Explosion Protection (For ProSafe-RS)

TI 32S01J30-01E

TI 32S01J30-01E©Copyright July 2006 (YK)

18th Edition June 2017 (YK)

Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JapanTel.: 81-422-52-5634 Fax.: 81-422-52-9802

Page 2: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Blank Page

Page 3: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

i

TI 32S01J30-01E

IntroductionThis book describes explosion protection compliance of ProSafe-RS. The engineering practice of explosion protection is regulated in each country, and in principle, construction technique including wiring should be done in accordance with the safety standards. When you build an explosion protection system for a real job, select products so as to comply with the standards of the country in which it is used, and check for construction technique beforehand. Please refer to CENTUM Explosion Protection (TI 33Q01J30-01E) for a general explanation of the explosion protections.

All Rights Reserved Copyright © 2006, Yokogawa Electric Corporation Jun. 18, 2008-00

Page 4: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

ii

TI 32S01J30-01E

Safety Precautions

Safety, Protection, and Modification of the Product• Inordertoprotectthesystemcontrolledbytheproductandtheproductitselfandtoensure

safe operation, observe the safety precautions described in the Technical Information (this book and ProSafe-RS Installation Guidance ) and the User’s Manuals. We assume no liability for safety if users fail to observe these instructions when operating the product.

• IfthisproductisusedinamannernotspecifiedintheTechnicalInformation,theprotectionprovided by this product may be impaired.

• Ifanyprotectionorsafetycircuitisrequiredforthesystemcontrolledbytheproductorforthe product itself, prepare it separately.

• BesuretousethesparepartsapprovedbyYokogawaElectricCorporation(hereaftersimply referred to as YOKOGAWA) when replacing parts or consumables.

• Donotusetheaccessories(Powersupplycordset,etc.)thatcamewiththeproductforanyother products.

• Modificationoftheproductisstrictlyprohibited.

• Thefollowingsymbolsareusedintheproductandthisbooktoindicatetherearesafetyprecautions:

Indicates that caution is required when handling the equipment. This symbol is labeled on the Product to indicate the possibility of dangers such as electric shock on personnel and equipment, and also indicate that the user must refer to the User’s Manuals for necessary actions. In the User’s Manuals, this symbol is used together with a signal word “WARNING” or “CAUTION” at the locations where precautions for avoiding dangers are described.

Indicates that caution is required for hot surface. Note that the devices with this symbol become hot. The risk of burn injury or some damages exists if the devices are touched or contacted.

Identifiesaprotectiveconductorterminal.Ensuretogroundtheprotectiveconductorterminal to avoid electric shock before using the product.

Identifiesafunctionalgroundingterminal.Aterm“FG”isalsoused.Thisterminalisequipped with the same function and used for purposes other than the protective grounding.Beforeusingtheproduct,groundtheterminal.

Indicates an AC supply.

IndicatesaDCsupply.

Indicates that the main switch is ON

Indicates that the main switch is OFF

Oct. 25, 2016-00

Page 5: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

iii

TI 32S01J30-01E

Symbols in this BookThis book has the following symbols.

WARNING Indicates precautions to avoid a danger that may lead to death or severe injury.

CAUTION Indicates precautions to avoid a danger that may lead to minor or moderate injury or

property damage.

IMPORTANT Identifiesimportantinformationrequiredtounderstandtheoperationsorfunctions.

TIP Identifiesadditionalinformation.

SEE ALSO

Identifiesasourcetobereferredto.

Oct. 25, 2016-00

Page 6: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

iv

TI 32S01J30-01E

Considerations for Using This Product in Safety

Power Supply Wiring

WARNINGThe connection of power cables and the selection of power cables must be done in accordance with this book and the Installation Guidance, and implement so as to comply with the standards and laws about explosion protection in the country or the area where the cables are laid.

Ground Wiring

WARNINGYou should implement so as to comply with the standards and laws about explosion protection in the country or the area where the cables are laid.

Input/Output Wiring

WARNING• Theconnectionofinputandoutputshouldbedoneinaccordancewiththisbookandthe

Installation Guidance, and implement so as to comply with the standards and laws about explosion protection in the country or the area where the cables are laid.

• Wiringmaterialandequipmentwhichiselectricallyconnectedtothisequipmentshouldbeproducts that complied with standards and laws about explosion protection in the country or the area where the cables are laid.

Oct. 25, 2016-00

Page 7: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

v

TI 32S01J30-01E

Replacement of fuse

WARNING • Thespecifiedfusemustbeusedtoreplacement.

• Beforereplacingfuse,confirmifthere’snodangerousgas,andthepowersupplyisOFF.

Maintenance

WARNING• Themaintenanceworkshouldbedoneonlybyoperatorswhoreceivedspecialtraining.

• Useavacuumcleanerandsoftclothtocleanuptheequipment.

• Atthetimeofthemaintenancework,putonwriststrapsandtakethemeasuresforElectrostaticDischarge.

• IfthelabelthatindicatesDangerisnotlegible,orifithaspeeledoff,orderanewlabelusingpartnumberT9029BX.

• Beforestartingthemaintenancework,confirmifthere’snodangerousgas.

Drawing ConventionsSomedrawingsdepictedintheuser’smanualmaybepartiallyemphasized,simplified,oromittedfor the convenience of description.

Trademarks

Trademarks• CENTUM,Vnet/IPandProSafe-RSareregisteredtrademarksofYokogawaElectric

Corporation.

• Allothercompanyandproductnamesmentionedinthetextbodyaretrademarksorregistered trademarks of their respective companies.

• WedonotusetheTMor®marktoindicatethesetrademarksorregisteredtrademarksinthis book.

Oct. 25, 2016-00

Page 8: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Blank Page

Page 9: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Toc-1

TI 32S01J30-01E

Explosion Protection(For ProSafe-RS)

June 30, 2017-00

CONTENTS

TI 32S01J30-01E 18th Edition

1. ProSafe-RS and Explosion Protection Instrumentation ...................... 1-11.1 Explosion Protection Standards that ProSafe-RS Complies ....................... 1-11.2 Explosion Protection Construction Adopted for ProSafe-RS Devices ...... 1-31.3 Overview of ProSafe-RS Connection to the Devices Installed in

a Hazardous Area ..............................................................................................1-5

2. Explosion Protection Instrumentation in Zone 2/Division 2 ............... 2-12.1 Non-Incendive ...................................................................................................2-12.2 Type “n” ...........................................................................................................2-12

3. Intrinsic Safety Explosion Protection Instrumentation ....................... 3-13.1 Intrinsic Safety Explosion Protection Instrumentation Using Barrier

base plates .........................................................................................................3-23.1.1 IntrinsicSafetyExplosionProtectionofATEXStandard ................... 3-2

3.1.2 Intrinsic Safety Explosion Protection of IEC Standard ...................... 3-3

3.1.3 Intrinsic Safety Explosion Protection of US (FM) Standard ............... 3-4

3.1.4 Intrinsic Safety Explosion Protection of Canada (FM) Standard ....... 3-5

3.2 Intrinsic Safety Explosion Protection Instrumentation Using Barriers ...... 3-6

Appendix 1. List of NI Compliant Products ............................................App.1-1Appendix 1.1 US (FM) NI Compliant Products .....................................................App.1-1Appendix 1.2 Canada (FM) NI Compliant Products .............................................App.1-9

Appendix 2. List of Type “n” Compliant Products .................................App.2-1Appendix 2.1 ATEX Type “n” Compliant Products ..............................................App.2-1Appendix 2.2 IECEx Type “n” Compliant Products ............................................App.2-7

Appendix 3. Lists of Parameters of Base Plate for Barrier (S2BN5D) ..App.3-1Appendix 4. US (FM) NI/Canada (FM) NI Control Drawing

for ProSafe-RS N-IO .........................................................................App.4-1Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing

for ProSafe-RS FIO ...........................................................................App.5-1Appendix 6. US (FM) NI/Canada (FM) NI Control Drawing

for S2BN5D ........................................................................................App.6-1

Page 10: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Blank Page

Page 11: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

1. ProSafe-RS and Explosion Protection Instrumentation 1-1

TI 32S01J30-01E

1. ProSafe-RS and Explosion Protection Instrumentation

1.1 Explosion Protection Standards that ProSafe-RS Complies

There are various standards for explosion protection in each region. Therefore, when we try to use equipment in a certain region, it needs to be approved by the explosion protection standards adoptedintheregion.ProSafe-RS,aglobalproduct,hasbeencertifiedaccordingtothestandards adopted in North America and Europe.The table below lists the explosion protection standards that ProSafe-RS complies and their certificationauthorities.Asshowninthetable,ProSafe-RSdevicescomplywiththeFMApprovalStandardforNon-IncendiveequipmentandsatisfytheprotectionATEXType“n”therefore,theycanbeinstalledinZone2orDivision2hazardousareas.Thischaptermainlydescribestheexplosion protection compliance of ProSafe-RS devices.

Table Explosion Protection Standards that ProSafe-RS Complies (1/2)

Explosion protection construction Complies standard Certification

authorities Applicable equipment

US (FM) Nonincendive

Class 3600 : 2011Class 3611 : 2004Class 3810 : 2005

FM Safety Control Unit, FIO, N-IO, and associated equipment

Class 3600:2011Class 3611:2004Class 3810:2005ANSI/ISA-60079-0(12.00.01)-2013ANSI/ISA-60079-15(12.12.02)-2012

FM S2BN5DBaseplateforbarrier(N-IO)

US (FM) intrinsic safe explosion protection

Class 3600:2011Class 3610:2010ANSI/ISA-60079-0(12.00.01)-2013ANSI/ISA-60079-11(12.02.01)-2014

FM S2BN5DBaseplateforbarrier(N-IO)

Canada (FM) Non-Incendive

C22.2 No.213-15CAN/CSA-C22.2No.61010-1-12CAN/CSA-IEC61010-2-201:14CAN/CSA-C22.2No.61010-2-030-12

FM FIO, N-IO, and associated equipment

CAN/CSA-C22.2No.61010-1-12CAN/CSA-C22.2No.60079-0:11CAN/CSA-C22.2No.213-M1987(R2013)CAN/CSA-C22.2No.60079-15:12

FM S2BN5DBaseplateforbarrier(N-IO)

Canada (FM) intrinsic safeexplosion protection

CAN/CSA-C22.2No.60079-0:11CAN/CSA-C22.2No.60079-11:14 FM S2BN5D

Baseplateforbarrier(N-IO)

ATEXType“n”

EN 60079-0: 2012+A11: 2013EN 60079-15: 2010 Self-declaration Safety Control Unit, FIO, N-IO,

and associated equipmentEN 60079-0:2012+A11:2013EN 60079-15:2010 EXA S2BN5D

Baseplateforbarrier(N-IO)

IECEx Type “n” IEC 60079-0:2011IEC 60079-15:2010 FM Safety Control Unit, N-IO, and

associated equipment

June 30, 2017-00

Note: Regardingthelatestconformitystandardforeachmodel,refertothegeneralspecifications.

Page 12: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

1. ProSafe-RS and Explosion Protection Instrumentation 1-2

TI 32S01J30-01E

ATEXType“i”(intrinsic safety explosion protection)

EN 60079-0: 2012+A11: 2013EN 60079-11 : 2012 EXA S2BN5D

BasePlateforbarrier(N-IO)

IECEx Type “i”(intrinsic safety explosion protection)

IEC 60079-0: 2011IEC 60079-11 : 2011 EXA S2BN5D

BasePlateforbarrier(N-IO)

Note: Regardingthelatestconformitystandardforeachmodel,refertothegeneralspecifications.

Apr. 26, 2017-00

Table Explosion Protection Standards that ProSafe-RS Complies (2/2)

Page 13: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

1. ProSafe-RS and Explosion Protection Instrumentation 1-3

TI 32S01J30-01E

1.2 Explosion Protection Construction Adopted for ProSafe-RS Devices

As described in 1.1, each country has its own standards and rules regarding technical methods for explosion protection. To install ProSafe-RS in hazardous areas, NI and Type “n” regulations are adopted as explosion protection construction. The adoption of NI and Type “n” makes it possibletoinstallProSafe-RSinDivision2orZone2thatcoversmosthazardousareas.Thiswidensamorevarietyofinstrumentation.Inaddition,itmakesitpossibletoconnecttofielddevicesinstalledinDivision2orZone2hazardousarea.(Therearesomerestrictions.)ToinstallProSafe-RSdevicesinahazardousarea,thenodesandterminalboardsaswellasI/Omodulesshouldcomplywiththestandards.ThefigurebelowshowsanexampleofNIcompliantdevices.The devices in shading and the cables shown in heavy line are NI compliant products. For NI compliant products, see Appendix 1, “List of NI compliant products and NI parameters.”

F010201E.ai

<Hazardous area Class I, Division 2> <Non-hazardous area>

Cabinet

YNT522D

YNT522D

V net

SSC10D SEC401

SSB401+T Branch

SNB10D

Signal cable

SEA4D

V net

Figure Example of the Configuration in Hazardous Area for V net

Oct. 25, 2016-00

Page 14: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

1. ProSafe-RS and Explosion Protection Instrumentation 1-4

TI 32S01J30-01E

F010202E.ai

<Hazardous area Class I, Division 2>

<Non-Hazardous area>

Cabinet

Cabinet

Vnet/IP Bus1Bus2

SNT10D

SNT501

SNT401

Fiber-optic cable

L2SW for Bus1

SSB401+T Branch

SNB10D

L2SW: Layer 2 switch

SEA4D SEA4D

SSB401+T Branch

SEC401

SSC60D

SNB10D

L2SW for Bus2

Figure Example of the Configuration in Hazardous Area for Vnet/IP

When the NI-compliant equipment is connected, energy exchange between them may affect the properties of NI-compliant equipment. Therefore, to ensure the properties, it is necessary to compare parameters among connected equipment in advance. With the results, it is necessary to determine whether general wiring can be used for connection in a hazardous area or dedicated wiringforDivision2isneeded.Tocompareparameters,itisrequiredtodisplayparametersonNI-compliant equipment.

Oct. 25, 2016-00

Page 15: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

1. ProSafe-RS and Explosion Protection Instrumentation 1-5

TI 32S01J30-01E

1.3 Overview of ProSafe-RS Connection to the Devices Installed in a Hazardous Area

This section describes the overview of ProSafe-RS connection to the devices installed in a hazardous area, giving some examples

Connection of Non-Incendive Compliant EquipmentNI-compliantequipmentcanbeconnectedtothedevicesinstalledinDivision2.Forconnectionto NI-compliant device, it is necessary to compare parameters of the device installed in a hazardous area and those of the ProSafe-RS equipment to determine whether connection is availableornot.NI-compliantequipmentcanbeinstalledinDivision2ifitisinakeyedmetalenclosureapprovedbycertificationauthorities.

Division 1 Division 2 Non-Hazardous Area

Flameproof equipment

ProSafe-RS Node unit

NI-compliant equipment

F010303E.ai

Wiring for Div.1/Div.2

Figure NI (Flameproof Wiring)

IMPORTANTFlameproofwiringshowscabling(withflameproofpacking)ormetaltubewiring(sealingfitting).Laywiringaccordingtoinstallationspecificationsoftheflameproofequipment.

Division 1 Division 2

Flameproof equipment

ProSafe-RS Node unit

NI-compliant equipment

F010304E.ai

Wiring for Div.1/Div.2

Figure NI (Installation in Division 2)

Oct. 25, 2016-00

Page 16: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

1. ProSafe-RS and Explosion Protection Instrumentation 1-6

TI 32S01J30-01E

Connecting Type “n”-compliant EquipmentProSafe-RS Type “n” equipment can be connected to the intrinsic safety equipment installed in Zone 0, Zone 1 and Zone 2 using a safety barrier and explosion-proof wiring as shown in thefollowingfigures.TheycanbeconnectedtoType“n”equipmentinstalledinZone2usingexplosion-proofwiringfortype”n”equipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion.Andtheycanbeconnectedtoflameproofequipmentusingexplosion-proofwiringforflameproofequipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion.Type“n”-compliantequipment(24VDCsuppliedmodel) can be installed in Zone 2 if it is in a keyed metal enclosure with protection rating of IP54 or higher.

Zone 1 Zone 2 Non-Hazardous Area

Flameproof equipment

Zone 0

Intrinsic safety equipment

ProSafe-RS Node unit

Intrinsic safety equipment

Type “n” equipment

*3

*1

*2

Intrinsic safety equipment

*1

F010301E.ai

SafetyBarrier

SafetyBarrier

SafetyBarrier

*1

*1: Explosion-proofwiringforintrinsicallysafecircuitsthatisdefinedinIEC/EN60079-14,IEC/EN60079-25andtherules/standardsof each country or region.

*2: Explosion-proofwiringfortype”n”equipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion.

*3: Explosion-proofwiringforflameproofequipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion.

Figure Type “n”

Oct. 25, 2016-00

Page 17: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

1. ProSafe-RS and Explosion Protection Instrumentation 1-7

TI 32S01J30-01E Oct. 25, 2016-00

Zone 1 Zone 2 Zone 0

Intrinsic safety equipment

Intrinsic safety equipment

ProSafe-RS Node unit

Intrinsic safety equipment

F010302E.ai

Type “n” equipment

*1

Safety Barrier

Safety Barrier

Safety Barrier

*2

*2

*2

*1 *2

*1

Flameproof equipment

*3

*1: Explosion-proofwiringforintrinsicallysafecircuitsthatisdefinedinIEC/EN60079-14,IEC/EN60079-25andtherules/standardsof each country or region.

*2: Explosion-proofwiringfortype”n”equipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion.

*3: Explosion-proofwiringforflameproofequipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion.

Figure Type “n” (Installation in Zone 2)

Page 18: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

1. ProSafe-RS and Explosion Protection Instrumentation 1-8

TI 32S01J30-01E

Overview of Connecting N-IO Components Overview of Connecting S2BN1D base plate for ATEX and IECEx

S2BN1DBaseplatecanbeconnectedtotheintrinsicsafetyequipmentinstalledinZone0,Zone1,andZone2usingabarrierandexplosion-proofwiringasshowninthefollowingfigures. They can be connected to Intrinsic safety equipment installed in Zone 0, 1, and 2 using Explosion-proofwiringforintrinsicallysafecircuitsthatisdefinedinIEC/EN60079-14,IEC/EN60079-25andtherules/standardsofeachcountryorregion. They can be connected to Type “n” equipment installed in Zone 2 using explosion-proof wiring for Type”n”equipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryor region. Andtheycanbeconnectedtoflame-proofequipmentusingexplosion-proofwiringforflame-proofequipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion. N-IOnodeunitincludingS2BN1DandSCUornodeunit(24VDCfeedingtype)canbeinstalledin Zone 2 by mounting in a keyed metal cabinet with protection rating of IP54 or higher.

S2BN1D Base plate

F010305E.ai

Zone1 Zone2 Non-Hazardous AreaZone0

SafetyBarrier

SafetyBarrier

SafetyBarrier

Flameproof equipment

Intrinsic safety equipment

Type "n" equipment

Intrinsic safety equipment

Intrinsic safety equipment

*1

*1

*3

*1

*2

*1: Explosion-proofwiringforintrinsicallysafecircuitsthatisdefinedinIEC/EN60079-14,IEC/EN60079-25andtherules/standardsof each country or region

*2: Explosion-proofwiringforType”n”equipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion

*3: Explosion-proofwiringforflameproofequipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion

Figure Connection of S2BN1D for ATEX and IECEx (1)

Oct. 25, 2016-00

Page 19: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

1. ProSafe-RS and Explosion Protection Instrumentation 1-9

TI 32S01J30-01E

Zone1 Zone2 Non-Hazardous AreaZone0

F010306E.ai

Intrinsic safety equipment

Intrinsic safety equipment

Intrinsic safety equipment

Type "n" equipment

SafetyBarrier

SafetyBarrier

SafetyBarrier

*1

*1

*1

*2

*2

*2

*2

S2BN1D Base plate

*3

Flameproof equipment

*1: Explosion-proofwiringforintrinsicallysafecircuitsthatisdefinedinIEC/EN60079-14,IEC/EN60079-25andtherules/standardsof each country or region

*2: Explosion-proofwiringforType“n”equipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion

*3: Explosion-proofwiringforflameproofequipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion

Figure Connection of S2BN1D for ATEX and IECEx (2)

Oct. 25, 2016-00

Page 20: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

1. ProSafe-RS and Explosion Protection Instrumentation 1-10

TI 32S01J30-01E

Overview of Connecting S2BN1D base plate for US (FM) and Canada (FM)S2BN1DbaseplatecanbeconnectedtothedevicesinstalledinDivision2.Fortheconnectiontoan NI-compliant module, it is necessary to compare parameters between the device installed in a hazardous area and the device of ProSafe-RS to evaluate whether connection is possible or not.N-IOnodeunitincludingS2BN1DcanbeinstalledinDivision2bymountinginakeyedmetalcabinet approved by approval authorities.

Non-Hazardous Area

Flameproof equipment

NI-compliant equipment

F010307E.ai

Division 1 Division 2

S2BN1D Base plate

Wiring for Div.1/Div.2

Figure Connection of S2BN1D for FM and CSA (1)

Division 1 Division 2 Non-Hazardous Area

Flameproof

NI-compliant equipment

F010308E.ai

S2BN1D Base plate

equipment

Wiring for Div.1/Div.2

Figure Connection of S2BN1D for FM and CSA (2)

Oct. 25, 2016-00

Page 21: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

1. ProSafe-RS and Explosion Protection Instrumentation 1-11

TI 32S01J30-01E

Overview of Connecting S2BN4D base plate for ATEX and IECExIntrinsic safety (hereinafter I.S.) barriers (*1) from MTL Instruments Group Limited (MTL) which canbemountedtothebaseplate(S2BN4D),complywithI.S.explosionprotectionstandard(*2). I. S. barriers can be connected to the I. S. equipment installed in the hazardous area with explosion-proofwiringasshowninthefollowingfigures.*1: Referto“BasePlatesforBarrier(forN-IO)”(GS32P06P10-01EN).*2: Refer to the MTL’s instruction manual for installation of the I.S. barriers.

Zone1 Zone2 Non-Hazardous AreaZone0

F010309E.ai

MTL’s I.S. Barriers

Intrinsic safety equipment

Intrinsic safety equipment

Intrinsic safety equipment

*1

*1

*1

Type “n”equipment

*2

Base plate for barrierS2BN4D

1: Explosion-proofwiringforintrinsicallysafecircuitsthatisdefinedinIEC/EN60079-14,IEC/EN60079-25andtherules/standardsof each country or region.

*2: Explosion-proofwiringforType”n”equipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion.

Figure Connection of S2BN4D for ATEX and IECEx (1)

Zone1 Zone2 Non-Hazardous AreaZone0

F010310E.ai

MTL’s I.S. Barriers

Intrinsic safety equipment

Intrinsic safety equipment

Intrinsic safety equipment

*1

*1

*1

Type “n”equipment

*2

Base plate for barrierS2BN4D

1: Explosion-proofwiringforintrinsicallysafecircuitsthatisdefinedinIEC/EN60079-14,IEC/EN60079-25andtherules/standardsof each country or region.

*2: Explosion-proofwiringforType”n”equipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion.

Figure Connection of S2BN4D for ATEX and IECEx (2)

Oct. 25, 2016-00

Page 22: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

1. ProSafe-RS and Explosion Protection Instrumentation 1-12

TI 32S01J30-01E

Overview of Connecting S2BN5D base plate for ATEX and IECExS2BN5DbaseplateforbarriercanbeconnectedtotheI.S./Type“n”equipmentinstalledinthehazardous area with explosion-proof wiring and can be installed in Zone 2 by mounting in a keyedmetalcabinetwithprotectionratingofIP54orhigherasshowninthefollowingfigures.Please refer to the instruction manual of P+F I.S. barriers for installation of I.S. barriers.

Zone1 Zone2 Non-Hazardous AreaZone0

F010311E.ai

P+F’s I.S. Barriers

Intrinsic safety equipment

Intrinsic safety equipment

Intrinsic safety equipment

*1

*1

*1

Intrinsic safety equipment

Base plate for barrierS2BN5D

*2

*1: Explosion-proofwiringforintrinsicallysafecircuitsthatisdefinedinIEC/EN60079-14,IEC/EN60079-25andtherules/standardsof each country or region.

*2: Explosion-proofwiringforType”n”equipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion.

Figure Connection of S2BN5D for ATEX and IECEx (1)

Zone1 Zone2 Non-Hazardous AreaZone0

F020315.ai

P+F’s I.S. Barriers

Intrinsic safety equipment

Intrinsic safety equipment

Intrinsic safety equipment

Base plate for barrierS2BN5D

*1

*1

*1

*1: Explosion-proofwiringforintrinsicallysafecircuitsthatisdefinedinIEC/EN60079-14,IEC/EN60079-25andtherules/standardsof each country or region.

Figure Connection of S2BN5D for ATEX and IECEx (2)

Oct. 25, 2016-00

Page 23: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

1. ProSafe-RS and Explosion Protection Instrumentation 1-13

TI 32S01J30-01E

Overview of Connecting S2BN5D barrier base plate for US (FM) and Canada (FM)S2BN5DbaseplateforbarriercanbeconnectedtothedevicesinstalledinDivision1andDivision2.ForconnectingtothedevicesinstalledinDivision1orDivision2,itisnecessarytocompareintrinsicsafetyparametersbetweenthedevicesinstalledandS2BN5Dtoevaluatewhether connection is possible or not.

Division2 Non-Hazardous AreaDivision1

Intrinsic safety equipment

NI equipmentIntrinsic safetyequipment

F010313E.ai

Base plate for barrierS2BN5D

P+F’s I.S. Barriers

Figure Connection of S2BN5D for US (FM) and Canada (FM) (1)

Division2 Non-Hazardous AreaDivision1

Intrinsic safety equipment

NI equipment Intrinsic safety equipment

F010314E.ai

Base plate for barrierS2BN5D

P+F’s I.S. Barriers

Figure Connection of S2BN5D for US (FM) and Canada (FM) (2)

Oct. 25, 2016-00

Page 24: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-1

TI 32S01J30-01E

2. Explosion Protection Instrumentation in Zone 2/Division 2

2.1 Non-IncendiveThisdocumentcontainsthedetailsofFMApprovalsCertification,NFM014-A13andNIE009-A101. The precautions on handling the Non-Incendive products, the notices on wiring the Incendive products and so on are explained in this document.Non-Incendive (hereinafter described as NI), especially in North America, represents one of the explosion protection constructions for explosion-proof apparatus used in hazardous areas. NI is a construction that enhances safety not to cause a spark, an arc or high surface temperatures inanormaloperation.Asafetycontrolunit,asafetynodeunit,unitforOpticalBusRepeaterModule,anI/Omodule,anopticalrepeater,andanN-IOnodeintheProSafe-RShaveacquiredNIcertificatesofthefollowingstandardsfromFM.ThecertificationensuresthattheproductsabovecanbeusedinClassI,Division2(*1)hazardous(classified)areasandthattheequipmentcanbedirectlyconnectedtoanNIapprovedfielddeviceinstalledinClassI,Division2hazardousareas. In addition, electrical equipment installed in non-hazardous areas can be directly connectedtoanNIapprovedlocaldeviceinstalledinClassI,Division2hazardousareas.*1: ClassI,Division2isaplacewheregasesorvaporsdonotformapotentiallyexplosiveatmosphereinanormalstate,andevenif

they do, it stays for only a short period of time.

Approved Types and StandardsUS (FM) NIClassI,Division2,GroupsA,B,CandD,TemperatureCodeT4Class 3600 : 2011 Class 3611 : 2004 Class 3810 : 2005For100-120VAC,220-240VACand24VDCpowersupply

Canada (FM) NIC22.2 No.213-15 CAN/CSA-C22.2No.61010-1-12 CAN/CSA-IEC61010-2-201:14 CAN/CSA-C22.2No.61010-2-030-12

June 30, 2017-00

Page 25: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-2

TI 32S01J30-01E

Precautions • Toinstalladeviceinaccordancewiththestandardsabove,thedeviceneedstobe

accommodated in a keyed metal cabinet and installed. As for US (FM), it is necessary to use a cabinet complying with FM Class 3810 and FM Class 3600 or approved by FM or local testing authorities for explosion-proof products. As for Canada (FM), it is necessary to use a cabinet approved by CSA or local testing authorities for explosion-proof products.

• Asarule,NIexplosionprotectionwhereFMapproveddeviceisconnectedtoCSAapproveddevice shall not be approved. It is necessary to connect devices approved by the same standard.

• Installation,wiringandmaintenanceofthedevicesshouldbecarriedoutbytheengineersorother professional personnel with related expertise.

• TheInstallationandthewiringshouldbeinaccordancewithNEC(theNationalElectricalCode:ANSI/NFPA-70),CEC(CanadianElectricalCode)orwiringconstructionstandardsofthe countries or regions where wiring is laid.

• Duringinstallation,theventingslotsofthedevicesmustnotbeblockedbycableparts,fixingaccessories, etc..

• Whenthedevicesareused,abidebythefollowingguidancesoastoensurethesafetyandperformance.

- Make sure that the door of the cabinet is closed when the devices are running.

- Make sure that all the empty slots in the cabinet should be properly covered with attached caps.

- Makesurethatallthecablesarerigidlyfixedinthecabinet.

- Make sure that the breakers are in the power supply circuits located in non-hazardous areas so that the power can be shutoff when abnormality occurs.

• BoththeinitialandperiodicalinspectionshouldbebasedontheregulationsofIEC60079-17 and carried out by the personnel who have received the professional training.

• PleaserefertotherelatedGS(GeneralSpecifications),“ProSafe-RSInstallationGuidance”TI32S01J10-01E,“ProSafe-RSInstallationGuidance(forVnet/IP)”TI32S51J10-01E.

• Pleaseobservethefollowingprecautionswhileproductisoperatingorundermaintenanceservice.

WARNINGWARNING-EXPOSURETOANYCHEMICALSMAYDEGRADETHESEALINGPROPERTIESOFMATERIALSUSEDINTHEFOLLOWINGDEVICES;SBD2D,SBD3D,SBD4DandS1BB4D.

WARNINGWARNING-EXPLOSIONHAZARD.DONOTREMOVEORREPLACELAMPSORFUSESUNLESSPOWERHASBEENDISCONNECTEDORWHENAFLAMMABLEORCOMBUSTIBLEATMOSPHEREISPRESENT.

June 30, 2017-00

Page 26: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-3

TI 32S01J30-01E

WARNINGWARNING-EXPLOSIONHAZARD.DONOTDISCONNECTEQUIPMENTWHENAFLAMMBLEORCOMBUSTBLEATMOSPHEREISPRESENT.

WARNINGWARNING-EXPLOSIONHAZARD.DONOTOPENENCLOSUREORREPLACEBATTERYWHENAFLAMMABLEORCOMBUSTIBLEATMOSPHEREISPRESENT.

NI approved Products and Their Configuration ExampleThefigurebelowisanexampleoftheconfigurationofNIapprovedproductswhichcanbeinstalled in hazardous areas.For details, refer to Appendix for NI approved products.

F020101E.ai

<Hazardous area Class I, Division 2> <Non-hazardous area>

Cabinet

YNT522D

YNT522D

V net

SSC10D SEC401

SSB401+T BranchSNB10D

Signal cable

SEA4D

V net

Figure Example of the Configuration of NI for V net

Oct. 25, 2016-00

Page 27: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-4

TI 32S01J30-01E

F020106E.ai

<Hazardous area Class I, Division 2>

<Non-Hazardous area>

Cabinet

Cabinet

Vnet/IP Bus1Bus2

SNT10D

Fiber-optic cable

SNT501

SNT401

L2SW for Bus1

L2SW: Layer 2 switch

SSB401+T Branch

SNB10D

SEA4D SEA4D

SSB401+T Branch

SEC401

SSC60D

SNB10D

L2SW for Bus2

Figure Example of the Configuration of NI for Vnet/IP

Apr. 1, 2013-00

Page 28: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-5

TI 32S01J30-01E

Power Supply Wiring Thepowercablesforthesafetycontrolunit,safetynodeunit,unitforopticalESBbusrepeatermodule,andN-IOnodemustbewiredfromanon-hazardousareabyusingspecifiedDivision2,explosion-proof wiring such as conduit wiring. In addition, do not apply stress on the both ends of the wiring cable. ThewiringshouldconformtotheNEC(NationalElectricalCode:ANSI/NFPA-70),CEC(Canadian Electrical Code) or wiring construction standards of the countries or regions where wiring is laid.

Signal WiringCables other than power cables should be wired to conform to NEC (National Electrical Code: ANSI/NFPA-70),CEC(CanadianElectricalCode)orthewiringconstructionstandardsofthecountries or regions where wiring is laid. Please follow the procedure below.• WhenVnetcables(10BASE-2),Vnet/IPcables,ESBbuscablesorGPSconnectioncables

areconnectedoutsidethecabinet,useDivision2wiring.

• WhenfieldwiringtoI/Omodules(includingterminalblocks,terminalboards,etc.)islaidoutsidethecabinet,useDivision2wiring.

• WhenanALR111,ALR121,ALE111,S2EN402orS2EN404CommunicationModuleisconnected,useDivision2wiring.

IMPORTANT(1) Attaching or removing a cable, a fuse or a card

In the system in operation, never attach or remove a cable, a fuse or a card in a explosive atmosphere.

(2) Product maintenance When product maintenance is carried out for the system in operation, never attach or remove the product in a explosive atmosphere.

<English> WARNING-EXPLOSIONHAZARD- DONOTDISCONNECTWHILECIRCUITISLIVEUNLESSAREAISKNOWNTOBENON-HAZARDOUS.

<French> AVERTISSEMENT-RISQUED’EXPLOSION.NEPASDE’BRANCHERTANTQUELECIRCUITESTSOUSTENSION,ÁMOINSQU’ILNES’AGISSED’UNEMPLACEMENTNONDANGEREUX.

June 30, 2017-00

Page 29: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-6

TI 32S01J30-01E

Parameters in NI Device Connection Since giving and receiving energy affects NI properties, parameters display is necessary for NI device connection to ensure the properties. To display parameters, NI devices are divided into one that gives energy and the other that receives energy.

Power Supply

+

-

Lc

Cc LiCi

A

B

Device that gives energy(The source device)

Device that receives energy(The load device)

F020102E.ai

Displayed parametersVoc: maximum open-circuit output voltageIsc: maximum short-circuit output current Ca: maximum allowable capacitanceLa: maximum allowable inductanceCc: capacitance of the external wiring (circuit) cableLc: inductance of the external wiring (circuit) cable

Displayed parametersVmax: maximum input voltageImax: maximum input currentCi: maximum internal capacitanceLi: maximum internal inductance

Figure Connection of Non-Incendive Devices and Associated Parameters

Parameters of the Device which Gives EnergyVoc:maximumopen-circuitoutputvoltage

Maximum voltage developed at the open terminal (part) when the Non-Incendive (NI) circuit is open

Isc: maximum short-circuit output current MaximumcurrentwhichflowswhentheNIisshortcircuitedandearthfaultoccurs

Ca: maximum allowable capacitance Maximum capacitance that can be connected to the NI circuit

La: maximum allowable inductance Maximum inductance that can be connected to the NI circuit

Cc: capacitance of the external wiring (circuit) cableLc: inductance of the external wiring (circuit) cable

Jun. 18, 2008-00

Page 30: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-7

TI 32S01J30-01E

Parameters of the Device which Receives EnergyVmax:maximuminputvoltage

Maximum voltage to maintain the NI properties of the device Imax: maximum input current

Maximum current to maintain the NI properties of the device Ci: maximum internal capacitance

Maximum internal capacitance of the devices that are considered to be connected to the NI circuit (the external wiring) when the load device is connected to the NI circuit (the external wiring)

Li: maximum internal inductance Maximum internal inductance of the devices that are considered to be connected to the NI circuit (the external wiring) when the load device is connected to the NI circuit (the external wiring)

How to Compare Parameters The following shows how to compare parameters when the device that gives energy and the device that receives energy are connected. If the parameters satisfy the following conditions, a FM NI explosion-proof device can be connected in a general wiring. If not, the wiring should be installedtoconformtoNEC(NationalElectricalCode:ANSI/NFPA-70)oranexplosion-proofwiringdefinedintherelevantcountry.

Devicethatgivesenergy DevicethatreceivesenergyVoc ≤ VmaxIsc ≤ ImaxCa ≥ summation of Ci in the device which

receives energy + summation of capacitance Cc in the external wiring

La ≥ summation of Li in the device which receives energy + summation of inductance Lc in the external wiring

Jun. 18, 2008-00

Page 31: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-8

TI 32S01J30-01E

Example Asanexample,weshowthecasewhereSAI143I/Omodule,apowerinputmoduleandEJA,a differential pressure transmitter of Yokogawa Electric Corporation are connected. EJA is connectedtocircuitofSAI143via100mcable,andinstalledinClassI,Division2hazardousarea.

Power Supply

Lc

Cc LiCi

Device that gives energy(The source device)

Device that receives energy(The load device)

F020103E.ai

Hazardous area (Class I, Division 2)

<SAI143> <Differential pressure transmitter EJA>

The defined parameters have the following values.(Voc) = 26.4 V(Isc) = 26 mA(Ca) = 0.13 μF(La) = 10 mHand,(Cc) = 200 pF/m 100 m = 0.0002 μF 100 = 0.02 μF(Lc) = 0.66 μH/m 100 m = 0.00066 mH 100 = 0.066 mH

therefore, Voc = 26.4 V < Vmax = 30 V Isc = 26 mA < Imax = 165 mA Ca = 0.13 μF > Ci + Cc = 0.0425 μF La = 10 mH > Li + Lc =0.796 mH

As the results above meet the combinational conditions, we can conclude that a field wiring can be installed in accordance with a general wiring construction.

(Vmax) = 30 V(Imax) = 165 mA(Ci) = 0.0225 μF(Li) = 0.73 mH

+

-

+

-

Figure Connection of SAI143 and EJA

Table Cable Parameter (*1)

Model Lc (μH/m)

Cc (pF/m) Remarks

YCB141 — — (*2)

YCB301 — — (*2)

KS1 1.50 110

AKB331 1.50 110

AKB651 — — (*2)

AKB131 — — (*2)

AKB132 — — (*2)

AKB135 — — (*2)

AKB136 — — (*2)

AKB161 — — (*2)

AKB611 2.00 200

AKB162 — — (*2)

*1: TheseparametersareappliedtoallmodesofeachmodelifthemodeisnotspecifiedintheRemarks.*2: WiringsmustcomplywithNEC(NationalElectricalCode:ANSI/NFPA-70)ortheregulationsoftherelevantcountry.

Oct. 25, 2016-00

Page 32: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-9

TI 32S01J30-01E

Example of Connection

Connecting a ProSafe-RS Device and a Device Installed in Division 2

<Hazardous area Class I, Division 2> <Non-hazardous area>

Cabinet

SSC10D SEC401

SSB401+T BranchSNB10D

Signal cable

~

SEA4D

Conduit wiring

F020104E.ai

Devices directly connected to a hazardous area must be NI standard compliant devices. Devices that are not directly connected to a hazardous area do not need to be standard compliant.

Explosion-proof wiring can be installed for devices that do not indicate electrical parameters.General wiring can be installedfor devices that indicate electrical parameters according to the results from comparing the parameters.

AEP7D

Figure Example of Connection (Flameproof Wiring)

• Connecttoafielddeviceinaccordancewithelectricalparameterdefinitionsofeachdevice.

• Towirethedevicesforwhichelectricalparametersarenotdefined,NEC(NationalElectricalCode:NFPA-70)orexplosion-proofwiring(suchasconduitwiring)definedineachcountryshould be installed.

Apr. 1, 2013-00

Page 33: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-10

TI 32S01J30-01E

Installing a ProSafe-RS device and a Device in Division 2<Hazardous area Class I, Division 2> <Non-hazardous area>

F020105E.ai

Cabinet

YNT522D

YNT522D

V net

V net

SSC10D SEC401

SSB401+T Branch

SNB10D

Signal cable

SEA4D

Conduit wiring

AEP7D

Conduit wiring

100 V AC Power supply220 V AC Power supply or24V DC Power supply

Grounding for explosion protection(based on NEC or laws defined in each country)

A keyed metalcabinet approved byapproval authoritiesshould be selected for a cabinet installedin Division 2.

Figure Example of Connection (Installation in Division 2) for V net

• Connecttoafielddeviceinaccordancewithelectricalparameterdefinitionsofeachdevice.

• Towirethedevicesforwhichelectricalparametersarenotdefined,NEC(NationalElectricalCode:NFPA-70)orexplosion-proofwiring(suchasconduitwiring)definedineachcountryshould be installed.

Apr. 1, 2013-00

Page 34: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-11

TI 32S01J30-01E

<Hazardous area Class I, Division 2>

<Non-Hazardous area>

F020107E.ai

Cabinet

Cabinet

Vnet/IP Bus1Bus2

SNT10D

Fiber-optic cable

SNT501 SNT401

L2SW for Bus1

SSB401+T Branch

SNB10D

SEA4D SEA4D

AEP7DAEP7D

SSB401+T Branch

SEC401

SSC60D

SNB10D

L2SW for Bus2

Conduit wiring

100 V AC Power supply220 V AC Power supply

or24 V DC Power supply

Conduit wiring

Fiber-optic cable orConduit wiring

L2SW: Layer 2 switch

Figure Example of Connection (Installation in Division 2) for V net/IP

Apr. 1, 2013-00

Page 35: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-12

TI 32S01J30-01E

2.2 Type “n”Type “n” is a construction to enhance safety where spark, arc or high surface temperature is not causedinanormaloperationandisavoidedunderdefinedconditionssuchasoverload.

Complied Standards TheProSafe-RSsafetyunit,safetynodeunit,I/Omodulesandopticalrepeatercomplywiththefollowing standards.

ATEX Type “n” [Explosion-proofspecifications](*1)

II3GExnAIICT4GcX(*2)(*5) II3GExnAnCIICT4GcX(*3)(*5) II3(1)GExnA[iaGa]IICT4Gc(*4)

[Compliedstandard] EN 60079-0:2012+A11:2013 EN 60079-15:2010 (for24VDCpowersupply)

ProSafe-RS devices and an optical repeater can be installed in Zone 2 hazardous area if they areplacedinakeyedcabinet(*6)withprotectionratingIP54orhigher.TheI/OmodulecanbeconnectedtoanintrinsicsafetyfielddeviceinstalledinZone0,Zone1andZone2hazardousarea using a safety barrier. In addition, it is possible to connect ProSafe-RS devices installed in anon-hazardousareaandanintrinsicsafetyfielddeviceinstalledinZone0,Zone1andZone2hazardous area using a safety barrier.Note: Regardingthelatestconformitystandardforeachmodel,refertothegeneralspecifications.

*1: Thetrailing“X”insymbolsindicatesspecificconditionsofuse.*2: Applied for products complied with Type “n”, except for SSC10, SSC50, SSC57, SSC60, S2SC70,SNB10D,SBD2D,

SBD3D,SBD4D,S2BN4D,andS2BN5D.*3: Applied for the below products. SSC10, SSC50, SSC57, SSC60, S2SC70,SNB10D,SBD2D,SBD3D,andSBD4D*4: AppliedforS2BN4DandS2BN5D.S2BN5DstyleS1cannotbeinstalledinthehazardousarea.*5: “Type of protection” of the below products is indicated together with modules installed in. SSC10, SSC50, SSC57, SSC60, S2SC70,SNB10D,andSNT10D*6: Cabinet

IfaProSafe-RSdeviceinstalledinanon-hazardousareaisconnectedtoafielddeviceinstalledinahazardousarea,itmustbeplaced in a keyed metal cabinet.

IECEx Type “n” [Explosion-proofspecifications]

ExnA[iaGa]IICT4Gc(*1) Ex nA IIC T4 Gc (*2)

[Compliedstandard] IEC 60079-0:2011 IEC 60079-15:2010

*1: AppliedforS2BN5D.S2BN5DstyleS1cannotbeinstalledinthehazardousarea.*2: AppliedforproductscompliedwithIECExType“n”,exceptforS2BN5D.

Apr. 26, 2017-00

Page 36: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-13

TI 32S01J30-01E

Precautions Refer to IM 32Q01J30-31E for the installation and the precaution for Type “n” compliant devices.

Specific conditions of use• Theequipmentshallonlybeusedinanareaofnotmorethanpollutiondegree2,asdefined

in IEC 60664-1.

• Theequipmentshallbeinstalledinanenclosurethatprovidesadegreeofprotectionnotless than IP54 in accordance with IEC 60079-15.

• Transientprotectionthatissetatalevelnotexceeding119Vd.c.shallbeprovidedatthesupply terminals to the equipment.

• Theequipmentshallbeusedwithin-10%/+20%ofspecifiedinput24VDCwithaddingripplerate1%p-pmaximumatthepowersupplyterminals.

Installation• Theequipmentshallbeinstalledandusedwithintheirratings.

• AllequipmentandwiringinhazardousareasshallbeinstalledinaccordancewithIEC/EN60079-14 and related local electrical codes and the installation shall also comply with the appropriate requirements for non-hazardous areas.

• InstructionsprovidedinGS(Generalspecifications),TI(TechnicalInformationofInstallationGuidance)and/orIM(User’sManuals)shallbeobserved.

• Theinstallationshallbecarriedoutonlybyqualifiedpersonnelwhosetraininghasincludedinstruction on the type of protection and installation practices, relevant rules and regulations and general principles of area classification.

• ThedegreeofprotectionnotlessthanIP54shallbemaintainedatcableentriesintothecabinet.

• Itmustbeobservedduringtheinstallationthattheventingslotsoftheequipmentarenotblocked off by cable parts, fixing accessories etc.

• Screwsofterminalsforfieldwiringconnectionsshallbetightenedwithspecifiedtorquevalues.

• Oncompletionoftheinstallationandpriortofirstuse,initialinspectionoftheequipmentandinstallationshallbecarriedoutinaccordancewithIEC/EN60079-17.

• Abidebythefollowingguidancesoastoensurethesafetyandperformance.

- Make sure that all the empty slots in the cabinet should be properly covered with attached caps.

- Make sure that all the cables are rigidly fixed in the cabinet.

Oct. 25, 2016-00

Page 37: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-14

TI 32S01J30-01E

Maintenance and Repair• Inspectionsandmaintenanceoftheequipmentandinstallationsshallbecarriedoutonlyby

qualifiedpersonnelandinaccordancewithIEC/EN60079-17.

• Repair,overhaul,reclamationoftheequipmentshallbecarriedoutonlybyqualifiedpersonnelandinaccordancewithIEC/EN60079-19.

• Repairsoftheequipmentshallbecarriedoutonlybytrained,experienced,skilled,knowledgeableand/orsupervisedpersonnel,orbytheserviceengineersrecognizedbyYokogawa. Otherwise, the type of protection may be invalidated.

• Modificationsshallnotbemadetotheequipmentwhichareoperatedinhazardousareas.

WARNINGWHENANEXPLOSIVEATMOSPHEREISPRESENT,DONOTOPENTHECABINETWHILETHEEQUIPMENTAREENERGIZED.

WARNINGWHENANEXPLOSIVEATMOSPHEREISPRESENT,DONOTREMOVEORREPLACETHEFUSEWHENENERGIZED.

WARNINGWHENANEXPLOSIVEATMOSPHEREISPRESENT,DONOTSEPARATETHECONECTIONSWHENENERGIZED.

Oct. 25, 2016-00

Page 38: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-15

TI 32S01J30-01E

Type “n” Compliant ProductsThefigurebelowisanexampleoftheconfigurationofType“n”compliantproductsthatcanbeinstalled in hazardous areas. See the table “the list of Type “n” compliant products” described in Appendix for detail.

F020201E.ai

<Hazardous area Zone 2> <Non-hazardous area>

Cabinet

YNT522D

YNT522D

Fiber-optic cable

V net

V net

SSC10D SEC401

SSB401+ T Branch SNB10D

Signal cable

SEA4D

AEP7D

24 V DC power supplyGrounding(based on IEC/EN60079-14 and the rules of each country or region)

*2

*2

*1 *2

Safety Barrier

Type “n” device

Intrinsic safety device

*1: Explosion-proofwiringforintrinsicallysafecircuitsthatisdefinedinIEC/EN60079-14,IEC/EN60079-25andtherules/standardsof each country or region.

*2: Explosion-proofwiringfortype”n”equipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion.

Figure Example of Type “n” Configuration for V net

Oct. 25, 2016-00

Page 39: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-16

TI 32S01J30-01E

F020205E.ai

<Hazardous area Zone 2>

<Non-Hazardous area>

Cabinet

Cabinet*1 *1

Vnet/IP Bus1Bus2

SNT10D

Fiber-optic cable

SNT501 SNT401

L2SW for Bus1

L2SW: Layer 2 switch

SNB10D

SEA4D

AEP7D

SEA4D

SSB401+T Branch

SSB401+T Branch

SEC401

SSC60D

SNB10D

L2SW for Bus2

*1

24 V DC Power supply

*1*1

Type “n” deviceType “n” device

AEP7D

*1: Explosion-proofwiringfortype”n”equipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion.

Figure Example of Type “n” Configuration for Vnet/IP

Apr. 26, 2017-00

Page 40: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-17

TI 32S01J30-01E

<Hazardous area Zone 2>

<Non-hazardous area>

F030207.ai

Cabinet

L2SW

S2SC70D

SNB10D

SSB401

L2SW

Cabinet

SNT401

N-IOI/O Module

FIOI/O Module

Fiber-optic cable

S2BN1D

S2BN1D

S2NN30D

S2EN501

SEC401

Type “n” Explosion protection equipmentType “n” Explosion protection equipment

Transient Protection

Transient Protection

*1

*1

*1

24 V DCPower Supply

(*2)Transient Protection

(*2)

Transient Protection

(*2)

(*2)

*1

N-IOI/O Module

24 V DCPower Supply

24 V DCPower Supply

*1 *1

*1: Explosion-proofwiringforType“n”equipmentthatisdefinedinEN/IEC60079-14andtherules/standardsofeachcountryorregion.

*2: Transientprotectionshallbeprovidedthatissetatalevelnotexceeding119VDCatthesupplyterminalofS2BN1D,S2BN4D,andS2BN5Dtotheequipment.

Figure Example of Typen “n” Configuration for Vnet/IP

Apr. 26, 2017-00

Page 41: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-18

TI 32S01J30-01E Apr. 26, 2017-00

Wiring of Type “n” DevicesWiringshouldbeinstalledtoconformtoIEC/EN60079-14andtherules/standardsofeachcountryorregion.Afterwiring,checkitoutaccordingtothechecklistinIEC/EN60079-17.

Example of a Connection

Connecting a ProSafe-RS Device and a Device Installed in Zone 2

<Hazardous area Zone 2> <Non-hazardous area>

Cabinet

SSC10D SEC401

SSB401+T BranchSNB10D

Signal cable

SEA4D

*2

F020203E.ai

Use a cabinet meeting the requirementsof EN 61010.

AEP7D

Type “n” deviceIntrinsic safetydevice

~

*1

SafetyBarrier

*2

*1: Explosion-proofwiringforintrinsicallysafecircuitsthatisdefinedinIEC/EN60079-14,IEC/EN60079-25andtherules/standardsof each country or region.

*2: Explosion-proofwiringfortype“n”equipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion.

Figure Example of Connection

Page 42: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-19

TI 32S01J30-01E

Installing ProSafe-RS and Associated Devices in Zone 2

F020204E.ai

<Hazardous area Zone 2> <Non-hazardous area>

Cabinet

YNT522D

YNT522D

Fiber-optic cable

V net

V net

SSC10D SEC401

SSB401+ T Branch SNB10D

Signal cable

SEA4D

AEP7D

24 V DC power supplyGrounding(based on IEC/EN60079-14 and the rules of each country or region)

*2

*2

*1 *2

Safety Barrier

Type “n” device

Intrinsic safety device

A keyed metal cabinet of protection rating IP54 or higher should be selected for a cabinet installed in Zone 2.

*1: Explosion-proofwiringforintrinsicallysafecircuitsthatisdefinedinIEC/EN60079-14,IEC/EN60079-25andtherules/standardsof each country or region

*2: Explosion-proofwiringfortype”n”equipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion.

Figure Example of Connection (Installation in Zone 2) for V net

Apr. 26, 2017-00

Page 43: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

2. Explosion Protection Instrumentation in Zone 2/Division 2 2-20

TI 32S01J30-01E

<Hazardous area Zone 2>

<Non-Hazardous area>

F020206E.ai

Cabinet

Fiber-optic cable

Cabinet

Vnet/IP Bus1Bus2

SNT10D SNT501 SNT401

L2SW for Bus1

L2SW: Layer 2 switch

SSB401+T Branch

SNB10D

SEA4D SEA4D

SSB401+T Branch

SEC401

SSC60D

SNB10D

L2SW for Bus2

*1 *1

AEP7DAEP7D

*1

24 V DC Power supply

*1

Type “n” device

*1

Type “n” device

*1: Explosion-proofwiringfortype”n”equipmentthatisdefinedinIEC/EN60079-14andtherules/standardsofeachcountryorregion.

Figure Example of Connection (Installation in Zone 2) for Vnet/IP

Apr. 26, 2017-00

Page 44: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

3. Intrinsic Safety Explosion Protection Instrumentation 3-1

TI 32S01J30-01E

3. Intrinsic Safety Explosion Protection Instrumentation

Intrinsic safety explosion protection is an electric circuit and a construction, which made so as not to ignite to gas by controlling the energy of electric circuit, if sparks, arc, and heat occur at the time of normal operating and an accident (short-circuit, earth fault, burnout). Intrinsic safety explosion protection equipments include intrinsic safety equipments and equipments related with intrinsic safety. Intrinsic safety equipments are able to be used in hazardous area. Equipments related with intrinsic safety are set up in non-hazardous area, and is connected with intrinsic safety equipment.

Nov. 27, 2015-00

Page 45: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

3. Intrinsic Safety Explosion Protection Instrumentation 3-2

TI 32S01J30-01E

3.1 Intrinsic Safety Explosion Protection Instrumentation Using Barrier base plates

3.1.1 Intrinsic Safety Explosion Protection of ATEX Standard

Base plate for barrier (S2BN5D)Baseplateforbarrier(S2BN5D)iscompliedwithI.S.explosionprotectionstandard.P+F’sI.S.barriers can be connected to the I. S. equipment installed in the hazardous area with explosion-proof wiring.

Explosion-proof Specifications and Complied Standard[Explosion-proof specifications]

II 3(1) G Ex nA [ia Ga] IIC T4 Gc II (1) D [Ex ia Da] III C I (M1) [Ex ia Ma] I

[Complied standard] EN 60079-0:2012+A11:2013 EN 60079-11:2012

Wiring of Intrinsic Safety Explosion ProtectionAn intrinsic safety circuit must be isolated from non-intrinsic safety circuit. Wiring should be prepared in accordance with EN 60079-14, or the standard of the country and the area in which it isset.Inregardstothefurtherwiringthanthebaseplateforbarrier(S2BN5D),takenoticethatitshould be an intrinsic safety circuit. The wiring in cabinet should keep the distance to non-intrinsic safety circuit.After setting, check the wiring according to the checklist described in EN 60079-17.

Parameter of Intrinsic SafetyPlease refer to the P+F’s instruction manual of I.S. barriers installed in the base plate for barrier (S2BN5D)fortheparameterofIntrinsicSafety.

Apr. 26, 2017-00

Page 46: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

3. Intrinsic Safety Explosion Protection Instrumentation 3-3

TI 32S01J30-01E

3.1.2 Intrinsic Safety Explosion Protection of IEC Standard

Base plate for barrier (S2BN5D)Baseplateforbarrier(S2BN5D)iscompliedwithI.S.explosionprotectionstandard.P+F’sI.S.barriers can be connected to the I. S. equipment installed in the hazardous area with explosion-proof wiring. [Explosion-proof specifications] Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] III C [Ex ia Ma] I

[Complied standard] IEC 60079-0:2011 IEC 60079-11:2011

Wiring of Intrinsic Safety Explosion ProtectionAn intrinsic safety circuit must be isolated from non-intrinsic safety circuit. Wiring should be prepared in accordance with IEC 60079-14, or the standard of the country and the area in which itisset.Inregardstothefurtherwiringthanthebaseplateforbarrier(S2BN5D),takenoticethatit should be an intrinsic safety circuit. The wiring in cabinet should keep the distance to non-intrinsic safety circuit.After setting, check the wiring according to the checklist described in IEC 60079-17.

Parameter of Intrinsic SafetyPlease refer to the P+F’s instruction manual of I.S. barriers installed in the base plate for barrier (S2BN5D)fortheparameterofIntrinsicSafety.

Nov. 27, 2015-00

Page 47: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

3. Intrinsic Safety Explosion Protection Instrumentation 3-4

TI 32S01J30-01E

3.1.3 Intrinsic Safety Explosion Protection of US (FM) Standard

S2BN5D base plate for barrierS2BN5DbaseplateforbarriercanbeconnectedtotheI.S.equipmentinstalledinthehazardousareawithexplosion-proofwiringandcanbeinstalledinDivision2bymountinginakeyedmetalcabinet approved by approval authorities. Please refer to the instruction manual of P+F I.S. barriers for installation of I.S. barriers.

Explosion-proof Specifications and Complied Standard[Explosion-proof specifications] Intrinsically Safe Associated Apparatus for Class I, II, III Division I Groups A, B, C, D, E, F and G Intrinsically Safe Associated Apparatus Class I Zone 0, Group IIC, Temperature Class T4 Intrinsically Safe Associated Apparatus Zone 20, Group IIIC

[Complied standard] Class 3600:2011 Class 3610:2010 ANSI/ISA-60079-0 (12.00.01)-2013 ANSI/ISA-60079-11 (12.02.01)-2014

Wiring of Intrinsic Safety Explosion ProtectionAn intrinsic safety circuit must be isolated from non-intrinsic safety circuit. Installation and wiring of Intrinsic Safety Explosion Protection shall be carried out in according with “Appendix 6. US (FM)NI/Canada(FM)NIControlDrawingforS2BN5D”.

Parameter of Intrinsic SafetyPleaserefertotheP+F’sinstructionmanualofI.S.barriersinstalledinS2BN5Dfortheparameterof Intrinsic Safety.

Oct. 25, 2016-00

Page 48: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

3. Intrinsic Safety Explosion Protection Instrumentation 3-5

TI 32S01J30-01E

3.1.4 Intrinsic Safety Explosion Protection of Canada (FM) Standard

S2BN5D base plate for barrierS2BN5DbaseplateforbarriercanbeconnectedtotheI.S.equipmentinstalledinthehazardousareawithexplosion-proofwiringandcanbeinstalledinDivision2bymountinginakeyedmetalcabinet approved by approval authorities. Please refer to the instruction manual of P+F I.S. barriers for installation of I.S. barriers.

Explosion-proof Specifications and Complied Standard[Explosion-proof specifications] Intrinsically Safe Associated Apparatus for Class I, II, III Division I Groups A, B, C, D, E, F and G Intrinsically Safe Associated Apparatus Class I Zone 0, Group IIC Intrinsically Safe Associated Apparatus Zone 20, Group IIIC

[Complied standard] CAN/CSA-C22.2 No. 60079-0:11 CAN/CSA-C22.2 No. 60079-11:14

Wiring of Intrinsic Safety Explosion ProtectionAn intrinsic safety circuit must be isolated from non-intrinsic safety circuit. Installation and wiring of Intrinsic Safety Explosion Protection shall be carried out in according with “Appendix 6. US (FM)NI/Canada(FM)NIControlDrawingforS2BN5D”.

Parameter of Intrinsic SafetyPleaserefertotheP+F’sinstructionmanualofI.S.barriersinstalledinS2BN5Dfortheparameterof Intrinsic Safety.

Oct. 25, 2016-00

Page 49: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

3. Intrinsic Safety Explosion Protection Instrumentation 3-6

TI 32S01J30-01E

3.2 Intrinsic Safety Explosion Protection Instrumentation Using Barriers

Category of BarriersClassifiedroughly,barriersincludesZenerbarriersandinsulatingbarriers(intrinsicsafetybarriers). Select the best one as your system, with the knowledge of their future.

(1) Feature of Zener barriers ZenerbarrierhasasimpleconstructionwhichconsistsofjustZenerDiodeandresistance. As the circuit of hazardous area and non-hazardous area are not insulated, they request

the single point ground by the bus bar of Zener barriers, so as not to be created the functionally unfavorable ground loop by double point ground. Moreover, in most countries, it is impossible to ground circuits in hazardous area.

A power supply for barrier is not required, because Zener barriers carry out the function for securityjustwithZenerDiodeandresistance.

(2) Feature of insulating barriers On the other hand, insulating barriers does not request intrinsic safety ground because

the place between input and output of them is insulated. It is possible to ground circuits in hazardousareaandusethem(singlepointground).However,apowersupplyforbarrierisadditionally required.

Considerations for Selection of Barrier Hereisageneralexplanationabouttheselectionofbarrier.Ontheoccasionofimplementingintrinsic safety Explosion Protection instrumentation, select a barrier according to the manufacture’sspecificationsandestimateswiththeequipment.

(1) Approved standard Make sure the barrier has the approved standard which is required for the installation site.(2) Cost Compared Zener barriers to insulating barriers about the general cost of the main unit only

per a channel, the approximate proportion are 1 to 2. Also, insulating barriers request a power supply.

(3) Volume(dimensions) Dimensionsmayinfluencethenumberofcabinetinwhichthebarrierisset.Compared

Zener barriers to insulating barriers about the size per a general channel, the approximate proportion are 1 to 2.

(4) Difficultyofwiring,necessityofinsulatinghazardousareacircuit Zener barriers always need intrinsic safety ground, and most model of them have the

construction grounded through the bus bar. All the circuit on the same bus bar in hazardous area and non-hazardous area are grounded to the same electric potential. Moreover, in mostcountries,circuitsinhazardousareaneedwithstandvoltageof500Vrms.Therefore,itis impossible to ground circuits in hazardous area and use them. Insulating barriers impose no restrictions like this, so it is possible to ground circuits in hazardous area and use them (singlepointground).However,apowersupplyforbarrierisadditionallyrequired.

Oct. 25, 2016-00

Page 50: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

3. Intrinsic Safety Explosion Protection Instrumentation 3-7

TI 32S01J30-01E

(5) Failure rate The construction of Zener barriers is simple, because they carry out the function for security

justwithZenerDiodeandresistance.Ontheotherhand,insulatingbarriersconsistofvarious parts, because they have the function of insulation and energy restriction. Therefore, the failure rate of insulating barriers is generally higher than that of Zener barriers. In Zener barriers, problems are usually solved by replacement and, in insulating barriers by modification.

(6) Accuracy, response In general, Zener barriers have advantages about accuracy and response, because

insulating barriers usually have more complex signal path than Zener barriers.(7) Withstand voltage Withstand voltage is a rating which only insulating barriers have. Most of the models have

250VormoreAC/DC,sothere’salmostnoproblematthetimeofinstrumentation.(8) Security rating Security rating indicates the scale of energy that can be occurred in hazardous area of

barrierinthecaseoftheaccident.Itisusuallydescribedbythesignage,suchasUo=nV,Io=nmA,Po=nW,Co=nµF,Lo=nmH(Um=nVrmsorDC:onlyinsulatingbarriers).

(In FM standard, it is called entity parameter, including the parameter of (10), and is describedsuchasVoc=nV,Isc=nmA,Ca=nµF,La=nmH).

(9) Permissible cable parameter Permissible cable parameter indicates the scale (capacity, inductance) of hazardous area

circuit (including cables) which can be connected to barriers. It is regulated by a barrier and a kind of gases. It is usually described by group (ex. IIC etc.=a kind of gases), n µF (capacity),nmHornµH/Ω(inductanceorL/Rratio).

(10) Voltageinnon-hazardousarea InregardstoZenerbarriers,Vwkg(maximumworkingvoltage)andVmax(maximum

permissible voltage) are regulated. In regards to insulating barriers, regulation of voltage is for power supply rating only, but the use conditions of circuit in non-hazardous area are different by models.

(11) Influencebyresistancevaluebetweeninputandoutput This is a matter of only Zener barriers. As resistance and fuse exist between terminals of

input and output in a barrier, in regards to an application that pass an electric current, it is necessary to take account of voltage drop inside the barrier. Moreover, in some application, itisnecessarytotakeaccountofDiodecurrentleakage(usuallyseveralµA).

Oct. 25, 2016-00

Page 51: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

3. Intrinsic Safety Explosion Protection Instrumentation 3-8

TI 32S01J30-01E Oct. 25, 2016-00

Wiring of Intrinsic Safety Explosion ProtectionAn intrinsic safety circuit must be isolated from non-intrinsic safety circuit.Wiring should be prepared in accordance with IEC 60079-14, NEC (National Electrical Code : NFPA-70), or the standard of the country and the area in which it is set. The wiring in cabinet should keep the distance to non-intrinsic safety circuit.After setting, check the wiring according to the checklist described in IEC 60079-17.An intrinsic safety circuit of barrier is indicated by the following ratings.

Maximum voltage of intrinsic safety circuit UoMaximum current of intrinsic safety circuit IoMaximum electricity of intrinsic safety circuit PoPermissible inductance of intrinsic safety circuit LoPermissible capacitance of intrinsic safety circuit Co

As a combination of intrinsic safety circuits connected with barriers and wiring, it is necessary to meet the following conditions to keep the intrinsic safety performance.

Uo ≤ UiIo ≤ IiPo ≤ PiLo ≥ Li+LwCo ≥ Ci+Cw

Page 52: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

3. Intrinsic Safety Explosion Protection Instrumentation 3-9

TI 32S01J30-01E Oct. 25, 2016-00

Intrinsic safety circuit should consist of barriers to meet these conditions of permissible voltage, current, and electricity, and should be wired so that inductance and capacitance of its wiring doesn’t exceed its permissible value.

Device that gives energy(The source energy)

Device that receives energy(The load device)

Intrinsic safety circuit

Intrinsic safety equipment

Non-intrinsic safety circuitBarrierPart for security

Uo:Io:Po:Lo:Co:

Maximum voltage of intrinsic safety circuitMaximum current of intrinsic safety circuitMaximum electricity of intrinsic safety circuitPermissible inductance of intrinsic safety circuitPermissible capacitance of intrinsic safety circuit

Ui:Ii:Pi:Li:Ci:

Permissible voltage of intrinsic safety circuitPermissible current of intrinsic safety circuitPermissible electricity of intrinsic safety circuitInternal inductanceInternal capacitance

Controller, indicator, recorder

Input/output module

F030201.ai

Figure Composition Used in a Barrier

Page 53: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 1 List of NI Compliant Products App.1-1

TI 32S01J30-01E

Appendix 1. List of NI Compliant Products

Appendix 1.1 US (FM) NI Compliant Products ProSafe-RS US (FM) NI Compliant ProductsTable US (FM) NI Approved Products (1/8)

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

1 Safety Control Units

SSC10S-S2E11SSC10S-S2E11/GPS

Safety Control Units100to120VACpowersupply -20 to 50 °C

SSC10S-S2E21SSC10S-S2E21/GPS

Safety Control Units220to240VACpowersupply -20 to 50 °C (*2)

SSC10S-S2E41SSC10S-S2E41/GPS

Safety Control Units24VDCpowersupply -20 to 50 °C

SSC10S-F2E11SSC10S-F2E11/GPS

Safety Control Units(Withfan,100to120VACpowersupply) -20 to 70 °C

SSC10S-F2E21SSC10S-F2E21/GPS

Safety Control Units(Withfan,220to240VACpowersupply) -20 to 70 °C (*2)

SSC10S-F2E41SSC10S-F2E41/GPS

Safety Control Units(Withfan,24VDCpowersupply) -20 to 70 °C

SSC10D-S2E11SSC10D-S2E11/GPS

DuplexedSafetyControlUnits100to120VACpowersupply -20 to 50 °C

SSC10D-S2E21SSC10D-S2E21/GPS

DuplexedSafetyControlUnits220to240VACpowersupply -20 to 50 °C (*2)

SSC10D-S2E41SSC10D-S2E41/GPS

DuplexedSafetyControlUnits24VDCpowersupply -20 to 50 °C

SSC10D-F2E11SSC10D-F2E11/GPS

DuplexedSafetyControlUnits(Withfan,100to120VACpowersupply) -20 to 70 °C

SSC10D-F2E21SSC10D-F2E21/GPS

DuplexedSafetyControlUnits(Withfan,220to240VACpowersupply) -20 to 70 °C (*2)

SSC10D-F2E41SSC10D-F2E41/GPS

DuplexedSafetyControlUnits(Withfan,24VDCpowersupply) -20 to 70 °C

2 Safety Control UnitsforVnet/IP

SSC50S-S2E1SSC50S-S2E1/ERFI

Safety Control Units100to120VACpowersupply -20 to 40 °C

SSC50S-S2E2SSC50S-S2E2/ERFI

Safety Control Units220to240VACpowersupply -20 to 40 °C (*2)

SSC50S-S2E4SSC50S-S2E4/ERFI

Safety Control Units24VDCpowersupply -20 to 40 °C

SSC50S-F2E1SSC50S-F2E1/ERFI

Safety Control Units(Withfan,100to120VACpowersupply) -20 to 70 °C

SSC50S-F2E2SSC50S-F2E2/ERFI

Safety Control Units(Withfan,220to240VACpowersupply) -20 to 70 °C (*2)

SSC50S-F2E4SSC50S-F2E4/ERFI

Safety Control Units(Withfan,24VDCpowersupply) -20 to 70 °C

SSC50D-S2E1SSC50D-S2E1/ERFI

DuplexedSafetyControlUnits100to120VACpowersupply -20 to 40 °C

SSC50D-S2E2SSC50D-S2E2/ERFI

DuplexedSafetyControlUnits220to240VACpowersupply -20 to 40 °C (*2)

SSC50D-S2E4SSC50D-S2E4/ERFI

DuplexedSafetyControlUnits24VDCpowersupply -20 to 40 °C

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

*2: TheACmainscircuit(220-240VAC)supplyingpowerto220-240VACpowersuppliesmustbesuppliedbyaNeutral-ReferencedSupplyCircuit.

Oct. 25, 2016-00

Page 54: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 1 List of NI Compliant Products App.1-2

TI 32S01J30-01E

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

2 Safety Control UnitsforVnet/IP

SSC50D-F2E1SSC50D-F2E1/ERFI

DuplexedSafetyControlUnits(Withfan,100to120VACpowersupply) -20 to 70 °C

SSC50D-F2E2SSC50D-F2E2/ERFI

DuplexedSafetyControlUnits(Withfan,220to240VACpowersupply) -20 to 70 °C (*2)

SSC50D-F2E4SSC50D-F2E4/ERFI

DuplexedSafetyControlUnits(Withfan,24VDCpowersupply) -20 to 70 °C

SSC57S-S2E1 Safety Control Units 100to120VACpowersupply -20 to 40 °C

SSC57S-S2E2 Safety Control Units 220to240VACpowersupply -20 to 40 °C (*2)

SSC57S-S2E4 Safety Control Units 24VDCpowersupply -20 to 40 °C

SSC57S-F2E1 Safety Control Units (Withfan,100to120VACpowersupply) -20 to 70 °C

SSC57S-F2E2 Safety Control Units (Withfan,220to240VACpowersupply) -20 to 70 °C (*2)

SSC57S-F2E4 Safety Control Units (Withfan,24VDCpowersupply) -20 to 70 °C

SSC57D-S2E1 DuplexedSafetyControlUnits 100to120VACpowersupply -20 to 40 °C

SSC57D-S2E2 DuplexedSafetyControlUnits 220to240VACpowersupply -20 to 40 °C (*2)

SSC57D-S2E4 DuplexedSafetyControlUnits 24VDCpowersupply -20 to 40 °C

SSC57D-F2E1 DuplexedSafetyControlUnits (Withfan,100to120VACpowersupply) -20 to 70 °C

SSC57D-F2E2 DuplexedSafetyControlUnits (Withfan,220to240VACpowersupply) -20 to 70 °C (*2)

SSC57D-F2E4 DuplexedSafetyControlUnits (Withfan,24VDCpowersupply) -20 to 70 °C

SSC60S-S2E1SSC60S-S2E1/ERFI

Safety Control Units100to120VACpowersupply -20 to 40 °C

SSC60S-S2E2SSC60S-S2E2/ERFI

Safety Control Units220to240VACpowersupply -20 to 40 °C (*2)

SSC60S-S2E4SSC60S-S2E4/ERFI

Safety Control Units24VDCpowersupply -20 to 40 °C

SSC60S-F2E1SSC60S-F2E1/ERFI

Safety Control Units(Withfan,100to120VACpowersupply) -20 to 70 °C

SSC60S-F2E2SSC60S-F2E2/ERFI

Safety Control Units(Withfan,220to240VACpowersupply) -20 to 70 °C (*2)

SSC60S-F2E4SSC60S-F2E4/ERFI

Safety Control Units(Withfan,24VDCpowersupply) -20 to 70 °C

SSC60D-S2E1SSC60D-S2E1/ERFI

DuplexedSafetyControlUnits100to120VACpowersupply -20 to 40 °C

SSC60D-S2E2SSC60D-S2E2/ERFI

DuplexedSafetyControlUnits220to240VACpowersupply -20 to 40 °C (*2)

SSC60D-S2E4SSC60D-S2E4/ERFI

DuplexedSafetyControlUnits24VDCpowersupply -20 to 40 °C

SSC60D-F2E1SSC60D-F2E1/ERFI

DuplexedSafetyControlUnits(Withfan,100to120VACpowersupply) -20 to 70 °C

SSC60D-F2E2SSC60D-F2E2/ERFI

DuplexedSafetyControlUnits(Withfan,220to240VACpowersupply) -20 to 70 °C (*2)

SSC60D-F2E4SSC60D-F2E4/ERFI

DuplexedSafetyControlUnits(Withfan,24VDCpowersupply) -20 to 70 °C

S2SC70S-S11 Safety Control Unit 100to120VACpowersupply -20 to 40 °C

Table NI Approved Products (2/8)

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

*2: TheACmainscircuit(220-240VAC)supplyingpowerto220-240VACpowersuppliesmustbesuppliedbyaNeutral-ReferencedSupplyCircuit.

Oct. 25, 2016-00

Page 55: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 1 List of NI Compliant Products App.1-3

TI 32S01J30-01E

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

2 Safety Control UnitsforVnet/IP

S2SC70S-S21 Safety Control Unit 220to240VACpowersupply -20 to 40 °C (*2)

S2SC70S-S41 Safety Control Unit 24VDCpowersupply -20 to 40 °C

S2SC70S-F11 Safety Control Unit (Withfan,100to120VACpowersupply) -20 to 70 °C

S2SC70S-F21 Safety Control Unit (Withfan,220to240VACpowersupply) -20 to 70 °C (*2)

S2SC70S-F41 Safety Control Unit (Withfan,24VDCpowersupply) -20 to 70 °C

S2SC70D-S11 DuplexedSafetyControlUnit 100to120VACpowersupply -20 to 40 °C

S2SC70D-S21 DuplexedSafetyControlUnit 220to240VACpowersupply -20 to 40 °C (*2)

S2SC70D-S41 DuplexedSafetyControlUnit 24VDCpowersupply -20 to 40 °C

S2SC70D-F11 DuplexedSafetyControlUnit (Withfan,100to120VACpowersupply) -20 to 70 °C

S2SC70D-F21 DuplexedSafetyControlUnit (Withfan,220to240VACpowersupply) -20 to 70 °C (*2)

S2SC70D-F41 DuplexedSafetyControlUnit (Withfan,24VDCpowersupply) -20 to 70 °C

3 Safety Node Units

SNB10D-1ESNB10D-1E/CU2NSNB10D-1E/CU2T

NodeUnitforDual-RedundantESBBus100to120VACpowersupply -20 to 70 °C

SNB10D-2ESNB10D-2E/CU2NSNB10D-2E/CU2T

NodeUnitforDual-RedundantESBBus220to240VACpowersupply -20 to 70 °C (*2)

SNB10D-4ESNB10D-4E/CU2NSNB10D-4E/CU2T

NodeUnitforDual-RedundantESBBus24VDCpowersupply -20 to 70 °C

4 Unit for OpticalBusRepeater Module

SNT10D-21EUnitforOpticalESBBusRepeater Module100to120VACpowersupply

-20 to 70 °C

SNT10D-22EUnitforOpticalESBBusRepeater Module220to240VACpowersupply

-20 to 70 °C (*2)

SNT10D-24EUnitforOpticalESBBusRepeater Module24VDCpowersupply

-20 to 70 °C

5 CPU Module SCP401-E1 Processor Module for SSC10 -20 to 70 °C (*3)SCP451-ESCP451-E/ERFI

Processor Module for SSC50 and SSC57 -20 to 70 °C (*4)

SCP461-E1SCP461-E1/ERFI

Processor Module for SSC60 and S2SC70 -20 to 70 °C (*5)

Power supply Module

SPW481-E3SPW481-E3/ERFI

100to120VACInputPowersupplymodule -20 to 70 °C (*3), (*4),

(*5)SPW482-E3SPW482-E3/ERFI

220to240VACInputPowersupplymodule -20 to 70 °C (*2), (*3),

(*4), (*5)SPW484-E3SPW484-E3/ERFI 24VDCInput Power supply module -20 to 70 °C (*3), (*4),

(*5)

S2PW503-S0130 24VDCOutputPowerSupplyUnit (100to240VACinputpowersupply) -40 to 70 °C

S2PW504-S0130 24VDCOutputPowerSupplyUnit (24VDCinputpowersupply) -40 to 70 °C

Table NI Approved Products (3/8)

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

*2: TheACmainscircuit(220-240VAC)supplyingpowerto220-240VACpowersuppliesmustbesuppliedbyaNeutral-ReferencedSupplyCircuit.

*3: For SSC10-F (with fan). -20 to 50°C for SSC10-S (without fan)*4: For SSC50-F and SSC57-F (with fan). -20 to 40°C for SSC50-S and SSC57-S (without fan)*5: For SSC60-F (with fan) and S2SC70-F (with fan). -20 to 40°C for SSC60-S (without fan) and S2SC70-S (without fan)

Oct. 25, 2016-00

Page 56: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 1 List of NI Compliant Products App.1-4

TI 32S01J30-01E

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

6 Coupler Unit AIP504-E3 VnetCouplerUnit -20 to 70 °C (*3)BusCouplerModule

SEC401-E1 ESBBusCouplerModule -20 to 70 °C

SEC402-E1 ESBBusCouplerModule(for 2-Port) -20 to 70 °C

BusInterfaceModule SSB401-E3 ESBBusInterfaceSlaveModule -20 to 70 °C

OpticalESBBusRepeaterModule

SNT401-ESNT401-E/CU1NSNT401-E/CU1T

OpticalESBBusRepeaterMaster Module -20 to 70 °C

SNT411-ESNT411-E/CU1NSNT411-E/CU1T

OpticalESBBusRepeaterMaster Module 5 to 50 km

-20 to 70 °C

SNT421-E3SNT421-E3/CU1NSNT421-E3/CU1T

OpticalESBBusRepeaterMaster Module (for Multimode Fiber) -20 to 70 °C

SNT501-E OpticalESBBusRepeaterSlave Module -20 to 70 °C

SNT511-EOpticalESBBusRepeaterSlave Module 5 to 50 km

-20 to 70 °C

SNT521-E3 OpticalESBBusRepeaterSlave Module (for Multimode Fiber) -20 to 70 °C

N-ESBBusCoupler Module

S2EN402-S0011 N-ESBBusCouplerModule -40 to 70 °C

S2EN404-S0011 N-ESBBusCouplerModule -40 to 70 °C

Node Interface Unit S2NN30D-430013 Node Interface Unit

(100to240VACinputpowersupply) -40 to 70 °C

S2NN30D-440013 Node Interface Unit (24VDCinputpowersupply) -40 to 70 °C

N-ESBBusModule S2EN501-S130 N-ESBBusModule -40 to 70 °C

7 Input/OutputModules

SAI143-SE3SAI143-SE3/K4A00SAI143-SE3/A4S00SAI143-SE3/A4S10SAI143-SE3/A4D00SAI143-SE3/A4D10SAI143-SE3/CCC01

Analog Input Module (4 to 20 mA, 16 channels, module isolation)

-20 to 70 °C

SAI143-SF3SAI143-SF3/PRPSAI143-HE3SAI143-HE3/A4S00SAI143-HE3/A4S10SAI143-HE3/A4D00SAI143-HE3/A4D10SAI143-HE3/CCC01SAI143-HECSAI143-HEC/A4S00SAI143-HEC/A4S10SAI143-HEC/A4D00SAI143-HEC/A4D10SAI143-HEC/CCC01

Analog Input Module (4 to 20 mA, 16 channels, module isolation)withHARTcommunication

-20 to 70 °C

SAI143-HF3SAI143-HF3/PRPSAI143-HFCSAI143-HFC/PRP

Table NI Approved Products (4/8)

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

*3: For SSC10-F (with fan). -20 to 50°C for SSC10-S (without fan)

Apr. 26, 2017-00

Page 57: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 1 List of NI Compliant Products App.1-5

TI 32S01J30-01E

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

7 Input/OutputModules

SAV144-SE3SAV144-SE3/K4A00SAV144-SE3/A4S00SAV144-SE3/A4S10SAV144-SE3/A4D00SAV144-SE3/A4D10SAV144-SE3/CCC01

Analog Input Module (1to5V/1to10V,16channels,moduleisolation)

-20 to 70 °C

SAV144-SF3SAV144-SF3/PRPSAT145-SF3SAT145-SF3/PRP

TC/mVInputModule (16 channels, Isolated Channels) -20 to 70 °C

SAR145-SF3SAR145-SF3/PRP

RTDInputModule (16 channels, Isolated Channels) -20 to 70 °C

SAI533-HE3SAI533-HE3/A4S00SAI533-HE3/A4S10SAI533-HE3/A4D00SAI533-HE3/A4D10SAI533-HE3/CCC01

Analog Output Module (4 to 20 mA, 8 channels, module isolation)

-20 to 70 °C

SAI533-HF3SAI533-HF3/PRPSDV144-SE3SDV144-SE3/B4S00SDV144-SE3/B4S10SDV144-SE3/B4D00SDV144-SE3/B4D10SDV144-SE3/CCC01SDV144-SE3/CCC02SDV144-SECSDV144-SEC/B4S00SDV144-SEC/B4S10SDV144-SEC/B4D00SDV144-SEC/B4D10SDV144-SEC/CCC01SDV144-SEC/CCC02

DigitalInputModule(16 channels, module isolation) -20 to 70 °C

SDV144-SF3SDV144-SF3/PRPSDV144-SFCSDV144-SFC/PRP

DigitalInputModule(16 channels, module isolation) -20 to 70 °C

SDV521-SF3SDV521-SF3/PRPSDV521-SFCSDV521-SFC/PRP

DigitalOutputModule(4 channels, module isolation) -20 to 70 °C

SDV531-SE3SDV531-SE3/D4A00SDV531-SE3/B4S00SDV531-SE3/B4S10SDV531-SE3/B4D00SDV531-SE3/B4D10SDV531-SE3/CCC01SDV531-SE3/CCC02

DigitalOutputModule(8 channels, module isolation) -20 to 70 °C

SDV531-SF3SDV531-SF3/PRP

Table NI Approved Products (5/8)

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

Apr. 26, 2017-00

Page 58: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 1 List of NI Compliant Products App.1-6

TI 32S01J30-01E

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

7 Input/OutputModules

SDV531-LE3SDV531-LE3/B4S00SDV531-LE3/B4S10SDV531-LE3/B4D00SDV531-LE3/B4D10SDV531-LE3/CCC01SDV531-LE3/CCC02SDV531-LECSDV531-LEC/B4S00SDV531-LEC/B4S10SDV531-LEC/B4D00SDV531-LEC/B4D10SDV531-LEC/CCC01SDV531-LEC/CCC02

DigitalOutputModule(8 channels, module isolation, long distance type)

-20 to 70 °C

SDV531-LF3SDV531-LF3/PRPSDV531-LFCSDV531-LFC/PRPSDV53A-SF3SDV53A-SF3/PRP

DigitalOutputModule(8 channels, module isolation) -20 to 70 °C

SDV541-SE3SDV541-SE3/B4S00SDV541-SE3/B4S10SDV541-SE3/B4D00SDV541-SE3/B4D10SDV541-SE3/CCC01SDV541-SE3/CCC02SDV541-SECSDV541-SEC/B4S00SDV541-SEC/B4S10SDV541-SEC/B4D00SDV541-SEC/B4D10SDV541-SEC/CCC01SDV541-SEC/CCC02

DigitalOutputModule(16 channels, module isolation) -20 to 70 °C

SDV541-SF3SDV541-SF3/PRPSDV541-SFCSDV541-SFC/PRPS2MMM843-SS1130 AnalogDigitalI/OModule -40 to 70 °CS2MDV843-0S1130 DigitalI/OModule -40 to 70 °C

ALR111-SE1 Serial Communication Module(RS-232C, 2-port) 0 to 60 °C

ALR121-SE1 Serial Communication Module (RS-422/RS-485,2-port) 0 to 60 °C

ALR121-SEB Serial Communication Module (RS-422/RS-485,2-port) 0 to 70 °C

ALR121-SE3 Serial Communication Module (RS-422/RS-485,2-port) -20 to 70 °C

ALE111-SE1 Ethernet communication Module 0 to 60 °C (*6)ALE111-SE3 Ethernet communication Module -20 to 70 °C (*6)

Table NI Approved Products (6/8)

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

*6: ALE111 supported in R3.02.00 or later can be mounted on S2SC70, SSC60, SSC50 or SSC57.

Apr. 26, 2017-00

Page 59: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 1 List of NI Compliant Products App.1-7

TI 32S01J30-01E

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

8 Terminal Board

SEA4D-0FSEA4D-1FSEA4D-0F/NTRYSEA4D-1F/NTRY

AnalogTerminalBoard(SingleandDual-Redundant,16 channels×2)

-20 to 70 °C

SED2D-0FSED2D-1FSED2D-0F/NTRYSED2D-1F/NTRY

DigitalTerminalBoard(SingleandDual-Redundant, 4 channels×4) -20 to 70 °C

SED3D-AFSED3D-AF/NTRY

DigitalTerminalBoard(SingleandDual-Redundant, 8 channels×4) -20 to 70 °C

SED4D-0FSED4D-1FSED4D-0F/NTRYSED4D-1F/NTRY

DigitalTerminalBoard(SingleandDual-Redundant, 16 channels×2) -20 to 70 °C

SBT4D-0FTerminalboardforTC/mV:DINrailmounttype(SingleandDual-redundant, 16 channels×1)

-20 to 70 °C

SBR4D-0FTerminalboardforRTDinput:DINrailmounttype(SingleandDual-redundant,16 channels×1)

-20 to 70 °C

SBA4D-0FTerminalboardforAnalog:DINrailmounttype(SingleandDual-redundant, 16 channels×1)

-20 to 70 °C

S1BB4D-0F TerminalBoardforAnalog,3-wire:DINrailmounttype -20 to 70 °C

SBD2D-0FTerminalboardforDigitaloutput:DINrailmounttype(SingleandDual-redundant,4channels×1,forSDV521)

-20 to 70 °C

SBD3D-0FSBD3D-AF

TerminalboardforDigitaloutput:DINrailmounttype(SingleandDual-redundant,8channels×1,forSDV53)

-20 to 70 °C

SBD4D-0FTerminalboardforDigital:DINrailmounttype(SingleandDual-redundant, 16channels×1,forSDV144/SDV541)

-20 to 70 °C

9 Power DistributionBoard

AEP7D-1F PrimaryPowerSupplyBusUnit(100to120VACinput) -20 to 70 °C

AEP7D-2F PrimaryPowerSupplyBusUnit(220to240VACinput) -20 to 70 °C (*2)

AEP7D-4F PrimaryPowerSupplyBusUnit(for24VDCinput) -20 to 70 °C

AEPV7D-11F PowerSupplyBusUnit,VerticalType(100to120VACinput) -20 to 70 °C (*7)

AEPV7D-21F PowerSupplyBusUnit,VerticalType(220to240VACinput) -20 to 70 °C (*2) (*7)

AEPV7D-41F PowerSupplyBusUnit,VerticalType(for24VDCinput) -20 to 70 °C (*7)

Fan AIP602 Fan Unit -20 to 70 °C

Table NI Approved Products (7/8)

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

*2: TheACmainscircuit(220-240VAC)supplyingpowerto220-240VACpowersuppliesmustbesuppliedbyaNeutral-ReferencedSupplyCircuit.

*7: For style code S1 and unit revision U:1 or later.

Apr. 26, 2017-00

Page 60: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 1 List of NI Compliant Products App.1-8

TI 32S01J30-01E Apr. 26, 2017-00

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

10 OpticalBusRepeater YNT511D-P41/NL

OpticalBusRepeaterforDual-RedundantBus(10BASE-2Cable)(Upto4kmTransmissionDistance,100to120VACPowerSupply)

0 to 50 °C

YNT511D-P42/NL

OpticalBusRepeaterforDual-RedundantBus(10BASE-2Cable)(Upto4kmTransmissionDistance,220to240VACPowerSupply)

0 to 50 °C (*2)

YNT511D-P44/NL

OpticalBusRepeaterforDual-RedundantBus(10BASE-2Cable)(Upto4kmTransmissionDistance,24VDCPowerSupply)

0 to 50 °C

YNT522D-P11/NL

OpticalBusRepeaterforDual-RedundantBus(10BASE-2Cable)(Upto15kmTransmissionDistance,100to120VACPowerSupply)

0 to 50 °C

YNT522D-P12/NL

OpticalBusRepeaterforDual-RedundantBus(10BASE-2Cable)(Upto15kmTransmissionDistance,220to240VACPowerSupply)

0 to 50 °C (*2)

YNT522D-P14/NL

OpticalBusRepeaterforDual-RedundantBus(10BASE-2Cable)(Upto15kmTransmissionDistance, 24VDCPowerSupply)

0 to 50 °C

PW501 Power Supply Unit(for YNT5,100to120VAC) 0 to 50 °C

PW502 Power Supply Unit(for YNT5,220to240VAC) 0 to 50 °C (*2)

PW504 Power Supply Unit (for YNT5,24VDC) 0 to 50 °C

AIP578OpticalTransceiverUnitforVnetRepeater(ForMax.4kmTransmissionDistance)

0 to 50 °C

AIP591OpticalTransceiverUnitforVnetRepeater(ForMax.15kmTransmissionDistance)

0 to 50 °C

AIP171 TransceiverControlUnitforVnetRepeater 0 to 50 °C

AIP571 ElectricalTransceiverUnitforVnetRepeater 0 to 50 °C

11 BasePlate S2BN1D-130 S2BN1D-130/L S2BN1D-130/T

BasePlatewithdisconnectingterminal -40 to 70 °C

S2BN5D-1210 BasePlateforBarrier -20 to 60 °C

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

*2: TheACmainscircuit(220-240VAC)supplyingpowerto220-240VACpowersuppliesmustbesuppliedbyaNeutral-ReferencedSupplyCircuit.

Table NI Approved Products (8/8)

Page 61: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 1 List of NI Compliant Products App.1-9

TI 32S01J30-01E

Appendix 1.2 Canada (FM) NI Compliant Products

ProSafe-RS Canada (FM) NI Compliant ProductsTable Canada (FM) NI Approved Products (1/4)

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

1 Safety Node Units

SNB10D-1ESNB10D-1E/CU2NSNB10D-1E/CU2T

NodeUnitforDual-RedundantESBBus100to120VACpowersupply -20 to 70 °C

SNB10D-4ESNB10D-4E/CU2NSNB10D-4E/CU2T

NodeUnitforDual-RedundantESBBus24VDCpowersupply -20 to 70 °C

2 Unit for OpticalBusRepeater Module

SNT10D-21EUnitforOpticalESBBusRepeater Module100to120VACpowersupply

-20 to 70 °C

SNT10D-24EUnitforOpticalESBBusRepeater Module24VDCpowersupply

-20 to 70 °C

3 Power supply Module

SPW481-E3SPW481-E3/ERFI

100to120VACInputPowersupplymodule -20 to 70 °C

SPW484-E3SPW484-E3/ERFI 24VDCInput Power supply module -20 to 70 °C

S2PW503-S0130 24VDCOutputPowerSupplyUnit (100to240VACinputpowersupply) -40 to 70 °C

S2PW504-S0130 24VDCOutputPowerSupplyUnit (24VDCinputpowersupply) -40 to 70 °C

4 BusInterfaceModule SSB401-E3 ESBBusInterfaceSlaveModule -20 to 70 °C

OpticalESBBusRepeaterModule

SNT401-EFSNT401-EF/CU1NSNT401-EF/CU1T

OpticalESBBusRepeaterMaster Module -20 to 70 °C

SNT411-EFSNT411-EF/CU1NSNT411-EF/CU1T

OpticalESBBusRepeaterMaster Module 5 to 50 km

-20 to 70 °C

SNT421-E3SNT421-E3/CU1NSNT421-E3/CU1T

OpticalESBBusRepeaterMaster Module (for Multimode Fiber) -20 to 70 °C

SNT501-EF OpticalESBBusRepeaterSlave Module -20 to 70 °C

SNT511-EFOpticalESBBusRepeaterSlave Module 5 to 50 km

-20 to 70 °C

SNT521-E3 OpticalESBBusRepeaterSlave Module (for Multimode Fiber) -20 to 70 °C

Node Interface Unit S2NN30D-430013 Node Interface Unit

(100to240VACinputpowersupply) -40 to 70 °C

S2NN30D-440013 Node Interface Unit (24VDCinputpowersupply) -40 to 70 °C

N-ESBBusModule S2EN501-S130 N-ESBBusModule -40 to 70 °C

Oct. 25, 2016-00

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

Page 62: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 1 List of NI Compliant Products App.1-10

TI 32S01J30-01E

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

5 Input/OutputModules

SAI143-SE3SAI143-SE3/K4A00SAI143-SE3/A4S00SAI143-SE3/A4S10SAI143-SE3/A4D00SAI143-SE3/A4D10SAI143-SE3/CCC01

Analog Input Module (4 to 20 mA, 16 channels, module isolation)

-20 to 70 °C

SAI143-SF3SAI143-SF3/PRPSAI143-HE3SAI143-HE3/A4S00SAI143-HE3/A4S10SAI143-HE3/A4D00SAI143-HE3/A4D10SAI143-HE3/CCC01SAI143-HECSAI143-HEC/A4S00SAI143-HEC/A4S10SAI143-HEC/A4D00SAI143-HEC/A4D10SAI143-HEC/CCC01

Analog Input Module(4 to 20 mA, 16 channels, module isolation)withHARTcommunication

-20 to 70 °C

SAI143-HF3SAI143-HF3/PRPSAI143-HFCSAI143-HFC/PRPSAV144-SE3SAV144-SE3/K4A00SAV144-SE3/A4S00SAV144-SE3/A4S10SAV144-SE3/A4D00SAV144-SE3/A4D10SAV144-SE3/CCC01

Analog Input Module (1to5V/1to10V,16channels,moduleisolation)

-20 to 70 °C

SAV144-SF3SAV144-SF3/PRPSAT145-SF3SAT145-SF3/PRP

TC/mVInputModule (16 channels, Isolated Channels) -20 to 70 °C

SAR145-SF3SAR145-SF3/PRP

RTDInputModule (16 channels, Isolated Channels) -20 to 70 °C

SAI533-HE3SAI533-HE3/A4S00SAI533-HE3/A4S10SAI533-HE3/A4D00SAI533-HE3/A4D10SAI533-HE3/CCC01

Analog Output Module (4 to 20 mA, 8 channels, module isolation)

-20 to 70 °C

SAI533-HF3SAI533-HF3/PRPSDV144-SE3SDV144-SE3/B4S00SDV144-SE3/B4S10SDV144-SE3/B4D00SDV144-SE3/B4D10SDV144-SE3/CCC01SDV144-SE3/CCC02SDV144-SECSDV144-SEC/B4S00SDV144-SEC/B4S10SDV144-SEC/B4D00SDV144-SEC/B4D10SDV144-SEC/CCC01SDV144-SEC/CCC02

DigitalInputModule(16 channels, module isolation) -20 to 70 °C

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

Table Canada (FM) NI Approved Products (2/4)

Apr. 26, 2017-00

Page 63: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 1 List of NI Compliant Products App.1-11

TI 32S01J30-01E

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

5 Input/OutputModules

SDV144-SF3SDV144-SF3/PRPSDV144-SFCSDV144-SFC/PRP

DigitalInputModule(16 channels, module isolation) -20 to 70 °C

SDV521-SF3SDV521-SF3/PRPSDV521-SFCSDV521-SFC/PRP

DigitalOutputModule(4 channels, module isolation) -20 to 70 °C

SDV531-SE3SDV531-SE3/D4A00SDV531-SE3/B4S00SDV531-SE3/B4S10SDV531-SE3/B4D00SDV531-SE3/B4D10SDV531-SE3/CCC01SDV531-SE3/CCC02

DigitalOutputModule(8 channels, module isolation) -20 to 70 °C

SDV531-SF3SDV531-SF3/PRPSDV531-LE3SDV531-LE3/B4S00SDV531-LE3/B4S10SDV531-LE3/B4D00SDV531-LE3/B4D10SDV531-LE3/CCC01SDV531-LE3/CCC02SDV531-LECSDV531-LEC/B4S00SDV531-LEC/B4S10SDV531-LEC/B4D00SDV531-LEC/B4D10SDV531-LEC/CCC01SDV531-LEC/CCC02

DigitalOutputModule(8 channels, module isolation, long distance type)

-20 to 70 °C

SDV531-LF3SDV531-LF3/PRPSDV531-LFCSDV531-LFC/PRPSDV53A-SF3SDV53A-SF3/PRP

DigitalOutputModule(8 channels, module isolation) -20 to 70 °C

SDV541-SE3SDV541-SE3/B4S00SDV541-SE3/B4S10SDV541-SE3/B4D00SDV541-SE3/B4D10SDV541-SE3/CCC01SDV541-SE3/CCC02SDV541-SECSDV541-SEC/B4S00SDV541-SEC/B4S10SDV541-SEC/B4D00SDV541-SEC/B4D10SDV541-SEC/CCC01SDV541-SEC/CCC02

DigitalOutputModule(16 channels, module isolation) -20 to 70 °C

SDV541-SF3SDV541-SF3/PRPSDV541-SFCSDV541-SFC/PRPS2MMM843-SS1130 AnalogDigitalI/OModule -40 to 70 °CS2MDV843-0S1130 DigitalI/OModule -40 to 70 °C

Apr. 26, 2017-00

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

Table Canada (FM) NI Approved Products (3/4)

Page 64: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 1 List of NI Compliant Products App.1-12

TI 32S01J30-01E

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

6 Terminal Board

SEA4D-0FSEA4D-1FSEA4D-0F/NTRYSEA4D-1F/NTRY

AnalogTerminalBoard(SingleandDual-Redundant,16 channels×2)

-20 to 70 °C

SED2D-0FSED2D-1FSED2D-0F/NTRYSED2D-1F/NTRY

DigitalTerminalBoard(SingleandDual-Redundant, 4 channels×4) -20 to 70 °C

SED3D-AFSED3D-AF/NTRY

DigitalTerminalBoard(SingleandDual-Redundant, 8 channels×4) -20 to 70 °C

SED4D-0FSED4D-1FSED4D-0F/NTRYSED4D-1F/NTRY

DigitalTerminalBoard(SingleandDual-Redundant, 16 channels×2) -20 to 70 °C

SBT4D-0FTerminalboardforTC/mV:DINrailmounttype(SingleandDual-redundant, 16 channels×1)

-20 to 70 °C

SBR4D-0FTerminalboardforRTDinput:DINrailmounttype(SingleandDual-redundant,16 channels×1)

-20 to 70 °C

SBA4D-0FTerminalboardforAnalog:DINrailmounttype(SingleandDual-redundant, 16 channels×1)

-20 to 70 °C

S1BB4D-0F TerminalBoardforAnalog,3-wire:DINrailmounttype -20 to 70 °C

SBD2D-0FTerminalboardforDigitaloutput:DINrailmounttype(SingleandDual-redundant,4channels×1,forSDV521)

-20 to 70 °C

SBD3D-0FSBD3D-AF

TerminalboardforDigitaloutput:DINrailmounttype(SingleandDual-redundant,8channels×1,forSDV53)

-20 to 70 °C

SBD4D-0FTerminalboardforDigital:DINrailmounttype(SingleandDual-redundant, 16channels×1,forSDV144/SDV541)

-20 to 70 °C

7 Power DistributionBoard

AEP7D-1F PrimaryPowerSupplyBusUnit(100to120VACinput) -20 to 70 °C

AEP7D-4F PrimaryPowerSupplyBusUnit(for24VDCinput) -20 to 70 °C

AEPV7D-11F PowerSupplyBusUnit,VerticalType(100to120VACinput) -20 to 70 °C

AEPV7D-41F PowerSupplyBusUnit,VerticalType(for24VDCinput) -20 to 70 °C

8 BasePlate S2BN1D-130 S2BN1D-130/L S2BN1D-130/T

BasePlatewithdisconnectingterminal -40 to 70 °C

S2BN5D-1210 BasePlateforBarrier -20 to 60 °C

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

Apr. 26, 2017-00

Table Canada (FM) NI Approved Products (4/4)

Page 65: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 2 List of Type “n” Compliant Products App.2-1

TI 32S01J30-01E

Appendix 2. List of Type “n” Compliant Products

Appendix 2.1 ATEX Type “n” Compliant ProductsTable The List of ATEX Type “n” Compliant Products (1/6)

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

1 Safety Control Units(*2)

SSC10S-S2E41SSC10S-S2E41/GPS/ATDOC

Safety Control Units24VDCpowersupply -20 to 50 °C

SSC10S-F2E41SSC10S-F2E41/GPS/ATDOC

Safety Control Units(Withfan,24VDCpowersupply) -20 to 70 °C

SSC10D-S2E41SSC10D-S2E41/GPS/ATDOC

DuplexedSafetyControlUnits24VDCpowersupply -20 to 50 °C

SSC10D-F2E41SSC10D-F2E41/GPS/ATDOC

DuplexedSafetyControlUnits(Withfan,24VDCpowersupply) -20 to 70 °C

2 Safety Control UnitsforVnet/IP(*3)

SSC50S-S2E4SSC50S-S2E4/ATDOC/ERFI

Safety Control Units24VDCpowersupply -20 to 40 °C

SSC50S-F2E4SSC50S-F2E4/ATDOC/ERFI

Safety Control Units(Withfan,24VDCpowersupply) -20 to 70 °C

SSC50D-S2E4SSC50D-S2E4/ATDOC/ERFI

DuplexedSafetyControlUnits24VDCpowersupply -20 to 40 °C

SSC50D-F2E4SSC50D-F2E4/ATDOC/ERFI

DuplexedSafetyControlUnits(Withfan,24VDCpowersupply) -20 to 70 °C

SSC57S-S2E4 SSC57S-S2E4/ATDOC

Safety Control Units24VDCpowersupply -20 to 40 °C

SSC57S-F2E4SSC57S-F2E4/ATDOC

Safety Control Units(Withfan,24VDCpowersupply) -20 to 70 °C

SSC57D-S2E4SSC57D-S2E4/ATDOC

DuplexedSafetyControlUnits24VDCpowersupply -20 to 40 °C

SSC57D-F2E4SSC57D-F2E4/ATDOC

DuplexedSafetyControlUnits(Withfan,24VDCpowersupply) -20 to 70 °C

SSC60S-S2E4SSC60S-S2E4/ATDOC/ERFI

Safety Control Units24VDCpowersupply -20 to 40 °C

SSC60S-F2E4SSC60S-F2E4/ATDOC/ERFI

Safety Control Units(Withfan,24VDCpowersupply) -20 to 70 °C

SSC60D-S2E4SSC60D-S2E4/ATDOC/ERFI

DuplexedSafetyControlUnits24VDCpowersupply -20 to 40 °C

SSC60D-F2E4SSC60D-F2E4/ATDOC/ERFI

DuplexedSafetyControlUnits(Withfan,24VDCpowersupply) -20 to 70 °C

S2SC70S-S41 S2SC70S-S41/ATDOC

Safety Control Unit 24VDCpowersupply -20 to 40 °C

S2SC70S-F41 S2SC70S-F41/ATDOC

Safety Control Unit (Withfan,24VDCpowersupply) -20 to 70 °C

S2SC70D-S41 S2SC70D-S41/ATDOC

DuplexedSafetyControlUnit 24VDCpowersupply -20 to 40 °C

S2SC70D-F41 S2SC70D-F41/ATDOC

DuplexedSafetyControlUnit (Withfan,24VDCpowersupply) -20 to 70 °C

3 Safety Node Units(*4)

SNB10D-4ESNB10D-4E/CU2N/ATDOCSNB10D-4E/CU2T/ATDOC

NodeUnitforDual-RedundantESBBus24VDCpowersupply

-20 to 70 °C

Apr. 26, 2017-00

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

*2: /GPSand/or/ATDOCcanbeselected.*3: /ATDOCand/or/ERFIcanbeselected.*4: /CU2Nand/or/ATDOCcanbeselected. /CU2Tand/or/ATDOCcanbeselected.

Page 66: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 2 List of Type “n” Compliant Products App.2-2

TI 32S01J30-01E

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

4 Unit for OpticalBusRepeater Module

SNT10D-24ESNT10D-24E/ATDOC

UnitforOpticalESBBusRepeaterModule24VDCpowersupply

-20 to 70 °C

5 CPU Module SCP401-E1 Processor Module for SSC10 -20 to 70 °C (*5)SCP451-ESCP451-E/ERFI

Processor Module for SSC50 and SSC57 -20 to 70 °C (*6)

SCP461-E1SCP461-E1/ERFI

Processor Module for SSC60 and S2SC70 -20 to 70 °C (*7)

Power supply Module SPW484-E3

SPW484-E3/ERFI 24VDCPowersupplymodule -20 to 70 °C(*5), (*6), (*7)

S2PW504-S0130 24VDCOutputPowerSupplyUnit (24VDCinputpowersupply) -40 to 70 °C

6 Coupler Unit AIP504-E3 VnetCouplerUnit -20 to 70 °C (*5)BusCouplerModule

SEC401-E1 ESBBusCouplerModule -20 to 70 °C

SEC402-E1 ESBBusCouplerModule (for 2-port) -20 to 70 °C

BusInterfaceModule SSB401-E3 ESBBusInterfaceSlaveModule -20 to 70 °C

OpticalESBBusRepeaterModule

SNT401-ESNT401-E/CU1NSNT401-E/CU1T

OpticalESBBusRepeaterMaster Module -20 to 70 °C

SNT411-ESNT411-E/CU1NSNT411-E/CU1T

OpticalESBBusRepeaterMaster Module 5 to 50 km

-20 to 70 °C

SNT421-E3SNT421-E3/CU1NSNT421-E3/CU1T

OpticalESBBusRepeaterMaster Module (for Multimode Fiber) -20 to 70 °C

SNT501-E OpticalESBBusRepeaterSlave Module -20 to 70 °C

SNT511-EOpticalESBBusRepeaterSlave Module 5 to 50 km

-20 to 70 °C

SNT521-E3 OpticalESBBusRepeaterSlave Module (for Multimode Fiber) -20 to 70 °C

N-ESBBusCoupler Module

S2EN402-S0011 N-ESBBusCouplerModule -40 to 70 °C

S2EN404-S0011 N-ESBBusCouplerModule -40 to 70 °C

Node Interface Unit

S2NN30D-440013 S2NN30D-440013/ATDOC

Node Interface Unit (24VDCinputpowersupply) -40 to 70 °C

N-ESBBusModule S2EN501-S130 N-ESBBusModule -40 to 70 °C

Table The List of ATEX Type “n” Compliant Products (2/6)

Apr. 26, 2017-00

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

*5: For SSC10-F (with fan). -20 to 50°C for SSC10-S (without fan)*6: For SSC50-F and SSC57-F (with fan). -20 to 40°C for SSC50-S and SSC57-S (without fan)*7: For SSC60-F (with fan) and S2SC70-F (with fan). -20 to 40°C for SSC60-S (without fan) and S2SC70-S (without fan)

Page 67: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 2 List of Type “n” Compliant Products App.2-3

TI 32S01J30-01E

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

7 Input/OutputModules

SAI143-SE3SAI143-SE3/A4S00SAI143-SE3/A4S10SAI143-SE3/A4D00SAI143-SE3/A4D10SAI143-SE3/CCC01

Analog Input Module (4 to 20 mA, 16 channels, module isolation)

-20 to 70 °C

SAI143-SF3SAI143-SF3/PRPSAI143-HE3SAI143-HE3/A4S00SAI143-HE3/A4S10SAI143-HE3/A4D00SAI143-HE3/A4D10SAI143-HE3/CCC01SAI143-HECSAI143-HEC/A4S00SAI143-HEC/A4S10SAI143-HEC/A4D00SAI143-HEC/A4D10SAI143-HEC/CCC01

Analog Input Module (4 to 20 mA, 16 channels, module isolation)WithHARTcommunication

-20 to 70 °C

SAI143-HF3SAI143-HF3/PRPSAI143-HFCSAI143-HFC/PRPSAV144-SE3SAV144-SE3/A4S00SAV144-SE3/A4S10SAV144-SE3/A4D00SAV144-SE3/A4D10SAV144-SE3/CCC01

Analog Input Module (1to5V/1to10V,16channels,module isolation)

-20 to 70 °C

SAV144-SF3SAV144-SF3/PRP

Analog Input Module (1to5V/1to10V,16channels,module isolation)

-20 to 70 °C

SAT145-SF3SAT145-SF3/PRP

TC/mVInputModule (16 channels, Isolated Channels) -20 to 70 °C

SAR145-SF3 SAR145-SF3/PRP

RTDInputModule (16 channels, Isolated Channels) -20 to 70 °C

SAI533-HE3SAI533-HE3/A4S00SAI533-HE3/A4S10SAI533-HE3/A4D00SAI533-HE3/A4D10SAI533-HE3/CCC01

Analog Output Module (4 to 20 mA, 8 channels, module isolation)

-20 to 70 °C

SAI533-HF3SAI533-HF3/PRPSDV144-SE3SDV144-SE3/B4S00SDV144-SE3/B4S10SDV144-SE3/B4D00SDV144-SE3/B4D10SDV144-SE3/CCC01SDV144-SE3/CCC02SDV144-SECSDV144-SEC/B4S00SDV144-SEC/B4S10SDV144-SEC/B4D00SDV144-SEC/B4D10SDV144-SEC/CCC01SDV144-SEC/CCC02

DigitalInputModule(16 channels, module isolation) -20 to 70 °C

Apr. 26, 2017-00

Table The List of ATEX Type “n” Compliant Products (3/6)

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

Page 68: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 2 List of Type “n” Compliant Products App.2-4

TI 32S01J30-01E

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

7 Input/OutputModules

SDV144-SF3SDV144-SF3/PRPSDV144-SFCSDV144-SFC/PRP

DigitalInputModule(16 channels, module isolation) -20 to 70 °C

SDV521-SF3SDV521-SF3/PRPSDV521-SFCSDV521-SFC/PRP

DigitalOutputModule(4 channels, module isolation) -20 to 70 °C

SDV531-SE3SDV531-SE3/B4S00SDV531-SE3/B4S10SDV531-SE3/B4D00SDV531-SE3/B4D10SDV531-SE3/CCC01SDV531-SE3/CCC02

DigitalOutputModule(8 channels, module isolation) -20 to 70 °C

SDV531-SF3SDV531-SF3/PRPSDV531-LE3SDV531-LE3/B4S00SDV531-LE3/B4S10SDV531-LE3/B4D00SDV531-LE3/B4D10SDV531-LE3/CCC01SDV531-LE3/CCC02SDV531-LECSDV531-LEC/B4S00SDV531-LEC/B4S10SDV531-LEC/B4D00SDV531-LEC/B4D10SDV531-LEC/CCC01SDV531-LEC/CCC02

DigitalOutputModule(8 channels, module isolation, long distance type)

-20 to 70 °C

SDV531-LF3SDV531-LF3/PRPSDV531-LFCSDV531-LFC/PRP

DigitalOutputModule(8 channels, module isolation, long distance type)

-20 to 70 °C

SDV53A-SF3SDV53A-SF3/PRP

DigitalOutputModule(8 channels, module isolation) -20 to 70 °C

SDV541-SE3SDV541-SE3/B4S00SDV541-SE3/B4S10SDV541-SE3/B4D00SDV541-SE3/B4D10SDV541-SE3/CCC01SDV541-SE3/CCC02SDV541-SECSDV541-SEC/B4S00SDV541-SEC/B4S10SDV541-SEC/B4D00SDV541-SEC/B4D10SDV541-SEC/CCC01SDV541-SEC/CCC02

DigitalOutputModule(16 channels, module isolation) -20 to 70 °C

SDV541-SF3SDV541-SF3/PRPSDV541-SFCSDV541-SFC/PRPS2MMM843-SS1130 AnalogDigitalI/OModule -40 to 70 °CS2MDV843-0S1130 DigitalI/OModule -40 to 70 °C (*8)

ALR111-SE1 Serial Communication Module(RS-232C, 2-port) 0 to 60 °C

Table The List of ATEX Type “n” Compliant Products (4/6)

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

*8: S2MDV843cannotbeusedwithS2BN4DforATEXType“n”.

Apr. 26, 2017-00

Page 69: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 2 List of Type “n” Compliant Products App.2-5

TI 32S01J30-01E

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

7 Input/OutputModules ALR121-SE1 Serial Communication Module

(RS-422/RS-485,2-port) 0 to 60 °C

ALR121-SEB Serial Communication Module (RS-422/RS-485,2-port) 0 to 70 °C

ALR121-SE3 Serial Communication Module (RS-422/RS-485,2-port) -20 to 70 °C

ALE111-SE1 Ethernet Communication Module 0 to 60 °C (*9)ALE111-SE3 Ethernet Communication Module -20 to 70 °C (*9)

8 TerminalBoard SEA4D-0FSEA4D-1FSEA4D-0F/NTRYSEA4D-1F/NTRY

AnalogTerminalBoard(SingleandDual-Redundant,16channels×2) -20 to 70 °C

SED2D-0FSED2D-1FSED2D-0F/NTRYSED2D-1F/NTRY

DigitalTerminalBoard(SingleandDual-Redundant,4channels×4) -20 to 70 °C

SED3D-AFSED3D-AF/NTRY

Digitalterminalboard(SingleandDual-Redundant,8channels×4) -20 to 70 °C

SED4D-0FSED4D-1FSED4D-0F/NTRYSED4D-1F/NTRY

Digitalterminalboard(SingleandDual-Redundant,16channels×2) -20 to 70 °C

SBT4D-0FTerminalboardforTC/mV:DINrailmounttype(SingleandDual-redundant,16 channels×1)

-20 to 70 °C

SBR4D-0FTerminalboardforRTDinput:DINrailmounttype(SingleandDual-redundant, 16 channels×1)

-20 to 70 °C

SBA4D-0FTerminalboardforAnalog:DINrailmounttype(SingleandDual-redundant, 16 channels×1)

-20 to 70 °C

S1BB4D-0F TerminalBoardforAnalog,3-wire:DINrailmounttype -20 to 70 °C

SBD2D-0F

TerminalboardforDigitaloutput:DINrailmounttype(SingleandDual-redundant,4channels×1,forSDV521)

-20 to 70 °C

SBD3D-0FSBD3D-AF

TerminalboardforDigitaloutput:DINrailmounttype(SingleandDual-redundant,8channels×1,forSDV53)

-20 to 70 °C

SBD4D-0F

TerminalboardforDigital:DINrailmounttype(SingleandDual-redundant, 16 channels×1, for SDV144/SDV541)

-20 to 70 °C

Power DistributionBoard

AEP7D-4F Primary power supply bus unit (for24VDCinput) -20 to 70 °C

AEPV7D-41FPowerSupplyBusUnit,VerticalType(for24VDCinput)

-20 to 70 °C (*10)

Fan AIP602 Fan Unit -20 to 70 °C

Table The List of ATEX Type “n” Compliant Products (5/6)

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

*9: ALE111 supported in R3.02.00 or later can be mounted on S2SC70, SSC60, SSC50 or SSC57. *10: For style code S1 and unit revision U:1 or later.

Apr. 26, 2017-00

Page 70: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 2 List of Type “n” Compliant Products App.2-6

TI 32S01J30-01E

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

9 OpticalBusRepeater YNT511D-P44/NL

OpticalBusRepeaterforDual-RedundantBus(10BASE-2Cable)(Upto4kmTransmissionDistance,24VDCPowerSupply)

0 to 50 °C

YNT522D-P14/NL

OpticalBusRepeaterforDual-RedundantBus(10BASE-2Cable)(Upto15kmTransmissionDistance,24VDCPowerSupply)

0 to 50 °C

PW504 Power Supply Unit (for YNT5,24VDC) 0 to 50 °C

AIP578

OpticalTransceiverUnitforVnetRepeater(For Max. 4 km Transmission Distance)

0 to 50 °C

AIP591

OpticalTransceiverUnitforVnetRepeater(For Max. 15 km Transmission Distance)

0 to 50 °C

AIP171 TransceiverControlUnitforVnetRepeater 0 to 50 °C

AIP571 ElectricalTransceiverUnitforVnetRepeater 0 to 50 °C

10 BasePlate S2BN1D-130 S2BN1D-130/L S2BN1D-130/T

BasePlatewithdisconnectingterminal -40 to 70 °C

S2BN4D-1010 BasePlateforBarrier -20 to 60 °C (*11)S2BN5D-1210 BasePlateforBarrier -20 to 60 °C (*12)

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

*11: S2BN4DforATEXType“n”cannotbeusedwithS2MDV843.*12: S2BN5DstyleS1cannotbeinstalledinthehazardousarea.

Table The List of ATEX Type “n” Compliant Products (6/6)

Apr. 26, 2017-00

Page 71: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 2 List of Type “n” Compliant Products App.2-7

TI 32S01J30-01E

Appendix 2.2 IECEx Type “n” Compliant Products

Table The List of IECEx Type “n” Compliant Products (1/2)

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

1 Safety Control UnitsforVnet/IP

S2SC70S-S41 S2SC70S-S41/ATDOC

Safety Control Unit 24VDCpowersupply -20 to 40 °C

S2SC70S-F41 S2SC70S-F41/ATDOC

Safety Control Unit (Withfan,24VDCpowersupply) -20 to 70 °C

S2SC70D-S41 S2SC70D-S41/ATDOC

DuplexedSafetyControlUnit 24VDCpowersupply -20 to 40 °C

S2SC70D-F41 S2SC70D-F41/ATDOC

DuplexedSafetyControlUnit (Withfan,24VDCpowersupply) -20 to 70 °C

2 Safety Node Units(*2)

SNB10D-4ESNB10D-4E/CU2N/ATDOCSNB10D-4E/CU2T/ATDOC

NodeUnitforDual-RedundantESBBus24VDCpowersupply

-20 to 70 °C

3 Unit for OpticalBusRepeater Module

SNT10D-24ESNT10D-24E/ATDOC

UnitforOpticalESBBusRepeaterModule24VDCpowersupply

-20 to 70 °C

4 CPU Module SCP461-E1SCP461-E1/ERFI

Processor Module for SSC60 and S2SC70 -20 to 70 °C (*3)

Power supply Module

SPW484-E3SPW484-E3/ERFI 24VDCPowersupplymodule -20 to 70 °C (*3)

S2PW504-S0130 24VDCOutputPowerSupplyUnit (24VDCinputpowersupply) -40 to 70 °C

5 BusCouplerModule

SEC401-E1 ESBBusCouplerModule -20 to 70 °CSEC402-E1 ESBBusCouplerModule(for2-port) -20 to 70 °C

BusInterfaceModule SSB401-E3 ESBBusInterfaceSlaveModule -20 to 70 °C

OpticalESBBusRepeaterModule

SNT401-EFSNT401-EF/CU1NSNT401-EF/CU1T

OpticalESBBusRepeaterMaster Module -20 to 70 °C

SNT411-EFSNT411-EF/CU1NSNT411-EF/CU1T

OpticalESBBusRepeaterMaster Module 5 to 50 km

-20 to 70 °C

SNT421-E3SNT421-E3/CU1NSNT421-E3/CU1T

OpticalESBBusRepeaterMaster Module (for Multimode Fiber) -20 to 70 °C

SNT501-EF OpticalESBBusRepeaterSlave Module -20 to 70 °C

SNT511-EFOpticalESBBusRepeaterSlave Module 5 to 50 km

-20 to 70 °C

SNT521-E3 OpticalESBBusRepeaterSlave Module (for Multimode Fiber) -20 to 70 °C

N-ESBBusCoupler Module

S2EN402-S0011 N-ESBBusCouplerModule -40 to 70 °C

S2EN404-S0011 N-ESBBusCouplerModule -40 to 70 °CNode Interface Unit

S2NN30D-440013 S2NN30D-440013/ATDOC

Node Interface Unit (24VDCinputpowersupply) -40 to 70 °C

N-ESBBusModule S2EN501-S130 N-ESBBusModule -40 to 70 °C

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

*2: /CU2Nand/or/ATDOCcanbeselected. /CU2Tand/or/ATDOCcanbeselected.*3: For S2SC70-F (with fan). -20 to 40°C for S2SC70-S (without fan)

Apr. 26, 2017-00

Page 72: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 2 List of Type “n” Compliant Products App.2-8

TI 32S01J30-01E

Numbers Classifications Type Names Products Temperature Range (*1) Remarks

6 Input/OutputModules

S2MMM843-SS1130 AnalogDigitalI/OModule -40 to 70 °CS2MDV843-0S1130 DigitalI/OModule -40 to 70 °C (*4)

ALR111-SE1 Serial Communication Module(RS-232C, 2-port) 0 to 60 °C

ALR121-SE1 Serial Communication Module (RS-422/RS-485,2-port) 0 to 60 °C

ALR121-SE3 Serial Communication Module (RS-422/RS-485,2-port) -20 to 70 °C

ALE111-SE1 Ethernet Communication Module 0 to 60 °C (*5)ALE111-SE3 Ethernet Communication Module -20 to 70 °C (*5)

7 Power DistributionBoard

AEPV7D-41FPowerSupplyBusUnit,VerticalType(for24VDCinput)

-20 to 70 °C

Fan AIP602 Fan Unit -20 to 70 °C8 BasePlate S2BN1D-130

S2BN1D-130/L S2BN1D-130/T

BasePlatewithdisconnectingterminal -40 to 70 °C

S2BN4D-1010 BasePlateforBarrier -20 to 60 °C (*6)S2BN5D-1210 BasePlateforBarrier -20 to 60 °C (*7)

*1: TheambienttemperaturearoundnotthecabinetbuteachunitsuchasSafetyControlUnit,SafetyNodeUnit,UnitforOpticalESBBusRepeaterModuleorTerminalBoardisshown.

*4: S2MDV843cannotbeusedwithS2BN4DforIECExType“n”.*5: ALE111 supported in R3.02.00 or later can be mounted on S2SC70, SSC60, SSC50 or SSC57. *6: S2BN4DforIECExType“n”cannotbeusedwithS2MDV843.*7: S2BN5DstyleS1cannotbeinstalledinthehazardousarea.

Table The List of IECEx Type “n” Compliant Products (2/2)

Apr. 26, 2017-00

Page 73: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

App.3-1

TI 32S01J30-01E

Appendix 3. Lists of Parameters of Base Plate for Barrier (S2BN5D)

Appendix 3. Lists of Parameters of Base Plate for Barrier (S2BN5D)

Table List of Parameters (ATEX) of Base Plate for Barrier (S2BN5D)

Modules Uo (V) Io (mA) Po (mW) Ui (V) Co (nF) Lo (mH) RemarksS2BN5D 30 — — 30 — — (*1)

Table List of Parameters (IECEx) of Base Plate for Barrier (S2BN5D)

Modules Uo (V) Io (mA) Po (mW) Ui (V) Co (nF) Lo (mH) RemarksS2BN5D 30 — — 30 — — (*1)

*1: The used P+F’s I.S. barriers determine the ultimate output parameters of the channel. Please refer to P+F’s instruction manual for the parameter of P+F’s I.S. barriers.

Nov. 27, 2015-00

Page 74: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 4. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS N-IO App.4-1

TI 32S01J30-01E

Appendix 4. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS N-IO

F040001.ai

Model: ProSafe-RS N-IO Date: August 24, 2015

1.P 101A-900EIN :.oN .coD 6102 ,1 rebmeceD :2.veR

Yokogawa Electric Corporation

Control Drawing (US)

I/O

Mod

ule

(in c

ase

of R

edun

dant

)I/

O M

odul

e

Apr. 26, 2017-00

Page 75: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 4. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS N-IO App.4-2

TI 32S01J30-01E

F040002.ai

Model: ProSafe-RS N-IO Date: August 24, 2015

Yokogawa Electric Corporation

2.P 101A-900EIN :.oN .coD 6102 ,1 rebmeceD :2.veR

Non-incendive field wiring parameters (Output parameter) Model Function Voc(V) Isc(mA) Ca(μF) La(mH) Remark

S2MMM843 Redundant Analog Input(Current Input) 24.0 80.0 0.05 0.66

2-wire transmitter input Single

Redundant Analog Output(Current Output) 28.0 23.0 0.05 0.66

-

Single

Redundant Digital Input30.0 7.2 0.05 0.66

-

Single

Redundant Digital Output— — — —

Nonincendive field wiring is not permitted.

Single

S2MDV843 Redundant Digital Input30.0 7.2 0.05 0.66

-

Single

Redundant Digital Output— — — —

Nonincendive field wiring is not permitted. Single

Non-incendive field wiring parameters (Input parameters)

Model Function Vmax(V)

Imax(mA)

Ci(μF) Li(μH) Remark

S2MMM843 Redundant Analog Input(Current Input) 30.0 — 0.02 10

4-wire transmitter input Single

Apr. 26, 2017-00

Page 76: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 4. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS N-IO App.4-3

TI 32S01J30-01E

F040003.ai

Model: ProSafe-RS N-IO Date: August 24, 2015

Yokogawa Electric Corporation

3.P 101A-900EIN :.oN .coD 6102 ,1 rebmeceD :2.veR

Specific condition of use: - The equipment shall be installed in a lo ckable metal cabinet. The suitability of the installation shall be determined by the authority having jurisdiction. - The Ambient Temperatures are as follows.

Model code Ambient Temperature S2SC70S-S41b110c -20 to 40 °C S2SC70S-F41b110c -20 to 70 °C S2SC70D-S41b110c -20 to 40 °C S2SC70D-F41b110c -20 to 70 °C

S2NN30D-4a0b0cd13e

When cd= 00, -40 to 70 °C  When cd= 01, 11, 21, 02, 12, 22, 10, 20, -40 to 70 °C  (altitude = ~2000m) When cd= 01, 11, 21, 02, 12, 22, 10, 20, -40 to 60 °C    (altitude = 2000~3000m)

S2PW503 -40 to 70 °C S2PW504 -40 to 70 °C S2EN402 -20 to 70 °C S2EN404 -20 to 70 °C

S2EN501-Sab130c

When ab= 00, -40 to 70 °C When ab= 01, 11, 21, 02, 12, 22, 10, 20, -40 to 70 °C (altitude = ~2000m) When ab= 01, 11, 21, 02, 12, 22, 10, 20, -40 to 60 °C (altitude = 2000~3000m)

S2MMM843 and S2MDV843

-40 to 70 °C When utilizing Digital output function, the total load current of all channels is limited as shown below according to the derating specifications due to the ambient temperature of modules. -40 to 40 °C: Max. 10.56 A 40 to 50 °C: Max.9.71 A 50 to 60 °C: Max.8.85 A 60 to 70 °C: Max.8 A

S2BN1D

-40 to 70 °C When utilizing Digital output function of S2MMM843, the total load current of all channels is limited as shown below according to the derating specifications due to the ambient temperature of modules. -40 to 40 °C: Max. 10.56 A 40 to 50 °C: Max.9.71 A 50 to 60 °C: Max.8.85 A 60 to 70 °C: Max.8 A

Apr. 26, 2017-00

Page 77: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 4. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS N-IO App.4-4

TI 32S01J30-01E Apr. 26, 2017-00

F040004.ai

Model: ProSafe-RS N-IO Date: August 24, 2015

Yokogawa Electric Corporation

4.P 101A-900EIN :.oN .coD

Notes: 1. No revision to this drawing without prior approval of FM.

2. In this control drawing, the term “installation” includes reconfiguration of the

function of each module, which is carried out in maintenance process.

3. Installation must be in accordance with the National Electrical Code (NFPA 70) and relevant local codes.

4. In the course of installation, the related documents of GS (General specifications), TI

(Technical Information of Installation Guidance), and IM (User ’s Manuals) should be referred to and the instructions described in the documents should be observed.

5. Modules can be mounted also on an FM-approved Base Plate S2BN5D. In such case,

installation must be in accordance also with the control drawing of these Base Plates.

6. PROSAFE-RS IS SUITABLE FOR USE IN CLASS 1, DIVISION 2, GROUPS A, B, C, and D OR NONHAZARDOUS LOCATIONS ONLY.

7. It must be observed during the installation that the venting slots of the devices are not

blocked by cable parts, fixing accessories etc.

8. The doors of the cabinets must be closed when ProSafe-RS is energized.

Page 78: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 4. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS N-IO App.4-5

TI 32S01J30-01E Apr. 26, 2017-00

F040005.ai

Model: ProSafe-RS N-IO Date: August 24, 2015

Yokogawa Electric Corporation

5.P 101A-900EIN :.oN .coD

9. Nonincendive field wiring is permitted for the modules listed in tables of the Nonincendive field wiring parameters.

9.1 The Nonincendive field wiring circuit concept allows interconnection of nonincendive

field wiring apparatus with associated nonincendive field wiring apparatus, using any of the wiring methods permitted for unclassified locations.

9.2 Field equipment or other equipment connected to ProSafe-RS by Nonincendive field

wiring must be FM approved.

9.3 The control drawing of field equipment or other equipment must be followed at the installation.

9.4 The following conditions must be met. See tables for the Nonincendive field wiring

parameters of ProSafe-RS.

Vmax ≥ Voc or Vt; Imax ≥ Isc or It; Ca ≥ Ci + Ccable; La ≥ Li + Lcable

9.5 For current controlled circuits, Imax of the nonincendive field wiring apparatus is not required and need not be aligned with parameter Isc or It of ProSafe-RS or other associated nonincendive field wiring apparatus.

10. WARNING – SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR

DIVISION 2.

11. WARNING – EXPLOSION HAZARD. DO NOT DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT.

12. WARNING – EXPLOSION HAZARD. DO NOT REMOVE OR REPLACE FUSES

UNLESS POWER HAS BEEN DISCONNECTED OR WHEN A FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT.

13. WARNING – EXPLOSION HAZARD. DO NOT OPEN ENCLOSURE OR REPLACE

BATTERY WHEN A FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT.

Page 79: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 4. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS N-IO App.4-6

TI 32S01J30-01E Apr. 26, 2017-00

F040006.ai

Model: ProSafe-RS N-IO Date: January 11, 2016

6.P 101A-900EIN :.oN .coD 6102 ,1 rebmeceD :1.veR

Yokogawa Electric Corporation

Control Drawing (Canada)

Disconnecting terminal

I/O

Mod

ule

(in c

ase

of R

edun

dant

)

PowerSupplyUnits

Base Platewith disconnecting terminal

FieldControl

Unit

Node Interface

Unit

A

B

“” denotes Channel number (1 to 16)

I/O

Mod

ule

Output/Input connection

Disconnecting terminal

A

B

Disconnecting terminal

A

B

Hazardous LocationZone 2, Group IIC, T4

Class I, Division 2, Groups A, B, C, D, T4

Non-hazardousLocation

N-ESBBus

Modules

Page 80: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 4. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS N-IO App.4-7

TI 32S01J30-01E Apr. 26, 2017-00

F040007.ai

Model: ProSafe-RS N-IO Date: January 11, 2016

Yokogawa Electric Corporation

7.P 101A-900EIN :.oN .coD 6102 ,1 rebmeceD :1 .veR

Non-incendive field wiring para meters (Output parameter) Model Function Voc(V) Isc(mA) Ca(μF) La(mH) Remark

S2MMM843 Redundant Analog Input(Current Input) 24.0 80.0 0.05 0.66

2-wire transmitter input Single

Redundant Analog Output(Current Output) 28.0 23.0 0.05 0.66

-

Single

Redundant Digital Input30.0 7.2 0.05 0.66

-

Single

Redundant Digital Output— — — —

Nonincendive field wiring is not permitted.

Single

S2MDV843 Redundant Digital Input30.0 7.2 0.05 0.66

-

Single

Redundant Digital Output— — — —

Nonincendive field wiring is not permitted.

Single

Non-incendive field wiring parameters (Input parameters)

Model Function Vmax(V)

Imax (mA)

Ci(μF) Li(μH) Remark

S2MMM843 Redundant Analog Input(Current Input) 30.0 — 0.02 10

4-wire transmitter input Single

Page 81: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 4. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS N-IO App.4-8

TI 32S01J30-01E Apr. 26, 2017-00

F040008.ai

Model: ProSafe-RS N-IO Date: January 11, 2016

Yokogawa Electric Corporation

8.P 101A-900EIN :.oN .coD 6102 ,1 rebmeceD :1.veR

Specific condition of use: - The equipment shall be installed in a lo ckable metal cabinet. The suitability of the installation shall be determined by the authority having jurisdiction. - The Ambient Temperatures are as follows.

Model code Ambient Temperature

S2NN30D-4a0b0cd13e

When cd= 00, -40 to 70 °C When cd= 01, 11, 21, 02, 12, 22, 10, 20, -40 to 70 °C (altitude = ~2000m) When cd= 01, 11, 21, 02, 12, 22, 10, 20, -40 to 60 °C (altitude = 2000~3000m)

S2PW503 -40 to 70 °C S2PW504 -40 to 70 °C

S2EN501-Sab130c

When ab= 00, -40 to 70 °C When ab= 01, 11, 21, 02, 12, 22, 10, 20, -40 to 70 °C (altitude = ~2000m) When ab= 01, 11, 21, 02, 12, 22, 10, 20, -40 to 60 °C (altitude = 2000~3000m)

S2MMM843 and S2MDV843

-40 to 70 °C When utilizing Digital output function, the total load current of all channels is limited as shown below according to the derating specifications due to the ambient temperature of modules. -40 to 40 °C: Max. 10.56 A 40 to 50 °C: Max.9.71 A 50 to 60 °C: Max.8.85 A 60 to 70 °C: Max.8 A

S2BN1D

-40 to 70 °C When utilizing Digital output function of S2MMM843, the total load current of all channels is limited as shown below according to the derating specifications due to the ambient temperature of modules. -40 to 40 °C: Max. 10.56 A 40 to 50 °C: Max.9.71 A 50 to 60 °C: Max.8.85 A 60 to 70 °C: Max.8 A

Page 82: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 4. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS N-IO App.4-9

TI 32S01J30-01E Apr. 26, 2017-00

F040009.ai

Model: ProSafe-RS N-IO Date: January 11, 2016

Yokogawa Electric Corporation

9.P 101A-900EIN :.oN .coD

Notes: 1. No revision to this drawing without prior approval of FM.

2. In this control drawing, the term “installation” includes reconfiguration of the

function of each module, which is carried out in maintenance process. 3. Installation must be in accordance with Canadian Electrical Code Part I (C22.1) and

relevant local codes.

4. In the course of installation, the related documents of GS (General specifications), TI (Technical Information of Installation Guidance), and IM (User ’s Manuals) should be referred to and the instructions described in the documents should be observed.

5. Modules can be mounted also on an FM-approved Base Plate S2BN5D. In such case,

installation must be in accordance also with the control drawing of these Base Plates. 6. PROSAFE-RS IS SUITABLE FOR USE IN ZONE 2, GROUP IIC; CLASS 1, DIVISION 2,

GROUPS A, B, C, and D OR NON-HAZARDOUS LOCATIONS ONLY. 7. It must be observed during the installation that the venting slots of the devices are not

blocked by cable parts, fixing accessories etc.

8. The doors of the cabinets must be closed when ProSafe-RS is energized. 9. The instrument modification or parts replacement by other than authorized

representative of Yokogawa Electric Corporation is prohibited and will void FM Non-incendive Certification.

Page 83: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 4. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS N-IOApp.4-10

TI 32S01J30-01E Apr. 26, 2017-00

F040010.ai

Model: ProSafe-RS N-IO Date: January 11, 2016

Yokogawa Electric Corporation

01.P 101A-900EIN :.oN .coD .veR

10. Nonincendive field wiring is permitted for the modules listed in tables of the Nonincendive field wiring parameters.

10.1 The Nonincendive field wiring circuit concept allows interconnection of nonincendive field wiring apparatus with associated nonincendive field wiring apparatus, using any of the wiring methods permitted for unclassified locations.

10.2 Field equipment or other equipment connected to ProSafe-RS by Nonincendive field wiring must be FM approved.

10.3 The control drawing of field equipment or other equipment must be followed at the

installation.

10.4 The following conditions must be met. See tables for the Nonincendive field wiring parameters of ProSafe-RS.

Vmax ≥ Voc or Vt; Imax ≥ Isc or It; Ca ≥ Ci + Ccable; La ≥ Li + Lcable

10.5 For current controlled circuits, Imax of the nonincendive field wiring apparatus is

not required and need not be aligned with parameter Isc or It of ProSafe-RS or other associated nonincendive field wiring apparatus.

11. WARNING – EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS MAY

IMPAIR SUITABILITY FOR CLASS I, DIVISION 2. AVERTISSEMENT – RISQUE D’EXPLOSION – LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CE MATÉRIEL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE 1. DIVISION 2.

12. WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT WHILE CIRCUIT IS

LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS. AVERTISSEMENT – RISQUE D’EXPLOSION. NE PAS DÉBRANCHER TANT QUE LE CIRCUIT EST SOUS TENSION, À MOINS QU’IL NE S’AGISSE D’UN EMPLACEMENT NON DANGEREUX.

13. WARNING – EXPLOSION HAZARD – DO NOT REPLACE FUSES UNLESS POWER

HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS. AVERTISSEMENT – RISQUE D’EXPLOSION – COUPER LE COURANT OU S’ASSURER QUE L’EMPLACEMENT EST DÉSIGNÉ NON DANGEREUX AVANT DE REPLACER LE COUPE-CIRCUIT À FUSIBLES.

14. WARNING – EXPLOSION HAZARD – BATTERIES MUST ONLY BE CHANGED IN AN

AREA KNOWN TO BE NON-HAZARDOUS. AVERTISSEMENT – RISQUE D’EXPLOSION – AFIN D’ÉVITER TOUT RISQUE D’EXPLOSION, S’ASSURER QUE L’EMPLACEMENT EST DÉSIGNÉ NON DANGEREUX AVANT DE CHANGER LA BATTRIE.

15. Use only the battery specified by Yokogawa Electric Corporation. Battery which is

mounted in SCP461 is S9185FA.

Page 84: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-1

TI 32S01J30-01E

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO

F050001.ai

5002 ,02 rebmeceD :etaD SR-efaSorP :ledoM

1.P 31A-410MFN :.oN .coD 6102 ,11 yraunaJ :2.veR

Yokogawa Electric Corporation

Control Drawing (US)

YNT522D

Non-HazardousLocation

Hazardous (Classified) LocationⅠClass ,Division 2

Groups A, B, C and D

ⅠClass ,Division 1

Cabinet

SEC401

SSB401+T Branch

YNT522D

SSC10D

SNB10D

SEA4D

Oct. 25, 2016-00

Page 85: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-2

TI 32S01J30-01E

F050002.ai

7002 ,60 hcraM :etaD SR-efaSorP :ledoM

1-1.P 31A-410MFN :.oN .coD 6102 ,11 yraunaJ :1.veR

Yokogawa Electric Corporation

SSC50D

SNB10D

SNT10D

SNB10D

SEA4DSEA4D

Non-HazardousLocation

Hazardous (Classified) LocationClass Ⅰ,Division 2

Groups A, B, C and D

Class Ⅰ,Division 1

Cabinet

Cabinet

SNT501

SNT401 SEC401

SSB401+T Branch

L2SW for Bus2L2SW for Bus1

Bus2

Bus1

SSB401+T Branch

Oct. 25, 2016-00

Page 86: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-3

TI 32S01J30-01E

F050003.ai

5002 ,02 rebmeceD :etaD SR-efaSorP :ledoM

2.P 31A-410MFN :.oN .coD 6102 ,11 yraunaJ :3.veR

Yokogawa Electric Corporation

Nonincendive Field Wiring Parameters (Output parameters) (*1)

(1/2)

Model Voc (V)

Isc (mA)

Ca(μF)

La (mH) Remarks

SCP451 Redundant - - - - (*2) Single - - - -

SCP461 Redundant - - - - (*2) Single - - - - AIP504 - - - - (*2) SEC401 - - - - (*2) SEC402 - - - - (*2) SSB401 - - - - (*2) SNT401 - - - - (*2) for YCB301 SNT501 - - - - (*2) for YCB301 SNT411 - - - - (*2) for YCB301 SNT511 - - - - (*2) for YCB301 SNT421 - - - - (*2) for YCB301 SNT521 - - - - (*2) for YCB301

SAI143

Redundant 26.4 26 0.13 10 -2-wire transmitter input -Included terminal block and terminal board but excluded cable. Single 26.4 26 0.13 10

Redundant 12.2 0.14 0.01 1 -Cable coming out detection (Wires connected to Pin No. 1 and 40) - Included terminal block and terminal board but excluded cable. Single 12.2 0.07 0.01 1

SAV144 Redundant 10 1.2 0.01 1 -Cable coming out detection

(Wires connected to Pin No. 1 and 40) -Included terminal block and terminal board but excluded cable. Single 10 0.6 0.01 1

SAI533

Redundant 18.9 23 0.16 10 -Output -Included terminal block and terminal board but excluded cable. Single 18.9 23 0.16 10

Redundant 10 220 0.01 1 -Cable coming out detection (Wires connected to Pin No. 1 and 40) -Included terminal block and terminal board but excluded cable. Single 10 110 0.01 1

SDV144 Redundant 11.6 1.4 0.01 1

-Cable coming out detection (Wires connected to Pin No. 1 and 50) -Included terminal block and terminal board but excluded cable Single 11.6 0.7 0.01 1

SDV531

Redundant - - - - Output (*2) Single - - - - Redundant 11.6 220 0.01 1 -Cable coming out detection

(Wires connected to Pin No. 1 and 50) -Included terminal block and terminal board but excluded cable

Single 11.6 110 0.01 1

SDV541

Redundant - - - - Output (*2) Single - - - -

Redundant 11.6 220 0.01 1 -Cable coming out detection (Wires connected to Pin No. 1 and 50) -Included terminal block and terminal board but excluded cable Single 11.6 110 0.01 1

(*1) These parameters are applied to all modes of each model if the mode is not otherwise remarked. (*2) Wiring for Division 2 (such as conduit systems) must comply with NEC or Local Electrical Code of each country.

Oct. 25, 2016-00

Page 87: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-4

TI 32S01J30-01E

F050004.ai

5002 ,02 rebmeceD :etaD SR-efaSorP :ledoM

3.P 31A-410MFN :.oN .coD 6102 ,11 yraunaJ :4.veR

Yokogawa Electric Corporation

Nonincendive Field Wiring Parameters (Output parameters) (*1)

(Continued) (2/2) Model Voc

(V) Isc

(mA) Ca

(μF)La

(mH) Remarks

SDV521

Redundant - - - - Output (*2) Single - - - - Redundant 11.6 220 0.01 1 -Cable coming out detection

(Wires connected to Pin No. 1 and 50) -Included terminal board but excluded cable Single 11.6 110 0.01 1

SDV53A

Redundant - - - - Output (*2) Single - - - -

Redundant 11.6 220 0.01 1 -Cable coming out detection (Wires connected to Pin No. 1 and 50) -Included terminal board but excluded cable Single 11.6 110 0.01 1

ALR111 Redundant - - - - (*2) Single - - - -

ALR121 Redundant - - - - (*2) Single - - - -

ALE111 Redundant - - - -

(*2) Single - - - - AEP7D - - - - (*2) AEPV7D - - - - (*2)AIP571 - - - - (*2) S9161FA - - - - Cable for GPS when SSC10-/GPS (*2)

SAT145

Redundant 1.5 1.0 0.01 0.14 -RJC input -Included terminal board but excluded cable Single 1.5 1.0 0.01 0.14

Redundant 6.0 3.0 0.45 3.74 -TC/mv input (Burn out) -Included terminal board but excluded cable Single 6.0 3.0 0.45 3.74

Redundant 6.0 20.0 0.01 0.14 -Cable coming out detection (Wires connected to Pin No. 1 and 50) -Included terminal board but excluded cable. Single 6.0 20.0 0.01 0.14

SAR145

Redundant 6.0 50.0 0.20 1.32 -RTD input -Included terminal board but excluded cable. Single 6.0 50.0 0.20 1.32

Redundant 6.0 70.0 0.01 0.14 -Cable coming out detection (Wires connected to Pin No. 1 and 50) -Included terminal board but excluded cable. Single 6.0 70.0 0.01 0.14

(*1) These parameters are applied to all modes of each model if the mode is not otherwise remarked. (*2) Wiring for Division 2 (such as conduit systems) must comply with NEC or Local Electrical Code

of each country.

Oct. 25, 2016-00

Page 88: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-5

TI 32S01J30-01E

F050005.ai

5002 ,02 rebmeceD :etaD SR-efaSorP :ledoM

4.P 31A-410MFN :.oN .coD 6102 ,11 yraunaJ :6.veR

Yokogawa Electric Corporation

Nonincendive Field Wiring Parameters (Input parameters) (*1)

(1/2)

(*1) These parameters are applied to all modes of each model if the mode is not otherwise remarked. (*2) Wiring for Division 2 (such as conduit systems) must comply with NEC or Local Electrical Code of each country

Model Vmax (V)

Imax(mA)

Ci (μF)

Li (μH) Remarks

SSC10S - - - - (*2) for TM1 of Fan Unit in SSC10S-F SSC10D - - - - (*2) for TM1 of Fan Unit in SSC10D-F SSC50S - - - - (*2) for TM1 of Fan Unit in SSC50S-F SSC50D - - - - (*2) for TM1 of Fan Unit in SSC50D-F SSC57S - - - - (*2) for TM1 of Fan Unit in SSC57S-F SSC57D - - - - (*2) for TM1 of Fan Unit in SSC57D-F SSC60S - - - - (*2) for TM1 of Fan Unit in SSC60S-F SSC60D - - - - (*2) for TM1 of Fan Unit in SSC60D-F SPW481 - - - - (*2) SPW482 - - - - (*2) SPW484 - - - - (*2)

SCP451 Redundant - - - - (*2) Single - - - -

SCP461 Redundant - - - - (*2) Single - - - - AIP504 - - - - (*2) SEC401 - - - - (*2) SEC402 - - - - (*2) SSB401 - - - - (*2) SNT401 - - - - (*2) for YCB301 SNT501 - - - - (*2) for YCB301 SNT411 - - - - (*2) for YCB301 SNT511 - - - - (*2) for YCB301 SNT421 - - - - (*2) for YCB301 SNT521 - - - - (*2) for YCB301

SAI143 Redundant 26.4 26 0.008 20 -4-wire transmitter input

-Included terminal block and terminal board but excluded cable Single 26.4 26 0.004 20

SAV144 Redundant 30 0.6 0.001 10 -Input

-Included terminal block and terminal board but excluded cable Single 30 0.3 0.001 10

SDV144

Redundant - - - - Input (*2)

Single - - - - Redundant - - - - Power supply (*2) Single - - - -

SDV531 Redundant - - - - Power supply (*2) Single - - - -

SDV541 Redundant - - - - Power supply (*2) Single - - - -

SDV521 Redundant - - - - Power supply (*2) Single - - - -

SDV53A Redundant - - - - Power supply (*2) Single - - - -

ALR111 Redundant - - - - (*2) Single - - - -

ALR121 Redundant - - - - (*2) Single - - - -

ALE111 Redundant - - - - (*2) Single - - - -

Oct. 25, 2016-00

Page 89: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-6

TI 32S01J30-01E

F050006.ai

8002 ,60 hcraM :etaD SR-efaSorP :ledoM

1-4.P 31A-410MFN :.oN .coD 6102 ,11 yraunaJ :4.veR

Yokogawa Electric Corporation

Nonincendive Field Wiring Parameters (Input parameters) (*1)

(Continued) (2/2)

(*1) These parameters are applied to all modes of each model if the mode is not otherwise remarked. (*2) Wiring for Division 2 (such as conduit systems) must comply with NEC or Local Electrical Code of each country.

Model Vmax (V)

Imax(mA)

Ci (μF)

Li (μH) Remarks

AEP7D - - - - (*2) AEPV7D - - - - (*2) PW501 - - - - (*2) PW502 - - - - (*2) PW504 - - - - (*2) AIP571 - - - - (*2)

S9161FA - - - - Cable for GPS when SSC10-/GPS (*2)

SAT145

Redundant 5 1.53 0.6 10 -TC/mV input -Included terminal board but excluded cable Single 5 1.53 0.6 10

SBD2D - - - - Ready input(*2) 60 20 0 0 Ready input DC

SBD3D - - - - Ready input(*2) 60 20 0 0 Ready input DC

SBD4D - - - - Ready input(*2) 60 20 0 0 Ready input DC

S1BB4D - - - - Ready input(*2) 60 20 0 0 Ready input DC

Oct. 25, 2016-00

Page 90: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-7

TI 32S01J30-01E

F050007.ai

5002 ,02 rebmeceD :etaD SR-efaSorP :ledoM

2-4.P 31A-410MFN :.oN .coD 6102 ,11 yraunaJ :7.veR

Yokogawa Electric Corporation

Specific condition of use: - The equipment shall be installed in a lockable metal cabinet. The suitability of the installation shall be determined by the authority having jurisdiction. - The Ambient Temperatures are as follows.

Model code Ambient Temperature

SSC10S-a2db1c When a = S, -20 to 50 °C When a = F, -20 to 70

SSC10D-a2db1c When a = S, -20 to 50 When a = F, -20 to 70

SSC50S-a2dbec When a = S, -20 to 40 When a = F, -20 to 70

SSC50D- a2dbec When a = S, -20 to 40 When a = F, -20 to 70

SSC57S- a2Ebdc When a = S, -20 to 40 When a = F, -20 to 70

SSC57D- a2Ebdc When a = S, -20 to 40 When a = F, -20 to 70

SSC60S-a2dbec When a = S, -20 to 40 When a = F, -20 to 70

SSC60D-a2dbec When a = S, -20 to 40 When a = F, -20 to 70

SNB10D -20 to 70 SNT10D -20 to 70 SCP401 -20 to 70 SCP451 -20 to 70 SCP461 -20 to 70 AIP504 -20 to 70 SEC401 -20 to 70 SEC402 -20 to 70 SSB401 -20 to 70 SPW481 -20 to 70 SPW482 -20 to 70 SPW484 -20 to 70 SNT401 -20 to 70 SNT501 -20 to 70 SNT411 -20 to 70 SNT511 -20 to 70 SNT421 -20 to 70 SNT521 -20 to 70 SAI143 -20 to 70 SAV144 -20 to 70 SAI533 -20 to 70

°C°C°C

°C°C°C°C°C°C°C°C°C°C°C°C

°C°C°C°C°C°C°C°C°C°C°C°C°C°C°C°C°C°C°C°C°C

Oct. 25, 2016-00

Page 91: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-8

TI 32S01J30-01E

F050008.ai

5002 ,02 rebmeceD :etaD SR-efaSorP :ledoM

3-4.P 31A-410MFN :.oN .coD 6102 ,11 yraunaJ :7.veR

Yokogawa Electric Corporation

Model code Ambient Temperature SAT145 -20 to 70 SAR145 -20 to 70 SDV144 -20 to 70 SDV531 -20 to 70 SDV541 -20 to 70 SDV521 -20 to 70 SDV53A -20 to 70 ALR111 0 to 60

ALR121-Sba When a = 1, 0 to 60 When a = B, 0 to 70 When a = 3, -20 to 70

ALE111-Sba When a = 1, 0 to 60 When a = 3, -20 to 70

SEA4D -20 to 70 SED4D -20 to 70 SED2D -20 to 70 SED3D -20 to 70 AIP602 -20 to 70 AEP7D -20 to 70 AEPV7D -20 to 70 SBA4D -20 to 70 SBT4D -20 to 70 SBR4D -20 to 70 SBD2D -20 to 70 SBD3D -20 to 70 SBD4D -20 to 70 S1BB4D -20 to 70 YNT511D 0 to 50 YNT522D 0 to 50 PW501 0 to 50 PW502 0 to 50 PW504 0 to 50 AIP578 0 to 50 AIP591 0 to 50 AIP171 0 to 50 AIP571 0 to 50

°C°C°C°C°C°C°C

°C°C°C

°C°C

°C°C°C°C°C°C°C°C°C°C°C°C°C°C°C

°C°C°C°C°C°C°C°C°C

Oct. 25, 2016-00

Page 92: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-9

TI 32S01J30-01E

F050009.ai

5002 ,02 rebmeceD :etaD SR-efaSorP :ledoM

3-4.P 31A-410MFN :.oN .coD 6102 ,11 yraunaJ :7.veR

Yokogawa Electric Corporation

Notes: 1. No revision to this drawing without prior approval of FM.

2. Installation must be in accordance with the National Electrical Code (NFPA 70) and

relevant local codes.

3. In the course of installation, the related documents of GS (General specifications), TI (Technical Information of Installation Guidance), and IM (User ’s Manuals) should be referred to and the instructions described in the documents should be observed.

4. PROSAFE-RS IS SUITABLE FOR USE IN CLASS 1, DIVISION 2, GROUPS A, B, C,

and D OR NONHAZARDOUS LOCATIONS ONLY. 5. It must be observed during the installation that the venting slots of the devices are

not blocked by cable parts, fixing accessories etc.

6. The doors of the cabinets must be closed when ProSafe-RS is energized.

Oct. 25, 2016-00

Page 93: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-10

TI 32S01J30-01E

F050010.ai

0102 ,41 yaM :etaD SR-efaSorP :ledoM

1-5.P 31A-410MFN :.oN .coD 6102 ,11 yraunaJ :2.veR

Yokogawa Electric Corporation

7. Nonincendive field wiring is permitted for the modules listed in tables of the

Nonincendive field wiring parameters.

7.1 The Nonincendive field wiring circuit concept allows interconnection of nonincendive field wiring apparatus with associated nonincendive field wiring apparatus, using any of the wiring methods permitted for unclassified locations.

7.2 Field equipment or other equipment connected to ProSafe-RS by Nonincendive field

wiring must be FM approved.

7.3 The control drawing of field equipment or other equipment must be followed at the installation.

7.4 The following conditions must be met. See tables for the Nonincendive field wiring

parameters of ProSafe-RS.

Vmax ≥ Voc or Vt; Imax ≥ Isc or It; Ca ≥ Ci + Ccable; La ≥ Li + Lcable

7.5 For current controlled circuits, Imax of the nonincendive field wiring apparatus is not required and need not be aligned with parameter Isc or It of ProSafe-RS or other associated nonincendive field wiring apparatus.

8. WARNING – SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR

DIVISION 2.

9. WARNING – EXPLOSION HAZARD. DO NOT DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT.

10. WARNING – EXPLOSION HAZARD. DO NOT REMOVE OR REPLACE FUSES

UNLESS POWER HAS BEEN DISCONNECTED OR WHEN A FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT.

11. WARNING – EXPLOSION HAZARD. DO NOT OPEN ENCLOSURE OR REPLACE

BATTERY WHEN A FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT.

12. WARNING – EXPOSURE TO ANY CHEMICALS MAY DEGRADE THE SEALING PROPERTIES OF MATERIALS USED IN THE RELAYS INCORPORATED IN THE FOLLOWING MODULES:

SBD2D SBD3D SBD4D S1BB4D

Oct. 25, 2016-00

Page 94: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-11

TI 32S01J30-01E

F050011.ai

5002 ,02 rebmeceD :etaD SR-efaSorP :ledoM

6.P 31A-410MFN :.oN .coD 6102 ,11 yraunaJ :3.veR

Yokogawa Electric Corporation

Control Drawing (Canada)

YNT522D

Non-HazardousLocation

Hazardous (Classified) LocationⅠClass ,Division 2

Groups A, B, C and D

ⅠClass ,Division 1

Cabinet

SEC401

SSB401+T Branch

YNT522D

SSC10D

SNB10D

SEA4D

Oct. 25, 2016-00

Page 95: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-12

TI 32S01J30-01E

F050012.ai

5002 ,02 rebmeceD :etaD SR-efaSorP :ledoM

7.P 31A-410MFN :.oN .coD 6102 ,11 yraunaJ :3.veR

Yokogawa Electric Corporation

SSC50D

SNB10D

SNT10D

SNB10D

SEA4DSEA4D

Non-HazardousLocation

Hazardous (Classified) LocationClass Ⅰ,Division 2

Groups A, B, C and D

Class Ⅰ,Division 1

Cabinet

Cabinet

SNT501

SNT401 SEC401

SSB401+T Branch

L2SW for Bus2L2SW for Bus1

Bus2

Bus1

SSB401+T Branch

Oct. 25, 2016-00

Page 96: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-13

TI 32S01J30-01E

F050013.ai

5002 ,02 rebmeceD :etaD SR-efaSorP :ledoM

8.P 31A-410MFN :.oN .coD 6102 ,11 yraunaJ :2.veR

Yokogawa Electric Corporation

Nonincendive Field Wiring Parameters (Output parameters) (*1)

(1/2)

Model Voc (V)

Isc (mA)

Ca(μF)

La (mH) Remarks

SSB401 - - - - (*2) SNT401 - - - - (*2) for YCB301 SNT501 - - - - (*2) for YCB301 SNT411 - - - - (*2) for YCB301 SNT511 - - - - (*2) for YCB301 SNT421 - - - - (*2) for YCB301 SNT521 - - - - (*2) for YCB301

SAI143

Redundant 26.4 26 0.13 10 -2-wire transmitter input -Included terminal block and terminal board but excluded cable. Single 26.4 26 0.13 10

Redundant 12.2 0.14 0.01 1 -Cable coming out detection (Wires connected to Pin No. 1 and 40) - Included terminal block and terminal board but excluded cable. Single 12.2 0.07 0.01 1

SAV144 Redundant 10 1.2 0.01 1 -Cable coming out detection

(Wires connected to Pin No. 1 and 40) -Included terminal block and terminal board but excluded cable. Single 10 0.6 0.01 1

SAI533

Redundant 18.9 23 0.16 10 -Output -Included terminal block and terminal board but excluded cable. Single 18.9 23 0.16 10

Redundant 10 220 0.01 1 -Cable coming out detection (Wires connected to Pin No. 1 and 40) -Included terminal block and terminal board but excluded cable. Single 10 110 0.01 1

SDV144 Redundant 11.6 1.4 0.01 1

-Cable coming out detection (Wires connected to Pin No. 1 and 50) -Included terminal block and terminal board but excluded cable Single 11.6 0.7 0.01 1

SDV531

Redundant - - - - Output (*2) Single - - - - Redundant 11.6 220 0.01 1 -Cable coming out detection

(Wires connected to Pin No. 1 and 50) -Included terminal block and terminal board but excluded cable

Single 11.6 110 0.01 1

SDV541

Redundant - - - - Output (*2) Single - - - -

Redundant 11.6 220 0.01 1 -Cable coming out detection (Wires connected to Pin No. 1 and 50) -Included terminal block and terminal board but excluded cable Single 11.6 110 0.01 1

(*1) These parameters are applied to all modes of each model if the mode is not otherwise remarked. (*2) Wiring for Division 2 (such as conduit systems) must comply with NEC or Local Electrical Code of each country.

Oct. 25, 2016-00

Page 97: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-14

TI 32S01J30-01E

F050014.ai

6102 ,11 yraunaJ :etaD SR-efaSorP :ledoM

9.P 31A-410MFN :.oN .coD .veR

Yokogawa Electric Corporation

Nonincendive Field Wiring Parameters (Output parameters) (*1)

(Continued) (2/2) Model Voc

(V) Isc

(mA) Ca

(μF)La

(mH) Remarks

SDV521

Redundant - - - - Output (*2) Single - - - - Redundant 11.6 220 0.01 1 -Cable coming out detection

(Wires connected to Pin No. 1 and 50) -Included terminal board but excluded cable Single 11.6 110 0.01 1

SDV53A

Redundant - - - - Output (*2) Single - - - -

Redundant 11.6 220 0.01 1 -Cable coming out detection (Wires connected to Pin No. 1 and 50) -Included terminal board but excluded cable Single 11.6 110 0.01 1

AEP7D - - - - (*2) AEPV7D - - - - (*2)

SAT145

Redundant 1.5 1.0 0.01 0.14 -RJC input -Included terminal board but excluded cable Single 1.5 1.0 0.01 0.14

Redundant 6.0 3.0 0.45 3.74 -TC/mv input (Burn out) -Included terminal board but excluded cable Single 6.0 3.0 0.45 3.74

Redundant 6.0 20.0 0.01 0.14 -Cable coming out detection (Wires connected to Pin No. 1 and 50) -Included terminal board but excluded cable. Single 6.0 20.0 0.01 0.14

SAR145

Redundant 6.0 50.0 0.20 1.32 -RTD input -Included terminal board but excluded cable. Single 6.0 50.0 0.20 1.32

Redundant 6.0 70.0 0.01 0.14 -Cable coming out detection (Wires connected to Pin No. 1 and 50) -Included terminal board but excluded cable. Single 6.0 70.0 0.01 0.14

(*1) These parameters are applied to all modes of each model if the mode is not otherwise remarked. (*2) Wiring for Division 2 (such as conduit systems) must comply with NEC or Local Electrical Code of each country.

Oct. 25, 2016-00

Page 98: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-15

TI 32S01J30-01E

F050015.ai

6102 ,11 yraunaJ :etaD SR-efaSorP :ledoM

01.P 31A-410MFN :.oN .coD .veR

Yokogawa Electric Corporation

Nonincendive Field Wiring Parameters (Input parameters) (*1)

(1/2)

(*1) These parameters are applied to all modes of each model if the mode is not otherwise remarked. (*2) Wiring for Division 2 (such as conduit systems) must comply with NEC or Local Electrical Code of each country.

Model Vmax (V)

Imax(mA)

Ci (μF)

Li (μH) Remarks

SPW481 - - - - (*2) SPW484 - - - - (*2) SSB401 - - - - (*2) SNT401 - - - - (*2) for YCB301 SNT501 - - - - (*2) for YCB301 SNT411 - - - - (*2) for YCB301 SNT511 - - - - (*2) for YCB301 SNT421 - - - - (*2) for YCB301 SNT521 - - - - (*2) for YCB301

SAI143 Redundant 26.4 26 0.008 20 -4-wire transmitter input

-Included terminal block and terminal board but excluded cable Single 26.4 26 0.004 20

SAV144 Redundant 30 0.6 0.001 10 -Input

-Included terminal block and terminal board but excluded cable Single 30 0.3 0.001 10

SDV144

Redundant - - - - Input (*2)

Single - - - - Redundant - - - - Power supply (*2) Single - - - -

SDV531 Redundant - - - - Power supply (*2) Single - - - -

SDV541 Redundant - - - - Power supply (*2) Single - - - -

SDV521 Redundant - - - - Power supply (*2) Single - - - -

SDV53A Redundant - - - - Power supply (*2) Single - - - -

Oct. 25, 2016-00

Page 99: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-16

TI 32S01J30-01E

F050016.ai

6102 ,11 yraunaJ :etaD SR-efaSorP :ledoM

11.P 31A-410MFN :.oN .coD .veR

Yokogawa Electric Corporation

Nonincendive Field Wiring Parameters (Input parameters) (*1)

(Continued) (2/2)

(*1) These parameters are applied to all modes of each model if the mode is not otherwise remarked. (*2) Wiring for Division 2 (such as conduit systems) must comply with NEC or Local Electrical Code of each country.

Model Vmax (V)

Imax(mA)

Ci (μF)

Li (μH) Remarks

AEP7D - - - - (*2) AEPV7D - - - - (*2)

SAT145

Redundant 5 1.53 0.6 10 -TC/mV input -Included terminal board but excluded cable Single 5 1.53 0.6 10

SBD2D - - - - Ready input(*2) 60 20 0 0 Ready input DC

SBD3D - - - - Ready input(*2) 60 20 0 0 Ready input DC

SBD4D - - - - Ready input(*2) 60 20 0 0 Ready input DC

S1BB4D - - - - Ready input(*2) 60 20 0 0 Ready input DC

Oct. 25, 2016-00

Page 100: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-17

TI 32S01J30-01E

F050017.ai

6102 ,11 yraunaJ :etaD SR-efaSorP :ledoM

21.P 31A-410MFN :.oN .coD .veR

Yokogawa Electric Corporation

Specific condition of use: - The equipment shall be installed in a lockable metal cabinet. The suitability of the installation shall be determined by the authority having jurisdiction. - The Ambient Temperatures are as follows.

Model code Ambient Temperature SNB10D -20 to 70 °C SNT10D -20 to 70 °C SSB401 -20 to 70 °C SPW481 -20 to 70 °C SPW484 -20 to 70 °C SNT401 -20 to 70 °C SNT501 -20 to 70 °C SNT411 -20 to 70 °C SNT511 -20 to 70 °C SNT421 -20 to 70 °C SNT521 -20 to 70 °C SAI143 -20 to 70 °C SAV144 -20 to 70 °C SAI533 -20 to 70 °C SAT145 -20 to 70 °C SAR145 -20 to 70 °C SDV144 -20 to 70 °C SDV531 -20 to 70 °C SDV541 -20 to 70 °C SDV521 -20 to 70 °C SDV53A -20 to 70 °C SEA4D -20 to 70 °C SED4D -20 to 70 °C SED2D -20 to 70 °C SED3D -20 to 70 °C SBA4D -20 to 70 °C SBT4D -20 to 70 °C SBR4D -20 to 70 °C SBD2D -20 to 70 °C SBD3D -20 to 70 °C SBD4D -20 to 70 °C S1BB4D -20 to 70 °C AEP7D -20 to 70 °C AEPV7D -20 to 70 °C

Oct. 25, 2016-00

Page 101: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-18

TI 32S01J30-01E Oct. 25, 2016-00

F050018.ai

6102 ,11 yraunaJ :etaD SR-efaSorP :ledoM

31.P 31A-410MFN :.oN .coD .veR

Yokogawa Electric Corporation

Notes: 1. No revision to this drawing without prior approval of FM.

2. Installation must be in accordance with Canadian Electrical Code Part I (C22.1) and

relevant local codes.

3. In the course of installation, the related documents of GS (General specifications), TI (Technical Information of Installation Guidance), and IM (User ’s Manuals) should be referred to and the instructions described in the documents should be observed.

4. PROSAFE-RS IS SUITABLE FOR USE IN CLASS 1, DIVISION 2, GROUPS A, B, C,

and D OR NON-HAZARDOUS LOCATIONS ONLY. 5. It must be observed during the installation that the venting slots of the devices are

not blocked by cable parts, fixing accessories etc.

6. The doors of the cabinets must be closed when ProSafe-RS is energized. 7. The instrument modification or parts replacement by other than authorized

representative of Yokogawa Electric Corporation is prohibited and will void FM Non-incendive Certification.

8. Nonincendive field wiring is permitted for the modules listed in tables of the

Nonincendive field wiring parameters.

8.1 The Nonincendive field wiring circuit concept allows interconnection of nonincendive field wiring apparatus with associated nonincendive field wiring apparatus, using any of the wiring methods permitted for unclassified locations.

8.2 Field equipment or other equipment connected to ProSafe-RS by Nonincendive field wiring must be FM approved.

8.3 The control drawing of field equipment or other equipment must be followed at the

installation.

8.4 The following conditions must be met. See tables for the Nonincendive field wiring parameters of ProSafe-RS.

Vmax ≥ Voc or Vt; Imax ≥ Isc or It; Ca ≥ Ci + Ccable; La ≥ Li + Lcable

8.5 For current controlled circuits, Imax of the nonincendive field wiring apparatus is

not required and need not be aligned with parameter Isc or It of ProSafe-RS or other associated nonincendive field wiring apparatus.

Page 102: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 5. US (FM) NI/Canada (FM) NI Control Drawing for ProSafe-RS FIO App.5-19

TI 32S01J30-01E Oct. 25, 2016-00

F050019.ai

6102 ,11 yraunaJ :etaD SR-efaSorP :ledoM

41.P 31A-410MFN :.oN .coD .veR

Yokogawa Electric Corporation

9. WARNING – EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS MAY

IMPAIR SUITABILITY FOR CLASS I, DIVISION 2. AVERTISSEMENT – RISQUE D’EXPLOSION – LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CE MATÉRIEL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE 1. DIVISION 2.

10. WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT WHILE CIRCUIT IS

LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS. AVERTISSEMENT – RISQUE D’EXPLOSION. NE PAS DÉBRANCHER TANT QUE LE CIRCUIT EST SOUS TENSION, À MOINS QU’IL NE S’AGISSE D’UN EMPLACEMENT NON DANGEREUX.

11. WARNING – EXPLOSION HAZARD – DO NOT REPLACE FUSES UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.

AVERTISSEMENT – RISQUE D’EXPLOSION – COUPER LE COURANT OU S’ASSURER QUE L’EMPLACEMENT EST DÉSIGNÉ NON DANGEREUX AVANT DE REPLACER LE COUPE-CIRCUIT À FUSIBLES.

12. WARNING – EXPLOSION HAZARD – BATTERIES MUST ONLY BE CHANGED IN

AN AREA KNOWN TO BE NON-HAZARDOUS. AVERTISSEMENT – RISQUE D’EXPLOSION – AFIN D’ÉVITER TOUT RISQUE LE D’EXPLOSION, S’ASSURER QUE L’EMPLACEMENT EST DÉSIGNÉ NON DANGEREUX AVANT DE CHANGER LA BATTRIE.

13. Use only the battery specified by Yokogawa Electric Corporation. Battery which is

mounted in SCP461 is S9185FA.

Page 103: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 6. US (FM) NI/Canada (FM) NI Control Drawing for S2BN5D App.6-1

TI 32S01J30-01E

Appendix 6. US (FM) NI/Canada (FM) NI Control Drawing for S2BN5D

F060001.ai

Model: S2BN5D-* Date: June 20, 2016

Rev. Doc. No.: IFM052-A100 P.1 Drawing: N. Nakahashi Approved: D. Harada

Yokogawa Electric Corporation

Control Drawing NOTES: 1 The Entity Concept allows interconnection of intrinsically safe apparatus with associated

apparatus not specifically examined in combination as a system when the approved values of Voc (or Uo) and Isc (or Io) for the associated apparatus are less than or equal to Vmax(Ui) and Imax(Ii) for the intrinsically safe apparatus. Capacitance and inductance of the field wiring from the intrinsically safe equipment to the associated apparatus shall be calculated and must be included in the system calculations. Cable capacitance, Ccable, plus intrinsically safe equipment capacitance, Ci must be less than the marked capacitance, Ca (or Co), shown on any associated apparatus used. The same applies for i nductance (Lcable, Li and La or Lo, respectively). Where the cable capacitance and inductance per foot are not known, the following values shall be used: Ccable = 60 pF/ft., Lcable = 0.2 μH/ft. The Entity Parameters of each channel depends on the barrier w hich is plug in the Base plate (see control drawing of the barrier).

2 This associated apparatus may also be connected to simple apparatus as defined in Article 504.2

and installed and temperature classified in accordance with Article 504.10(B) of the Nati onal Electrical Code (ANSI/NFPA 70), or other local codes, as applicable.

3 Where multiple circuits extend from the same piece of associated apparatus, they must be installed

in separate cables or in one cable having suitable insulation. Refer to Article 5 04.30(B) of the National Electrical Code (ANSI/NFPA 70) and Instrument Society of America Recommended Practice ISA RP12.6 for installing intrinsically safe equipment.

4 Intrinsically safe circuits must be wired and separated in accordance with Article 504. 20 of the

National Electrical Code (ANSI/NFPA 70) or other local codes, as applicable. 5 Associated apparatus must be installed in an enclosure suitable for the application in accordance

with the National Electrical Code (ANSI/NFPA 70) for installation in t he United States, the Canadian Electrical Code for installations in Canada, or other local codes, as applicable.

6 The Base plates shall not be connected to any device which uses or generates internally any voltage in excess of the maximum voltage Um of the barriers which are plug in the Base plate (see Control drawing of the barrier) unless the device has been determined to adequately isolate the voltage from the Base plate.

7 Wiring methods must be in accordance with the National Electrical Code for installations in the United States, the Canadian Electrical Code for installations in Canada, or other local codes, as applicable.

Any Simple Apparatus or approved device wi th Ent i ty Concept parameters (Vm a x, Im a x, C i , L i ) appropriate for connect ion to Associated Apparatus wi th Ent i ty Concept parameters l is ted in Table 1.

NONHAZARDOUS LOCATION or HAZARDOUS (CLASSIFIED) LOCATION CLASS I, DIVISION 1, GROUPS A,B,C,D CLASS II, DIVISION 1, GROUPS E,F,G CLASS III, DIVISION 1 or CLASS I, ZONE 0 and 1, IIC ZONE 20 and 21, IIIC

NONHAZARDOUS LOCATION

or CLASS I, DIVISION 2, GROUPS A,B,C,D

or CLASS I, ZONE 2, GROUP IIC

Base Plate for Barrier

Intrinsically Safe Connections Non-Intrinsically Safe

Connections

2 1

4 3

5 8 9

7 6

Oct. 25, 2016-00

Page 104: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

Appendix 6. US (FM) NI/Canada (FM) NI Control Drawing for S2BN5D App.6-2

TI 32S01J30-01E

F060002.ai

Model: S2BN5D-* Date: June 20, 2016

Rev. Doc. No.: IFM052-A100 P.2 Drawing: N. Nakahashi Approved: D. Harada

Yokogawa Electric Corporation

8 The Base plates are rated ‘Nonincendive’ for use in Class I, Division 2 or Zone 2 or non -hazardous locations. A temperature rating of T4 applies. If the Base plates are intended to be mounted in a Division 2 location, they must be mounted in an enclosure with a minimum ingress protection of IP2X. If the Base plates are intended to be mounted in a Zone 2 location, they must be mounted in an enclosure that is AEx certified (for US) or Ex certified (for Canada) with a minimum ingress protection of IP54 and installed in an area of not more than pollution degree 2.

9 Temperature range is -20 to +60°C. WARNING - Substitution of components may impair intrinsic safety and suitability for use in Class I, Div. 2/Zone 2. AVERTISSEMENT - La substitution de composants peut compromettre la sécurité intrinsèque et l 'adéquation à une utilisation en Classe I, Div. 2/Zone 2. WARNING - Do not disconnect the equipment when it is energized and an explosive atmosphere is present. AVERTISSEMENT - Ne pas débrancher l 'équipement lorsqu'il est sous tension et exposé à une atmosphère explosive. WARNING - Do not remove or replace fuse when energized. AVERTISSEMENT - Ne pas retirer ni remplacer de fusible sous tension

Oct. 25, 2016-00

Page 105: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

i

TI 32S01J30-01E

Revision InformationTitle : ExplosionProtection(ForProSafe-RS)ManualNo. : TI32S01J30-01E

June 2006/1st EditionNewly published

June 2007/2nd EditionAddition of new compliant products to FM NI and Type “n”.

June 2008/3rd Edition1.1 Complied standard number in the table “Explosion Protection Standards that ProSafe-RS Complies”

was revised.2.1 Sample in the title “Example” was changed into SAI143 from AAI141.2.2 Complied standard number of the “Complied Standards” was revised.

Nov. 2008/4th EditionAppendix1. SDV531-L,SDV521,SED2D,SNT411,SNT511andAKB651wereadded.Appendix2. SDV531-L,SDV521,SED2D,SNT411,SNT511andAKB651wereadded.

Nov. 2010/5th EditionAppendix1. SSC60S,SSC60D,SCP461,SEC402,SDV53A,SED3D,AKB331-M/SDV53Awere added. IscparametersforSDV521,SDV531andSDV541of“TableParameters(TheSource Devices)”wererevised.Appendix2. IoparametersforSDV521,SDV531andSDV541of“TableParameters(TheSource Devices)”wererevised.

June 2012/6th Edition1.1 Type “n” Complies standards were changed.2.1 precautions are added.2.2 Type “n” Complies standards were changed.Appendix1. SAT145,SAR145,SBT4D,SBR4D,SBA4D,SBD2D,SBD3D,SBD4D,AEPV7D,

AKB331-M/SAT14,AKB651-M/DV53L,AKB651-M/DV53A, AKB651-M/DV541,AKB611-MandAKB611-M/SAR14wereadded.Notes

were added. (TheSourceDevices),SAT145andSAR145wereadded.Notewasrevised. (TheLoadDevices)SAT145,SBD2D,SBD3DandSBD4Dwereadded.Notewasrevised

and added.Appendix2. SAT145,SAR145,SBT4D,SBR4D,SBA4D,SBD2D,SBD3D,SBD4D,AEPV7D,

AKB331-M/SAT14,AKB651-M/DV53L,AKB651-M/DV53A, AKB651-M/DV541,AKB611-MandAKB611-M/SAR14wereadded. (TheSourceDevices),SAT145andSAR145wereadded.Notewasrevised. (TheLoadDevices)SAT145wasadded.Notewasrevisedandadded.

Nov. 2012/7th Edition2.1 ALE111 was added.Appendix1. ALR121-S0BandALE111-S01wereadded. Modules of high-density installation were added. TemperatureRangeofAEPV7Dwasrevised. (TheSourceDevices)ALE111wasadded. (TheLoadDevices)ALE111wasadded.Appendix2. ALR121-S0BandALE111-S01wereadded. Modules of high-density installation were added. TemperatureRangeofAEPV7Dwasrevised. (TheSourceDevices)ALE111wasadded. (TheLoadDevices)ALE111wasadded.

Nov. 28, 2012-00

Page 106: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

ii

TI 32S01J30-01E

Apr. 2013/8th EditionGeneral Clerical error correction1.1 Type “n” standard number was changed. DescriptionsofNIstandardwererevised.1.2 DescriptionsandfigureswererevisedforchangeofType“n”standards.1.3 DescriptionsandfigureswererevisedforchangeofType“n”standards.2.1 DescriptionsofNIstandardwererevised.2.2 Type “n” standard number was change. DescriptionsandfigureswererevisedforchagneofType“n”standards.Appendix1. AEP7D-0,AEPV7D-0andAEPV7D-0 were deleted.Appendix2. Suffixcodesforexplosionprotectionwerechanged. Parameters of Type “n” were deleted. AEP7D-40,AEPV7D-40andAEPV7D-40 were deleted. STK4A-00andSTD4A-00weredeleted.

Sep. 2013/9th EditionGeneral Clerical error correctionAppendix1. Suffixcodesforexplosionprotectionwerechanged. SSC57 was added.Appendix 2. SSC57 was added.

Dec. 2013/10th EditionAppendix1. Suffixcodesforexplosionprotectionwerechanged.

Oct. 2014/11th EditionSafety Precautions [“Protective grounding terminal” was changed to “Protective conductor terminal”

(BasedonIEC61010-1)]1.1 “Table Explosion Protection Standards that ProSafe-RS Complies” [Reviseddescriptivetexts]2.1 Non-Incendive approved types and standards [Reviseddescriptivetexts]2.2 Type “n” complied standards [Reviseddescriptivetexts]Appendix 1. “Table NI Approved Products” [SNT421-E3,SNT421-E3/CU1N,SNT421-E3/CU1T,andSNT521-E3areadded] “TableParameters(TheSourceDevices)” [SNT421andSNT521areadded] “TableParameters(TheLoadDevices)” [SNT421andSNT521areadded]Appendix 2. “Table the List of Type “n” Compliant Products” [SNT421-E3,SNT421-E3/CU1N,SNT421-E3/CU1T,andSNT521-E3areadded]

Feb. 2015/12th EditionSafety Precautions Precautions were added.Appendix 1. ALR121-SE3 and ALE111-SE3 were added.Appendix 2. ALR121-SE3 and ALE111-SE3 were added.

Aug. 2015/13th EditionGeneral Clerical error correction1.1 ATEXType“n”standardnumberwasrevised.2.2 ATEXType“n”standardnumberwasrevised.Notewasadded.Appendix2. ATEXwasaddedinfrontofType“n”.

Nov. 2015/14th Edition1.1 Type “i” of “Table Explosion Protection Standards that ProSafe-RS Complies” was added.1.3 “Overview of Connecting N-IO Components” was added.2.2 S2BN5DofATEXType“n”wasadded. IECEx Type “n” was added.3 “3. Intrinsic Safety Explosion Protection Instrumentation” was added.

Nov. 27, 2015-00

Page 107: Technical Explosion Protection Information (For ProSafe-RS) · 2018-02-07 · book and ProSafe-RS Installation Guidance ) and the User’s Manuals. ... • Be sure to use the spare

iii

TI 32S01J30-01E June 30, 2017-00

Appendix2. S2BN5Dof“TableListofATEXType“n”CompliantProducts”wasadded. “Appendix 2.2 IECEx Type “n” Compliant Products” was added.Appendix3. “Appendix3.ListsofParametersofBasePlateforBarrier(S2BN5D)”wasadded.

June 2016/15th EditionAppendix1. SuffixcodeofSCP451isrevised.Appendix2. SuffixcodeofSCP451isrevised. Clerical error correction.

Oct. 2016/16th EditionGeneral FM Non-Incendive is changed into US(FM) Non-Incendive.SafetyPrecautions Descriptionsofsymbolsarerevised.1.1 “Table Explosion Protection Standards that ProSafe-RS Complies” is revised.1.2 OverviewofConnectingS2BN1D,S2BN4D,andS2BN5Disadded.2.1 DescriptionsofCanada(FM)NIareadded.2.2 DescriptionsofIECExType”n”arerevised.3.1.4 “Intrinsic Safety Explosion Protection of US (FM) Standard” is added.3.1.5 “Intrinsic Safety Explosion Protection of Canada (FM) Standard” is added.Appendix 1 N-IO-Related Products are added. NI Parameters are deleted.Appendix 1.2 “Canada(FM) NI Compliant Products” is added.Appendix 2 N-IO-Related Products are added.Appendix4 “US(FM)NI/Canada(FM)NIControlDrawingforProSafe-RSN-IO”isadded.Appendix5 “US(FM)NI/Canada(FM)NIControlDrawingforProSafe-RSFIO”isadded.Appendix6 “US(FM)NI/Canada(FM)NIControlDrawingforS2BN5D”isadded.

Apr. 2017/17th Edition1.1 Clerical error correction2.1 Clerical error correction2.2 Clerical error correction “ExampleofType“n”ConfigurationforVnet/IP”isadded.3.1 Clerical error correctionAppendix1 S2MDV843isadded. Optioncode/NTRYforTerminalBoardisadded.Appendix2 S2MDV843isadded. Optioncode/NTRYforTerminalBoardisadded. Clerical error correction.Appendix4 “US(FM)NI/Canada(FM)NIControlDrawingforProSafe-RSN-IO”isrevised.

June 2017/18th Edition1.1 Canada (FM) standard number was revised.2.1 Canada (FM) standard number was revised. Precautions were revised.