If you can't read please download the document
Upload
hubert-dickerson
View
344
Download
11
Embed Size (px)
DESCRIPTION
Part A : “SUBSTATION LAYOUT” Single line diagram CONTENTS Part A : “SUBSTATION LAYOUT” Single line diagram Substation Switchyard Accessories Lightning Arrestor CVT Earthing switch Wave trap Isolator Current transformer Circuit Breaker Power Transformer Reactors and capacitors Other Switchyard Equipments
Citation preview
SUBSTATION LAYOUT AND ACCESSORIES
& BUSBAR ARRANGEMENT Part A : SUBSTATION LAYOUT Single line
diagram
CONTENTS Part A : SUBSTATION LAYOUT Single line diagram Substation
Switchyard Accessories Lightning Arrestor CVT Earthing switch Wave
trap Isolator Current transformer Circuit Breaker Power Transformer
Reactors and capacitors Other Switchyard Equipments PART B: BUSBAR
ARRANGEMENT
PLCC SCADA PART B: BUSBAR ARRANGEMENT Single bus system Single bus
system with bus sectionalizer Double bus system Double breaker bus
system One and a half breaker bus system Main and transfer bus
system Double bus system with bypass isolator Ring main bus system
PART- A SWITCHYARD LAYOUTING CLASSIFICATION OF SUBSTATIONS
Based on working Generating substation (step up s/s) Grid
substation Switching substation Secondary substation a) sub
transmission voltage b) primary distribution c) distribution
substation Based on structure Outdoor conventional air insulated
substation (AIS) Indoor substation Compressed air insulated G I S
SINGLE LINE DIAGRAM LIGHTNING ARRESTOR Alightning arresteris a
device used on electricalpower systemsto protect theinsulationon
the system from the damaging effect oflightning. Metal oxide
varistors (MOVs) have been used for power system protection since
the mid 1970s. The typical lightning arrester also known assurge
arrester has a high voltage terminal and a ground terminal. Current
from the surge is diverted around the protected insulation in most
cases to earth. PICTURES OFSURGE DIVERTER (LIGHTNING ARRESTOR) CVT
Capacitor Voltage Transformer(CVT), CapacitanceCoupled Voltage
Transformer(CCVT) To step downextra high voltage signals and
provide alow voltage . For measurement or to operate aprotective
relay. EARTHING SWITCH Earth Switch is used to discharge the
voltageon the circuit to the earth for safety. Earth switch is
mounted on the frame of the isolators. It is located for each
incomer transmission line and each side of the busbar section.
Connected in series with the power (transmission) line.
LINE TRAP (WAVE TRAP) Connected in series with the power
(transmission) line. It blocks the high frequency carrier waves
(24KHz to 500KHz) and letpower waves (50 Hz - 60 Hz) to pass
through. It is basically an inductor of rating in Milli henry
(approx 1 milli Henry for 220 KV 1250 Amp.). It has three main
components:- 1. Main coil. 2. Tuning Device. 3.Lightning Arrestor.
ISOLATOR Disconnector orIsolator switchis used to make sure that an
electrical circuit can be completely de-energised for service or
maintenance. Isolator is anoff-loaddevice. Types of Isolators are
1. Central rotating, horizontal swing 2. Centre-Break 3. Vertical
swing 4. Pantograph type CURRENT TRANSFORMER Current transformers
are used for Stepping down current for measurement, protection and
control. Current transformers are of two types 1. Protective CT 2.
Measuring CT CIRCUITBREAKERS ACircuit breakeris an automatically
operatedelectrical switchdesigned to protectanelectrical
circuitfrom damage caused byoverloadorshort circuit. Its basic
function is to detect a fault condition and, by interrupting
continuity, to immediately discontinueelectrical flow. All circuit
breakers have common features in their operation, although details
vary substantially depending on the voltage class, current rating
and type of the circuit breaker. Once a fault is detected, contacts
within the circuit breaker must open to interrupt the circuit.
Small circuit breakers may be manually operated; larger units
havesolenoids to trip the mechanism, and electric motors to restore
energy to the springs. Different techniques are used to extinguish
the arc
: Lengthening / deflection of the arc : Intensive cooling (in jet
chambers) : Division into partial arcs : Zero point quenching :
Connectingcapacitorsin parallel with contacts in DC circuits
High-voltage breakers are broadly classified by the medium used to
extinguish the arc Bulk oil Minimum oil Air blast Vacuum SF6 BUSBAR
Busbars receive power from incoming circuits and deliver power to
outgoing circuits. POWER TRANSFORMERS Power Transformers are used
to step up or step down a.c. voltages and to transfer electrical
power from one voltage level to another. SHUNT REACTORS Shunt
Reactors are used for long EHV transmission lines to control
voltage during low load period. Shunt reactors is also used to
compensate shunt capacitance of transmission line during low load
periods. Usually Shunt reactors are unswitched. SEREIS REACTORS
Series reactors are used to limit short circuit current and to
limit current surges associated with fluctuating loads. Series
reactors are located at the strategic locations such that the fault
levels are reduced. SHUNT CAPACITORS Shunt capacitors are used for
compensating reactive power of LPF. They are used for improving the
power factor. It is also used for voltage control during heavy
lagging power factor loads. Theyare located at the receiving
stations and distribution substations. They are switched on during
heavy loads and switched off during low loads. SERIES CAPACITOR
Series Capacitors are used for some long EHV a.c. lines to improve
power transferability. They located at the sending end / receiving
end of the lines. Theyare provided with by pass circuit breaker and
protective spark gaps. NEUTRAL GROUNDING EQUIPMENT
Neutral Grounding Equipment are Resistors and reactors. They are
used to limit the short circuit current during ground fault. They
are connected between neutral point and ground. OTHER SWITCHYARD
EQUIPMENTS
. MARSHALLING KIOSKS . STATION EARTHING SYSTEM . POWER CABLES .
CONTROL CABLES . INSULATORS . METERING, RELAY AND CONTROL PANEL .
SUPPLY SYSTEM POWER LINE CARRIER COMMUNICATION
PLCC is mainly used for telecommunication, tele-protection and
tele-monitoring between electrical substations through power lines
at high voltages, such as 110 kv, 220 kv, 400 kv. The voice signal
is converted/compressed into the 300 Hz to 4000 Hz range. It is
known as: Power line Digital Subscriber Line (PDSL) mains
communication power line telecom (PLT) power line networking (PLN)
Broadband over Power Lines (BPL) WHAT IS SCADA ? SCADA stands for
Supervisory Control And Data Acquisition. It is not a full control
system, but rather focuses on the supervisory level. It is a purely
software package that is positioned on top of hardware to which it
is interfaced. ( via Programmable Logic Controllers(PLCs)) . The
SCADA systems are arranged to perform the following tasks.
Data Collection (Data Acquisition) Data transmission (telemetry)
Scanning, Indication, Monitoring, Logging. Control and indication.
Ensure sequential events. Data presentation, display, reporting
Execution of operating, commands: on/off,raise/lower. Network
supervision, alarms and report any uncommon change of state. PART B
BUS BAR ARRANGEMENT CONDUCTOR USED FOR BUSES
All Aluminum conductor (AAC) All Aluminum alloy conductor (AAAC)
Aluminum conductor with aluminum alloy reinforced (ACAR) Aluminum
conductor with steel reinforced (ACSR) SINGLE BUS SYATEM
Advantages: 1.Simple in Design 2.Less Expenditure
Disadvantages: 1.In case of bus fault or bus bar isolator fault or
maintenance total Substation is out of service. 2.In case of
maintenance of transformer circuit breaker the associated
transformer has also to be shut-down. Similarly for Line also.
SINGLE BUS WITH BUS SECTIONALISER
Advantages: 1. One complete section can be taken out for
Maintenance without disturbing the continuity of other section. 2.
If a fault occurs on one section of the Bus, that faulty section
alone will be isolated. Disadvantages: It will be a little more
costly with the addition of one isolator and some cases with
Circuit breaker, C.Ts and C&R panel. DOUBLE BUS SYSTEM
Advantages:
: Double Bus Bar Arrangement increases the flexibility of system.
Disadvantages: :The arrangement does not permit breaker maintenance
with out interruption. DOUBLE BREAKER BUS SYSTEM
Advantages: There is no need of bus coupler as because the
operation is done by breakers instead of isolator Disadvantages:
Most expensive as it involves additional breaker, CTIsolators etc
for each circuit. ONE AND A HALF BREAKER BUS SYSTEM
Advantages: During any fault on any one of the buses, that faulty
bus will be cleared instantly without interrupting any feeders in
the system since all feeders will continue to feed from other
healthy bus. Disadvantages: This scheme is much expensive due to
investment for third breaker. MAIN AND TRANSFER BUS SYSTEM
Switching operation: 1.First close the isolators at both side of
the bus coupler breaker. 2. Then close the bypass isolator of the
feeder which is to be transferred to transfer bus. 3. Now energized
the transfer bus by closing the bus coupler circuit breaker from
remote. 4.After bus coupler breaker is closed, now the power from
main bus flows to the feeder line through its main breaker as well
as bus coupler breaker viatransfer bus. 5. Now if main breaker of
the feeder is switched off, total power flow will instantaneously
shift to the bus coupler breaker and hence this breaker will serve
the purpose of protection for the feeder. 6. At last the operating
personnel open the isolators at both sides of the main circuit
breaker to make it isolated from rest of the live system. DOUBLE
BUS SYSTEM WITH BYPASS ISOLATOR
Advantages: It permits breaker maintenance without interruption of
power which is not possible in double bus system but it provides
all the advantages of double bus system. Disadvantages: It however
requires one additional isolator (bypass isolator) for each feeder
circuit and introduces slight complication in system layout. RING
BUS SYSTEM Advantages:
It provides a double feed to each feeder circuit, opening one
breaker under maintenance or otherwise does not affect supply to
any feeder. But this system has two major disadvantages.
Flexibility for breaker maintenance Each breaker removable without
disconnecting load Only one breaker needed per branch, Each branch
connected to network by two breakers All change-over switching done
with circuit-breakers & hence flexible. THANK YOU