33
Tel: +45 8691 5542 Fax: +45 7734 4371 Mobile +45 2096 8598 EC VAT no.: DK3159 2585 www.ChimneyLab.dk [email protected] ChimneyLab Europe ApS Godthaabsvej 6 DK-8370 Hadsten Test report Requested by........................... Näldens Värmeindustri AB Date ....................... 02-06-2011 Contact person ........................ Mr Carlolof Hallström Page....................... 1 of 22 Address .................................... Näldenvägen 40 No of appendices . 3 Town ......................................... SE-83540 Nälden Country..................................... Sweden Telephone ................................ +0046 0640-681160 Email ......................................... [email protected] Report no ................................. ChimneyLab-101 Order no ................................... 0232 Product: Manufacturer ........................... Näldens Värmeindustri AB, Sweden Function ................................... Chimney Type .......................................... NVI 2000 Serial no ................................... - Received date .......................... 12-05-2011 Test date................................... 18-05-2011 30-05-2011 Procedure................................. Thermal test according to EN 1856-1:2009 and EN 1859:2009, Paragraph 4.5, only heat stress test and different test rig. Results ..................................... See Chapter 5 Conclusion ............................... See Chapter 6 Terms........................................ This test report or extracts from it may not be reproduced without the written permission of ChimneyLab Europe ApS. The test results concern only the tested objects. Lyngaa, Denmark 02-06-2011 Finn Petersen Process Engineer

Test report - nvi.fi · Test report Requested by ... \ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc The chimney was …

  • Upload
    volien

  • View
    219

  • Download
    1

Embed Size (px)

Citation preview

Tel: +45 8691 5542

Fax: +45 7734 4371

Mobile +45 2096 8598

EC VAT no.: DK3159 2585

www.ChimneyLab.dk [email protected]

ChimneyLab Europe ApS

Godthaabsvej 6

DK-8370 Hadsten

Test report Requested by ........................... Näldens Värmeindustri AB Date ....................... 02-06-2011 Contact person ........................ Mr Carlolof Hallström Page ....................... 1 of 22 Address .................................... Näldenvägen 40 No of appendices . 3 Town ......................................... SE-83540 Nälden Country ..................................... Sweden Telephone ................................ +0046 0640-681160 Email ......................................... [email protected]

Report no ................................. ChimneyLab-101 Order no ................................... 0232

Product: Manufacturer ........................... Näldens Värmeindustri AB, Sweden Function ................................... Chimney Type .......................................... NVI 2000 Serial no ................................... -

Received date .......................... 12-05-2011 Test date................................... 18-05-2011 – 30-05-2011 Procedure................................. Thermal test according to EN 1856-1:2009 and EN 1859:2009,

Paragraph 4.5, only heat stress test and different test rig.

Results ..................................... See Chapter 5 Conclusion ............................... See Chapter 6 Terms ........................................ This test report or extracts from it may not be reproduced without the written

permission of ChimneyLab Europe ApS. The test results concern only the tested objects.

Lyngaa, Denmark 02-06-2011

Finn Petersen Process Engineer

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 2 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

Table of Content

1. Introduction ............................................................................................................................... 3

2. Description of test specimen ..................................................................................................... 3

2.1. Double wall steel chimney .............................................................................................. 3

3. Test description ......................................................................................................................... 4

3.1. Gas tightness test............................................................................................................. 4

3.2. Thermal test ChimneyLab-101-A ................................................................................... 4

3.3. Thermal test ChimneyLab-101-B ................................................................................... 9

3.4. Thermal test ChimneyLab-101-C ................................................................................. 14

4. Instrumentation ....................................................................................................................... 19

5. Test results .............................................................................................................................. 20

5.1. Thermal results ChimneyLab-101-A ............................................................................ 20

5.2. Thermal results ChimneyLab-101-B ............................................................................ 21

5.3. Thermal results ChimneyLab-101-C ............................................................................ 21

6. Conclusion .............................................................................................................................. 22

7. Remarks .................................................................................................................................. 22

Appendices

Appendix 1: Thermal results

Appendix 2: Paroc pipe section 140

Appendix 3: Rockwool wired mat 105

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 3 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

1. Introduction

The purpose of this test is to determine the chimney thermal behaviour with insulated floor

penetration.

The thermal performance test was accomplished according to EN 1856-1:2009 and EN

1859:2009, paragraph 4.5, only heat stress test, and with modified test rig, which is described in

paragraph 3.

The test was carried out at ChimneyLab Europe ApS in Lyngaa, Denmark, by Process Engineer

Finn Petersen.

2. Description of test specimen

2.1. Double wall steel chimney

The test specimen is a black modular chimney, consisting of two circular steel pipes.

Between the two pipes is 60 mm insulation.

The tested chimney has a nominal diameter of 190 mm.

The standard modular length is 1170 mm, and the construction length 1150 mm. The chimney

modules are provided with nipple and sleeve, which gives a depth of the insert joint of 30 mm

for the outer pipe.

The cylindrical joints of the outer pipe are provided with circular beads, and secured by locking

bands which cover the joint. The width of the locking bands is 44 mm.

There are no metallic connections between inner and outer pipe.

Between the two pipes is 60 mm insulation, Paroc Pro Section 140 ALC F2, which is aluminium

coated on the outside, and is delivered in 1 whole piece. The insulation has a nominal density of

140 kg/m3 and a thermal conductivity of 0,083 W ∙ m-1 ∙ K-1 at an average temperature of 300

°C (without aluminium coating).

According to EN 1856-1:2009, paragraph 6.5.2, the inner pipe is manufactured in material type

60 (material no.1.4436) with a wall thickness of 1,0 mm.

The outer pipe is manufactured in hot-dip galvanized powder coated sheet steel and has a wall

thickness of 0,70 mm.

The chimney is CE-marked with the certificate number 0402-CPD-265403.

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 4 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

3. Test description

3.1. Gas tightness test

The chimney is classified as pressure type N1. As the chimney is already CE-marked, no gas

tightness tests are performed.

3.2. Thermal test ChimneyLab-101-A

Thermal test according to EN 1859:2009, paragraph 4.5, but the test rig is a modified type, to

enable test of penetrations with insulation heights up to 1000 mm. The test rig has only 1st floor

penetration, and no walls, since the critical temperatures are in the 1st floor penetration.

The chimney was mounted in modified thermal test rig with a distance of 102 mm to

combustibles,, and in 1st floor penetration the chimney was insulated with Paroc Pro Lock

Section 140, with an insulation height of 800 mm.

The pipe section has a nominal inner diameter of 324 mm and the outer diameter is 518 mm.

Between the chimney and pipe section is an air gap of approx. 5 mm.

The pipe section has a nominal density of 140 kg/m3 and a thermal conductivity of 0,083 W ∙ m-

1 ∙ K-1 at an average temperature of 300 °C

A blank ceiling plate was mounted below 1st floor. In the air gap between the chimney and the

ceiling plate was mounted a silicon rubber sealing.

Temperature sensors were mounted on combustibles in the test rig according to EN 1859:2000

Annex E (1) but with a distance of 100 mm between the thermocouples. Temperature sensor for

flue gas temperature was placed 50 mm before inlet of the tee.

Flue gas is generated by an LPG (Light Propane Gas) burner with a nominal thermal output of

90 kW.

The flue gas temperature is controlled via a programmable temperature controller and a thermal

mass flow controller.

Flue gas flow according to EN 1859:2009, Table 1, is controlled by the combustion air flow,

which is delivered to the combustion chamber by a centrifugal ventilator.

For this chimney, with a nominal diameter of 190 mm, the flue gas flow is set to 134 Nm3/h for

550 °C flue gas temperature.

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 5 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

Photo 1: Chimney installed in test rig

Photo 2: Top of floor penetration

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 6 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

Side 1

TE 1.1-1.5

Position of thermocouples

A A

Joist 1st floor

80

0

980

10

0

23

00

Side 3

TE 3.1-3.5

Side 4

TE 4.1-4.5

Side 1

TE 1.1 to 1.5

A-A

Joist 1st floor

Side 2

TE 2.1 to 2.5

Side 3

TE 3.1 to 3.5Side 4

TE 4.1 to 4.5

Air gap 7,5 mm

520

330

556

315

X = Thermocouples on combustibles

1 = Ceiling plate

2 = Sealing between chimney and ceiling plate

3 = Costumer insulation in floor penetration

4 = Building insulation

1

2

3

4

21

00

95

0

Figure 1: Test ChimneyLab-101-A

Position of thermocouples

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 7 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

The chimney was mounted and tested under the following conditions:

Test no. ChimneyLab-101-A

Temperature class T450

Pressure class N1

Soot fire test (1000 °C) No

Distance to walls in zone B, mm -

Shaft in zone B -

1st floor penetration:

Distance to combustibles, mm 102

Ceiling plate below floor penetration Yes

Air gap between lower ceiling plate and chimney, mm 0

Rubber gasket on lower ceiling plate Yes

Ceiling plate above floor penetration No

Air gap between upper ceiling plate and chimney, mm -

Rubber gasket on upper ceiling plate -

Insulation height in floor penetration, mm 800

Insulation type in floor penetration Air gap/Paroc Pro Section 140

Table 1: Test conditions

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 8 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

The chimney was tested in the following order:

Test order Description EN 1859:2009

Paragraph

1 Installation of chimney in thermal test rig. 4.5.3

2 Heat stress test T450 1st time

550 °C until steady state

4.5.3.1

Table 2: Thermal test order

Chimney elements used for the test were weighted and measured before installation:

Element

No.

Description Color Total

weight

kg

1 Tee Black 12,44

2 0,55 m section Black 9,21

3 0,55 m section Black 9,30

4 1,2 m section Black 18,64

5 1,2 m section Black 19,09

6 0,55 m section Black 9,01

Table 3: Chimney elements used in the test

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 9 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

3.3. Thermal test ChimneyLab-101-B

Thermal test according to EN 1859:2009, paragraph 4.5, but the test rig is a modified type, to

enable test of penetrations with insulation heights up to 1000 mm. The test rig has only 1st floor

penetration, and no walls, since the critical temperatures are in the 1st floor penetration.

The chimney was mounted in modified thermal test rig with a distance of 102 mm to

combustibles, and in 1st floor penetration the chimney was insulated with 200 mm height and a

thickness of 100 mm of Rockwool wired mat 105, On the next 600 mm the chimney was

insulated with 50 mm Rockwool wired mat 105, outside the wired mat was an air gap of 52 mm.

The wired net mat has a nominal density of 105 kg/m3 and a thermal conductivity of 0,087 W ∙

m-1 ∙ K-1 at an average temperature of 300 °C.

A blank ceiling plate was mounted below 1st floor. In the air gap between the chimney and the

ceiling plate was mounted a silicon rubber sealing.

Temperature sensors were mounted on combustibles in the test rig according to EN 1859:2000

Annex E (1) but with a distance of 100 mm between the thermocouples. Temperature sensor for

flue gas temperature was placed 50 mm before inlet of the tee.

Flue gas is generated by an LPG (Light Propane Gas) burner with a nominal thermal output of

90 kW.

The flue gas temperature is controlled via a programmable temperature controller and a thermal

mass flow controller.

Flue gas flow according to EN 1859:2009, Table 1, is controlled by the combustion air flow,

which is delivered to the combustion chamber by a centrifugal ventilator.

For this chimney, with a nominal diameter of 190 mm, the flue gas flow is set to 136 Nm3/h for

700 °C flue gas temperature.

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 10 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

Photo 4: Chimney installed in test rig

Photo 3: Floor penetration

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 11 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

Side 1

TE 1.1-1.5

Position of thermocouples

A A

Joist 1st floor

80

0

980

10

0

23

00

Side 3

TE 3.1-3.5

Side 4

TE 4.1-4.5

Side 1

TE 1.1 to 1.5

A-A

Joist 1st floor

Side 2

TE 2.1 to 2.5

Side 3

TE 3.1 to 3.5Side 4

TE 4.1 to 4.5

Air gap 7,5 mm

520

324

556

315

X = Thermocouples on combustibles

1 = Ceiling plate

2 = Sealing between chimney and ceiling plate

3 = Costumer insulation in floor penetration

4 = Building insulation

1

2

3

4

21

00

95

0

Figure 2: Test ChimneyLab-101-B

Position of thermocouples

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 12 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

The chimney was mounted and tested under the following conditions:

Test no. ChimneyLab-101-B

Temperature class T600

Pressure class N1

Soot fire test (1000 °C) No

Distance to walls in zone B, mm -

Shaft in zone B -

1st floor penetration:

Distance to combustibles, mm 102

Ceiling plate below floor penetration Yes

Air gap between lower ceiling plate and chimney, mm 0

Rubber gasket on lower ceiling plate Yes

Ceiling plate above floor penetration No

Air gap between upper ceiling plate and chimney, mm -

Rubber gasket on upper ceiling plate -

Insulation height in floor penetration, mm 800

Insulation type in floor penetration Rockwool wired mat/air gap

Table 4: Test conditions

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 13 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

The chimney was tested in the following order:

Test order Description EN 1859:2009

Paragraph

1 Installation of chimney in thermal test rig. 4.5.3

2 Heat stress test T600 1st time

700 °C until steady state

4.5.3.1

Table 5: Thermal test order

Chimney elements used for the test were weighted and measured before installation:

Element

No.

Description Color Total

weight

kg

1 Tee Black 12,44

2 0,55 m section Black 9,21

3 0,55 m section Black 9,30

4 1,2 m section Black 18,64

5 1,2 m section Black 19,09

6 0,55 m section Black 9,01

Table 6: Chimney elements used in the test

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 14 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

3.4. Thermal test ChimneyLab-101-C

Thermal test according to EN 1859:2009, paragraph 4.5, but the test rig is a modified type, to

enable test of penetrations with insulation heights up to 1000 mm. The test rig has only 1st floor

penetration, and no walls, since the critical temperatures are in the 1st floor penetration.

The chimney was mounted in modified thermal test rig with a distance of 50 mm to

combustibles, and in 1st floor penetration the chimney was insulated with 400 mm height and a

thickness of 50 mm of Rockwool wired mat 105.

The wired net mat has a nominal density of 105 kg/m3 and a thermal conductivity of 0,087 W ∙

m-1 ∙ K-1 at an average temperature of 300 °C

A blank ceiling plate was mounted below 1st floor. In the air gap between the chimney and the

ceiling plate was mounted a silicon rubber sealing.

Temperature sensors were mounted on combustibles in the test rig according to EN 1859:2000

Annex E (1) with a distance of 50 mm between the thermocouples. Temperature sensor for flue

gas temperature was placed 50 mm before inlet of the tee.

Flue gas is generated by an LPG (Light Propane Gas) burner with a nominal thermal output of

90 kW.

The flue gas temperature is controlled via a programmable temperature controller and a thermal

mass flow controller.

Flue gas flow according to EN 1859:2009, Table 1, is controlled by the combustion air flow,

which is delivered to the combustion chamber by a centrifugal ventilator.

For this chimney, with a nominal diameter of 190 mm, the flue gas flow is set to 134 Nm3/h for

550 °C flue gas temperature.

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 15 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

Photo 5: Chimney installed in test rig

Photo 6: Top of floor penetration

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 16 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

Side 1

TE 1.1-1.5

Position of thermocouples

Joist 1st floor

40

0

990

50

23

00

Side 3

TE 3.1-3.5

Side 4

TE 4.1-4.5

Side 1

TE 1.1 to 1.5

A-A

Joist 1st floor

Side 2

TE 2.1 to 2.5

Side 3

TE 3.1 to 3.5Side 4

TE 4.1 to 4.5

Air gap 7,5 mm

415

451

315

X = Thermocouples on combustibles

1 = Ceiling plate

2 = Sealing between chimney and ceiling plate

3 = Costumer insulation in floor penetration

4 = Building insulation

1

2

3

4

25

00

95

0

A A

Figure 3: Test ChimneyLab-101-C

Position of thermocouples

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 17 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

The chimney was mounted and tested under the following conditions:

Test no. ChimneyLab-101-C

Temperature class T450

Pressure class N1

Soot fire test (1000 °C) No

Distance to walls in zone B, mm -

Shaft in zone B -

1st floor penetration:

Distance to combustibles, mm 50

Ceiling plate below floor penetration Yes

Air gap between lower ceiling plate and chimney, mm 0

Rubber gasket on lower ceiling plate Yes

Ceiling plate above floor penetration No

Air gap between upper ceiling plate and chimney, mm -

Rubber gasket on upper ceiling plate -

Insulation height in floor penetration, mm 400

Insulation type in floor penetration Rockwool wired mat

Table 7: Test conditions

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 18 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

The chimney was tested in the following order:

Test order Description EN 1859:2009

Paragraph

1 Installation of chimney in thermal test rig. 4.5.3

2 Heat stress test T450 1st time

550 °C until steady state

4.5.3.1

Table 8: Thermal test order

Chimney elements used for the test were weighted and measured before installation:

Element

No.

Description Color Total

weight

kg

1 Tee Black 12,44

2 0,55 m section Black 9,21

3 0,55 m section Black 18,83

4 1,2 m section Black 18,51

5 1,2 m section Black 9,35

6 0,55 m section Black 9,13

Table 9: Chimney elements used in the test

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 19 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

4. Instrumentation

Table 10 shows the equipment used for the test.

Instrument Type Reference Accuracy

Vibration table ChimneyLab CLE-014 -

Thermal test rig ChimneyLab CLE-075 -

Data acquisition unit HP 34970A CLE-009 -

Data acquisition software TIDop DTI -

Gas burner ChimneyLab CLE-003 -

Flow combustion air Orifice, ChimneyLab CLE-003-001 ± 0,5 Nm3/h

Flow combustion air Micro manometer TSI

8702-M-GB

CLE-008-001 ± 1 Pa

Temperature controller CAL 9500 CLE-003-003 ± 0,5 °C

Thermocouple, flue gas inlet Type K CLE-001-201 ± 0,5 °C

Thermocouples, surface temperatures Type K CLE-022-101 to 120 ± 0,5 °C

Gas tightness, flow ChimneyLab CLE-011 ± 0,1 Nm3/h

Gas tightness, pressure Dwyer Magnehelic CLE-011-005 ± 1 Pa

Weight Mettler Toledo BBA 422-35LA CLE-006 ± 0,5 g

Circumference Echwenk CJU 950 CLE-012 ± 0,5 mm

Circumference Echwenk CJU 2200 CLE-013 ± 0,5 mm

Wall thickness Schut electronic gear micrometer CLE-010 ± 0,005mm

Table 10: Test equipment

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 20 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

5. Test results

5.1. Gas tightness test

The chimney is classified as pressure type N1. As the chimney is already CE-marked, no gas

tightness tests are performed.

5.2. Thermal results ChimneyLab-101-A

The chimney as described in paragraph 2 and installed as described in paragraph 3, achieved the

following maximum temperatures, all corrected to 20 °C ambient temperature:

Heat stress

T450 1st time

Limit

acc. to

EN 1856-1

*

Below

maximum

limit*

Flue gas temperature °C 550 - -

Max. 1st floor, joist °C 67 85 (Yes)**

Table 11: Results of thermal tests

All surface temperatures corrected to 20 °C ambient

* According to EN 1856-1:2009 the maximum temperature limit on all combustibles surfaces is

for Heat Stress Test 85 °C.

** The test was stopped after 6,5 hours at 550 °C. At that time the maximum rise of rate of the

thermocouples on combustibles in 1st floor was 4 °C/30 minutes. The demand is for EN

1859:2009 2 °C/30 minutes. The demand for EN 13216-1:2004 is also 2 °C/30 minutes but

maximum test time is 6 hours.

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 21 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

5.3. Thermal results ChimneyLab-101-B

The chimney as described in paragraph 2 and installed as described in paragraph 3, achieved the

following maximum temperatures, all corrected to 20 °C ambient temperature:

Heat stress

T600 1st time

Limit

acc. to

EN 1856-1

*

Below

maximum

limit*

Flue gas temperature °C 700 - -

Max. 1st floor, joist °C 58 85 Yes

Table 12: Results of thermal tests

All surface temperatures corrected to 20 °C ambient

* According to EN 1856-1:2009 the maximum temperature limit on all combustibles surfaces is

for Heat Stress Test 85 °C.

5.4. Thermal results ChimneyLab-101-C

The chimney as described in paragraph 2 and installed as described in paragraph 3, achieved the

following maximum temperatures, all corrected to 20 °C ambient temperature:

Heat stress

T450 1st time

Limit

acc. to

EN 1856-1

*

Below

maximum

limit*

Flue gas temperature °C 550 - -

Max. 1st floor, joist °C 73 85 Yes

Table 13: Results of thermal tests

All surface temperatures corrected to 20 °C ambient

* According to EN 1856-1:2009 the maximum temperature limit on all combustibles surfaces is

for Heat Stress Test 85 °C.

ChimneyLabEurope

Date: 02-06-2011 Report No. ChimneyLab-101 Page 22 of 22

E:\ChimneyLab\A Prøvninger\ChimneyLab-101 NVI Finsk prøvning\ChimneyLab-101 Report.doc

6. Conclusion

The chimney, tested under the conditions described in chapter 3, meets the requirements in EN

1856-1:2009 regarding:

Combustibles surface temperatures during 1st heat stress test

However test ChimneyLab-101-A was stopped after 6,5 hours without having reached

steady state.

7. Remarks

All information from the manufacturer regarding materials used for the chimney has been

assumed by ChimneyLab Europe ApS. The materials have not been subject to any qualitative

tests, except from an immediate visual evaluation.

This report is not an approval, but the result of a test. Producer/importing company are obligated

to ensure that all relevant regulations during sale and installation of the chimney are fulfilled.

Report no. ChimneyLab-101 Appendix 1B, page 1 of 3

ChimneyLab-101-A

Internal diameter, mm = 190 T450

Chimney insulation thickness, mm = 60

Distance to combustibles, mm = 102 T = 550 °C

Ceiling plate below floor? = Yes

Ceiling plate above floor = no Max.

Gap ceiling plate, mm = 0

Insulation heigth in 1st floor, mm = 800 0

Insulation heigth in 2nd floor, mm = -

Total height, m = 5.2 Steady State

[°C]

Fluegas inlet 553Joist 1st floor Side 1,1 40Joist 1st floor Side 1,2 50Joist 1st floor Side 1,3 55

Joist 1st floor Side 1,4 58Joist 1st floor Side 1,5 58Joist 1st floor Side 2,1 40Joist 1st floor Side 2,2 50

Joist 1st floor Side 2,3 57Joist 1st floor Side 2,4 61Joist 1st floor Side 2,5 62Joist 1st floor Side 3,1 49Joist 1st floor Side 3,2 58Joist 1st floor Side 3,3 65Joist 1st floor Side 3,4 67Joist 1st floor Side 3,5 65

Joist 1st floor Side 4,1 53Joist 1st floor Side 4,2 60Joist 1st floor Side 4,3 64Joist 1st floor Side 4,4 66Joist 1st floor Side 4,5 64Room1 24Room2 24

Report no. ChimneyLab-101 Appendix 1B, page 2 of 3

ChimneyLab-101-A, T = 550 °C

0

100

200

300

400

500

600

10:00 12:00 14:00 16:00 18:00 20:00 22:00

Time

Tem

pera

ture

[°C

]

Fluegas inlet

18-05-2011

Flue Gas Temperatures

ChimneyLab-101-A, T = 550 °C

0

10

20

30

40

50

60

70

80

10:00 12:00 14:00 16:00 18:00 20:00 22:00

Time

Tem

pera

ture

[°C

]

Joist 1st floor Side 1,1 Joist 1st floor Side 1,2 Joist 1st floor Side 1,3 Joist 1st floor Side 1,4 Joist 1st floor Side 1,5

Joist 1st floor Side 2,1 Joist 1st floor Side 2,2 Joist 1st floor Side 2,3 Joist 1st floor Side 2,4 Joist 1st floor Side 2,5

Joist 1st floor Side 3,1 Joist 1st floor Side 3,2 Joist 1st floor Side 3,3 Joist 1st floor Side 3,4 Joist 1st floor Side 3,5

Joist 1st floor Side 4,1 Joist 1st floor Side 4,2 Joist 1st floor Side 4,3 Joist 1st floor Side 4,4 Joist 1st floor Side 4,5

18-05-2011

Combustible 1st floor temperatures

Max. Temperature(20 °C) during test = 67.4 °C

All temperatures corrected to 20°C ambient

Report no. ChimneyLab-101 Appendix 1B, page 3 of 3

ChimneyLab-101-A, T = 550 °C

0

5

10

15

20

25

10:00 12:00 14:00 16:00 18:00 20:00 22:00

Time

Tem

pera

ture

[°C

]

Room1 Room2

18-05-2011

Ambient Temperatures

Report No. ChimneyLab-101 Appendix 1B, page 1 of 3

ChimneyLab-101-B

Internal diameter, mm = 190 T600

Chimney insulation thickness, mm = 60

Distance to combustibles, mm = 102 T = 700 °C

Ceiling plate below floor? = Yes

Ceiling plate above floor = no Max.

Gap ceiling plate, mm = 0

Insulation heigth in 1st floor, mm = 800 0

Insulation heigth in 2nd floor, mm = - 16:24

Total height, m = 5.2 Steady State

[°C]

Fluegas inlet 702

Joist 1st floor Side 1,1 48

Joist 1st floor Side 1,2 34

Joist 1st floor Side 1,3 33

Joist 1st floor Side 1,4 34

Joist 1st floor Side 1,5 37

Joist 1st floor Side 2,1 49

Joist 1st floor Side 2,2 35

Joist 1st floor Side 2,3 35

Joist 1st floor Side 2,4 34

Joist 1st floor Side 2,5 37

Joist 1st floor Side 3,1 58

Joist 1st floor Side 3,2 36

Joist 1st floor Side 3,3 35

Joist 1st floor Side 3,4 36

Joist 1st floor Side 3,5 50

Joist 1st floor Side 4,1 56

Joist 1st floor Side 4,2 34

Joist 1st floor Side 4,3 34

Joist 1st floor Side 4,4 35

Joist 1st floor Side 4,5 45

Ceiling plate 85 mm from chimney 46

Ceiling 200 mm from chimney 37

Room1 24

Room2 24

Report No. ChimneyLab-101 Appendix 1B, page 2 of 3

ChimneyLab-101-B, T = 700 °C

0

100

200

300

400

500

600

700

800

10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00

Time

Tem

pera

ture

[°C

]

Fluegas inlet

24-05-2011

Flue Gas Temperatures

ChimneyLab-101-B, T = 700 °C

0

10

20

30

40

50

60

70

10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00

Time

Tem

pera

ture

[°C

]

Joist 1st floor Side 1,1 Joist 1st floor Side 1,2 Joist 1st floor Side 1,3 Joist 1st floor Side 1,4 Joist 1st floor Side 1,5

Joist 1st floor Side 2,1 Joist 1st floor Side 2,2 Joist 1st floor Side 2,3 Joist 1st floor Side 2,4 Joist 1st floor Side 2,5

Joist 1st floor Side 3,1 Joist 1st floor Side 3,2 Joist 1st floor Side 3,3 Joist 1st floor Side 3,4 Joist 1st floor Side 3,5

Joist 1st floor Side 4,1 Joist 1st floor Side 4,2 Joist 1st floor Side 4,3 Joist 1st floor Side 4,4 Joist 1st floor Side 4,5

24-05-2011

Combustible 1st floor temperatures

Max. Temperature(20 °C) at Steady State = 58.0 °C

All temperatures corrected to 20°C ambient

Report No. ChimneyLab-101 Appendix 1B, page 3 of 3

ChimneyLab-101-B, T = 700 °C

0

5

10

15

20

25

30

35

40

45

50

10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00

Time

Tem

pera

ture

[°C

]

Ceiling plate 85 mm from chimney Ceiling 200 mm from chimney

24-05-2011

Ceiling temperatures

Max. Temperature(20 °C) at Steady State = 46.3 °C

All temperatures corrected to 20°C ambient

ChimneyLab-101-B, T = 700 °C

0

5

10

15

20

25

30

10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00

Time

Tem

pera

ture

[°C

]

Room1 Room2

24-05-2011

Ambient Temperatures

Report no. ChimneyLab-101 Appendix 1C, page 1 of 3

ChimneyLab-101-C

Internal diameter, mm = 190 T450

Chimney insulation thickness, mm = 60

Distance to combustibles, mm = 50 T = 550 °C

Ceiling plate below floor? = Yes

Ceiling plate above floor = no Max.

Gap ceiling plate, mm = 0

Insulation heigth in 1st floor, mm = 400 0

Insulation heigth in 2nd floor, mm = - 22:52

Total height, m = 5.2 Steady State

[°C]

Fluegas inlet 551Joist 1st floor Side 1,1 60Joist 1st floor Side 1,2 64Joist 1st floor Side 1,3 66

Joist 1st floor Side 1,4 67Joist 1st floor Side 1,5 62Joist 1st floor Side 2,1 59Joist 1st floor Side 2,2 62

Joist 1st floor Side 2,3 64Joist 1st floor Side 2,4 65Joist 1st floor Side 2,5 63Joist 1st floor Side 3,1 66Joist 1st floor Side 3,2 70Joist 1st floor Side 3,3 71Joist 1st floor Side 3,4 71Joist 1st floor Side 3,5 66

Joist 1st floor Side 4,1 65Joist 1st floor Side 4,2 70Joist 1st floor Side 4,3 73Joist 1st floor Side 4,4 72Joist 1st floor Side 4,5 68Ceiling plate 50 mm from chimney, side 1 40Ceiling plate 50 mm from chimney, side 4 38Room1 25

Room2 25

Report no. ChimneyLab-101 Appendix 1C, page 2 of 3

ChimneyLab-101-C, T = 550 °C

0

100

200

300

400

500

600

14:00 16:00 18:00 20:00 22:00 00:00 02:00 04:00 06:00 08:00 10:00

Time

Te

mp

era

ture

[°C

]

Fluegas inlet

30-05-2011

Flue Gas Temperatures

ChimneyLab-101-C, T = 550 °C

0

10

20

30

40

50

60

70

80

14:00 16:00 18:00 20:00 22:00 00:00 02:00 04:00 06:00 08:00 10:00

Time

Te

mp

era

ture

[°C

]

Joist 1st floor Side 1,1 Joist 1st floor Side 1,2 Joist 1st floor Side 1,3 Joist 1st floor Side 1,4 Joist 1st floor Side 1,5

Joist 1st floor Side 2,1 Joist 1st floor Side 2,2 Joist 1st floor Side 2,3 Joist 1st floor Side 2,4 Joist 1st floor Side 2,5

Joist 1st floor Side 3,1 Joist 1st floor Side 3,2 Joist 1st floor Side 3,3 Joist 1st floor Side 3,4 Joist 1st floor Side 3,5

Joist 1st floor Side 4,1 Joist 1st floor Side 4,2 Joist 1st floor Side 4,3 Joist 1st floor Side 4,4 Joist 1st floor Side 4,5

30-05-2011

Combustible 1st floor temperatures

Max. Temperature(20 °C) at Steady State = 73.2 °C

All temperatures corrected to 20°C ambient

Report no. ChimneyLab-101 Appendix 1C, page 3 of 3

ChimneyLab-101-C, T = 550 °C

0

5

10

15

20

25

30

35

40

45

14:00 16:00 18:00 20:00 22:00 00:00 02:00 04:00 06:00 08:00 10:00

Time

Te

mp

era

ture

[°C

]

Ceiling plate 50 mm from chimney, side 1 Ceiling plate 50 mm from chimney, side 4

30-05-2011

Ceiling temperatures

Max. Temperature(20 °C) at Steady State = 40.2 °C

All temperatures corrected to 20°C ambient

ChimneyLab-101-C, T = 550 °C

0

5

10

15

20

25

30

14:00 16:00 18:00 20:00 22:00 00:00 02:00 04:00 06:00 08:00 10:00

Time

Te

mp

era

ture

[°C

]

Room1 Room2

30-05-2011

Ambient Temperatures

Mer info på www.paroc.se

PRODUKTER ■

11

Industri- och processrörskålar

PAROC Pro Bend 100 PAROC Pro Bend 140

AnvändningPAROC Pro Bend 100 och 140 är en prefabricerad isolering för rörböjar. Är i kombination med PAROC Pro Section en systemlösning. PAROC Pro Bend 100 och 140 rekommenderas vid tuffa miljöer såsom höga temperaturer, vibrationer m m.

ProduktdataRörskålsböj av stenull.Förpackning: Wellpappkartong.Pallstorlek: 1200 x 1200 mm.Densitet: Ca 100 respektive 140 kg/m3.Högsta rekommenderade användningstemperatur: 700°C. Brandteknisk klass: Euroklass A1 (obrännbart material).

Värmekonduktivitet λ, W/m °CProdukt Medeltemperatur, °C 10 50 100 150 200 300 400

PAROCPro Bend 100 0,034 0,037 0,042 0,049 0,059 0,083 0,116

PAROCPro Bend 140 0,037 0,039 0,043 0,049 0,057 0,077 0,104

PAROCPro Segment 100 0,034 0,037 0,042 0,049 0,059 0,083 0,116

PAROCPro Segment 140 0,037 0,039 0,043 0,049 0,057 0,077 0,104

PAROCPro Segment 100 DL 0,034 0,037 0,042 0,049 0,059 0,083 0,116

PAROCPro Segment 140 DL 0,037 0,039 0,043 0,049 0,057 0,077 0,104

PAROC Pro Segment 100 PAROC Pro Segment 140

AnvändningPAROC Pro Segment 100 och 140 är en prefabricerad isolering för rörböjar. Är i kombination med PAROC Pro Section en systemlösning. PAROC Pro Segment 100 och 140 rekommenderas vid tuffa miljöer såsom höga temperaturer, vibrationer m m.

ProduktdataRörskålsböj av stenull.Förpackning: Plast emballage på pall. Staplas som en rörskål. Toppen och bot-ten är transportskydd och inte en del av rörskålsböjen.Pallstorlek: 1200 x 1200 mm.Densitet: Ca 100 respektive 140 kg/m3.Högsta rekommenderade användningstemperatur: 700°C. Brandteknisk klass: Euroklass A1 (obrännbart material).

PAROC Pro Segment 100 DL PAROC Pro Segment 140 DL

AnvändningPAROC Pro Segment 100 DL och 140 DL är en prefabricerad isolering för stora rörböjar. Är i kombination med PAROC Pro Section DL och PAROC Pro Lock en systemlösning. PAROC Pro Segment100 DL och 140 DL rekommenderas vid tuffa miljöer såsom höga temperaturer, vibrationer m m.

ProduktdataTvå rörskålsböjar av stenull för montage i dubbla lager.Förpackning: Plast emballage på pall. Staplas som en rörskål. Toppen och bot-ten är transportskydd och inte en del av rörskålsböjen.Pallstorlek: 1200 x 1200 mm.Densitet: Ca 100 respektive 140 kg/m3.Högsta rekommenderade användningstemperatur: 700°C. Brandteknisk klass: Euroklass A1 (obrännbart material).

Format, standardProdukt Inner- Tjocklek Längd diam. mm mm mm

PAROC 22-168 20-120 Pro Bend 100 och140

PAROC 102-1016 30-200 Pro Segment100 och140

PAROC 168-914 80-300 Pro Segment 100 DL och140 DL

ChimneyLab-101, Appendix 2, page 1 of 1

Alu-Trådvævsmåtte 105

Tekniske egenskaber

Kvalitetssikring

Produkt

Anvendelse

Rockwool Alu-Trådvævsmåtte 105 er fremstillet af stenuld. Forsiden er beklædt med armeret alufolie og 

påsyet 1” galvaniseret trådnet.. Bagsiden af Rockwool Alu-Trådvævsmåtte 105 er ubeklædt.

Højtemperaturisolering af rør, beholdere, ovne, røggaskanaler, kedler, skorstene og plane flader, hvor der 

især er pladskrav. Gode lyddæmpende egenskaber.

 

Emne Værdi Standarder  og Godkendelser

Isoleringsevneλ-værdi

T  °C 10 50 100 150 200 250 300 400

mW/m∙K 34 39 45 54 63 74 87 116

VIF-kontrol

λ-værdi, beregning λ(T )=3,324∙10  + 0,940 ∙10  ∙ T  + 2,832 ∙10  ∙ T

 

Maxanvendelsestemp.

Uldside 750°C  . Alu-belagt side 250 °C. 

Galvanisering trådnet 550°C

 

Brand Ubrændbar ISO 1182

Vandabsorption < 1 vol. % BS2972:75

Fugtabsorption Ca. 0,002 vol. % v. 90 % RF  

Dampdiffusionstal Ca. 0,15 kg/GPa ∙ m ∙ s  

Dimensionsstabilitet Længdeudvidelseskoefficient =  0   Svind (krympning) =  0

 

Specifik varme 0,8 kJ/Kg. ∙ K  

 

Rockwool A/S har et kvalitetsstyringssystem, som er certificeret efter DS/EN ISO 9001. Rockwool A/S er medlem af VIF ( Dansk

forening af Fabrikanter af varmeisoleringsmaterialer), og Rockwool A/S produkter er med i Keymark-ordningen , etableret af den

europæiske standardiseringsorganisation CEN (undtaget for CE og Keymark er dog produkterne Hulrumsfyld, Granulat PRO og 

Loftgranulat).

Rockwool Byggeprodukter er løbende under udvikling og produkternes tekniske specifikationer er angivet med forbehold for ændringer.

Rockwool A/S er tilsluttet byggeleveranceklausulen for leverancer til byggeri i Danmark.

m

m-2 -4

m-7

m2

01-06 2011 01:05 - http://guiden.rockwool.dk/produkter/teknisk-isolering/alu-traadvaevsmaatte-105?&w=psheet 1 / 1

ChimneyLab-101, Appendix 3, page 1 of 1