VIMAP D.O.O. Brace Jerkovic 137, 11000 Belgrade, Serbia tel.:+381 11 63 257 853, fax: +381 11 24 69 724 [email protected] www.vimap-technics.com .......... ..... ................. Case study TRANSFORMER 7.5 MVA, 110/27.5 kV TRANSFORMERS 7.5 MVA, 110/27.5 kV Manufacturer: Minel Ripanj, 1968. year, oil quantity: 9 t Serbian Railways, Electric-traction substations, Serbia ON SITE POWER TRANSFORMERS INSULATION OIL REGENERATION/RECLAMATION Oil regeneration in transformer was performed in off-line mode, according to the contractor request. Treatment lasted for ten days on each of transformers. Improvement of all oil characteristcs requested by contractor was obviously achieved. INSULATION OIL CHARACTERISTICS UNIT MARTINCI T2 INĐIJA T2 RESNIK T1 VODANJ T2 BEFORE AFTER BEFORE AFTER BEFORE AFTER BEFORE AFTER Dielectric strength kV/cm 226 287 208 300 218 283 155 > 250 Interfacial tension mN/m 18.1 38.2 20 35.6 28.6 43.1 26.7 37.63 Neutralization number mgKOH/g 0.017 0.01 0.115 0.02 0.10 0.011 0.12 0.018 DDF, tgδ of oil(90°C) x 10 -3 56.3 7.1 84.8 8.9 31 4.75 50.1 9.9

vimap-technics.com MVA Serbian Railways.pdf · 2014. 12. 18. · MARTINCI T2 INĐIJA T2 RESNIK T1 VODANJ T2 BEFORE AFTER BEFORE AFTER BEFORE AFTER BEFORE AFTER Dielectric strength

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: vimap-technics.com MVA Serbian Railways.pdf · 2014. 12. 18. · MARTINCI T2 INĐIJA T2 RESNIK T1 VODANJ T2 BEFORE AFTER BEFORE AFTER BEFORE AFTER BEFORE AFTER Dielectric strength

VIMAP D.O.O.

Brace Jerkovic 137, 11000 Belgrade, Serbia tel.:+381 11 63 257 853, fax: +381 11 24 69 724

[email protected] www.vimap-technics.com

.................

.................

Case study TRANSFORMER 7.5 MVA, 110/27.5 kV

TRANSFORMERS 7.5 MVA, 110/27.5 kV Manufacturer: Minel Ripanj, 1968. year, oil quantity: 9 t Serbian Railways, Electric-traction substations, Serbia

ON SITE POWER TRANSFORMERS INSULATION OIL REGENERATION/RECLAMATION

Oil regeneration in transformer was performed in off-line mode, according to the contractor request. Treatment lasted for ten days on each of transformers. Improvement of all oil characteristcs requested by contractor was obviously achieved.

INSULATION OIL CHARACTERISTICS

UNIT MARTINCI T2 INĐIJA T2 RESNIK T1 VODANJ T2

BEFORE AFTER BEFORE AFTER BEFORE AFTER BEFORE AFTER

Dielectric strength kV/cm 226 287 208 300 218 283 155 > 250

Interfacial tension mN/m 18.1 38.2 20 35.6 28.6 43.1 26.7 37.63

Neutralization number mgKOH/g 0.017 0.01 0.115 0.02 0.10 0.011 0.12 0.018

DDF, tgδ of oil(90°C) x 10-3 56.3 7.1 84.8 8.9 31 4.75 50.1 9.9