    GB-DAS lnstallation lnstructions _ Devireg- S3O, S3l, and 532

    The Devireg* 530 series is a line of electronicthermostats used for control of indoor heatingThe Devireg- 530 is used for control of floor heatinginstallations. The thermostat is equipped with a floorsensor for control of the desired floor temperature.The Devireg" 531 is used for control of room heatinginstallations. The thermostat is equipped Hnth a buih-inair sensor for control of the desired room temprdure.The Devireg" 532 is used for room heating instal-lations. The thermostat is equipped with a built-inroom sensor and an external floor limiter sensor. Theroom sensor is used for control of the room tempera-ture. The floor limiter sensor is used for maximumtemperature limitation in wooden floors and otherheat sensitive floors.

    The Devireg- 530 series has a LED indicator abovethe 2 pole safety switch (see illustration).The LED has four indications:

    . No light means the system is off.

    . Red light means system is heating.

    . Green light means system is standirg by.. Flalhing green light means there is a problemwith the floor sensor (onry appricable for 530and 532). Please refer to section about ,,Troubleshooting" for further information.

    * tt. is used for setting the thermostat in frost protec-tion mode, i.e. keeping the room/floor temperature(depending on type of thermostat) at 5"c ut *y time.

    nnWWWWWffiWW

    WWHTWWWffiWWEDindicator

  • 7/29/2019 Upatstvo Devi 535

    2/8

    n---GIE3EE

    Applications an d functionsMaximum floor temperoture settingLig ht indi cotia ns (LED)

    In stallation i nstru ctionslnstall sensor for Devireg* 530 and 532Placement of Devireg^ 530, 531, and 532Connection diagrams for Devireg^ 530, 531 , and 532

    Trouble shootingTechn i cal s pe cifi catio n sG u ara ntee co n d itio n s an d g u a ra ntee ce rtifi cate

    Maximum floor temperature is preset at the factoryto 35oC for cable temperature safety.

    $ focal building regulations must be observed whenchanging the ma:rimum preset temperature.You canlmust set the ma:rimum floor temperatureon the Deviregl 532by taking offthe front cover andwith a screwdriver adjust the sunken temperature dialin the top left hand corner between 20o to 50"C.

    When installing a thermostat from Devireg- 530series, you must first remove the front cover.To remove the front cover, gently press the releasetabs in the vents, at both sides and then puil off thefront.You do not need to remove the set point dial.

    A m. installation must only be carried out by *authorised electrician.

    @ for wooden floor constructions DEVI- recommendthe temperature is limited to a ma:rimumof 30'C.Maximum temperature setting for different floorconstructions:

    Tiles on chipboard 300cCarpet/vinyl on chipboard 35"CWooden floors (parquet, plank, etc.) 300cOther (concrete, screed, etc.) 450C

    WnWWffiWWWW IIIIt,

    ffiWWruWWWWW

    3WW

  • 7/29/2019 Upatstvo Devi 535

    3/8

    The floor sensor should be mounted in a 5.7 mminstallation pipe which is sealed at the end to preventpenetration of concrete into the pipe. Minimumbending radius for the pipe is 50 mm.The sensor cable must be placed in between twostrings of the heating cable.

    A fo avoid cracks in the concrete floor you must ensurethat the floor is completely hardened before the heatis switched on.

    If a floor sensor is used, it is recommended to installit inside an insulating conduit, sealed at the end in thefloor, enabling easy replacement of the floor sensor ifrequired- If installed without a conduit, the floorsensor must be installed so that it is inaccessible andnot in contact with any conductive building parts.If the supplied floor sensor is too short, longer onescan be purchased from you local DEVI supplier or itcan be extended with proper materials.The floor sensor is a LIVE cable; therefore anyextension made to the sensor wiring should betreated as for normal mains voltage cabling.

    WWWWtrnWWffiW

    \WWWWWtrTWWNot on a wall where it will be subjected to direct sunlight.

    Not on the inner side of a wall facing the outside.

  • 7/29/2019 Upatstvo Devi 535

    4/8

    ffiffiWWffiruWWW

    WffiWffiWffireWW

    Devireg" 530

    Instdlation height' tyPically between 80-150 cm., when Devireg* 531/532 is used as room sensor.

    In damp rooms it should be installed on an even surface, according to local buildingregulations.

    At least 50 cm away from windows/doors that will be left open occasionally.

    Devireg" 531

    NC = no connection NC = no connection10

  • 7/29/2019 Upatstvo Devi 535

    5/8

    Devireg" 532 WWWffiffiffiHffiffi

  • 7/29/2019 Upatstvo Devi 535

    6/8

    WWWWWWWreW

    Control of functioningIf the heat is not turned on by activating the ther-mostat, check the residual current device (RCD)and safety devices before contacting an authorisedelectrician.Fault No heat1) GeneralFirst of all, make sure that all cables, connected tothe thermostat, are properly installed - making surethat each wire connected to the thermostat, createsa solid contact to the screw terminal located on thethermostat.

    2) Mains voltage (terminal 1 and 3)Measure the live supply voltage at terminal 1 and 3.The reading should be within specified range, accord-ing to the technical specifications. If not, check themain fuse.3) Thermostat output (terminal 2 and 4)Measure the voltage at terminal 2 and4, (activatedthermostat, red light). The reading should be thesame as previously measured at terminal 1 and 3.If the reading is OK, continue to the next step;if not - replace the thermostat.

    12

    WWWffiWWWruffi

    5) External sensor input NTC (only for Devireg'" 530and"532)Disconnect the external NTC sensor 5 and 6 on thethermostat.Connect an ohm meter to the NTC sensor wire, andmeasure the ohm value (please refer to table on page15 for correct ohm value).The measured value should be within the specifiedrange according to the technical specifications. If not,replace the NTC sensor.

    Fault Constant heatRelav constantlv on

    -

    Measure the voltage at terminal 2 and4, (non-activated thermostat, no light, green light or flashinggreen light). There should be no voltage at terminal 2and 4. If voltage is measured, replace the thermostat.

    14

    NNWWffiWWNIH

    Operation voltage 230 VAC +I0o/o I -20o/o,50 HzPower consumption Max.0.25WRelays:. Resistive load. Inductive load 230V - l5Acos I = 0.3 Ma:r. 4ASensing unit NTC 15 kOhm at25"CSensing values:. OoC.20"C. 50oC

    42 kOhm18 kOhm6 kOhm

    Hysteresis +l- 0.2"CAmbient temperature -10o to +30oCFrost protection 5"c

    16

  • 7/29/2019 Upatstvo Devi 535

    7/8

    Temperature range:. 530. 531.5325-45"C5-35"C5-35"C, floor temperature limiter range: 20-50" C

    Sensor failure monitoring The thermostat has a built-in monitoring circuit, whichwill switch offthe heating if the sensor is disconnectedor short-circuited.

    LED indicator:. No light. Red light. Green light. Green light flashing

    The system is off.The temperature set point is not reached-The temperature set point is reached.Floor sensor is defect.

    IP class 3rDimensions 85mmx85mm

    WWWWffiffiNWffi

    Guarantee CertificateThe DEVI" Guarantee is granted to:

    Postal code:

    Please observe!ln order to obtain the DEVI- Guarantee, the following must becarefully filled in. See other conditions on previous pag.

    Electrical lnstallation by: lnstallation date:Type of thermortat: Production code:-------------uppliers Stamp:

    DEVIA/SDK.7100VejlePhone +45764247 O0Fax +45764247 03 19

  • 7/29/2019 Upatstvo Devi 535

    8/8

    You have purchased a DEVI heating system which we are sure willserve to improve the comfort and economy of your home.DEVI provides a complete heating solution with deviflex" heatingcables or devimat- heating mats, Devireg" thermostats and devi-fast" fi"ittg strips. Should you, against all expectations, experiencea problem with your DEVI heating system, you will find thatDEVI, whose products are manufactured in Denmark and soldthroughout the European Union, is subject to the standard regula-tions pertaining to product liability as specified in EU directive85l374lCEE as well as all applicable legislation in the individualcountries on the following conditions:DEVI offers a lg-year guarantee on all deviflex" heating cablesand devimat" heating mats, and a Z-yeat guarantee against mate-rial defects and production defects in connection with any otherDEVI products.The guarantee shall be valid only if the GUARANTEE CERTIFI-CATE is completed correctly and in accordance with the instruc-tions, and provided the fault is inspected by or submitted to DEVIor an authorised DEVI dealer.Please note that the GUARANTEE CERTIFICATE must be com-pleted in English or local language.

    DEVI shall undertake any repair free of charge or supply the cus-tomer with a new unit. Repairs shall be carried out at no furthercost to the customer. In the case of faulty Devireg" thermostats,DEVI reserves the right to repair the unit free of chaqge andwithout any unreasonable delap for the customer.The DEVI Guarantee shall not cover installations that have beencarried out by non-authorised electricians, faults which arise as aresult of misuse by other suppliers, damage caused by third par-ties, incorrect installations or consequential damage. All work willbe invoiced in full if DEVI is required to inspect or repair faultsthat have arisen as a result of any of the above.The DEVI Guarantee shall not extend to equipment which has notbeen paid in full.DEVI will, at all times, provide a rapid, effective and honest re-sponse to all queries and reasonable demands from our customers.The above guarantee covers product liability only, rryhile purchasesare subject to national legislation.