    Time Current Curves TD012036EN Effective December 2015

    Contents

    Description Page

    Catalog Number Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

    Digitrip RMS 310+ Electronic Trip Units

    MDL, HMDL, CMDL, CHMDL, MDLB, HMLDB; 800A; 3- and 4-pole; LS and LSG . . . . . TD012051EN. . . . . . . . .6MDL, HMDL, CMDL, CHMDL, MDLB, HMLDB; 800A; 3- and 4-pole; LSI, LSIG,ALSI, ALSIG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TD012052EN . . . . . . . .7

    Ground Fault Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TD012053EN. . . . . . . . .8Maintenance Mode Setting; ALSI and ALSIG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TD012054EN. . . . . . . . .9

    Digitrip RMS 310 Electronic Trip UnitsMDL, HMDL, CMDL, CHMD; 800A; 3- and 4-pole; LS and LSG . . . . . . . . . . . . . . . . . . . . . SC-7204-99 . . . . . . . .10MDL, HMDL, CMDL, and CHMD; 800A 3- and 4-pole; LSI, LSIG, ALSI, ALSIG. . . . . . . . . . SC-6913-98 . . . . . . . .11Ground Fault Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-6914-98 . . . . . . . .12

    MT Thermal/Magnetic Trip Unit

    MDL, HMDL, MDLB, and HMDLB, 300-600A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-6911-98 . . . . . . . .13MDL, HMDL, MDLB, and HMDLB, 700-800A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-6912-98 . . . . . . . .14

    Note:Time/Current characteristic curves for Series C M-frame circuit breakers--voltages shown in curve headings aremaximum at which the breaker may be applied. Interrupting capacity of inidvidual breaker is tabulated on each curve.

    Note:The following curves are UL489 Listed for use in North America.The following circuit breakers are derived from Eaton, Westinghouse, or Cutler-Hammer history.

    Time Current Curves are engineering reference documents for application and coordination purposes only.For field testing molded case circuit breakers, refer to NEMA AB 4 guidelines.

    Series C MDL-Frame 400-800A, 240-600V

  • 7/25/2019 Td012036en Series c - Mdl-frame

    2/16

    ote:N Unless noted below, all curves remain unchanged from their prior revision.

    Revision Curve Number Page Date

    2 EATONwww.eaton.com

    Time Current Curves TD012036ENEffective December 2015

    Series CM-Frame

    Changed trip labels on page 5

  • 7/25/2019 Td012036en Series c - Mdl-frame

    3/16EATONwww.eaton.com

    Time Current Curves TD012036EEffective December 20

    Series CM-Frame

    Catalog Number Selection

    This information is presented only as an aid to understanding catalog numbers.It is not to be used to build catalog numbers for circuit breakers or trip units.

    MDL 3 800 F

    Circuit Breaker/

    Frame Type

    MDL, MDLBHMDL, HMDLB

    Number of Poles

    2

    3= Two-pole

    = Three-pole

    Circuit Breaker/Frame

    Ampere Rating

    300350400450500

    600700800

    Suffix

    FKV

    WX

    Y

    = Frame only

    = High magnetic molded case switch

    = 500C (thermal-magnetic trip units only)

    = Without terminals

    = Load side terminals only

    = Line side terminals only

    Table 2. Circuit Breaker/Frame

    1

    1

    MT 3 800 T

    Trip Unit Type

    MTMES

    Number of Poles

    23

    = Two-pole

    = Three-pole

    Trip Unit

    Ampere Rating

    300350400450500600700

    800

    Suffix

    TV

    LSLSILSGLSIG

    = Thermal-magnetic

    = 500C (thermal-magnetic trip units only)

    = Digitrip RMS 310

    = Digitrip RMS 310

    = Digitrip RMS 310

    = Digitrip RMS 310

    Table 1. Thermal-Magnetic Trip Unit

    1

    1

    Note

    1 Thermal-magnetic only.

  • 7/25/2019 Td012036en Series c - Mdl-frame

    4/164

    Time Current Curves TD012036EN

    Effective December 2015

    Series C

    M-Frame

    EATONwww.eaton.com

    MES 3 800 ALSIG B21

    Trip

    Unit Type

    MES

    Poles

    3 = Three Amperes

    800

    Features

    BlankB20B21

    B22

    ZG

    = No feature

    = High load alarm

    = Ground fault

    alarm, with trip

    = Ground fault

    alarm, no trip

    = Zone selective

    interlocking

    Trip Unit

    LSLSILSG

    LSIGALSI

    ALSIG

    = 310+ Electronic LS

    = 310+ Electronic LSI

    = 310+ Electronic LSG

    = 310+ Electronic LSIG

    = 310+ Electronic LSI with

    Maintenance Mode

    = 310+ Electronic LSIG with

    Maintenance Mode

    Table 4. MDL Electronic Trip Unit

    MDLB 3 800 F T36 B21 W

    Performance at 480 VacPoles

    3 = ThreeAmperes

    800 Features

    BlankB20B21

    B22

    ZG

    = No feature= High load alarm= Ground fault alarm, with trip= Ground fault

    alarm, no trip= Zone selective

    interlocking

    Trip Unit

    T33T32T35T36T38

    T39

    = 310+ Electronic LS= 310+ Electronic LSI= 310+ Electronic LSG= 310+ Electronic LSIG= 310+ Electronic LSI with Maintenance Mode

    = 310+ Electronic LSIG with Maintenance Mode

    FrameDesignation

    F

    MDLB

    HMDLBCMDLB

    CHMDLB

    = 50 kAIC

    = 65 kAIC= 50 kAIC 100% rated

    = 65 kAIC 100% rated

    Terminals

    W = No terminals

    Table 3. MDL Breaker Assembly

    MDL 3 800 F

    Performance at 480 Vac

    Poles

    3 = Three Amperes

    800

    Frame Designation

    F

    MDLHMDLCMDL

    CHMDL

    = 50 kAIC

    = 65 kAIC

    = 50 kAIC

    100% rated

    = 65 kAIC

    100% rated

    Table 5. MDL Frame Only

    Note

    1 Maintenance Mode and ZSI are only available with LSI and LSIG trip units.

    2 B21 and B22 features available only with LSG, LSIG and ALSIG trip units.

    3 B2x suffixes cannot be combined with other B2x suffixes.

  • 7/25/2019 Td012036en Series c - Mdl-frame

    5/16

    Time Current Curves TD012036EEffective December 2

    Series C

    M-Frame

    EATONwww.eaton.com

    Figure 1. Digitrip 310+ Faceplates

    ALSIG (With Maintenance Mode)

    LS

    LSI

    LSG

    LSIG

    ALSI (With Maintenance Mode)

  • 7/25/2019 Td012036en Series c - Mdl-frame

    6/166

    Time Current Curves TD012036EN

    Effective December 2015

    Series C

    M-Frame

    EATONwww.eaton.com

    .

    .

    .

    .

    .

    .

    0.01

    2

    10

    20

    30

    40

    50

    60708090100

    1000900800700600

    500

    400

    300

    200

    2000

    3000

    4000

    5000

    6000700080009000

    10,000

    0.02

    0.03

    0.04

    0.05

    0.060.070.080.090.1

    0.2

    0.3

    0.4

    0.50.60.70.80.9

    etuniM1

    sruoH2

    sdnoceSniemiT

    ruo

    H

    1

    Current in Multiples of (Ir)

    1 2 3 4 5 7 10 20 300.5 0.7

    Current in Multiples of (In)Current in Multiples of (Ir)I2t Trip Style (LS and LSG)

    12

    1 2 3 4 5 7 10 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 1000.5 0.7 12

    Available Short DelayPickup Settings

    28 x Ir 5%(See Notes 7 and 10)

    Application

    DeterminesEnd of Curve

    InstantaneousOverride

    (See Note 10)

    I2t Short Delay(See Note 8)

    67 ms

    See Note 9

    0.01

    0.02

    0.03

    0.04

    0.05

    0.060.070.080.090.1

    0.2

    0.3

    sdnoce

    SniemiT

    3

    4

    5

    6789

    Maximum Total

    Clearing Time

    Minimum Total

    Clearing Time

    1.15

    Available Long Delay Time(Seconds +0/30%):

    2*, 4*, 7*, 10, 12, 15*, 20, 24**Shown below at 6x

    15

    24

    1

    7

    4

    2

    2 4

    3

    5

    7

    8

    6

    .

    Digitrip 310+ Circuit Breaker Time/Current Curves (Phase Current)

    Series C M-Frame Circuit Breakers (800A)

    Catalog Types: MDL, HMDL, CMDL, CHMDL, MDLB, HMLDB

    Trip Unit Types: 33 (LS), 35 (LSG)

    Figure 2. Digitrip 310+ Trip Units (800A), Long Delay Response and Short Delay with I2T Response Curve and Override(LS, LSG) - TD012051EN, October 2014

    MDL, MDLB, CMDL 65 50 25

    HMDL, HMDLB, CHMDL 100 65 35

    Interrupting Rating

    UL/CSA rms Sym. kA, 50/60 Hz

    Breaker Type 240V 480V 600V

    Notes:

    1 Curve accuracy applies from 20C to +55C ambient . For possible continuous ampere

    derating for ambient above 40C, refer to Eaton . Temperatures above +88C cause an

    over-temperature protection trip.

    2 Application frequency is 50/60 Hertz.

    3 There is a memory effect that can act to shorten the long delay. The memory effect comes

    into play if a current above the long delay pickup value exists for a time and then is cleared

    by the tripping of a downstream device or the circuit breaker itself. A subsequent overload

    will cause the circuit breaker to trip in shorter time than normal. The amount of time

    reduction is inverse to the amount of time that has elapsed since the previous overload.

    Approximately five minutes is required between overloads to completely reset the memory.

    4 The right portion of the curve is determined by the interrupting rating of the circuit breaker.

    5 The left portion of the curve is shown as a multiple of the Long Delay Setting.

    (Long Delay Pickup = 115% of Ir). Range is 110%120%.

    6 Total clearing times shown include the response times of the trip unit, the breaker opening,

    and the interruption of the current.

    7 The Short Delay Pick Up has 7 settings/positions, 28 Ir

    8 Short Delay I2T band has a tolerance of 15%.

    9 Breakpoint back to FLAT response occurs at 8x IRfor upper line of the I2T curve.

    10 For high fault current levels, an additional fixed instantaneous hardware override is providedat 6800A (Tolerance 15%).

    A 320A

    B 400A

    C 450A

    D 500A

    E 600A

    F 630A

    G 700A

    H 800A

    AvailableSensors Amperes(Ir)/(In) 800A

  • 7/25/2019 Td012036en Series c - Mdl-frame

    7/16

    Time Current Curves TD012036EEffective December 2

    Series C

    M-Frame

    EATONwww.eaton.com

    .

    .

    .

    .

    .

    1 2 3 4 5 7 10 20 300.5 0.7 12

    1000900800

    2000

    3000

    5000

    6000700080009000

    10,000

    30

    40

    50

    60708090

    100

    700600

    500

    400

    300

    200

    4000

    etuniM1

    sruoH2

    ru

    oH

    1

    0.01

    2

    0.02

    0.03

    0.04

    0.05

    0.060.070.080.090.1

    0.2

    0.3

    0.4

    0.5

    0.60.70.80.9

    3

    4

    5

    6789

    10

    20

    sdnoceSniemiT

    Maximum TotalClearing Time

    1.15

    Available

    Long Delay Time(Seconds +0/30%):

    2*, 4*, 7*, 10, 12, 15*, 20, 24**Shown below at 6x

    MinimumTotalClearingTime

    Available ShortDelay Pickup

    Settings 28, x Ir5%

    (See Note 7)

    300 ms

    (P, Q, R)

    120 ms

    (M, N, O)

    Inst.

    (J, K, L)

    1

    Current in Multiples of (Ir)

    Current in Multiples of (Ir)

    Current in Multiples of (In)

    1 2 3 4 5 7 10 20.5 0.7

    Adjustable Flat Trip Style (LSI, LSIG, ALSI, ALSIG)

    12 001070504030201743 50.01

    0.02

    0.03

    0.04

    0.05

    0.060.070.080.090.1

    0.2

    0.3

    0.4

    sdnoce

    SniemiT

    ApplicationDetermines

    End of Curve

    InstantaneousOverride (See Note 8)

    20 30 40 50 70 100

    7

    2 4

    3

    5

    6

    8

    2

    4

    7

    15

    24

    Figure 3. Digitrip 310+ Trip Units (800A), Long Delay Response and Short Delay with Flat Response Curve and Override(LSI, LSIG, ALSI, ALSIG) - TD012052EN, October 2014

    Digitrip 310+ Circuit Breaker Time/Current Curves (Phase Current)

    Series C M-Frame Circuit Breakers (800A)Catalog Types: MDL, HMDL, CMDL, CHMDL, MDLB, HMLDB

    Trip Unit Types:32 (LSI), 36 (LSIG), 38 (ALSI), and 39 (ALSIG)

    Notes:

    1 Curve accuracy applies from 20C to +55C ambient . For possible continuous ampere

    derating for ambient above 40C, refer to Eaton . Temperatures above +88C cause an

    over-temperature protection trip.

    2 Application frequency is 50/60 Hertz.

    3 There is a memory effect that can act to shorten the long delay. The memory effect comes

    into play if a current above the long delay pickup value exists for a time and then is clearedby the tripping of a downstream device or the circuit breaker itself. A subsequent overload

    will cause the c ircuit breaker to trip in shorter time than normal. The amount of time

    reduction is inverse to the amount of time that has elapsed since the previous overload.

    Approximately five minutes is required between overloads to completely reset the memory.

    4 The right portion of the curve is determined by the interrupting rating of the circuit breaker.

    5 The left portion of the curve is shown as a multiple of the Long Delay Setting .(Long Delay). Range is 110%120%.

    6 Total clearing times shown include the response times of the trip unit, the breaker

    Pickup = 115% of Ir opening, and the interruption of the current.

    7 The Short Delay Pick Up has 7 settings/positions, 28 IR

    8 For high fault current levels, an additional fixed instantaneous hardware override is provided

    at 5620A (Tolerance 15%).

    A 320A

    B 400A

    C 450A

    D 500A

    E 600A

    F 630A

    G 700A

    H 800A

    AvailableSensors Amperes(Ir)/(In) 800A

    MDL, MDLB, CMDL 65 50 25

    HMDL, HMDLB, CHMDL 100 65 35

    Interrupting Rating

    UL/CSA rms Sym. kA, 50/60 Hz

    Breaker Type 240V 480V 600V

  • 7/25/2019 Td012036en Series c - Mdl-frame

    8/168

    Time Current Curves TD012036EN

    Effective December 2015

    Series C

    M-Frame

    EATONwww.eaton.com

    0.01

    2

    3

    4

    5

    6

    8

    10

    20

    30

    40

    50

    60708090

    100

    1000900800700600

    500

    400

    300

    200

    0.02

    0.03

    0.04

    0.05

    0.060.070.080.090.1

    0.2

    0.3

    0.4

    0.5

    0.60.70.80.9

    1

    7

    9

    2000

    3000

    40005000

    6000700080009000

    10,000

    etuniM1

    Ground Current in Multiple of (In)

    0.1 0.2 0.3 0.4 0.5 0.7 1 2

    0.1 0.2 0.3 0.4 0.5 0.7 1 2

    Ground Fault Pickup Settings

    (Tolerance 10%)

    0.4X

    0.3X

    0.2X 1X0.6X

    0.8X

    Inst.

    (J, M, P)

    120 ms

    (K, N, Q)

    300 ms

    (L, O, R)

    sdnoceSniemiT

    Figure 4. Ground Fault Delay Response Curve (LSG, LSIG, ALSIG) - Curve Number TD012053EN

    Digitrip 310+ Circuit Breaker Time/Current Curves (Ground Current)Series C M-Frame Circuit Breakers (800A)

    Catalog Types:MDL, HMDL, CMDL, CHMDL, MDLB, HMLDB

    Trip Unit Types:LSG, LSIG, ALSIG

    Notes:

    Curve accuracy applies from 20C to +55C ambient. For possible continuous ampere deratingfor ambient above 40C, refer to Eaton.

    Digitrip RMS 310 trip units are suitable for functional field testing with test kit C at. No. STK2.For field testing using primary injection methods, follow NEMA publications

  • 7/25/2019 Td012036en Series c - Mdl-frame

    9/16

    Time Current Curves TD012036EEffective December 2

    Series C

    M-Frame

    EATONwww.eaton.com

    Current in Multiples of Rating( )In

    .01

    2

    .02

    .03

    .04

    .05

    .06

    .07

    .08

    .09

    .1

    .2

    .3

    .4

    .5

    .6

    .7

    .8

    .9

    1

    3

    4

    5

    6

    7

    8

    9

    10

    1 2 3 4.

    5 .6

    .7 .

    8.

    910

    20

    30

    40

    505 6 7 8 9

    2.5

    Maintenance Mode Trip

    TIMEINSECONDS

    Applicationdeterminesend of curve

    .

    Figure 5. Maintenance Mode Setting (ALSI, ALSIG) - Curver Number - TD012054EN, October 2014

    Digitrip 310+ Circuit Breaker Time/Current Curves

    Maintenance Mode Setting

    Trip Unit Types: 38 (ALSI) and 39 (ALSIG)

    Series C M-Frame Trip Unit Nameplates

    Notes:

    1 The Maintenance Mode feature must be ENABLED via application of

    24 Vdc for these curves to apply. The blue LED is lit when in Maintenance Mode.

    2 The end of the curve is determined by the interrupting rating of the circuit breaker.

    3 Total clearing times shown include the response times of the trip unit,

    the breaker opening, and the interruption of the current.

    4 Nominal Values (Pickup) (Tolerance is 15%) 2.5 x In.

    5 The total clearing times shown are conservative and consider the maximum response

    time of the trip unit, the circuit breaker opening, and the interruption of the current in the worst case conditions such as: maximum rated voltages, single-phase interruption,

    and minimum power factor. Faster clearing times are possible depending on the specific

    system conditions.

    Contact Eaton for additional information.

    Ir= Continuous Current Setting or Rating Plug Value, Is= Current Sensor Frame Rating,

    In= Rating Plug Value, Ig= Ground Current Pickup Multiplier, Ii= Instantaneous Override Pickup.

    Left Side of Breaker

    YellowBlack

    Blue

    Red

    24 Vdc

    Relay Wiring

    NO

    C

    ALSI

    ALSIG

  • 7/25/2019 Td012036en Series c - Mdl-frame

    10/16

    6X

    8X

    4X

    7X

    2X

    Long Delay Minimum TotalClearing Time

    Long Delay Maximum TotalClearing Time

    Standard FixedRating Plug

    Short DelayPick UpSettings(Tolerance10%)

    5X

    3X

    CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In )

    .5

    .5

    TIMEINS

    ECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HOURS

    20106. 8. 1

    1.8.6

    CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

    .7 .9 6 7 8 9

    20102 6 7 8 9.7 .9

    Fixed InstantaneousOverride

    10,000

    .1

    .01

    1000

    5000

    4000

    3000

    2000

    20,000

    .001

    SECONDS

    30,000

    40,000

    50,000

    100,000

    .02

    .03

    .04

    .05

    InterruptingRating

    DeterminesEnd ofCurve

    CURRENT IN AMPERES

    2 3 4 5

    +

    3 4 5

    1.15

    Figure 6. MDL, HMDL, CMDL, and CHMDL, types MES3800LS and MES3800LSG - Curve Number SC-7204-99, June 2007

    Circuit Breaker Time/Current Curves (Phase Current)

    Series C M-Frame Circuit Breakers

    Equipped With Type MES Digitrip RMS 310 Trip Units

    Catalog Types: MES3800LS and MES3800LSG Digitrip RMS 310 Trip Units for usewith Circuit Breaker Types MDL, HMDL, CMDL and CHMDL 3 Poles.

    Fixed Short Delay Time Typical Trip Unit Nameplate

    Engaged

    Remove

    Cat.

    In

    Digitrip RMS 310 Rating Plug

    Push to Trip

    Short DelayPickup x In

    5

    7

    2 8

    4 6 Digitrip RMS 310Trip Unit40oCAmbient

    Test

    3

    Notes:

    Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2.For field testing using primary injection methods, follow NEMA AB4 publications.

    Calibration response in short delay pick-up range is same for 1, 2 or 3 poles in series.

    There is a memory effect that can act to shorten the long delay. The memory effect comesinto play if a current above the long delay pick-up value exists for a time and then is clearedby the tripping of a downstream device or the circuit breaker itself. A subsequent overloadwill cause the circuit breaker to trip in shorter time than normal. The amount of time delay

    reduction is inverse to the amount of time that has elapsed since the previous overload.Approximately five minutes is required between overloads to completely reset the memory.

    1 Curve accuracy applies from 20C to +55C ambient. For possible continuous ampere derating for ambient above 40C, refer to Eaton.

    2 For high fault current levels a fixed instantaneous override is provided at 6800A. (Tolerance 15%).

    3 The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation.

    4 Long delay pickup is 115% of In, +/- 15%.

    800 Fixed 8MES800T 1600-6400

    700 Fixed 8MES700T 1400-5600

    600 Fixed 8MES600T 1200-4800

    500 Fixed 8MES500T 1000-4000

    400 Fixed 8MES400T 800-3200

    400, 500, 600, 800 Adjustable A8MES800T1 800-6400

    AmpereRating(In)

    Available Rating Plugs

    Type

    Rating PlugCatalogNumber

    Short DelayPickup RangeAmperes

    UL/CSA rms Sym. kA, 50/60 Hz

    MDL, MDLB, CMDL, CMDLB 65 50 25

    HMDL, HMDLB, CHMDL, CHMDL 100 65 35

    240V 480V 600VBreaker Type

    IEC 60947-2 rms Sym. kA, 50/60 Hz

    Icu Ics Icu Ics Icu Ics

    MDL, MDLB, CMDL, CMDLB 65 65 50 50 20 10

    HMDL, HMDLB, CHMDL, CHMDL 100 100 70 50 25 13

    240V 380/415V 690VBreaker Type

    Utilization Category A

    UIMP= 8 kV

    Interrupting Rating

    Types MDL, HMDL, CMDL, and CHMDL Equipped with Type MES Digitrip RMS 310 Trip Units, Types MES3800LS and MES3800LSG

    10 EATONwww.eaton.com

    Time Current Curves TD012036ENEffective December 2015

    Series CM-Frame

  • 7/25/2019 Td012036en Series c - Mdl-frame

    11/16

    6X

    8X

    4X

    7X

    3X

    2X

    Standard FixedRating Plug

    100 ms

    300 ms5X

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HOURS

    CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

    .5

    .5 20106. 8. 1

    1.8.6

    CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

    .7 .9 6 7 8 9

    20102 6 7 8 9

    Short DelayPickupSettings(Tolerance+10%)

    Long Delay Minimum TotalClearing Time

    Long Delay Maximum TotalClearing Time

    .7 .9

    Fixed InstantaneousOverride

    InterruptingRatingDeterminesEnd ofCurve

    10,000

    .1

    .01

    1000

    5000

    4000

    3000

    2000

    20,000

    .001

    SECONDS

    CURRENT IN AMPS

    30,000

    40,000

    50,000

    100,000

    .02

    .03

    .04

    .05

    200 ms

    I

    2 3 4 5

    3 4 5

    1.15

    Figure 7. MDL, HMDL, CMDL, and CHMDL, types MES3800LSI and MES3800LSIG Curve Number - SC-6913-98, June 2007

    Circuit Breaker Time/Current Curves (Phase Current)

    Series C M-Frame Circuit Breakers

    Equipped With Type MES Digitrip RMS 310 Trip Units

    Catalog Types: MES3800LSI and MES3800LSIGDigitrip RMS 310 Trip Units for use

    with Circuit Breaker Types MDL, HMDL, CMDL, CHMDL 3 Poles.

    Adjustable Short Delay Time Typical Trip Unit Nameplate

    Engaged

    Remove

    Cat.

    In

    Digitrip RMS 310 Rating Plug

    Push to TripDigitrip RMS 310Trip Unit40oCAmbient

    Test

    5

    7 3

    2 8

    4 6

    Short DelayPickup x In

    300

    100

    I

    200

    TimeMIsec

    Notes:

    Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2.For field testing using primary injection methods, follow NEMA AB4 publications.

    Calibration response in short delay pick-up range is same for 1, 2 or 3 poles in series.

    There is a memory effect that can act to shorten the long delay. The memory effect comesinto play if a current above the long delay pick-up value exists for a time and then is clearedby the tripping of a downstream device or the circuit breaker itself. A subsequent overloadwill cause the circuit breaker to trip in shorter time than normal. The amount of time delayreduction is inverse to the amount of time that has elapsed since the previous overload.Approximately five minutes is required between overloads to completely reset the memory.

    1 Curve accuracy applies from 20C to +55C ambient. For possible continuous ampere derating for ambient above 40C, refer to Eaton.

    2 For high fault current levels a fixed instantaneous override is provided at 6800A. (Tolerance 15%).

    3 The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation.

    4 Long delay pickup is 115% of In, +/- 5%.

    800 Fixed 8MES800T 1600-6400

    700 Fixed 8MES700T 1400-5600

    600 Fixed 8MES600T 1200-4800

    500 Fixed 8MES500T 1000-4000

    400 Fixed 8MES400T 800-3200

    400, 500, 600, 800 Adjustable A8MES800T1 800-6400

    AmpereRating(In)

    Available Rating Plugs

    Type

    Rating PlugCatalogNumber

    Short DelayPickup RangeAmperes

    UL/CSA rms Sym. kA, 50/60 Hz

    MDL, MDLB, CMDL, CMDLB 65 50 25HMDL, HMDLB, CHMDL, CHMDL 100 65 35

    240V 480V 600VBreaker Type

    IEC 60947-2 rms Sym. kA, 50/60 Hz

    Icu Ics Icu Ics Icu Ics

    MDL, MDLB, CMDL, CMDLB 65 65 50 50 20 10

    HMDL, HMDLB, CHMDL, CHMDL 100 100 70 50 25 13

    240V 380/415V 690VBreaker Type

    Utilization Category A

    UIMP= 8 kV

    Interrupting Rating

    Types MDL, HMDL, CMDL, and CHMDL Equipped with Type MES Digitrip RMS 310 Trip Units, Types MES3800LSI and MES3800LSIG

    Time Current Curves TD012036EEffective December 2

    Series CM-Frame

    EATONwww.eaton.com

  • 7/25/2019 Td012036en Series c - Mdl-frame

    12/16

    Ground Fault PickupSettings(Tolerance +10%Except 20% on1xIGSetting)

    3xIG

    1

    4xIG

    2xIG

    1xIG

    2 3 4 5 6 7 8 910 100

    GROUND CURRENT-AMPERES

    TIMEI

    NSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MIN

    UTE

    2HOURS

    16000

    GROUND CURRENT-IN MULTIPLES OF Ig= 160A

    1600

    960

    800

    640

    480

    320

    160

    1120

    1280

    1440

    5xIG

    I

    500 ms

    300 ms

    150 ms

    +

    Figure 8. MDL, HMDL, CMDL, and CHMD Ground Fault Protection - Curve Number SC-6914-98, June 2007

    Circuit Breaker Time/Current Curves (Ground Current)

    Series C M-Frame Circuit BreakersEquipped With Type MES Digitrip RMS 310 Trip Unitsfor Ground Fault Protection

    Catalog Types: MES3800LSG and MES3800LSIG Digitrip RMS 310 Trip Units for usewith Circuit Breaker Types MDL, KMDL, CMDL, CHMDL.

    Engaged

    Remove

    Cat.

    In

    Digitrip RMS 310 Rating Plug

    Push to TripDigitrip RMS 310Trip Unit40oCAmbient

    Test

    500

    150

    3004

    2

    1

    3 5

    Ig=160A

    5

    7 3

    2 8

    4 6

    Short DelayPickup x In

    I

    Ground FaultPickup x Ig

    TimeMIsec

    300

    100

    I

    200

    TimeMIsec

    Fixed Short Delay Time

    Adjustable Short Delay Time

    Typical Trip Unit Nameplate

    Typical Trip Unit Nameplate

    Engaged

    Remove

    Cat.

    In

    Digitrip RMS 310 Rating Plug

    Push to TripDigitrip RMS 310Trip Unit40oCAmbient

    Test

    500

    150

    3004

    2

    1

    3 5

    Ig=160A

    5

    7 3

    2 8

    4 6

    Short DelayPickup x In

    I

    Ground FaultPickup x Ig

    TimeMIsec

    Notes:

    Curve accuracy applies from 20C to +55C ambient. For possible continuous ampere derating

    for ambient above 40C, refer to Eaton.

    Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. Forfield testing using primary injection methods, follow NEMA publication (AB4).

    Types MDL, HMDL, CMDL, and CHMDL Equipped with Type MES Digitrip RMS 310 Trip Units, Ground Fault Protection

    Time Current Curves TD012036ENEffective December 2015

    Series CM-Frame

    12 EATONwww.eaton.com

  • 7/25/2019 Td012036en Series c - Mdl-frame

    13/16EATONwww.eaton.com

    MaximumMinimum

    Maximum SinglePole Trip Timesat 25oC 1

    Adjustable Magnetic Trip

    5X

    10X+20% 10%

    TypicalTrip UnitNameplate

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2H

    OURS

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HOURS

    100

    80

    60

    90

    70

    50

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    10,

    000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    10,

    000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    80

    60

    90

    70

    50

    100,

    000

    80,0

    00

    60,0

    00

    90,0

    00

    70,0

    00

    50,0

    00

    40,0

    00

    30,0

    00

    20,0

    00

    Maximum Interrupting Time

    CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

    CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

    Interrupting RatingDetermines End ofCurve

    10,000

    Individual Pole

    Adjustments

    ThermalMagneticTrip Unit

    C Push to Trip

    MagneticMultiples Of In

    10

    7.5

    10 5

    7.5

    10 5

    Amps(In)

    Cat.No.40

    oC

    7.5

    5

    +

    Circuit Breaker Time/Current Curves

    Series C M-Frame Circuit Breakers

    Equipped With Type MT Thermal-Magnetic Trip UnitCatalog Types: MDL, HMDL, MDLB, HMDLB Circuit Breakers, 2 and 3 Poles.

    For application and coordination purposes only. Thermal calibration based on 40C ambient, coldstart. Connected with four (4) feet of rated wire (75C) per terminal. Tested in open air with

    current in all poles. Instantaneous calibration based on single-pole tests.

    Maximum Voltage:600V, AC (50/60 Hz) 250V, DC

    Notes:

    For additional in formation on the trip uni t, see IL 29C607.

    1 Single pole data at 25C based on NEMA Procedures (AB 4) for verifying performance ofmolded case circuit breakers.

    UL/CSA rms Sym. kA, 50/60 Hz kA, DC

    MDL, MDLB 65 50 25 22

    HMDL, HMDLB 100 65 35 25

    240V 480V 600V 250VBreaker Type

    IEC 60947-2 rms Sym. kA, 50/60 Hz kA, DC

    Icu Ics Icu Ics Icu Ics

    MDL, MDLB 65 65 50 50 20 10 20 10

    HMDL, HMDLB 100 100 70 50 25 13 20 10

    240V 380V 415V 250VBreaker Type

    Utilization Category A

    UIMP= 8 kV

    Breaker Rating

    Rated

    Amperes (In)

    Instantaneous Trip Amperes

    (See Figure Below)

    300 - 600 500 to 1000% of trip unit rating (DC values are approximately 40% higher)

    Figure 9. MDL, HMDL, MDLB, and HMDLB, 300-600A - Curve Number SC-6911-98, June 2007

    Types MDL, HMDL, MDLB, and HMDLB Equipped with Type MT Thermal-Magnetic Trip Unit, 300 to 600 Amperes

    Interrupting Rating

    Time Current Curves TD012036EEffective December 2

    Series CM-Frame

  • 7/25/2019 Td012036en Series c - Mdl-frame

    14/1614

    Time Current Curves TD012036EN

    Effective December 2015

    Series C

    M-Frame

    EATONwww.eaton.com

    MaximumMinimum

    Maximum SinglePole Trip Timesat 25oC 1

    Adjustable Magnetic Trip

    TypicalTrip UnitNameplate

    Individual PoleAdjustments

    ThermalMagneticTrip Unit

    Push to Trip

    MagneticMultiples Of In

    Amps(In)

    Cat.No.

    oC

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    T

    IMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HOURS

    TIMEINSECO

    NDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2H

    OURS

    100

    80

    60

    90

    70

    50

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    10,

    000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    10,0

    00

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    80

    60

    90

    70

    50

    100,0

    00

    80,0

    00

    60,0

    00

    90,0

    00

    70,0

    00

    50,0

    00

    40,0

    00

    30,0

    00

    20,0

    00

    Maximum Interrupting Time

    CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

    CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

    Interrupting RatingDetermines End ofCurve

    10,000

    8

    6

    4 8

    6

    4 8

    6

    4

    4X

    +

    8X 10%20% +

    Circuit Breaker Time/Current CurvesSeries C M-Frame Circuit Breakers

    Equipped With Type MT Thermal-Magnetic Trip Unit

    Catalog Types: MDL, HMDL, MDLB, HMDLB Circuit Breakers, 2 and 3 Poles.

    For application and coordination purposes only. Thermal calibration based on 40C ambient, cold

    start. Connected with four (4) feet of rated wire (75C) per terminal. Tested in open air with

    current in all poles. Instantaneous calibration based on single-pole tests.

    Maximum Voltage:600V, AC (50/60 Hz) 250V, DC

    Notes:

    For additional information on the trip uni t, see IL 29C607.

    1 Single pole data at 25C based on NEMA Procedures (AB 4) for verifying performance ofmolded case circuit breakers.

    UL/CSA rms Sym. kA, 50/60 Hz kA, DC

    MDL, MDLB 65 50 25 22

    HMDL, HMDLB 100 65 35 25

    240V 480V 600V 250VBreaker Type

    IEC 60947-2 rms Sym. kA, 50/60 Hz kA, DC

    Icu Ics Icu Ics Icu Ics

    MDL, MDLB 65 65 50 50 20 10 20 10

    HMDL, HMDLB 100 100 70 50 25 13 20 10

    240V 380V 415V 250VBreaker Type

    Utilization Category A

    UIMP= 8 kV

    Breaker Rating

    Rated

    Amperes (In)

    Instantaneous Trip Amperes

    (See Figure Below)

    700 - 800 400 to 800% of trip unit rating (DC values are approximately 40% higher)

    Figure 10. MDL, HMDL, MDLB, and HMDLB, 700-800A - Curve Number SC-6912-98, June 2007

    Types MDL, HMDL, MDLB, and HMDLB Equipped with Type MT Thermal-Magnetic Trip Unit, 700 and 800 Amperes

    Interrupting Rating

  • 7/25/2019 Td012036en Series c - Mdl-frame

    15/16EATONwww.eaton.com

    Time Current Curves TD012036EEffective December 2

    Series CM-Frame

  • 7/25/2019 Td012036en Series c - Mdl-frame

    16/16

    Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton.com

    2014 EatonAll Rights ReservedPrinted in USAPublication No. TD012036EN / KDCApril 2014

    Eaton is a registered trademark.

    All other trademarks are propertyof their respective owners.

    Series CM-Frame

    Time Current Curves TD012036ENEffective December 2015