(Www.sayedsaad.com)ProteccioBUS
Embed Size (px)
DESCRIPTION
protection
Citation preview
PowerPoint PresentationMultirestraint differential system
Overcurrent differential protection
Other protection systems
It is of essential importance that the instrument transformers can
withstand the rated primary currents and the fault currents that
can arise. If the CT breaks down, the entire associated equipment
will be left unprotected since no information then will be supplied
to the protective relays.
If the relays don’t get any signals the protection system is out of
order and severe damages can occur in the HV net.
© ABB Power Technology 1_114Q07- * -
Multirestraint differential system
Overcurrent differential protection
Other protection systems
It is of essential importance that the instrument transformers can
withstand the rated primary currents and the fault currents that
can arise. If the CT breaks down, the entire associated equipment
will be left unprotected since no information then will be supplied
to the protective relays.
If the relays don’t get any signals the protection system is out of
order and severe damages can occur in the HV net.
© ABB Power Technology 1_114Q07- * -
Introduction
A bus is a critical element of a power system, as it is the point
of convergence of many circuits, transmission, generation, or
loads.
The effect of a single bus fault is equivalent to many simultaneous
faults and usually, due to the concentration of supply circuits,
involves high-current magnitudes.
High-speed bus protection is often required to limit the damaging
effects on equipment and system stability or to maintain service to
as much load as possible.
The bus protection described refers to protection at the bus
location, independent of equipment at remote locations
© ABB Power Technology 1_114Q07- * -
Ct saturation and its solutions on bus protection
Differential protection is the most sensitive and reliable method
for protecting a station bus.
The phasor summation of all the measured current entering and
leaving the bus must be 0 unless there is a fault within the
protective zone.
For a fault not in the protective zone, the instantaneous direction
of at least one current is opposite to the others.
However, a current transformer saturation problem can result from
the large number of circuits involved and the different
energization levels encountered in these circuits for external
faults.
For example, if there is an external fault on one circuit of a
six-circuit bus, five of the current transformers may supply
varying amounts of fault current, but the sixth and faulted circuit
must balance out the total of all the others.
Consequently, this circuit is energized at a much higher level,
near saturation or with varying degrees of saturation, giving rise
to possible high false differential currents.
© ABB Power Technology 1_114Q07- * -
For the same reasons, dc saturation also is unequal.
Dc saturation is much more serious than ac saturation because a
relatively small amount of dc from an asymmetrical fault wave will
saturate the current transformer core and appreciably reduce the
secondary output.
The L/R ratio of the power-system impedance, which determines the
decay of the dc component of fault current, should strongly
influence the selection of the bus protective relaying.
Typically, the dc time constants for the different circuit elements
can vary from 0.01 sec for lines to 0.3 sec or more for generating
plants.
The nearer a bus location is to a strong source of generation, the
greater the L/R ratio and the slower the decay of the resulting dc
component of fault current.
© ABB Power Technology 1_114Q07- * -
Ct saturation and its solutions on bus protection
Of the several available methods for solving the unequal
performance of current transformers, four are in common use:
Eliminating the problem by eliminating iron in the current
transformer [a linear coupler (LC) system]
Using a multi-restraint, variable-percentage differential relay,
which is specifically designed to be insensitive to dc
saturation
Using a high-impedance differential relay with a series resonant
circuit to limit sensitivity to ct saturation
Using a restraint differential relay with moderately high impedance
to limit sensitivity to ct saturation
© ABB Power Technology 1_114Q07- * -
Information required
When local bus protection is applied, the following information is
required for the scheme selection, relay selection, and setting
calculations:
Bus configuration information.
Current transformer information, including
There is one set of bus relays per bus section.
Use a dedicated ct for bus differential protection.
If possible, the connection of meters, auxiliary cts, and other
relays in differential-type bus schemes should be avoided since
these devices introduce an additional burden into the main
circuit.
Lead resistance, as well as ct winding resistance, contributes to
ct saturation. Therefore, the length of secondary lead runs should
be held to a minimum.
Usually, the full-ct secondary winding tap should be used. This has
two advantages. It minimizes the burden effect of the cable and,
second, leads by minimizing the secondary current and makes use of
the full-voltage capability of the ct.
© ABB Power Technology 1_114Q07- * -
Normal Practices on Bus Protection
Normally, there is no bus relay required for the transfer bus on a
main-and-transfer bus arrangement, because the transfer bus is
normally deenergized and will be included in the main bus section
when it is energized.
No bus relay is required for a ring bus because the bus section
between each pair of circuit breakers is protected as a part of the
connected circuit.
Special arrangements should be considered if there is any other
apparatus, such as station service transformers, capacitor banks,
grounding transformers, or surge arresters, inside the bus
differential zone.
There is no simple scheme available for a double-bus-single-breaker
arrangement , because its current transformers are normally located
on the line side.
© ABB Power Technology 1_114Q07- * -
Multirestraint differential system
Overcurrent differential protection
Other protection systems
It is of essential importance that the instrument transformers can
withstand the rated primary currents and the fault currents that
can arise. If the CT breaks down, the entire associated equipment
will be left unprotected since no information then will be supplied
to the protective relays.
If the relays don’t get any signals the protection system is out of
order and severe damages can occur in the HV net.
© ABB Power Technology 1_114Q07- * -
The linear coupler scheme provides a highly reliable bus
protection.
Of the four systems commonly in use,
it has a fast operating time;
is the easiest to apply, set, and maintain;
can readily accommodate switching or changes in the bus
layout.
Since iron is eliminated, an air-core transformer, a linear
coupler, is required.
Adding a linear coupler can be a disadvantage, particularly in
existing installations where adequate current transformers
exist.
© ABB Power Technology 1_114Q07- * -
Linear couplers are air-core mutual reactors wound on nonmagnetic
toroidal cores.
Linear couplers are designed to fit into the same space as a
conventional current transformer.
Bushing or wound-type units are available for most of the voltage
classes.
They are usually mounted in a circuit breaker or transformer
bushing.
The single conductor through the center of the unit forms the
primary of an air-core reactor and provides a definite linear
relationship between the primary current and secondary
voltage.
© ABB Power Technology 1_114Q07- * -
The linear coupler differential system
The linear couplers have a negligible dc response, so only the
steady-state conditions need be considered.
The linear coupler method of differential protection is a voltage
differential scheme in which a series circuit is used.
All the linear coupler secondaries of a particular phase are
connected in series with one relay to form a closed loop.
Under normal conditions or when external faults occur, the induced
voltages in all the linear couplers add to 0.
On the internal faults, the net voltage will operate the
relay.
© ABB Power Technology 1_114Q07- * -
The linear coupler differential system
The linear coupler bus protection system can easily accommodate
system changes and future expansion. In addition, it can be applied
to an unlimited number of circuits.
Since the linear couplers do not contain iron, there are no
saturation or transient problems.
The setting is calculated using only Ohm's law.
The operating time is between 32 ms and 16 ms.
Relays require minimum panel space.
The operating voltages are safe for personnel and well within the
insulation limits of all connected apparatus.
Since linear couplers may be open- or short-circuited with complete
safety, circuits can be switched among several bus sections much
more easily than conventional current transformers.
© ABB Power Technology 1_114Q07- * -
The linear coupler differential system
In connecting linear couplers, the four wires from the
star-connected couplers should be transposed with respect to all
other circuits and carried in the same conduit or duct.
If a multiconductor cable is used, the other conductors should not
be employed unless there is no possibility of their inducing
tripping voltages into the linear coupler circuits.
Manual test auxiliaries are used to check the scheme during
installation and at regular test intervals.
To check for correct connections and a shorted coupler, three
high-resistance voltmeters are connected across the relays.
With load currents flowing, these voltages should be very low or
0.
Since the circuit might also be open at some point, a second test,
which requires opening the trip circuit, is also applied. A low
series voltage of 0.6 or 1.2 V is introduced into the differential
source. Approximately half this test voltage will appear across the
voltmeter; the remainder will appear across the rest of the loop.
An open circuit will cause the voltmeter to register 0 voltage or
full test voltage, depending on whether the coupler or relay
circuit is open.
© ABB Power Technology 1_114Q07- * -
Multirestraint differential system
Overcurrent differential protection
Other protection systems
It is of essential importance that the instrument transformers can
withstand the rated primary currents and the fault currents that
can arise. If the CT breaks down, the entire associated equipment
will be left unprotected since no information then will be supplied
to the protective relays.
If the relays don’t get any signals the protection system is out of
order and severe damages can occur in the HV net.
© ABB Power Technology 1_114Q07- * -
Multirestraint differential schemes use conventional current
transformers, which may saturate on heavy external faults.
For this reason, the secondary current output may not represent the
primary.
In a differential scheme, the current transformers and relay
function as a team.
When the current transformers do not perform adequately, the relay
can within limits make up for the deficiency.
For this scheme, a more complex relay is required than that
described for the linear coupler bus protection system.
More elaborate application rules are also necessary, since there is
a limit of current transformer performance beyond which the relay
cannot compensate.
© ABB Power Technology 1_114Q07- * -
The multi-restraint differential scheme uses the
variable-percentage differential relay, which consists of three
induction restraint units and one induction-operating unit.
Two of the units are placed opposite each other and operate on a
common disc.
In turn, the two discs are connected to a common shaft with the
moving contacts.
All four of the units are unidirectional; that is, current flow in
either direction through the windings generates contact-opening
torque for the restraint units or contact-closing torque for the
operating unit.
© ABB Power Technology 1_114Q07- * -
Multirestraint differential system
Each restraint unit (called R, S, and T) also has two windings to
provide restraint proportional to the sum or difference, depending
on the direction of the current flow.
If the currents in the two paired windings are equal and opposite,
the restraint is cancelled.
Thus, the paired restraint windings have a polarity with respect to
each other. With this method six restraint windings arc
available.
© ABB Power Technology 1_114Q07- * -
In addition to providing multiple restraint, the
variable-percentage characteristic helps in overcoming current
transformer errors.
At light fault currents, current transformer performance is good,
and the percentage is small for maximum sensitivity.
For heavy external faults, current transformer performance is
likely to be poor, and the percentage is large.
The variable-percentage characteristic is obtained by energizing
the operating unit through a built-in saturating
autotransformer.
© ABB Power Technology 1_114Q07- * -
Multirestraint differential system
The saturating autotransformer also presents a high impedance to
the false differential current, which tends to limit the current
through the operating coil and to force more equal saturation of
the current transformers.
On internal faults, in which a desirable high differential current
exists, saturation reduces the impedance.
A further advantage of the saturating autotransformer is that it
provides a very effective shunt for the dc component, appreciably
reducing the dc sensitivity of the operating units.
At the minimum pickup current of 0.15 ± 5% A, the restraining coils
are ineffective.
© ABB Power Technology 1_114Q07- * -
Multirestraint differential system
Figure on the left may be used if only three circuits are involved.
The term circuit refers to a source or feeder group.
When several circuits exist and the bus can be reduced to four
circuits, then the second scheme may be used.
For example, assume a bus consists of two sources and six feeders,
and that the feeders are lumped into two groups.
The bus now reduces to four circuits.
© ABB Power Technology 1_114Q07- * -
Multirestraint differential system
In paralleling current transformers, each feeder group must have
less than 14-A load current (restraint coil continuous
rating).
If the bus reduces to more than four circuits, then the scheme
should be used.
Each primary circuit must be identified as either a source or
feeder.
Next, a number of feeders are lumped into a feeder group by
paralleling feeder current transformers.
Each feeder group must have less than 14-A load current and not
contribute more than 10% of the total phase or ground fault current
for a bus fault.
Then connect the “source” and “feeder groups” alternately as shown
in Figure.
© ABB Power Technology 1_114Q07- * -
Multirestraint differential system
Overcurrent differential protection
Other protection systems
It is of essential importance that the instrument transformers can
withstand the rated primary currents and the fault currents that
can arise. If the CT breaks down, the entire associated equipment
will be left unprotected since no information then will be supplied
to the protective relays.
If the relays don’t get any signals the protection system is out of
order and severe damages can occur in the HV net.
© ABB Power Technology 1_114Q07- * -
Overcurrent Differential Protection
The differential scheme is obtained by paralleling all the current
transformers per phase with an induction disc overcurrent relay
across their output.
It is permissible to use auxiliary ct's to match ratios.
It is most desirable for all ct's to have the same ratio on the tap
used so that auxiliary ct's are not required.
© ABB Power Technology 1_114Q07- * -
Overcurrent Differential Protection
Relays must be set above the maximum false differential current for
an external fault.
That is, very little saturation can be allowed if any degree of
internal fault sensitivity is to be obtained.
A certain amount of dc or ac saturation can be tolerated,
because
(1) the operation of induction disc relays on the dc component is
less efficient, and
(2) the relay operation is not instantaneous.
To increase the response of these schemes, the dc time decrement
must be short.
This requirement virtually limits applications to substation buses
remote from large generating stations.
Although the relay cost is low, the engineering cost is usually
high, since considerable study or experience is required to assure
correct operation.
© ABB Power Technology 1_114Q07- * -
Improved Overcurrent Differential Protection
The sensitivity of the overcurrent differential scheme can be
improved by externally connecting a series resistor with each
overcurrent relay, as shown in Figure a.
These resistors are called stabilizing resistors.
© ABB Power Technology 1_114Q07- * -
Multirestraint differential system
Overcurrent differential protection
Other protection systems
It is of essential importance that the instrument transformers can
withstand the rated primary currents and the fault currents that
can arise. If the CT breaks down, the entire associated equipment
will be left unprotected since no information then will be supplied
to the protective relays.
If the relays don’t get any signals the protection system is out of
order and severe damages can occur in the HV net.
© ABB Power Technology 1_114Q07- * -
Although the high-impedance differential scheme also uses
conventional current transformers, it avoids the problem of unequal
current transformer performance by loading them with a
high-impedance relay.
This arrangement tends to force the false differential currents
through the current transformers rather than the relay operating
coil.
Actually, the high-impedance differential concept comes from the
above “improved overcurrent differential” approach. It uses a
high-impedance voltage element instead of “a low impedance
overcurrent element plus an external resistor.”
© ABB Power Technology 1_114Q07- * -
The high-impedance differential relay consists of an instantaneous
overvoltage cylinder unit (V), a voltage-limiting suppressor
(varistor), an adjustable tuned circuit, and an instantaneous
current unit (IT).
On external faults, the voltage across the relay terminals will be
low, essentially 0, unless the current transformers are unequally
saturated.
On internal faults, the voltage across the relay terminals will be
high and will operate the over voltage unit. Since the impedance of
the over voltage unit is 2600 ohm, this high voltage may approach
the open-circuit voltage of the current transformer secondaries.
The varistor limits this voltage to a safe level.
© ABB Power Technology 1_114Q07- * -
High-impedance differential system
Since offset fault current or residual magnetism exists in the
current transformer core, there is an appreciable dc component in
the secondary current.
The dc voltage that appears across the relay will be filtered out
by the tuned circuit, preventing relay pickup.
The IT current unit provides faster operation on severe internal
faults and also backup to the voltage unit.
The relay has successfully performed operations up to external
fault currents of 200 A secondary and down to an internal fault
current of 0.27 A secondary. Its typical operating speed is 25
msec.
© ABB Power Technology 1_114Q07- * -
Multirestraint differential system
Overcurrent differential protection
Other protection systems
It is of essential importance that the instrument transformers can
withstand the rated primary currents and the fault currents that
can arise. If the CT breaks down, the entire associated equipment
will be left unprotected since no information then will be supplied
to the protective relays.
If the relays don’t get any signals the protection system is out of
order and severe damages can occur in the HV net.
© ABB Power Technology 1_114Q07- * -
They combine the advantages of high-impedance and percentage
restraint differential characteristics in one unique operating
principle, which provides reliable operation for internal faults
and secure restraint on external faults.
They can accommodate a large range of line ct ratios, other relays
may be included with the same ct circuit, and the bus arrangement
can easily be changed or added to without concern.
The relay generally connects to the system with a special auxiliary
ct required for each restraint circuit when 5-A-rated cts are
used.
One restraint circuit is required for each phase of each circuit or
combination of circuits connected to the bus.
The auxiliary ct permits the use of unmatched ct ratios to bring
the overall ratios into agreement and permit the possible use of
other burdens in the ct circuits.
© ABB Power Technology 1_114Q07- * -
Moderately high-impedance relay
The relay operates on the principle of a differential comparison
between all incoming and out-going lines to the bus.
Circuits L1, L2, ... Lx, are connected to auxiliary ct's TM1, TM2,
.... TMx, respectively, which balance the main ct ratios.
Current fed into the relay becomes IL1, IL2, ... ILX, combining for
a total input of IT at terminal K.
The comparator circuit is made up of resistors RS, Rd3, Rd1, and
transformer TMD.
© ABB Power Technology 1_114Q07- * -
Moderately high-impedance relay
Resistor Rs, across which is developed the restraint voltage VS, is
composed of two equal resistors.
Operate voltage Vd3 is developed across resistor Rd3. The
differential resistor Rd1 is a series connection of resistors that
are connected depending on the characteristics of the ct´s and the
required total circuit resistance.
© ABB Power Technology 1_114Q07- * -
Moderately high-impedance relay
The TMD is a toroidal core transformer. The voltage developed
across the primary Vd1 is proportional to the differential current
Id1. This produces the transformer secondary voltage Vd2. Secondary
current Id2 flow in such a way as to develop operating voltage Vd3
is greater than the restraint voltage VS.
The toroidal reactor TMZ and associated diodes D1 and D2 make up
the voltage-limiting circuit. The start function is used to
supervise the trip.
© ABB Power Technology 1_114Q07- * -
Multirestraint differential system
Overcurrent differential protection
Other protection systems
It is of essential importance that the instrument transformers can
withstand the rated primary currents and the fault currents that
can arise. If the CT breaks down, the entire associated equipment
will be left unprotected since no information then will be supplied
to the protective relays.
If the relays don’t get any signals the protection system is out of
order and severe damages can occur in the HV net.
© ABB Power Technology 1_114Q07- * -
Protecting a bus that includes a transformer bank
Ideally, when the bus includes a power transformer bank, separate
protection should be provided for the bus and transformer, even
though both protection schemes must trip all breakers around the
two units.
Such a system offers maximum continuity of service, since faults
are easier to locate and isolate.
Also, using a bus differential relay for bus protection and
transformer differential relay for transformer protection provides
maximum sensitivity and security with minimum application
engineering.
However, economics and location of current transformers often
dictate that both units be protected in one differential
zone.
© ABB Power Technology 1_114Q07- * -
Protecting a bus that includes a transformer bank
A typical application, shown in Figure, protects a three-winding
transformer bus with four circuits.
© ABB Power Technology 1_114Q07- * -
Multirestraint differential system
Overcurrent differential protection
Other protection systems
It is of essential importance that the instrument transformers can
withstand the rated primary currents and the fault currents that
can arise. If the CT breaks down, the entire associated equipment
will be left unprotected since no information then will be supplied
to the protective relays.
If the relays don’t get any signals the protection system is out of
order and severe damages can occur in the HV net.
© ABB Power Technology 1_114Q07- * -
Protecting a double-bus single breaker with bus tie
arrangement
The double-bus single breaker with bus tie provides economic and
operating flexibility comparable to the double-bus double-breaker
arrangement.
However, the ct's are normally on the line-side location, which
results in increased differential relaying problems.
© ABB Power Technology 1_114Q07- * -
Protecting a double-bus single breaker with bus tie
arrangement
Two different approaches have been used in the bus protection of
such arrangements:
the fully switched scheme
© ABB Power Technology 1_114Q07- * -
the paralleling switch scheme
They are both complicated (inserting switch contacts in the ct
circuits) and / or imperfect in protection.
These schemes either require switching ct's and/or disabling the
bus protection before any switching operation.
This is a period when the probability of a bus fault occurring is
high and it is most desirable that the bus protection be in
service.
© ABB Power Technology 1_114Q07- * -
A third scheme can be considered.
It is similar to the paralleling switched scheme except a
check-zone relay is added as shown.
Two bus differential zones are provided, one for each bus, with
each one overlapping the bus breaker.
Each primary circuit is normally switched to a specific bus, and
relay input circuits and breaker control circuits are wired
accordingly.
© ABB Power Technology 1_114Q07- * -
The additional check-zone device supervises the trip
circuits.
If it becomes necessary to clear one of the buses, all the primary
circuits may be switched to the opposite bus and it is needless to
disable the bus protection before any switching operation.
However, this scheme still has two drawbacks when any one or all of
the primary circuits is switched to the opposite bus:
(1) It will lose its selectivity, and
(2) it will reduce its sensitivity since the two relays are
paralleled.
© ABB Power Technology 1_114Q07- * -
Multirestraint differential system
Overcurrent differential protection
Other protection systems
It is of essential importance that the instrument transformers can
withstand the rated primary currents and the fault currents that
can arise. If the CT breaks down, the entire associated equipment
will be left unprotected since no information then will be supplied
to the protective relays.
If the relays don’t get any signals the protection system is out of
order and severe damages can occur in the HV net.
© ABB Power Technology 1_114Q07- * -
Partial differential relaying
This type of protection is also referred to as “bus over-load” or
“selective backup” protection.
It is a variation of the differential principle in which currents
in one or more of the circuits are not included in the phasor
summation of the current to the relay.
In this scheme, only the source circuits are differentially
connected, as shown in Figure, using a high-set over current relay
with time delay.
The ct's protecting the feeders or circuits are not in the
differential.
© ABB Power Technology 1_114Q07- * -
Essentially, this arrangement combines time-delay bus protection
with feeder backup protection.
The sensitivity and speed of this scheme are not as good as with
complete differential protection.
This method may be used as a backup to a complete differential
scheme, as primary protection for a station with loads protected by
fuses, or to provide local breaker failure protection for load
breakers.
Some partial differential circuits use distance-type relays in the
scheme.
The use of a distance relay for this scheme produces both faster
and more sensitive operation than the over current scheme.
© ABB Power Technology 1_114Q07- * -
Directional comparison relaying
Occasionally, it is desirable to add bus protection to an older
substation where additional ct's and control cable are too costly
to install.
In this instance, the existing ct circuits used for line relaying
can also be used for the directional comparison bus relaying
protection.
As shown in Figure, the directional comparison relaying uses
individual directional over current relays on all sources and
instantaneous over current relays on all feeders.
© ABB Power Technology 1_114Q07- * -
Directional comparison relaying
The directional relays close contacts when fault power flows into
the bus section. Back contacts on the over current relays open when
the fault is external on the feeder.
All contacts are connected in series, and when the fault occurs on
the bus, the trip circuit is energized through a timer.
A time delay of at least four cycles will allow all the relays to
decide correctly the direction of the fault and to permit contact
coordination.
In this scheme, the ct's in each circuit do not require the same
ratio and can be used for other forms of relaying and
metering.
The disadvantage of this scheme is the large number of contacts and
complex connections required. There is also the remote possibility
of the directional elements not operating on a solid three-phase
bus fault as a result of 0 voltage.
© ABB Power Technology 1_114Q07- * -
Fault Bus (Ground-Fault Protection Only)
This method requires that all the bus supporting structure and
associated equipment be interconnected and have only one connection
to ground.
An over current relay is connected in this ground path.
Any ground fault to the supporting structure will cause fault
current to flow through the relay circuit, tripping the bus through
the multiple contact auxiliary tripping relay.
A fault detector, energized from the neutral of the grounded
transformer or generator, prevents accidental tripping.
This scheme requires special construction measures and is
expensive.