Communication Issues in Distribution Automation –the CESC experience

Debasis GuptaDCE (Distribution Automation)

CESC Limited, [email protected]

www.cesc.co.in

GridWeek Asia 2012

#GridAsia Mumbai, India Jan 16-18, 2012 2

CESC Limited - Powering Kolkata since 1899

Year ending 31.3.11

Units Sold: 8135 MU (HT 36%, LT 64%)System Met: 1657 MWT&D Losses : 13 %Energy Generated = 7995 MUEnergy Imported = 1485 MUEnergy Exported = 110 MU

HT Consumers: 1763LT Consumers: 2.48 Million

Licensed Area: 567 Sq Kms

Installed Generation Capacity: 1225 MW

India's first fully integrated electrical utility, generating and distributing electrical power in Kolkata and Howrah since 1899.

GridWeek Asia 2012

#GridAsia Mumbai, India Jan 16-18, 2012 3

6 kV

11 kV

33 kV

132 kV

220 kV

“Substations”19 Nos

“Distribution Stations”100 Nos

“DTs”7000+

5 ImportPoints

4 CESC Gen StnsInstalled Capacity= 1225 MW

400 /230 VMV / LV

“Transmission” SCADA “Distribution” SCADA/DMS system

RMUAutomation

AMR –DTs

AMR –High end Tariff Meters & Street Lights

“RMUs”3500+

Distribution Automation Activities in CESC

Communications: WirelineFibre Optic Transmission System

Communications: WirelessGPRS/ CDMA

Excellent communications- SDH STM4- Gigabit Ethernet- CESC owns 500 Kms of OF lines

POOR throughputOK for AMR applicationsNOT yet suitable for Feeder Automation

GridWeek Asia 2012

#GridAsia Mumbai, India Jan 16-18, 2012 4

Working well … SCADA Systems on Fibre Optic Communications

“Transmission” SCADA MCC “Distribution” SCADA/DMS MCC RTU & MDF at a Distribution Station

PDH / SDH (STM4) Panels PDH / SDH NMS Data Centre with Gigabit Ethernet

Mostly from Siemens, Sinaut-Spectrum, AK1703 & TM 1703 RTUs IEC 870-5-101 & IEC-870-5-104 protocols Tight response times on Fibre Optic Transmission Systems

CESC’s own OF cables ~ 500 Kms including OPGW SDH/PDH from ABB – At 35 Nodes - Fox 515, Fox 515T Gigabit Ethernet – At 100 Nodes - CISCO products

GridWeek Asia 2012

#GridAsia Mumbai, India Jan 16-18, 2012 5

Working reasonably well… AMR systems on GSM/ GPRS

Mostly from Secure Meters & Genus Majority on GPRS, some on GSM

More than 8000 meters read at present GPRS throughputs better than GSM, but re-runs required at times

Communicable Meters being tested Tariff Meter at HT Consumer premises Meter Reading Setup for GSM Modems

Street Lighting AMR/ Controller Meter Reading Setup for GPRS ModemsAMR at DTs

GPRS

GridWeek Asia 2012

#GridAsia Mumbai, India Jan 16-18, 2012 6

Problem Area… RMU (Feeder) Automation on GPRS/ CDMA

ABB Areva Schneider

Over 3500 Nos 11 kV & 6 kV RMUs commissioned in CESC network over the last 3 years.

Installation of RMUs has reduced restoration time on HT faults to < 1 hour:3-way and 4-way Ring Main UnitsIsolators – not CBs – in legs: load-break, fault-makeFault Passage Indicators (FPIs) fitted on all legsRestoration time of 11 kV & 6 kV Feeders already reduced from 4 hours to less than 1 hour by installing & manually operating the RMUs

Automation will further reduce restoration time to 15 minutes:Status of FPIs to be transmitted to SCADA/ DMSRetro-fitting of Motors to remotely operate Isolators through SCADA/ DMS. 24V DC Motors used.IEC-870-5-104 protocol

Issues:In CESC, all RMUs installed outdoorson roadsidesPoor, unreliable cellular data communications

GridWeek Asia 2012

#GridAsia Mumbai, India Jan 16-18, 2012 7

HMIClient – Initiated VPN: Preferred SIMs can be from any service

provider Security/ Encryption in our control Dynamic IPs – M2M technology used

through Internet

Service Provider – Initiated VPN

HMI

SIMs must be from any ONE service provider

Security/ Encryption in Service Provider’s control

Static IPs – no Internet needed

We have commissioned pilot projects using both options Facing major communications issues with poor throughputs

VPN

VPN

LL

IEC 104

Static IP

FRTUModem

RMU

RMUStatic IP

RMU

Static IP

HMI

CDMA/ GPRS

VPN

M2M Server

Public Static IP

VPN

VPNVPN

IEC 104

LL

Dynamic IP

VPN

RMU

FRTUModem

RMU

Dynamic IP

RMU

Dynamic IP

Problem Area… RMU (Feeder) Automation on GPRS/ CDMA

GridWeek Asia 2012

#GridAsia Mumbai, India Jan 16-18, 2012 8

Problem Area… RMU (Feeder) Automation on GPRS/ CDMA

Equipment INTERNALLY mounted Equipment EXTERNALLY mounted

SchematicDiagramIssues:

Internally mounted arrangement impracticalPoor, unreliable cellular data communications using IEC-870-5-104 protocol

GridWeek Asia 2012

#GridAsia Mumbai, India Jan 16-18, 2012 9

Problem Area… RMU (Feeder) Automation on GPRS/ CDMA

Sample throughputs shown

Continuous efforts by all our partners to fine-tune system/ communication network

Dis-satisfied end users: we have put large-scale deployment on hold till more reliable solutions are available

Path forward ?

GridWeek Asia 2012

#GridAsia Mumbai, India Jan 16-18, 2012 10

Problem Area… RMU (Feeder) Automation on GPRS/ CDMA

We are automating RMU clusters –where possible –on Fibre Optic cables.

This will be possible only in limited locations.

RMU cluster at Writers Building area – communication using Fibre Optics

GridWeek Asia 2012

#GridAsia Mumbai, India Jan 16-18, 2012 11

Thank You