  • A REPORT TO

    THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES

    Electrical

    Mechanical

    '' ..,

    Civil/

    Protection & Control

    -

    Transmission & Distribution

    Telecontrol

    System Planning

    UPGRADE TRANSMISSION LINE CORRIDORBay d'Espoir to Western Avalon

    September 2011

    newfoundland labrador

    hydroa nalcor energy company

  • UpgradeTransmissionLineCorridorBaydEspoirtoWesternAvalon

    NewfoundlandandLabradorHydro i

    TableofContents

    1 INTRODUCTION................................................................................................................ 1

    2 PROJECTDESCRIPTION..................................................................................................... 3

    3 EXISTINGSYSTEM............................................................................................................. 73.1 AgeofEquipmentorSystem ............................................................................... 93.2 MajorWorkand/orUpgrades ............................................................................. 93.3 AnticipatedUsefullife........................................................................................ 103.4 MaintenanceHistory ......................................................................................... 113.5 OutageStatistics ................................................................................................ 113.6 IndustryExperience ........................................................................................... 123.7 MaintenanceorSupportArrangements............................................................ 133.8 VendorRecommendations ................................................................................ 133.9 AvailabilityofReplacementParts ...................................................................... 133.11 Retirements........................................................................................................ 143.12 SafetyPerformance ........................................................................................... 143.13 EnvironmentalPerformance.............................................................................. 143.14 OperatingRegime .............................................................................................. 14

    4 JUSTIFICATION ............................................................................................................... 154.1 NetPresentValue .............................................................................................. 354.2 LevelizedCostofEnergy .................................................................................... 354.3 CostBenefitAnalysis.......................................................................................... 354.4 LegislativeorRegulatoryRequirements............................................................ 364.5 HistoricalInformation........................................................................................ 364.6 ForecastCustomerGrowth................................................................................ 364.7 EnergyEfficiencyBenefits.................................................................................. 374.8 LossesDuringConstruction ............................................................................... 374.9 StatusQuo.......................................................................................................... 384.10 Alternatives........................................................................................................ 38

    5 CONCLUSION.................................................................................................................. 405.2 ProjectSchedule ................................................................................................ 41

  • UpgradeTransmissionLineCorridorBaydEspoirtoWesternAvalon

    NewfoundlandandLabradorHydro Page1

    1 INTRODUCTION

    NewfoundlandandLabradorHydro(Hydro)ownsandoperateseleven230kVlinestotaling

    627kminlengthconnectingtheBaydEspoirGeneratingStationtothemajorloadcenters

    andgeneration intheeasternportionoftheprovince. Figure1providesadiagramofthe

    BaydEspoirEast230kVtransmissionsystem.

    Bayd'Espoir

    TL202

    TL206

    Sunnyside

    ComeByChance

    TL203

    TL207 TL237

    Holyrood

    WesternAvalon

    TL217

    TL201

    Hardwoods OxenPond

    TL218

    TL236

    TL242

    Transmissionlinecrossingsremovedforclarity

    Figure1BaydEspoirEast230kVTransmissionSystem

    TheBaydEspoirEast230kVtransmissionsystemischaracterizedasbeingaheavilyloaded

    system.Conversely,the230kVtransmissionsystemwestofBaydEspoirischaracterizedas

    beingamorelightlyloadedsystem.Table1providesasummaryofeastandwestloadsat

    thetimeofsystempeaksfortheperiod20062010.Bycomparisonthe230kV

    transmissionsystemeastofBaydEspoirisloadedtoapproximatelytwicetheloadingofthe

    230kVtransmissionsystemwestofBaydEspoir.Theheavyloadingontheeasternportion

    ofthesystemiscoupledwiththeincentivetoprovideleastcostpowertocustomersby

    minimizingHolyroodproductionandmaximizingproductionfromhydroelectricresources

    locatedinBaydEspoirandwest.Constantmonitoringoftheloadontheeasternportionof

    thesystemisthereforerequired.Thermalloadlimitsonthelinesmustbestrictlyenforced

    toavoidunacceptablelinesagand/orpotentialconductordamage.Furtherloading

    pressureswillbeplacedupontheBaydEspoirEastsystemwiththeadditionoftheVale

    processingplantatLongHarbourandhasalreadyoccurredduetothelossofloadandnet

    hydroelectricgenerationincreaseattributedtotheclosureoftheAbitibiBowaterpapermill

  • UpgradeTransmissionLineCorridorBaydEspoirtoWesternAvalon

    NewfoundlandandLabradorHydro Page2

    inGrandFallsWindsor.

    Table1BaydEspoirEastandWest230kVTransmissionSystemPeakLoads2006to2010Year BaydEspoirEast1 BaydEspoirWest22006 836 4312007 848 4502008 827 4362009 858 4282010 833 378

    Notes1 BaydEspoirEastloadequaltoTL202andTL206flowplusParadiseRiver,Holyrood

    andHardwoodsgenerationattimeofpeak.2 BaydEspoirWestloadequaltoTL204andTL231flowplusCatArm,HindsLake,

    Stephenville,HawkesBay,St.AnthonyDieselPlantgenerationandNonUtilityGenerationpurchasesattimeofpeak.

    3 ConnaigrePeninsulaloadsnotincluded4 ValuesbasedontheHydroEnergyManagementSystem(EMS)hourlydataandnot

    weatheradjusted

    LowerChurchillImpacts

    GiventhattheLowerChurchillProjecthasyettoreceivefinalprojectsanction,analysisof

    theBaydEspoirEast230kVtransmissionsystemmustconsiderboththecontinuedIsolated

    IslandScenarioandtheLabradorInfeedScenario.Ineffect,theproposedprojectmustbe

    appropriatetoeitheranIsolatedIslandorLabradorInterconnectedfuture.

    Toaccomplishthis,theBaydEspoirEast230kVtransmissionsystemwassplitintotwo

    sectionsBaydEspoirtoWesternAvalonandWesternAvalontoSt.Johns.Thisproject

    considersonlytheupgraderequirementsfortheBaydEspoirtoWesternAvalonsectionof

    theBaydEspoirEast230kVtransmissionsystem.TheWesternAvalontoSt.Johnssection

    canonlybeconsideredoncethedecisionontheLowerChurchillProjectandsubsequent

    needfortheSoldiersPondTerminalStationismade.WiththefinaldecisionontheLower

    ChurchillProjectscheduledforlate2011orearly2012,Hydrointendstosubmitany

    necessaryupgradeprojectsfortheWesternAvalontoSt.JohnssectionoftheBaydEspoir

    East230kVtransmissionsystemassociatedwiththeproposedLowerChurchillProjectto

    TheBoardaspartofits2013capitalbudgetapplication.

  • UpgradeTransmissionLineCorridorBaydEspoirtoWesternAvalon

    NewfoundlandandLabradorHydro Page3

    2 PROJECT DESCRIPTION TheUpgradeTransmissionLineCorridorBaydEspoirtoWesternAvalonprojectwill

    consistofanew230kVtransmissionline,188kminlengthconnectingBaydEspoirand

    WesternAvalonTerminalStations.Thisincludesconstructionofa230kVsteeltower

    transmissionlinecompletewithoverheadgroundwireoveritsentirelength.Aminimum

    conductorsizeof795kcmil,26/7ACSRDRAKEwitha75Cconductortemperaturerating

    or804kcmil54/19AACSR/TWwithan80Cconductortemperatureisrequiredtoprovide

    thenecessarythermalratingforthenewcircuit.AtBaydEspoirTerminalStation,three

    230kVcircuitbreakers,six230kVmotoroperateddisconnectswitchesandassociated

    controlpanelswillbeaddedtocompletethebreakerandonehalfarrangementonthefirst

    twolegsofthestationlayoutandaccommodatethenew230kVtransmissionline

    terminationonathirdleg.Figure2providesasinglelinediagramwiththeproposed

    additionsinred.

  • UpgradeTransmissionLineCorridorBaydEspoirtoWesternAvalon

    NewfoundlandandLabradorHydro Page4

    Figure2BaydEspoirTerminalStation#2AdditionsforNew230kVTransmissionLine

    AtWesternAvalonTerminalStationanew230kVringbusconsistingoffour230kVcircuit

    breakersisproposedforthesouthernendoftheterminalstation.Ratherthanconstruct

    thenewringbususingtraditionalgasfilled,airinsulatedcircuitbreakersandmotor

    operateddisconnectswitches,Hydroisproposingtouseacompactgasinsulated

    switchgear(GIS)ringbusconfiguration.TherationalefortheuseoftheGISequipmentisto

    limitthecivilworksfortheringbusaddition.TheWesternAvalonTerminalStationis

    situatedonthesideofahillnearChapelArm.Thelandtothewestoftheterminalstation

    consistsofanupwardslopingsteepembankmentwhichhashaddrainageissuesinthepast.

    Excavationtothewestwouldtobeextremelycostlyasitwouldrequireadditionalslope

  • UpgradeTransmissionLineCorridorBaydEspoirtoWesternAvalon

    NewfoundlandandLabradorHydro Page5

    stabilityanddrainageworkalongwithrelocationoftheexistingaccessroad.Thelandto

    theeastconsistsofadownwardslopingsteepembankmenttoRoute201.Expansioninthis

    directionwouldrequireextensiveamountsoffill.Ifacquisitionofbuildinglotsforpr