Upload
allovid
View
381
Download
17
Embed Size (px)
Citation preview
7/29/2019 wehre
1/8
1
8. Multi-pressure systems.
Example No. 1Calculate the power needed to compress 1.2 kg/s of ammonia from saturated vapor at 80 kPa to1000 kPa (a) by single-stage compression and (b) by two-stage compressiron with intercooling byliquid refrigerant at 300 kPa.
Given:Mass of ammonia = 1.2 kg/sFrom saturated vapor at 80 kPa to 1000 kPa.Intercooling at 300 kPaRequired:a. Power by single-stage compression.b. Power by two-stage compression with intercooling.Solution:
(a) Single stage compression (1-3-6)From properties of Ammonia.At state point 1. Saturated at 80 kPa
kgkJh 14101=
KkgkJs = 207261
.
At state point 3, 1000 kPa, s3= s1. (Superheated ammonia)kgkJh 1800
3=
Power required = ( ) ( ) kWhhw 468141018002113
== .
(b) By two-stage compression with intercooling.From properties of Ammonia.At state point 1. Saturated at 80 kPa
7/29/2019 wehre
2/8
2
kgkJh 14101=
KkgkJs = 207261
.
At state point 2, 300 kPa, s2= s1. (Superheated ammonia)
kgkJh 15882=
At state point 4, saturated at 300 kPa
kgkJh 14504 = KkgkJs = 74515
4.
At state point 5, 1000 kPa, s5= s4. (Superheated ammonia)
kgkJh 16285=
At state point 6, 1000 kPa, saturated liquid.
kgkJh 3166=
The flow rate of ammonia compressed in the high stage can be calculated by making a heat and amass balance about the intercooler, as shown in Figure 6.
Heat balance:
442266hwhwhw =+
( ) ( )( ) ( )kgkJwkgkJskgkgkJw 145015882131646
=+ .
Mass balance:
426www =+
4621 ww =+ .
Solving gives:
skgw 34614
.=
Power required = ( ) ( )454122hhwhhw +
Power required = ( ) ( ) kW24531450162834611410158821 ... =+=
Intercooling the ammonia with liquid refrigerant reduced the power requirement from 468 to 453.2kW.
7/29/2019 wehre
3/8
3
Example No. 2Calculate the power required by the two compressors in an ammonia system which serves a 250-kWevaporator at -25 C. The system uses two-stage compression with intercooling and removal of flashgas. The condensing temperature is 35 C.Given:Required:Solution:First sketch the schematic diagram of the system (Figure 10a) and the corresponding pressure-enthalpy diagram (Figure 10b). The functions of the intercooler and flash tank are combined in onevessel.
7/29/2019 wehre
4/8
4
Determine the intermediate pressure for optimum economy.ps= saturation pressure at -25 C = 152 kPapd= saturation pressure at 35 C = 1352 kPa
( )( ) kPappp dsi 4531352152 ===
The enthalpies at all points can now be determined from ammonia table of properties.At state point 1
h1 = hgat -25 C = 1430 kJ/kgs1 = 5.9813 kJ/kg-KAt state point 2, s2= s1h2= hat 453 kPa after isentropic compression = 1573 kJ/kgAt state point 3h3= hgat 453 kPas3= 5.6001 kJ/kgAt state point 4, s4= s3
h4 = h at 1352 kPa after isentropic compression = 1620 kJ/kg
At state point 5
h5= hfat 35 C = 366 kJ/kg
At state point 6
h6= h5 = 366 kJ/kgAt state point 7
h7= hfat 453 kPa = 202 kJ/kg
At state point 8
h8 = h7= 202 kJ/kg
Mass rates of flow:
Heat balance about the evaporator:
7/29/2019 wehre
5/8
5
skghh
Qm A 2040
2021430
250
81
1.=
=
=
skgmmmm 20408721
.====
Heat and mass balance about the intercooler:
33776622hmhmhmhm +=+
36 mm = and 27 mm =
( ) ( ) ( ) ( )146320220403661573204033
mm +=+ ..
skgm 25503
.=
Low-stage power: m1(h2 h1) = (0.204 kg/s)(1573 1430 kJ/kg) = 29.2 kW
High-stage power: m3(h4 h3) = (0.255 kg/s)(1620 1463 kJ/kg) = 40.0 kW
Total power: 29.2 + 40.0 = 69.2 kW
Example No. 3
In an ammonia system one evaporator is to provide 180 kW of refrigeration at -30 C and another
evaporator is to provide 200 kW at 5 C. The system uses two-stage compression with intercooling
and is arranged as in Figure 11a. The condensing temperature is 40 C. Calculate the power required
by the compressors.
Given:
180 kw of refrigeration at -30 C
200 kw of refrigeration at 5 C
Condensing temperature is 40 C
Required:
Power required by the compressor.
Solution:
Sketch the pressure-enthalpy diagram of the cycle as in Figure 11b.
7/29/2019 wehre
6/8
6
7/29/2019 wehre
7/8
7
The discharge pressure of the low-stage compressor and the suction pressure of the high stage
compressor are the same as the pressure in the 5 C evaporator.
Enthalpies at the state points.
At state point 1
h1 = hg at -30 C = 1423 kJ/kg
s1= sg at -30 C = 6.0636 kJ/kg-K
At state point 2
h2 = h at 517 kPa after isentropic compression =1630 kJ/kg
At state point 3
h3 = hg at 5 C = 1467 kJ/kg
s3= sg at 5 C = 5,5545 kJ/kg-K
At state point 4
h4 = h at 1557 kPa after isentropic compression = 1652 kJ/kg
At state point 5
h5 = hfat 40 C = 390.6 kJ/kgAt state point 6
h6 = h5 = 390.6 kJ/kg
At state point 7
h7= hfat 5 C = 223 kJ/kg
At state point 8
h8 = h7= 223 kJ/kg
Mass rates of flow:
skgkgkJ
kW
hh
Qm A 1500
2231423
180
81
1
1.=
=
=
skgmmmm 15001287
.====
Probably the simplest way to calculate the mass rate of flow handled by the high-stage compressor
is to make a heat and mass balance about both the high temperature evaporator and the
intercooler, as shown in Figure 12.
7/29/2019 wehre
8/8
8
Heat balance:773322255hmhmhmQhm A +=++
Mass balance:
skgmm 150072
.==
Therefore:
35mm =
Combining gives:
( ) ( ) ( ) ( )2231500146716301500200639033
... +=++ mm
Solving leads to
skgm 38203
.=
The power required by the compressors can now be calculated:
Low-stage power: ( ) ( ) kWhhm 131142316301500343 .. ==
High-stage power: ( ) ( ) kWhhm 460146716253820121
.. ==
Total = 91.5 kW