    are also shown.

    Any installation, adjustment, maintenance and repair of the equipment must only be carried out by trained,authorized personnel. At all times, personnel must comply with any safety notices and instructions.

    Specific hazards are indicated by symbol labels on or near the affected parts of the equipment. The labelsconform to international standards, are triangular in shape, and are coloured black on a yellowbackground. An informative text label may accompany the symbol label.

    Hazard labeling is supplemented by safety notices in the appropriate equipment manual. These noticescontain additional information on the nature of the hazard and may also specify precautions.

    Warning:

    These draw the attention of personnel to hazards that may cause death or injury to the operator or others.Examples of use are cases of high voltage, laser emission, toxic substances, point of high temperature,etc.

    Alert:These draw the attention of personnel to hazards that may cause damage to the equipment. An exampleof use is the case of static electricity hazard.

    Caution notices may also be used in the handbook to draw attention to matters that do not constitute arisk of causing damage to the equipment but where there is a possibility of seriously impairing itsperformance, e.g. by mishandling or gross maladjustment. Warnings and Cautions within the main text donot incorporate labels and may be in shortened form.

    CAUTION: danger of explosion if battery is incorrectly replaced. Replace only with the same or equivalenttype.

    End of Section

  • 8/11/2019 RX-1939_QI_1-0-0

    9/36

  • 8/11/2019 RX-1939_QI_1-0-0

    10/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 10ENU Status : 1-0-0

    2 EQUIPMENT DESCRIPTION

    2.1 SYSTEM DIAGRAM

    DLPA

    ULPA

    MODEM

    DT MT

    DT

    Duplexer

    Li-ion

    Battery

    PSUAC 100V 240V

    Digital

    RF

    Monitor

    ing

    Module

    MODEM

    ANT

    LNA

    LNA VSWR

    Power

    ConversionFan

    Duplex

    Coupling

    MT

    Duplexer

    Figure 2: RX-1939 System Diagram

    As shown in the above figure, the downlink BS signals go through DT port to the system and then todownlink by duplexer separation. The DL signals will go through DT duplexer then to digital RF monitoringmodule for digital filtering and self-oscillation elimination. Then the DL signals will be sent to downlink PAto amplify power and filter via duplexer. After amplification, the signals are transmitted at the MT port to

    the service antenna.

    On the UL, the signals transmitted by the mobile go through MT integration duplexer and digital RFmonitoring module then to uplink PA to power amplify and filter via duplexer, finally get back to BS bydonor antenna.

  • 8/11/2019 RX-1939_QI_1-0-0

    11/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 11ENU Status : 1-0-0

    2.2 EQUIPMENT LAYOUT

    The following figure shows RX-1939 internal layout.

    MT DuplexerDT Duplexer

    Door Open

    Switch

    DL PAUL PAPower Supply

    Convert Module

    Surge

    Arrestor

    Integrated Module

    PSU

    Figure 3: RX-1939 Internal Layout

    2.3 EQUIPMENT CONSTITUTION

    RX-1939 consists of the modules described as below:

    Identifier Functional Description

    Power Supply Unit (PSU)converts the input voltage into a stable DC toprovide power for the internal functional modulesand to charge the internal Li-ion battery.

    Surge Arrestoris assumed that the antenna system will haveample lightning protection.

    Integrated Module consists of digital processing unit, RF unit andmonitoring unit.

    DT Duplexer realizes UL/DL TX/RX isolation, build-in DL LNA isused to amplify the DL low noise signal.

    MT Duplexer realizes UL/DL TX/RX isolation, build-in UL LNA isused to amplify the UL low noise signal while DLVSWR detects DL output power and VSWR.

    Table 1: Equipment Constitution

  • 8/11/2019 RX-1939_QI_1-0-0

    12/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 12ENU Status : 1-0-0

    2.4 KIT OF PARTS

    For this system, the following are shipped:

    Product Identifier Description Quantity

    RX-1939 QI This equipment manual on CD-Rom 1

    CPC Connector X14J7P 1

    Ground Cable BVR10mm2, 2m 1

    Key N/A 2

    Ethernet Cable 2m 1

    Modem Antenna XD-WCDMA 1

    Masonry Bolt M10110 4

    U Bolt (with 2 nuts, flat washer,spring washer per bolt)

    M10x85x110 2

    Power Supply Cable n/a 1

    Allen Key 5.5mm 1T-shape Pentagon ScrewWrench

    5mm 1

    OMT V5.0 or above OMT software on CD-Rom 1

    Factory Test Report N/A 1

    Table 2: Equipment KOP

    End of Section

  • 8/11/2019 RX-1939_QI_1-0-0

    13/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 13ENU Status : 1-0-0

    3 INSTALLATION

    3.1 WARNINGS AND ALERTS

    Radio Frequency Energies

    There may be situations, particularly for workplace environments near high-powered RF sources, whererecommended limits for safe exposure of human beings to RF energy could be exceeded. In such cases,restrictive measures or actions may be necessary to ensure the safe use of RF energy.

    High Voltage

    The equipment has been designed and constructed to prevent, as far as reasonably, practicable danger.Any work activity on or near equipment involving installation, operation or maintenance must be, as far asreasonably, free from danger.

    Where there is a risk of damage to electrical systems involving adverse weather, extreme temperatures,wet, corrosive or dirty conditions, flammable or explosive atmospheres, the system must be suitablyinstalled to prevent danger.

    Protective Earthing

    Equipment provided for the purpose of protecting individuals from electrical risk must be suitable for thepurpose and properly maintained and used.

    Handling Precautions

    This covers a range of activities including lifting, lowering, pushing, pulling, carrying, moving, holding orrestraining an object, animal or person. It also covers activities that require the use of force or effort, suchas pulling a lever, or operating power tools.

    Electrostatic Discharge (ESD)

    Observe standard precautions for handling ESD-sensitive devices. Assume that all solid-state electronicdevices are ESD-sensitive. Ensure the use of a grounded wrist strap or equivalent while working withESD-sensitive devices. Transport, store, and handle ESD-sensitive devices in static-safe environments.

  • 8/11/2019 RX-1939_QI_1-0-0

    14/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 14ENU Status : 1-0-0

    3.2 SITE PLANNING CONSIDERATIONS

    Site Considerations

    The site considerations are listed below:

    The distance between the donor antenna and the BS should satisfy line of sight requirements formaximum coverage area. The received spots accept field intensity at least -70dBm.

    Make sure that TX and RX antennas isolation should more than the max gain that of -15dB.

    Supply power near by the BS and easily access to the grounding spot.

    Installation Location

    Mounting surface shall be capable of supporting the weight of the equipment.

    In order to avoid electromagnetic interference, a proper Mounting location must be selected to minimizeinterference from electromagnetic sources such as large electrical equipment.

    Chassis output interface should install higher 1.2m than the ground.

    Environmental

    Humidity has an adverse effect on the reliability of the equipment. It is recommended to install theequipment in locations having stable temperature and unrestricted air-flow which should under thetemperature that of -40

    oC ~+55

    oC and relative humidity of maximal 95%.

    The installation location for the product should be well ventilated. The equipment has been designed tooperate at the temperature range and humidity level as stated in the product specifications in thedatasheet.

    Direct sun light exposure to the equipment should be avoided. Provide additional shelter if necessary.

    PoweringThe power supply unit (PSU) provides power to all modules within the equipment. Depending on theproduct variant, it is recommended that the PSU operates on a dedicated circuit breaker or fused circuit.

    Grounding Requirement

    Verify that the equipment has been well grounded. This includes antennas and all cables connected to thesystem. Ensure lightning protection for the antennas is properly grounded.

    Cable Routing

    Depending on equipment configuration, a variety of types of cables are required. Where applicable,ensure cables are properly routed and secured so that they are not damaged.

    Cable requirements are as follow:

    Cable Connection Description

    Coaxial Cable N to N Connect BS cable to DT port

    Coaxial Cable N to N Connect serve antenna cable toMT port

    Local Commissioning Cable RJ45 Connect with PC to realize localcommissioning

    Table 3: Cable Connection

    Manual Handling

    During transportation and installation, take necessary handling precautions to avoid potential physical

    injury to the installation personnel and the equipment.

  • 8/11/2019 RX-1939_QI_1-0-0

    15/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 15ENU Status : 1-0-0

    3.3 INSTALLATION PROCEDURES

    3.3.1 GOODS INWARDS INSPECTION

    1. Verify the number of packages received against the packing list.

    2. Check all packages for external damage; report any external damage to the shipping courier. If thereis damage, a shipping agent should be present before unpacking and inspecting the contentsbecause damage caused during transit is the responsibility of the agent.

    3. Open and check each package against the packing list. If any items are missing, please contactComba.

    4. Do not remove items from antistatic packing until ready for installation. If damage is discovered at thetime of installation, contact the shipping agent.

    3.3.2 TOOLS

    See Appendix A for a full list of the recommended tools required for installation and maintenance.

    3.3.3 PREPARATION

    Wall mounting with the masonry bolts supplied, which make use of the outer holes.

    Pole Mounting with the clamp kit supplied, which make use of the inner holes.

    200

    85

    402

    Figure 4: Mounting Rack Overview

  • 8/11/2019 RX-1939_QI_1-0-0

    16/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 16ENU Status : 1-0-0

    3.3.4 WALL MOUNTING

    Drill holes on the wall by using the position of the four round holes on the Mounting rack as a guide.

    Insert the masonry bolts M10x110 through the round holes and tighten them to take the weight of theentire enclosure.

    Hook the enclosure up onto the mounting rack and align the hole positions to that of the mountingrack, then installed the hex bolt (M8 x 20) to complete the installation.

    Spring Washer

    Plain Washer

    M10 Nut

    M8x20 Hex Bolt

    Masonry Bolt

    Figure 5: Wall Mounting

  • 8/11/2019 RX-1939_QI_1-0-0

    17/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 17ENU Status : 1-0-0

    3.3.5 POLE MOUNTING OF MOUNTING RACK

    The equipment can be mounted on a pole of about 60~75mm in diameter.

    Insert and tighten the two U bolts to secure the mounting rack onto the pole.

    The remaining installation to secure the enclosure to the mounting rack is identical to wall mounting.

    M8x20 Hex Bolt

    Mounting

    Rack

    Pole

    M10 Nut

    Plain

    Washer

    Spring Washer

    U Bolt

    Side Bolt

    Figure 6: Pole Mounting Overview

    3.3.6 FAN INSTALLATION AND MAINTENANCE

    The fan is installed pre-hand before delivery. Refer to the following procedure in case of maintenance.

    Disconnect the fan from the connector, use T shaped pentagon key wrench to loosen the fourrecessed pentagon socket bolts and then take the old fan unit away.

    See the following installation procedure to complete the fan installation.

  • 8/11/2019 RX-1939_QI_1-0-0

    18/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 18ENU Status : 1-0-0

    M5 Hex Socket Bolt with plain

    washer and spring washer

    Fan

    Figure 7: Fan Installation

    3.3.7 DRIP-LOOP

    Comba recommends that every horizontal cable entry to the equipment forms a 'U' before its entry to theequipment. Water on the cable will drip down at the bottom of the loop and will not accumulate at the

    equipment connectors.

  • 8/11/2019 RX-1939_QI_1-0-0

    19/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 19ENU Status : 1-0-0

    3.4 EQUIPMENT CONNECTORS

    3.4.1 CONNECTORS

    .

    FAN

    POWERLAN MODEM ANT EXT_ALM

    DT MT

    Figure 8: Bottom Panel Interface Diagram

    The connection interfaces are shown below:

    Connector Description

    MT N-female connector, for external mobile antenna

    DT N-female connector, for external donor antenna

    Fan 12-pin CPC connector.

    EXT_ALM 7-pin CPC connector for external alarm interface.

    LAN RJ45 connector, connects with Ethernet cable.

    POWER1 Power supply interface

    MODEM ANT SMA connector, connects with external antenna.

    Table 4:RX-1939 Connectors

    1The voltage identification is a variant due to electricity system diversity of global regions. The power cable glandmight be identified for AC 220V, AC 110V, AC 220V/110V, DC -48V, or DC +24V respectively. Please refer tospecific product or contact local sales if any doubt.

  • 8/11/2019 RX-1939_QI_1-0-0

    20/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 20ENU Status : 1-0-0

    3.4.2 GROUNDING CONNECTION

    Ground Connection

    To ensure safe operation of the product, a ground (earth) connection is required. For single phase AC

    power source, the product must be grounded by connecting the earth wire of the power cord to theground terminal of the AC supply.

    3.4.3 LI-ION BATTERY CONNECTION

    Li-ion battery which located in the side panel of enclosure is provided with this system to ensure power is

    supplied to the system integrated module and MCU and connect the connectors as illustrated below

    after system commissioning to ensure the alarm message could be sent to OMC effectively in

    case of mains power failure.

    Caution: Be careful of the risk of explosion if battery is replaced by an incorrect type. Dispose of usedbatteries according to the instructions.

    Figure 9: Li-ion Battery Connection

    3.4.4 RF CONNECTION

    Donor antenna connection:Connect the cable form donor antenna to DT port

    Mobile antenna connection: Connect the cable form mobile antenna to MT port

    3.4.5 EXTERNAL ALARM CONNECTION

    The external alarm port is used to connect with other external equipment and alarm ports. Connection isnot must in case there is no external alarm port.

  • 8/11/2019 RX-1939_QI_1-0-0

    21/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 21ENU Status : 1-0-0

    3.4.6 CONNECTION BETWEEN PC AND EQUIPMENT

    The below shows the connection:

    LAN Port

    GSM

    Network/PSTN

    WirelessBuild-in

    GSM

    Modern

    Realizeremote

    monitor

    LocalMonitoring

    Wire/Wireless

    Modem

    Monitoring Center

    RJ45 Ethernet cable

    Figure10: The Connection between Equipment and PC

    Note that when connect the RJ45 Ethernet cable with PC, the equipment should be power off and Li-ion

    battery output connector is disconnected.

    3.4.7 EXT ALARM CONNCETION

    The EXT ALARM port is a 7-pin CPC connector. The following figure and table show the pin allocationand definition. Pin numbering are shown looking-into the connector on the enclosure.

    21

    6 7

    3 54

    Figure 1: Pins Allocation for EXT_ALM Port

    Pin number 1 2 3 4 5 6 7

    Alarmdefinition

    EXT.Alarm 1

    EXT.Alarm 2

    EXT.Alarm 3

    GNDEXT.

    Alarm 4Reserved Reserved

    Table 1: Pin Definition of EXT_ALM Port

    End of Section

  • 8/11/2019 RX-1939_QI_1-0-0

    22/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 22ENU Status : 1-0-0

    4 COMMISSIONING

    4.1 PRE-COMMISSIONING TASKS

    After equipment installation, perform the following steps before equipment powering and commissioning,check that the expected voltage, current, and power levels do not violate any ratings. Double check allconnections including ground before applying power. Do not manipulate circuits or make changes whenpower is applied:

    Visually inspect the power connection within the equipment. Ensure that the power cable is correctlyand securely connected, including grounding wire, RF cable and optical cable.

    Check grounding connection and verify that the ground resistance is less than 5. Connect the equipment to the PC installed with OMT software.

    Check antenna system return loss which working frequency band return loss should less than -14dB(VSWR < 1.5)

    The online commissioning can be commenced with following the commissioning steps.

    4.2 MCU LED INDICATORS

    Three diagnostic LEDs are located on integrated module; each indicates the status of a particularfunction:

    LED_ALARM

    LED_MODEM

    LED_RUN

    Figure 2: LEDs

    Identifier Colour Indication

    LED_RUN GreenOperation indicatorFlashes once every second to indicatenormal system operation.

    LED_ALARM Red Alarm indicator. ON = alarm; OFF = no alarm

    LED_MODEM RedModem status indicator. Flashes during initiating, and go offafter that. If the indicator is continuous on then the initiatingfails.

    Table 2: LED Indicators

  • 8/11/2019 RX-1939_QI_1-0-0

    23/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 23ENU Status : 1-0-0

    4.3 COMMISSIONING PROCEDURES

    Perform the following procedures for system commissioning.

    On line& InquiryStatus

    ExternalAlarm

    Yes

    EnableExternalAlarmandConfigure

    VoltageappliedtoEXTAlarm

    SetChannelNO.

    AdjustDownlinkATTandMeasure

    DownlinkOutputPower

    SignalInput

    ExitfromOMT

    RemoteConnectiontoOMC

    Yes

    Configure[EquipmentID]

    Comm.Comfig

    SelectMonitoringParameters

    No

    No

    Test-Call

    DoubleCheckNoInterferencetoBTSand

    AntennaIsolationMeetsRequirements

  • 8/11/2019 RX-1939_QI_1-0-0

    24/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 24ENU Status : 1-0-0

    Commissioning Tasks Observation

    1. On-line and Inquiry status

    Activate the OMT Main window. The system Initialization willcompleted in about 2 minutes.

    Click Connectbutton to enquire the repeaters status. Proceed if

    there is no alarm; else check the failure and attend to the alarm.2. Set Channel No. Keep RF switch ON and set the channel number of the repeaters

    operating frequency.

    3. Adjust Downlink OutputPower and align donorantenna

    Observe DL input power from measured value. Align the direction ofdonor antenna until the DL input power reading is maximized.

    Note: To ensure that the measured DL input power is accurate, oneshould set the DL ATT to 0 before performing the check.

    4. Configure [Equipment ID] Go to [Properties Info] and set [Equipment ID].

    5. Comm. Config Enable the power supply by selecting Onin [RF] -> [Switch]; go to

    [Properties Info.] -> [Comm. Config.] and set OMC Phones No. , theservice No. of SMSC, Report Mode.

    6. Select MonitoringParameters

    Select the equipment controlled and monitored parameters. If the external devices are connected to the equipment for

    management, please enable in the [External Alarm Info.] Interface.

    7. Test coverage area fieldintensity and adjustservice antenna.

    Use test-handset to verify field intensity within the coverage area. Ifneeded, realign the service antenna to achieve the desiredcoverage.

    Note: If during operation, the equipment gain could not be set tomaximum or the output power is not high enough due to insufficientdonor and service antennas isolation, then the antennas positionshould be changed to increase isolation. If the output power is toohigh and ALC is activated, then adjust the DL ATT to achieveoptimal DL Gain.

    8. Verify UL gain and ensuretest call produces goodvoice quality and there isno interfering BTS

    Adjust UL gain and perform test calls. Typically, the UL gain is setaround 5dB less than DL gain. Perform test calls in the coveragearea while adjusting UL gain if required.

    Note: If the repeater is near the BTS and the test call performanceis poor, this may be due to UL noise interference to the BTS. Userscan calculate and determine if the repeater UL noise will interferewith the BTS.

    Verify again that there is no unacceptable interference to BTS.

    Table 3: Commissioning

    End of Section

  • 8/11/2019 RX-1939_QI_1-0-0

    25/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 25ENU Status : 1-0-0

    5 OMT

    The equipment can be monitored and controlled by OMT software running on a local PC with localcommissioning cable, remote connection to the equipment via wireless GSM / CDMA network.

    OMT software running on a local PC with serial connection to the equipment. OMC (optional) software with remote connection to the equipment over wireless GSM / CDMA

    network.

    This chapter is to introduce how to apply local and remote connection to OMT for the first installation, forthe detailed OMT information, please refer to OMT user manual and other references.

    Notice: The OMC software with remote connection to the equipment over wireless GSM / CDMA networkis optional for customers.

    5.1 LOCAL AND REMOTE CONNECTIONS TO OMT

    After installing OMT software on the PC, connection to the equipment can be done locally or remotely.

    Double click the OMT explorer icon, the OMT Explorer main screen window will appear.

    5.1.1 CONNECTION VIA ETHERNET (UDP)

    In order to access to equipment via Ethernet (UDP), the PC must be set with proper IP address andsubnet mask in advance.

    Figure 3: PC Protocol Setting

    The default IP address of repeater is 195.60.16.254. To access the repeater for the first time, the PCmust be set with proper IP address: 195.60.16.X (X=1~253), subnet mask: 255.255.255.0.

    After the PC protocol has been properly set, please connect the RJ45 cable to PC and equipment

    Ethernet port.

    Choose Connection via Ethernet (UDP) and click ONLINE.

  • 8/11/2019 RX-1939_QI_1-0-0

    26/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 26ENU Status : 1-0-0

    After database configuration is done successfully, the following window will pop up and select [Connectionvia Ethernet (UDP)] for connection.

    Figure 4: Connection Type

    After clicking ONLINE, a window will pop up for user configuring IP Address and Port No.

    Items Default Value

    PC IP Address 195.60.16.X (X=1~253)

    Device IP Site Port NO. 7025 (defaults)

    PC Subnet Mask 255.255.255.0

    Repeater IP Address 195.60.16.254

    Table 4: IP Setting Quick Look-up Table

    5.1.1 REMOTE CONNECTION TO OMT

    If remote connection is needed, users can select [Remote connection via modem] in connection typewindow. Select desired serial port and click OKin [Serial Port Configuration] window to go to OMT mainwindow and start modem initialization. Click connectand the [Remote Connection] window will show up.

  • 8/11/2019 RX-1939_QI_1-0-0

    27/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 27ENU Status : 1-0-0

    Figure 11: Remote Connection

    Config: Enter the correct phone number (Users don't have to enter the password) and click connect, itwill be connected remotely.

    Notice: Please enable the SIM card to support Circuit Switch Data.

    5.2 OMT CONFIGURATION

    After entering the OMT main screen, click the Connectbutton on the toolbar, to connect the equipmentto the OMT. Successful connection will be indicated by a message Online Okand equipmentparameters can be read and/or set.

    Users can configure the parameters, and then offset the parameters according to desired coverage leveland interference to other BTS signals.

    OMT parameters include: Common Information, RF Information, Alarm Information, and PropertiesInformation.

    Figure 12: OMT Main Window

    5.3 RF PARAMETER

    It is recommended to configure the following RF parameters for the first installation.

  • 8/11/2019 RX-1939_QI_1-0-0

    28/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 28ENU Status : 1-0-0

    5.3.1 SWITCH

    Switch is to enable/disable power for internal modules. When user checks and sets non-RF parameters,such as checking physical antenna connection, switching off will disable equipment power temporarily toprotect PA in operation.

    Figure 13: Switch

    RF Switch: Turn off DL PA and UL PA.

    Config:Select the required state in setting columns of RF information window for RF switch, then press [Enter] or[Config] button to finish the configuration operation.

    5.3.2 CHANNEL NO.

    Channel No. includes Low Edge Channel No. and High Edge Channel No. The value in [MaxValue]column is the upper limit of the range, while the value in [MinValue] column is the lower limit of the range.

    Figure 14: Channel No.

    Here takes the GSM channel NO. setting as an example. In case setting WCDMA, please follow the stepsbelow.

    Config:Enter the required value in setting columns and click [Config] button to finish the configuration operation.There are two methods to insert the channel number: Insert the desired channel number (within the setting range) into the [Setting] column directly Right click the [Setting] column, the [Frequency Calculator] dialogue window seen as below will pop-

    up, insert the desired channel number. Then the corresponding frequency will turn up automatically.This function makes it easier for user to configure.

    Figure 15: Frequency Calculator

  • 8/11/2019 RX-1939_QI_1-0-0

    29/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 29ENU Status : 1-0-0

    5.3.3 ATT

    ATT adjustment includes UL/DL ATT adjustment. The purpose of adjusting the ATT is to adjust systemgain.

    DL/UL ATT setting range: 0~30dB

    Figure 16: ATT

    Config:Select the required value in setting columns of RF information window for ATT, and press [Enter] or[Config] button to finish the configuration operation.

    5.3.4 ALARM THRESHOLD

    Alarm Threshold includes Power threshold, Temperature threshold and VSWR threshold.Users can set alarm threshold according to the specific situation. If the measured value is lower than thethreshold lower limit or more than the threshold upper limit, the appropriate alarm will be generated.

    Figure 17: Alarm Threshold

    Config:Enter the required value in setting columns of RF information window for Alarm threshold, and press[Enter] or [Config] button to finish the configuration operation.

    5.3.5 ALARM INFORMATION

    Alarm information operation is to select alarm parameters for monitoring. Alarm parameters includeMaster Alarm, Channel Alarm, External Alarm and Fan Alarm.

    Click any tree node in [Alarm Info] group, [Alarm Parameter Information] window will appear in the rightside. The picture below shows the master alarm information.

  • 8/11/2019 RX-1939_QI_1-0-0

    30/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 30ENU Status : 1-0-0

    Figure 18: Master Alarm

    Figure 19: Channel Alarm

    Figure 20: External Alarm

    Figure 21: Fan Alarm

    Config:Tick the check box of [Item select] and [Enable] of the desired parameters and click [config] button tofinish configuration operation.

    Notice: [Enable] box is to enable the alarm monitoring for system. Only if users enable the alarm byticking the [Enable] box, the alarms can be monitored by the OMT/OMC.

    On the MCU, if any alarm is generated and this alarm is also enabled in [Enable] box, LED H2 turns RED;while it is OFF when normal working. On the OMT/OMC window, [Alarm Status] indicator keeps GREEN ifno alarm and turns RED if an alarm is generated.

  • 8/11/2019 RX-1939_QI_1-0-0

    31/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 31ENU Status : 1-0-0

    5.4 PROPERTIES INFO.

    5.4.1 EQUIPMENT ID

    Equipment ID is to be configured after local commission has been completed, which includes Site ID, and

    Site Sub ID.

    Figure 22: Equipment ID

    See the table below for configuration details of each parameter.

    Item Description

    Site ID Site ID is the unique equipment identification. It is a hexadecimal string of eightcharacters in the range of [00000000~FFFFFFFF]. e.g. 00000000

    Site Sub ID Site Sub ID is used for Master-Slave System. It is the unique identification ofeach Master/ Slave Unit and is a hexadecimal string of two characters in therange of [00~FF].For the system located with single equipment, the Site Sub ID should be FF.For Master-Slave system, the Site Sub ID for Master Unit is 00, and the Site SubID for each Slave Unit is represented in the range of [01~FE] in ascending order.

    e.g. Master Site ID: 00, Slave Site ID: 01

    5.4.2 COMM. CONFIG

    If the equipment is to be monitored by OMC software over wireless GSM / CDMA network, users mustfinish the [Comm. Config.] in the next step.

    The Comm. Config information requires to be manually entered by users after successful connection tothe equipment.

  • 8/11/2019 RX-1939_QI_1-0-0

    32/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 32ENU Status : 1-0-0

    Figure 23: Com. Config.

    See the table below for configuration details of each parameter.

    Item Description

    Checking Control Select Enableor Disablefrom the drop down menu as shown to enable or

    disable the Phone Number Authentication feature. Refer to [Phone No.] indetails.

    OMC Server IP Based on the current network conditions, users can enter the IP addressinformation of the equipment, which is connected to the OMT/OMC viaEthernet. This connection via Ethernet is not available at this stage.

    Phone No. This is designed for authentication purpose when remote connection viamodem is required. It is the phone number to dial the equipment. Only thephone number pre-defined in this field, will it be allowed to dial theequipment. It is required to manually enter the phone number. Up to 5 phonenumbers are allowed. The use of phone number authentication can avoidunauthorized use of the OMT. In addition, it can prevent the equipmentreceiving piles of spam short messages, thus help the operator greatly

    reduce the cost.

    Report Config The Report No. is the SIM card number of the modem built into the OMCServer computer. The equipment will send alarm SMS to this number.If remote communication is needed via modem, users have to enable SMSmode and set the report phone No. by entering the SIM card number of theequipment built-in modem.

    SMSC No. It specifies the SMS center. Users have to set the service No. of SMSC forthe first installation, so that the alarms can be sent to OMC.

    End of Section

  • 8/11/2019 RX-1939_QI_1-0-0

    33/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 33ENU Status : 1-0-0

    6 MAINTENANCE

    The RX-1939 repeater is designed for trouble-free operation and generally does not need maintenance.Maintenance activities should only be carried out by trained personnel.

    The equipment operation status can be observed remotely through OMC.

    Periodic inspection of the repeater equipment(s) is recommended, the recommended tasks includes:

    Inspect and record operation status and output power of the repeater from OMC or OMT. Verify the direction and position of antennas. Re-align if necessary. Make sure the cable gland and sealing on the RF cable connectors are not damaged. Verify lightning and grounding protection is in good condition.

    End of Section

  • 8/11/2019 RX-1939_QI_1-0-0

    34/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 34ENU Status : 1-0-0

    7 APPENDICES

    7.1 APPENDIX A: TOOLS FOR INSTALLATION AND MAINTENANCE

    The following are the recommended list of tools new installation and routine maintenance:

    Slotted screwdriver

    Philips screwdriver

    Ring spanner (Assorted size: 12~20mm)

    Electrically operated drill and masonry drill bits 10mm

    Anti-static wrist strap

    Allen key (M5.5)

    Side cutter

    Frequency counter (e.g. FLUKE PM6685R)

    RF Power Meter (e.g. Bird 5000)

    T-shaped Pentagon Key Wrench

  • 8/11/2019 RX-1939_QI_1-0-0

    35/36

    USER MANUAL FOR RX-1939

    RX-1939 QI Copyright - refer to title page Page 35ENU Status : 1-0-0

    7.2 APPENDIX B: RMA (RETURN MATERIAL AUTHORIZATION) FORM

    End of Section

    End of Document

  • 8/11/2019 RX-1939_QI_1-0-0

    36/36

    USER MANUAL for RD-XXXX