wehre

  • Upload
    allovid

  • View
    381

  • Download
    17

Embed Size (px)

Citation preview

  • 7/29/2019 wehre

    1/8

    1

    8. Multi-pressure systems.

    Example No. 1Calculate the power needed to compress 1.2 kg/s of ammonia from saturated vapor at 80 kPa to1000 kPa (a) by single-stage compression and (b) by two-stage compressiron with intercooling byliquid refrigerant at 300 kPa.

    Given:Mass of ammonia = 1.2 kg/sFrom saturated vapor at 80 kPa to 1000 kPa.Intercooling at 300 kPaRequired:a. Power by single-stage compression.b. Power by two-stage compression with intercooling.Solution:

    (a) Single stage compression (1-3-6)From properties of Ammonia.At state point 1. Saturated at 80 kPa

    kgkJh 14101=

    KkgkJs = 207261

    .

    At state point 3, 1000 kPa, s3= s1. (Superheated ammonia)kgkJh 1800

    3=

    Power required = ( ) ( ) kWhhw 468141018002113

    == .

    (b) By two-stage compression with intercooling.From properties of Ammonia.At state point 1. Saturated at 80 kPa

  • 7/29/2019 wehre

    2/8

    2

    kgkJh 14101=

    KkgkJs = 207261

    .

    At state point 2, 300 kPa, s2= s1. (Superheated ammonia)

    kgkJh 15882=

    At state point 4, saturated at 300 kPa

    kgkJh 14504 = KkgkJs = 74515

    4.

    At state point 5, 1000 kPa, s5= s4. (Superheated ammonia)

    kgkJh 16285=

    At state point 6, 1000 kPa, saturated liquid.

    kgkJh 3166=

    The flow rate of ammonia compressed in the high stage can be calculated by making a heat and amass balance about the intercooler, as shown in Figure 6.

    Heat balance:

    442266hwhwhw =+

    ( ) ( )( ) ( )kgkJwkgkJskgkgkJw 145015882131646

    =+ .

    Mass balance:

    426www =+

    4621 ww =+ .

    Solving gives:

    skgw 34614

    .=

    Power required = ( ) ( )454122hhwhhw +

    Power required = ( ) ( ) kW24531450162834611410158821 ... =+=

    Intercooling the ammonia with liquid refrigerant reduced the power requirement from 468 to 453.2kW.

  • 7/29/2019 wehre

    3/8

    3

    Example No. 2Calculate the power required by the two compressors in an ammonia system which serves a 250-kWevaporator at -25 C. The system uses two-stage compression with intercooling and removal of flashgas. The condensing temperature is 35 C.Given:Required:Solution:First sketch the schematic diagram of the system (Figure 10a) and the corresponding pressure-enthalpy diagram (Figure 10b). The functions of the intercooler and flash tank are combined in onevessel.

  • 7/29/2019 wehre

    4/8

    4

    Determine the intermediate pressure for optimum economy.ps= saturation pressure at -25 C = 152 kPapd= saturation pressure at 35 C = 1352 kPa

    ( )( ) kPappp dsi 4531352152 ===

    The enthalpies at all points can now be determined from ammonia table of properties.At state point 1

    h1 = hgat -25 C = 1430 kJ/kgs1 = 5.9813 kJ/kg-KAt state point 2, s2= s1h2= hat 453 kPa after isentropic compression = 1573 kJ/kgAt state point 3h3= hgat 453 kPas3= 5.6001 kJ/kgAt state point 4, s4= s3

    h4 = h at 1352 kPa after isentropic compression = 1620 kJ/kg

    At state point 5

    h5= hfat 35 C = 366 kJ/kg

    At state point 6

    h6= h5 = 366 kJ/kgAt state point 7

    h7= hfat 453 kPa = 202 kJ/kg

    At state point 8

    h8 = h7= 202 kJ/kg

    Mass rates of flow:

    Heat balance about the evaporator:

  • 7/29/2019 wehre

    5/8

    5

    skghh

    Qm A 2040

    2021430

    250

    81

    1.=

    =

    =

    skgmmmm 20408721

    .====

    Heat and mass balance about the intercooler:

    33776622hmhmhmhm +=+

    36 mm = and 27 mm =

    ( ) ( ) ( ) ( )146320220403661573204033

    mm +=+ ..

    skgm 25503

    .=

    Low-stage power: m1(h2 h1) = (0.204 kg/s)(1573 1430 kJ/kg) = 29.2 kW

    High-stage power: m3(h4 h3) = (0.255 kg/s)(1620 1463 kJ/kg) = 40.0 kW

    Total power: 29.2 + 40.0 = 69.2 kW

    Example No. 3

    In an ammonia system one evaporator is to provide 180 kW of refrigeration at -30 C and another

    evaporator is to provide 200 kW at 5 C. The system uses two-stage compression with intercooling

    and is arranged as in Figure 11a. The condensing temperature is 40 C. Calculate the power required

    by the compressors.

    Given:

    180 kw of refrigeration at -30 C

    200 kw of refrigeration at 5 C

    Condensing temperature is 40 C

    Required:

    Power required by the compressor.

    Solution:

    Sketch the pressure-enthalpy diagram of the cycle as in Figure 11b.

  • 7/29/2019 wehre

    6/8

    6

  • 7/29/2019 wehre

    7/8

    7

    The discharge pressure of the low-stage compressor and the suction pressure of the high stage

    compressor are the same as the pressure in the 5 C evaporator.

    Enthalpies at the state points.

    At state point 1

    h1 = hg at -30 C = 1423 kJ/kg

    s1= sg at -30 C = 6.0636 kJ/kg-K

    At state point 2

    h2 = h at 517 kPa after isentropic compression =1630 kJ/kg

    At state point 3

    h3 = hg at 5 C = 1467 kJ/kg

    s3= sg at 5 C = 5,5545 kJ/kg-K

    At state point 4

    h4 = h at 1557 kPa after isentropic compression = 1652 kJ/kg

    At state point 5

    h5 = hfat 40 C = 390.6 kJ/kgAt state point 6

    h6 = h5 = 390.6 kJ/kg

    At state point 7

    h7= hfat 5 C = 223 kJ/kg

    At state point 8

    h8 = h7= 223 kJ/kg

    Mass rates of flow:

    skgkgkJ

    kW

    hh

    Qm A 1500

    2231423

    180

    81

    1

    1.=

    =

    =

    skgmmmm 15001287

    .====

    Probably the simplest way to calculate the mass rate of flow handled by the high-stage compressor

    is to make a heat and mass balance about both the high temperature evaporator and the

    intercooler, as shown in Figure 12.

  • 7/29/2019 wehre

    8/8

    8

    Heat balance:773322255hmhmhmQhm A +=++

    Mass balance:

    skgmm 150072

    .==

    Therefore:

    35mm =

    Combining gives:

    ( ) ( ) ( ) ( )2231500146716301500200639033

    ... +=++ mm

    Solving leads to

    skgm 38203

    .=

    The power required by the compressors can now be calculated:

    Low-stage power: ( ) ( ) kWhhm 131142316301500343 .. ==

    High-stage power: ( ) ( ) kWhhm 460146716253820121

    .. ==

    Total = 91.5 kW