U P S Uninterruptible Power System Line Interactive Network Protection Pure Sine Wave Output UPS Tower Models 600VA/ 800VA/ 1000VA/ 1250VA/ 1500VA/ 2000VA/ 2500VA/ 3000VA Rack Mount Models 600VA/ 800VA/ 1000VA/ 1250VA/ 1500VA/ 2000VA/ 2500VA/ 3000VA Extended Run-Time Models 1000AL/ 2000AL/ 3000AL USER‘S MANUAL

Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

  • Upload
    vandung

  • View
    214

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 1 頁 2003/3/4

U P S Uninterruptible Power System

Line Interactive Network Protection

Pure Sine Wave Output UPS

Tower Models 600VA/ 800VA/ 1000VA/ 1250VA/

1500VA/ 2000VA/ 2500VA/ 3000VA

Rack Mount Models 600VA/ 800VA/ 1000VA/ 1250VA/

1500VA/ 2000VA/ 2500VA/ 3000VA

Extended Run-Time Models 1000AL/ 2000AL/ 3000AL

■■■■USER‘S MANUAL■■■■

Page 2: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 2 頁 2003/3/4

IMPORTANT SAFETY INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS ●CAUTION (UPS Having Internal Batteries): Risk of electric shock - Hazardous live parts

inside this unit are energized from the battery supply even when the input AC power is disconnected.

●CAUTION (No User serviceable Parts): Risk of electric shock, do not remove cover. No

user serviceable parts inside. Refer servicing to qualified service personnel. ●CAUTION (Non-isolated Battery supply): Risk of electric shock, battery circuit is not isolated from AC input, hazardous voltage may exist between battery terminals and ground. Test before touching. ●WARNING (Fuses): To reduce the risk of fire, replace only with the same type and rating

of fuse. ●WARNING: Intend for installation in a controlled environment. ●CAUTION: Do not dispose of batteries in a fire, the battery may explore. ●CAUTION: Do not open or mutilate the battery, released electrolyte is harmful to the skin

and eyes. ●CAUTION: A battery can present a risk of electric shock and high short circuit current. The

following precaution should be observed when working on batteries Remove watches, rings or other metal objects. Use tools with insulated handles.

●To reduce the risk of electric shock, disconnect the UPS from the mains supply before

installing a computer interface signal cable. Reconnect the powers cord only after signaling interconnections have been made.

● Servicing of batteries should be performed or supervised by personnel knowledge of

batteries and the required precautions. Keep unauthorized personnel away from batteries.

When replacing batteries, replace with four 12V/7Ah

¡

Page 3: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 3 頁 2003/3/4

TABLE OF CONTENTS

IM P O R T A N T SA F E T Y IN S T R U C T I O N S ……………………………………………..……… ¡

TABLE OF CONTENTS…………………………………………………………………………………..¡¡

INTRODUC TION………………………………………………………………………………¡¡¡

1. PRESENTATION………………...………….………………………………………………………..1

2. INS TAL L A TION……………………………………………………………………………9

3. OPERATION………………………………………………………………………………13

4. ALARM………………….………….….…………………………………………………14

5. SOFTWARE AND INTERFACE……………………………………….….…………………...………14

6. MAINTENANCE AND STORAGE………………….…………..…………………………16

7. BATTER Y AND BATTER Y CABINE T……………………………………………………17

AP P E N D IX A. TR O U B LE S HO O TI N G………………………………………………………18

APPENDIX B. SPECIFICATIONS……………………………………………………………19 Revision 1.9 Revised April 17, 2002.

¡¡

Page 4: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 4 頁 2003/3/4

INTRODUCTION

SAVE THESE INSTRUCTIONS Please read and save this manual!

Thank you for selecting this uninterruptible power system (UPS). It provides you with a perfect protection for connected equipment. The manual is a guide to install and use the UPS. It includes important safety instructions for operation and correct installation of the UPS. If you should have any problems with the UPS, please refer to this manual before calling customer service.

Please save or recycle the packaging materials! The UPS‘s shipping materials are designed with great care to provide protection within delivery. These materials are invaluable if you ever have to return the UPS for service. Damage happened during transit is not covered under the warranty.

Intelligent microprocessor control The product is an advanced line-interactive UPS based on microprocessor control. This means that it operates with the newest technology, high performance and powerful function.

The line-interactive UPS is an intelligent protector and provides pure, reliable AC power to the critical loads - protecting them from utility power blackout, swells, sags, surges and interference. The loads could include sensitively medical instruments, computers, telecommunication systems, and industrially automatic equipment. Under power normal condition, the line-interactive design enables the system to adjust and filter power fluctuations continuously and automatically. In the event of power failure, it can provide immediately back-up power from the batteries without any interruption. Complete transference will be achieved within 4m seconds, with no interruption.

Beside this, when the utility power is connected, the charger would work automatically even under power switch is OFF. Furthermore, in order to save the battery energy, UPS can automatically turn it off under backup mode if none of the connected loads is operating.

Advanced battery management The visual and audible indications of the UPS present the battery’s status including capacity degree and battery condition. Self-test function let UPS detect a weak battery before it is put into service. The UPS normally perform a self-test at power up and manual self-test condition. Self-test function can be conducted manually with the ON/TEST switch at any time.

Advanced monitoring software The line-interactive UPS and UPS-MON series monitoring software (optional kits) make your computer operate intelligent and provide you with the ability of perfect protection of your critical devices. The software is available for most operation systems and is supplied with a communication cable that connects to the UPS.

Note: There is no guarantee that interference to radio/TV will not occur in a particular installation. If this UPS causes interference to radio or television reception, which can be determined by turning the UPS off and on, the user is encouraged to try to correct the interference by one or more of following measures:

1. Connect the equipment to an outlet at a circuit different from the connected radio/TV. 2. Increase the separation between the equipment and the receiver or reorient the receiving

antenna.

¡¡¡

Page 5: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 5 頁 2003/3/4

1. PRESENTATION

1.1 Front LED Panel 1.1.1 “ON/TEST” button: With the UPS plugged in, press the ON/TEST button to turn on the UPS and power the loads. ON/TEST also activates the UPS‘s self-test and utility line voltage displays.

1.1.2 “OVERLOAD” indicator (RED LED): The LED lights when the loads connected to the UPS exceed the UPS‘s capacity. See Section 5.3.

1.1.3 “BACK UP” indicator (GREEN LED): The LED illuminates when the UPS is supplying battery power to the loads.

1.1.4 “REPLACE BATTERY” indicator (RED LED): The LED illuminates when the UPS‘s battery is no longer useful and must be replaced.. Note: When replace battery, disconnect the utility power then open the case and take notice of the battery‘s polarity while install the new battery to avoid short circuit. See section 8.

1.1.5 “BUCK AVR (VOLTAGE REDUCTION)” indicator (YELLOW LED): The LED illuminates when the UPS is correcting a high utility voltage condition. The loads receive normal power.

1.1.6 “LINE NORMAL” indicator (GREEN LED): The LED illuminate when the line input voltage is normal.

1.1.7 “BOOST AVR (VOLTAGE BOOST)” indicator (YELLOW LED): The LED illuminates when the UPS is correcting a low utility voltage condition. The loads receive normal power.

1.1.8 LOAD bar graph: The display shows the power being drawn by the load.

1.1.9 POWER bar graph (BATTERY CHARGE): The display shows the present battery charge as a percentage of battery capacity.

1.1.10 “OFF” button: Press the OFF button to turn off the UPS and the loads.

1.2 Front LCD Panel

ON

OFF

SELECT

1

Page 6: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 6 頁 2003/3/4

1.2.1 “LINE” indicator: The indicator illuminates when the line input voltage is normal. 1.2.2 “BY PASS” indicator: The indicator illuminates when the loads are supplied from the utility power, through the by-pass direction. 1.2.3 “INV” or “INVERTER” indicator: The indicator illuminates when the output power of UPS is supplied from the inverter circuit. 1.2.4 “BACKUP” indicator (LCD Panel only): The indicator illuminates when the power is supplied from the batteries. 1.2.5 “FAULT” indicator: It shows something wrong concerning about the UPS. 1.2.6 “ON” button: With the UPS plugged in, press the “ON” button to turn on the UPS and power the loads. “ON” also activates the UPS‘s self-test and utility line voltage displays. 1.2.7 “OFF” button: Press the OFF button to turn off the UPS and the loads. 1.2.8 “SELECT” button (LCD Panel only): The relevant value appears on the upper screen. There are four display modes can be selected. Output voltage display Input voltage display Input frequency Temperature inside the UPS Output frequency. Load level at percent. 1.2.9 “BATT” bar graph (RECTANGLE INDICATOR): The rectangle indicator shows the percentage of battery capacity. 1.2.10 “LOAD” bar graph (RECTANGLE INDICATOR): The indicator shows the power being drawn by the load. 1.2.11 “FAULT” codes (LCD Panel only): The relevant value appears at the upper screen. There are seven kinds of fault modes can be displayed. Err0: UPS Fault. Err1: Warning of overload. (exceeding 120%)

Load Indicator Light no.5 Light no.4 Light no.3 Light no.2 Light no.1

% of Load Value over 96%

76-95 % 51-75 % 26-50 % 10-25 %

Battery Indicator Light no.5 Light no.4 Light no.3 Light no.2 Light no.1

% of Bat Level over 91 % 76-90 % 51-75 % 26-50% 0-25%

2

Page 7: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 7 頁 2003/3/4

1.3 Rear Panel 1.3.1 TEL./MODEM connector Telecom transfer ports provide users to extend the applications. ●Caution: To reduce the risk of fire, use only No. 26AWG or larger telecommunication line

cord. 1.3.2 EXTERNAL BATTERY PACK CONNECTOR (optional) CAUTION: Use only factory supplied or authorized connecting cable for external battery! CAUTION: Use only factory supplied or authorized SNMP monitoring cable! 1.3.3 OUTPUT POWER RECEPTACLES 1.3.4 AC INPUT POWER RECEPTACLE 1.3.5 INPUT CIRCUIT BREAKER/ FUSE It trips when the connected loads exceed the protected receptacle‘s capacity, The center plungers of the circuit breakers/ fuse extend when tripped. 1.3.6 SITE WIRING FAULT INDICATORS (RED LED) It comes on when the UPS is connected to an improperly wired AC power outlet. Note: This device is available on 110 Vac model only. 1.3.7 COMPUTER INTERFACE Provide both RS-232 and relay signal to support NOVELL, UNIX, DOS, WINDOWS and other operating systems. 1.3.8 SNMP INTERFACE PORT (optional) Provide the SNMP adapters for 10-BaseT Ethernet and Token Ring connectors. Through RS232 communication port, the SNMP adapter make your UPS becomes “SNMP manageable”, provide a real time UPS and power status information for the network manager. Note: It‘s not necessary to use this function.

3

Page 8: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 8 頁 2003/3/4

4

FRONT VIEW

1.1.8 1.1.5 1.1.6 1.1.7 1.1.10

1.19 1.12

1.13

1.14

1.1.1

1KAL (220V)

1.3.11.3.2

1.3.3

1.3.4

1.3.6

1.3.7

1.3.5

600~1250VA (220V)

REAR VIEW

600~1250VA (110V)

Page 9: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 9 頁 2003/3/4

5

REAR VIEW

1.5K/2KVA (110V/220V)

3KVA/3KAL(110V)

2KAL(110V)

Page 10: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 10 頁 2003/3/4

6

1.5KVA/2KVA/2.5KVA(220V) 2KAL/3KVA/3KAL(220V)

1KAL(220V) 600VA/800VA/1KVA/1.25KVA(220V)

REAR VIEW

Page 11: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 11 頁 2003/3/4

7

FRONT VIEW ( 800~3KVA(L) RM)

1.1.1 1.1.8 1.1.5 1.1.9 1.1.2

1.1.10 1.1.4 1.1.3 1.1.7 1.1.6

REAR VIEW 1.3.2 1.3.1 1.3.5 1.3.4 1.3.3 1.3.7

800~1250VA RM(110V)

1.5K~2.5KVA RM(110V)

Page 12: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 12 頁 2003/3/4

8

600VA RM (2U)

FRONT/ REAR VIEW

Page 13: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 13 頁 2003/3/4

2. INSTALLATION Inspect the UPS upon receipt. The packaging is recyclable; keep it for reuse or be disposed of properly.

2.1 Placement: Install the UPS in a protected area with adequate flowing air and free of excessive dust. Do not operate the UPS where the temperature and humidity is out of the specified limits.

2.2 Connect Computer Interface (optional): UPS-MON series software (or other power management software) and an interface kits can be used with this UPS. Use only kits supplied or approved by the manufacturer. If used, connect the interface cable to the 9-pin computer interface port on the back panel of the UPS. Note: Computer interface connection is optional. The UPS works properly without a computer interface connection.

CAUTION: Use only factory supplied or authorized UPS monitoring cable!

2.3 Connect external battery pack (optional): Before connecting, make sure the external battery pack and the connector cable are compatible. Note: External battery connection is not necessary. The UPS works properly without external battery pack connection. (Except AL models only)

CAUTION: Use only factory supplied or external battery connection cable!

2.4 Charge the battery: The UPS charges its battery whenever it is connected to utility power. For best results, charge the battery for 8 hours in the initial use.

2.5 Connect to Utility: See figure a. Please check the following items to connect the AC input power to terminal block and power up the UPS.

2.6 Connect the loads: Connect the loads with the terminal block at the rear of the UPS. To use the UPS as a master on/off switch, make sure all of the loads are switched on.

CAUTION: Never connect a laser printer or plotter to the UPS with other computer equipment. A laser printer or plotter periodically draws significantly more power than when its idle status, and may overload the UPS.

2.7 Check the Site Wiring Fault Indicator: After plugging in the loads and the UPS, check the site wiring fault indicator on the rear panel. See section 3.17 for location of the indicator on the back panel. It lights if the UPS is plugged into an improperly wired AC power outlet. Wiring faults detected include ground, hot-neutral polarity reversal, and overloaded neutral circuit.

9

2.5cm (1 inch)

Page 14: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 14 頁 2003/3/4

2.8 Installations with accessories of “Vertical” and “Wall-mounted” types: Please install the vertical and wall-mounted types of units according to the following illustration. Vertical Installation Wall-mounted installation.

10

Page 15: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 15 頁 2003/3/4

2.9 Installation with accessories of “Rack-mounted” types: Please install the types of units according to the following illustration. Installation with bottom bracket. Part No: RMB-06, 2 PCS. Screw: M5*11, 4 PCS.

Installation with rear bracket Part No: RMB-01, 2PCS. Screw: M5*11, 4 PCS.

11

Page 16: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 16 頁 2003/3/4

2.10 Installation with accessories of “Stack” types: Please install the types of units according to the following illustration. Stack installation

12

Page 17: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 17 頁 2003/3/4

3. OPERATION 3.1 Switch on: While utility input is connected to the UPS, press the "ON" button and keep pressing over than 0.5 second. After that, connect the electrical cords of the equipment that is going to be used such as computer or monitor with the terminalon the rear panel of UPS. Don't overload the machine with all the equipment used. The buzzer will beep continuously to indicate overload status. UPS will shut down automatically to protect the machine.

Attention: If the power of UPS isn't supplied by utility but by the internal batteries to engage the UPS, press the "ON" button and keep pressing for over 3 seconds.

CAUTION: Never connect a laser printer or plotter to the UPS with other computer equipment. A laser printer or plotter periodically draws significantly more power than when its idle status, and may overload the UPS.

3.2 Switch off: By pressing and holding OFF button until the “LINE NORMAL” or “BACK UP” LED off.

3.3 Silence: When UPS is under “BACKUP” mode, press “ON” button more than 1 second to silence the audible alarm. (The function is disable when UPS is under condition of “LOW BATTERY” or “OVERLOAD”) Note: At back-up mode, UPS can be automatically turned off if none of the connected loads is operating.

3.4 Self-test: Use the self-test to verify both the operation of the UPS and the condition of the battery. In normal utility power, push the ON/TEST button more than 1 second and UPS performs a self-test function. During the self-test, the UPS operates a back up mode. Note: During the self-test, the UPS briefly operates the loads on-battery (the on-battery LED comes on). If the UPS passed the self-test, it returns to line-interactive operation. The on-battery LED goes off and the line-interactive LED goes on steadily. If the UPS is failed to pass the self-test, it returns to line-interactive operation and lights the replace battery LED. The loads are not affected. Recharge the battery overnight and perform the self-test again. If the replace battery LED is still on, ask our nearest dealer to replace battery.

3.5 Load bar graph: The 5-LED display (See section 2.8 for location of the indicator on the front panel) shows the power drawn from the UPS by load. The display indicates the percentage of the UPS‘s rated capacity. For example. If three LEDs are lit, the load is drawing between 50% and 67% of the UPS’s capacity. If the UPS is overloaded, the overload LED lights and alarm sounds. See section 5.3

3.6 Battery charge bar graph: The 5-LED display (see section 3.9 for location of the indicator on the front panel) shows the present charge of the UPS‘s battery as a percentage of the battery capacity. When all five LEDs light, the battery is fully charged. When only two LED lights, the battery can supply less than two minutes of run time for the load.

3.7 Cold start: When the UPS is off and there is no utility power, use the cold start feature to apply power to the loads from UPS‘s battery. Press the ON/TEST button (see section 3.1 for location of the indicator on the front panel) until the UPS beeps.

3.8 Shutdown mode: In shutdown mode the UPS stops supplying power to the load, waiting for return of utility power. If there is no utility power present, external devices (e.g., servers) connected to the computer interface can command the UPS to shutdown. This is normally done to preserve battery capacity after the graceful shutdown of protected servers. The UPS will scroll the front panel indicators sequentially in shutdown mode.

13

Page 18: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 18 頁 2003/3/4

4. ALARM 4.1 “BACKUP”(slow alarm): When the UPS is working under “BACKUP” mode, the UPS would emit audible alarm. The alarm stops when the UPS is return to “LINE” mode operation. Anyone can stop the alarm by press the “ON” button during backup mode.

Attention: The alarm of “BACKUP” is going to beep every four seconds. (Slow-speed beep).

Attention: The UPS provides mute function for the warning. When the beeping sound occurs, press "ON" to stop it; and press "ON" again to regain the sound.

4.2 “LOW BATTERY” (rapid alarm): In the “BACKUP” mode, when the energy of battery becomes to lower level. (about 20%~30%) The UPS beeps rapidly until the UPS shuts down from battery exhaustion or returns to “LINE” mode operation.

Attention: The alarm of the batteries caused by low voltage beeps every second. (Fast-speed beep).

Attention: The rapid alarm under “LOW BATTERY” condition can't be erased. 4.3 “FAULT” (continuous alarm): Here is listing some “FAULT” conditions as following for reference.

4.3.1 “err 0” (LCD Panel only) The UPS emits continuous beeps and the “FAULT” illuminates when the UPS fails. 4.3.2 “err 1” (LCD Panel only) When the UPS is working under overload condition (the connected loads exceed the

maximum rated capacity), the UPS will emit continuous alarm to warn an overload condition. In order to protect the unit and the loads, the UPS will be automatic shutdown. Disconnect nonessential devices from UPS to eliminate the overload alarm.

5. SOFTWARE AND INTERFACE PORT 5.1 Power Monitoring Software: The UPS-MON series software (or other power monitoring software) is applied standard RS-232 interface to perform monitoring functions, and then provides an orderly shutdown of a computer in the event of power failure. Moreover, UPS-MON displays all the diagnostic symptoms on monitor, such as Voltage, Frequency, Battery level and so on. The software is available for DOS, Windows 3.1x, Windows 95, Windows NT V3.5 or later, Novell Netware and others. Call your dealer for more information on computer OS compatible solutions. 5.2 Interface Kits: A series of interface kits is available for operation systems that provide UPS monitoring. Each interface kit includes the special interface cable required to convert status signals from the UPS into signals which individual operating system recognize. The interface cable at UPS side must be connected to REMOTE PORT, at computer side can be either COM 1 or COM 2. The other installation instructions and powerful features please refer to READ.ME file.

CAUTION: Use only factory supplied or authorized UPS monitoring cable!

14

Page 19: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 19 頁 2003/3/4

5.3 The characteristics of computer interface port: The computer interface port has the following characteristics: The communication port on the back of the UPS may be connected to host computer. This port allows the computer to monitor the status of the UPS and control the operation of the UPS in some cases. Its major functions normally include some or all of the following:

To broadcast a warning when power fails. To close any open file before the battery is exhausted. To turn-off the UPS.

Some computers are equipped with a special connector to link with the communication port. In addition, special plug-in cord may be needed. Some computers may need special UPS monitoring software. Contact your dealer for the details on the various interface Kits. 5.4 The pin of computer interface port: The pin of computer interface port has the following characteristics:

5.4.1. Pin 5 and 2 are open collector outputs that must be pulled up to a common referenced supply no greater than DC +40V. The transistors are capable of a maximum nonconductive load of DC 25 mA, Use only pin 7 as the common.

5.4.2. Pin 5 generates a High to Low signal when the battery inside the UPS has less than 5 minutes back up time left.

5.4.3. Pin 2 generates a High to Low signal when the line is fail. 5.4.4. The UPS will shut down when a high RS-232 level is sustained on pin 6 for 0.36

seconds. 5.4.5. Pin 9 is the RS-232 data output. 5.4.6. Pin 6 is also RS-232 data input (RxD) NOTE: 1. Switch rating +40V, 0.25A non-inductive. 2. Pin 7 should be connected to ground only.

Communicating Interface Port We provide a standard RS232 line (that is compatible with DB9 line) socket on the rear panel of UPS. That port possesses several signals as explained below: Pin# Function Explanation I/O 2 Power Fail-normally open status, will become closed during active OUTPUT 4 Reference GND for pin2,5 OUTPUT 5 Battery Low- normally open status, will become closed during

active OUTPUT

6 Remote shutdown UPS-keep this pin at high voltage(+5V~+12V) 500ms to shutdown UPS. Activates at battery mode

INPUT

7 Reference GND for pin6 INPUT

15

Page 20: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 20 頁 2003/3/4

6. MAINTENANCE AND STORAGE 6.1 Maintenance

6.1.1. Keep the unit clean and vacuum the ventilation intake periodically. 6.1.2. Wipe with soft loose and damp cloth. 6.1.3. Check for loose and bad connections monthly. 6.1.4. Never leave the unit on an uneven surface. 6.1.5. Position the unit to allow at least 10 cm clearance between the rear panel and the

wall. Keep the ventilation intake open. 6.1.6. Avoid direct sunlight, rain and high humidity. 6.1.7. Stay away from fire and extremely hot location. 6.1.8. Do not stack materials on top of the unit. 6.1.9. The unit should not be exposed to corrosive air. 6.1.10. The normal operating temperature is 0-40 ℃.

6.2 Storage conditions: Store the UPS covered and upright in a cool and dry location, with its battery fully charged. Before storing, charger the UPS for at least 4 hours. Remove any accessories in the accessory slot and disconnect any cables connected to the computer interface port to avoid unnecessary draining the battery. 6.3 To extend the storage: 6.3.1. During the environment where the ambient temperature is -15 to +30 ℃ (+5 to +86 ℉), charge the UPS‘s battery every 6 months. 6.3.2. During the environment where the ambient temperature is +30 to +45 ℃ (+86 to +113 ℉), charge the UPS‘s battery every 3 months.

16

Page 21: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 21 頁 2003/3/4

7. BATTERY AND BATTERY CABINET 7.1 Battery’s life of UPS The battery’s life of UPS is about 3-6 years under normal usage. 7.2 Installation of battery cabinet and UPS (For AL and AXL models only): Please follow the listed steps to complete the installation. 7.2.1 Turn off the UPS and remove the connector metal cover from the back panel of UPS. 7.2.2 Connect the battery cabinet’s DC wire to the UPS and fix the motel cover via a screwdriver. Beside this, make sure the connection is reliable. 7.2.3 Turn on the UPS and plug the loads behind the UPS.

CAUTION: Do not dispose of battery in fire. CAUTION: Do not attempt to open the battery. CAUTION: The following precautions should be taken when replacing the battery a. Remove watches, rings, etc… b. Use tools with insulated handles

17

Page 22: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 22 頁 2003/3/4

APPENDIX A TROUBLESHOOTING Problems Possible Reasons Solutions

Input power source mistake

Check out the power source

Non-fuse switch on the rear panel hasn't been opened

Press the non-fuse switch to its "on" position

Time of pressing the ON button is too short

Keep pressing the ON button over 1 second

1. UPS can't operate after pressing On/Off switches

2. No lights on, no warning sounds

Output short circuit or overload on UPS

Turn off UPS, take off all load to make sure there are no problems on it or any internal short circuit. Keep pressing the ON button over 1 second

No power source input Check out the input power source Indicates no utility, and it warns every several seconds

Non-fuse switch on the rear panel hasn't been opened

Press the Non-fuse switch to its "on" position

Fault light is on, the buzzer keeps beeping

UPS is broken Contact the dealer or service center for help

Buzzer keeps beeping

Overload Take off some load

There is an open circuit on UPS input protector

Move the Input Non-fuse switch back to its normal position, re-engage UPS

Utility Indicating light is shining

The voltage of utility is exceeding UPS input range

Save the digital data and shutdown the applying program to make sure utility is within UPS range

1. Batteries haven't been charged

2. UPS overload 3. Batteries are aged

and can't be charged fully

Keep UPS "ON" for over 3 hours to recharge the batteries. Check out the loading and take off any non-crucial load equipment

Available time of the batteries is too short

The charger is out of order

Contact the dealer or service center for help

The battery’s light is flashing when the power of UPS is supplied by utility.

The voltage of batteries is too low or the batteries haven't been connected

Check out the batteries part of UPS, make sure they are well connected. If there is any damage on battery packs, replace new ones ASAP

18

Page 23: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 23 頁 2003/3/4

APPENDIX B.1 SPECIFICATION MODEL 600VA 800VA 1000VA 1250VA 1500VA 2000VA

Capacity 600VA 800VA 1000VA 1250VA 1500VA 2000VA Voltage 100V, 110V, 120V, 220V, 230V, 240V, +/-25%,Single phase

INPUT

Frequency 50 or 60Hz +/-5% (auto sensing) OUTPUT Voltage (on

battery) Pure sine wave output at nominal +/-5%

Frequency (on battery)

50 or 60Hz +/-0.5%

Voltage Regulation AVR

AVR automatically increase output voltage 15% above input voltage if -9% to-25% of nominal. AVR decrease output

voltage 15% below input voltage if+9% to +25% of nominal

PROTECTION Spike Protection 320 Joules, 2ms AND Unit Input Fuse for overload & short circuit protection FILTERING EMI/RFI filter 10dB at 0.15MHz, 50dB at 30MHz

Overload Protection

UPS automatic shutdown if overload exceeds 110% of nominal at 20 second and 125% at 2 seconds.

Transfer Time 2~4 milliseconds, including detection time Short Circuit UPS output cut off immediately or input fuse

protection BATTERY Type Hot swappable, Sealed, Maintenance-free lead acid Typical Recharge

Time 4 hours (to 90% of full capacity)

Protection Automatic self-test & discharge protection, Replace battery indicator

Back – up Time 10 - 30 minutes (depending on computer load) PHYSICAL Net Weight

Kg(lbs) 13.8

(30.4) 14.5

(31.9) 15

(33.0) 15.8 (34.8)

25 (55.0)

30 (66.0)

Shipping Weight Kg(lbs)

14.8 (32.6)

15.5 (34.1)

16 (35.2)

16.8 (37.0)

27 (59.4)

32 (70.4)

Dimension(mm) WxDxH

140x445x200 170x450x215

Input Inlet IEC 320 power inlet Receptacles NEMA 5-15R (115V)/IEC 320 female appliance

coupler (230V) ALARM Battery Back-Up Slow beeping sound (about 0.25Hz) Battery Low Rapid beeping sound (about 1.00Hz) Overload Continue beeping sound INTERFACE RS-232 Interface Bi-directional communication port APPROVALS Safety UL, FCC, C-UL(CSA), BSMI, CE, GS/TUV Surge Meet IEEE 587 standard Warranty Two years ENVIRONMENT Operation Elevation: 6,000m max, Humidity: 0%-95%(without

condensation formation), Temperature: 0-40 deg C Audible noise <40dBA (1 meter

from surface) <45dBA (1 meter from surface)

Storage condition 15000 meters max. elevation

19

Page 24: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 24 頁 2003/3/4

APPENDIX B.2 SPECIFICATION MODEL 2500VA 3000VA 1000AL 2000AL 3000AL

Capacity 2500VA 3000VA 1000VA 2000VA 3000VA Voltage 100V, 110V, 120V, 220V, 230V, 240V, +/-25%,Single

phase

INPUT

Frequency 50 or 60Hz +/-5% (auto sensing) OUTPUT Voltage

(on battery) Pure sine wave output at nominal +/-5%

Frequency (on battery)

50 or 60Hz +/-0.5%

Voltage Regulation AVR

AVR automatically increase output voltage 15% above input voltage if -9% to-25% of nominal. AVR decrease output voltage

15% below input voltage if+9% to +25% of nominal

Spike Protection

320 Joules, 2ms

Unit Input Breaker for overload & short circuit protection

PROTECTION AND FILTERING

EMI/RFI filter 10dB at 0.15MHz, 50dB at 30MHz Overload

Protection UPS automatic shutdown if overload exceeds 110% of

nominal at 20 second and 125% at 2 seconds. Transfer Time 2~4 milliseconds, including detection time Short Circuit UPS output cut off immediately or input fuse protection BATTERY Type Hot swappable, Sealed, Maintenance-free lead acid Typical Battery

Life 3 to 6 years, depending on number of discharge cycles

and ambient temperature Typical

Recharge Time 4 hours (to 90% of full capacity)

Nominal Battery Voltage

48V 48V 24V 48V 48V

Charge Current 2A 2A 4A 4A 4A Supplied

Battery Packs Built-in External

Pack Upon

request Upon

request Upon

request Protection Automatic self-test & discharge protection, Replace

battery indicator Back – up Time 10 – 30 minutes (depending on computer load) PHYSICAL Net Weight

Kg(lbs) 30

(66.1) 110V 20.2

(44.5)

220V 19

(41.9)

10 (22.0)

19 (41.9)

26.8 (59.0)

Shipping Weight Kg(lbs)

32 (70.5)

22.7 (50)

21 (46.3)

11 (22.2)

21 (46.3)

29.3 (64.5)

Dimension(mm) WxDxH

170 x450 x226

170 x580 x226

170 x450 x226

140 x436 x210

170 x450 x226

170 x580 x226

Input Inlet IEC 320 power inlet Receptacles NEMA 5-15R (115V)/IEC 320 female appliance coupler

(230V)

20

Page 25: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 25 頁 2003/3/4

APPENDIX B.3 SPECIFICATION MODEL 2500VA 3000VA 1000AL 2000AL 3000AL ALARM Battery Back-Up Slow beeping sound (about 0.25Hz) Battery Low Rapid beeping sound (about 1.00Hz) Overload Continue beeping sound INTERFACE RS-232 Interface Bi-directional communication port APPROVALS Safety approvals UL, C-UL(CSA)-UL 1778

CE/LVD, GS/TUV-EN50091 & EN60950 EMC verifications CISPER 22 Class B verified (FCC,BSMI,CE/EMC) Electromagnetic

immunity IEC-801-2 level IV, 801-3 level III, 801-4 level IV

Surge Meet IEEE 587 standard Warranty Two years ENVIRONMENT Operating

Temperature 0 ℃ to +48 ℃

Storage Temperature

-15 ℃ to +45 ℃

Operating and storage relative humidity

0 to 95%, non-condensing

Operating elevation

0 to +3500 m

Storage elevation 0 to +15000m Audible noise <40dBA (1 meter from

surface) <45dBA (1 meter

from surface)

Note Characteristics are subject to change without prior notice

21

Page 26: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 26 頁 2003/3/4

APPENDIX B.4 SPECIFICATION MODEL 800

VA RM

1000 VA

RM

1250 VA

RM

1500 VA

RM

2000 VA

RM

2500 VA

RM

600VARM (2U)

Capacity 800 VA

1000 VA

1250 VA

1500 VA

2000 VA

2500 VA

600 VA

Voltage 100V, 110V, 120V, 220V, 230V, 240V, +/-25%,Single phase

INPUT

Frequency 50 or 60Hz +/-5 Hz (auto sensing) OUTPUT Voltage

(on battery) Pure sine wave output at nominal +/-5%

Frequency (on battery)

50 or 60Hz +/-0.5%

Voltage Regulation AVR

AVR automatically increase output voltage 15% above input voltage if -9% to-25% of nominal. AVR decrease output

voltage 15% below input voltage if+9% to +25% of nominal Spike Protection

320 Joules, 2ms

Unit Input Fuse for overload & short circuit protection

PROTECTION AND FILTERING

EMI/RFI filter 10Db at 0.15MHz, 50dB at 30MHz

Overload Protection

UPS automatic shutdown if overload exceeds 110% of nominal at 20 second and 125% at 2 seconds.

Transfer Time 2~4 milliseconds, including detection time Short Circuit UPS output cut off immediately or input fuse protection BATTERY Type Hot swappable, Sealed, Maintenance-free lead acid Typical

Recharge Time 4 hours (to 90% of full capacity)

Protection Automatic self-test & discharge protection, Replace battery indicator

Back – up Time 10 - 30 minutes (depending on computer load) PHYSICAL Net Weight

Kg(lbs) 18.0

(39.6) 18.0

(39.6) 23.5

(51.7) 26.1

(57.4) 28.4 (62.4)

28.4 (62.4)

15.7 (34.6)

Shipping Weight Kg(lbs)

19.5 (42.9)

19.5 (42.9)

25.0 (55.0)

27.7 (60.9)

30.0 (66.0)

30.0 (66.0)

18.7 (41.2)

Dimension (mm) WxDxH

483x381x130 483 x351 x84

Input Inlet IEC 320 power inlet Receptacles NEMA 5-15R (115V)/IEC 320 female appliance coupler

(230V) Storage

condition 15000 meters max. elevation

22

Page 27: Uninterruptible Power System - PowerMatic · 661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc KEVIN KU 第 2 頁 2003/3/4 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS

661-SK60-002-21D:\manual\UM_PCM-SMK\661-SK60-002-21.doc

KEVIN KU 第 27 頁 2003/3/4

APPENDIX B.5 SPECIFICATION MODEL

800 VA RM

1000VA

RM

1250VA

RM

1500VA

RM

2000VA

RM

2500VA

RM

600VA RM (2U)

ALARM Battery Back-Up Slow beeping sound (about 0.25Hz) Battery Low Rapid beeping sound (about 1.00Hz) Overload Continue beeping sound INTERFACE RS-232

Interface Bi-directional communication port

CONFORMANCE Safety approvals

UL, C-UL(CSA)-UL 1778 CE/LVD, GS/TUV-EN50091 & EN60950

EMC verifications

CISPER 22 Class B verified (FCC,BSMI,CE/EMC)

Electromagnetic immunity

IEC-801-2 level IV, 801-3 level III, 801-4 level IV

Surge Meet IEEE 587 standard Warranty Two years ENVIRONMENT Operating

Temperature 0 ℃ to +40 ℃

Storage Temperature

-15 ℃ to +45 ℃

Operating and storage relative humidity

0 to 95%, non-condensing

Operating elevation

0 to +3000 m

Storage elevation

0 to +15000m

Audible noise <40dBA (1 meter from surface)

<45dBA (1 meter from surface)

Note: Characteristics are subject to change without prior notice