> MainspecificationsQuantities measured: 1, 2, 3, 4 to be chosen from I, V, U, F, FP, P, Q, S, cosϕ, ϕ, ϕU, ϕV, tanϕConfiguration of TRIAD 2: in factory or by the user with the TRIADJUST 2 softwareAccuracy (programmable): Class 0.1 / 0.15 / 0.2 /0.5 / 1Current inputs: 1 A and 5 AVoltage inputs: 100 to 480 V (ph-ph) or 100 / √3 to 480 / √3 V (ph-N)Transfer curves: linear, 2 slopes or quadraticOutput signals: ± 1 mA, ± 5 mA, ± 20 mA, ± 1V, ± 10VResponse time in Class 0.2: 200 msOperating frequency: 50 or 60 HzAuxiliary power supply with wide dynamic range: 80 to 265 V ac/dc or 19 to 58 V dcCompliance with CE directiveDigital technology
Multi-function,economicalinstrumentwith4functionsinthesamecasing
Communication,EthernetRS485oropticalhead
Accessibilityandsafety:large-dimensionterminalsInsulatedcircuits
Ergonomic:easymountingonDINrailorswitchboard
194
2010>
Mea
sure
men
t an
d in
stru
men
tatio
n Pro
gram
mab
le d
igita
l tra
nsdu
cers
TRIAD 2 rangeProgrammable digital transducers with 1 to 4 analogue outputsProgrammable accuracy class
PRODUCT ADVANTAGES
Upto4 ProgrammaBlE analoguE outPuts
4 kV insulation
configuraBlE and modifiaBlE
usingtheTRIADJUST2software
adJustaBlE accuracywithinClass0.1asperIEC60688
adJustaBlE rEsPonsE timE
downto50ms
digital outPut availableasan oPtion
> Environmentandstandards
EMC IMMUnITy (standardofreference:IEC60688,IEC61326-1,IEC61000-6-5)ShockvoltageasperIEC61000-4-5
2kvindifferentialmode4kvincommonmode
OscillatingwaveasperIEC61000-4-12
1kvindifferentialmode2.5kvincommonmode
FastelectricaltransientsinburstsasperIEC61000-4-4
2kvonpowersupply2kvoninputs/outputs
ElectrostaticdischargeasperIEC61000-4-2
8kvintheair6kvincontact
EMradiatedfieldasperIEC61000-4-3 10v/m(80MHzto3GHz)
voltagedipsasperIEC61000-4-11
30%reductionduring20ms60%reductionduring1s
voltageinterruptionsasperIEC61000-4-11
100%reductionduring100ms100%reductionduring100ms
EMC emissionsRadiatedandconducted AsperCISPR11Climatic specifications (IEC600682-1/2-2/2-30)Operatingtemperature -10°Cto+55°CStoragetemperature -40°Cto+70°CRelativehumidity ≤95%to55°CSafety specifications (IEC61010-1)Installationcategory 3Pollutionlevel 2Fireresistance UL94,severityv0Mechanical specifications (IEC600682-6/2-27/2-29/2-32/2-63)Protectionrating IP20Mechanicalshocks IEC60068-2-27vibrations IEC60068-2-6Droptestwithpackaging NF0042-1
> MountingaccessoriesModel ReferencePlatemountingforT1xy ACCT1007PlatemountingforT3xy ACCT1006
> CasingWeight 320g(T1xy)/700g(T3xy)Mounting DINrail43700orplatemounting TerminalswithmobilestirrupclampwithConnection screwfor4single-wire6mm²conductorsor 2multi-wire4mm²conductors
TRIAD2Programmablemodel
■ The transducer delivered is ready to operate and can be connected to the electrical network in order to deliver output signals tailored for your installation.
■ To benefit from this, you simply need to know the exact specifications of your electrical installation:• Type of network: single-phase, balanced or
unbalanced three-phase , 3 or 4 wires.• Type of electrical connections. • Number of electrical quantities to be measured:
1, 2, 3 or 4.• Precise measurement ranges of the input/output
quantities to be measured.Users can modify a factory configuration at any time with the TRIADJUST 2 software if the specifications of the electrical network change.
>Factory-programmable >ProgrammableviaTRIADJUST2■ With the TRIADJUST 2 software and one of the
3 communication modes available (Ethernet, RS485 or optical head) you can program all the parameters characterizing a TRIAD 2 transducer.
■ To do so, simply choose a model which suits your electrical installation:• Type of network: single-phase, balanced or unba-
lanced three-phase, 3 or 4 wires. • Number of analogue outputs required (1, 2 3 or 4).• Value of the auxiliary source.
■ You are then free to configure the TRIAD 2 transducer delivered as you wish and to print out the stickers corresponding to the parameters programmed.
195
EnEr
gy
PErf
orm
ancE
1
nEtw
ork
Qual
ity
2
mEa
surE
mEn
t an
d in
stru
mEn
tati
on
3
network Function T1xy model T3xy model
Single-phase
v • •I • •F • •P • •Q • •S • •FP • •
Tanϕ • •Cosϕ • •ϕ • •
Balanced3-phase,3wires
U12,U23,U31 • •I1,I2,I3 • •
F • •Pt • •Qt • •St • •FPt • •
Tanϕ • •Cosϕt • •ϕt • •
Balanced3-phase,4wires
v1,v2,v3 • •U12,U23,U31 • •
I1,I2,I3 • •F • •
P1,P2,P3,Pt • •Q1,Q2,Q3,Qt • •S1,S2,S3,St • •
FP1,FP2,FP3,FPt • •Tanϕ • •
Cos(ϕ1,ϕ2,ϕ3,ϕt) • •ϕ1,ϕ2,ϕ3,ϕt • •
Unbalanced3-phase,3/4wires
v1,v2,v3 •U12,U23,U31 •
I1,I2,I3 •F •
P1,P2,P3,Pt •Q1,Q2,Q3,Qt •S1,S2,S3,St •
FP1,FP2,FP3,FPt •Tanϕ •
Cos(ϕ1,ϕ2,ϕ3,ϕt) •ϕ1,ϕ2,ϕ3,ϕt •
ϕ (U12/U23,U23/U31,U31/U12) •ϕ (v1/v2,v2/v3,v3/v1) •
The TRIAD 2 T1xy and T3xy are fully configurable with the TRIADJUST 2 software which allows users to modify the characteristics of their products right up to the last minute.
Model1=smallmodel3=largemodel
Communication module0=opticalhead1=opticalhead+RS4852=opticalhead+Ethernet
T3 x y
number of analogue outputs0=none1=1output2=2outputs3=3outputs4=4outputs
T1 x y
number of analogue outputs0=none1=1output
Example:T314=Large-modelTRIAD2withopticalheadandRS485+4analogueoutputs
196
2010TRIAD 2 range
> Hardwareidentification>
Mea
sure
men
t an
d in
stru
men
tatio
n Pro
gram
mab
le d
igita
l tra
nsdu
cers
Voltage input
RatedvalueT1:from57.7vacto276vacmax.T3:from57.7vacto480vacmax.
Frequency 50Hz:42.5...57.5Hz60Hz:51...69Hz
Max.measuredvoltageonprimary 650kv(ph-ph)
Acceptableoverloads T1:300vacpermanent-460vac/10sT3:520vacpermanent-800vac/10s
Consumption <0.2AInputimpedance 400kΩCurrent inputsRatedvalue 0to10Amax.Max.measuredcurrentonprimary 25,000AAcceptableoverload 50In/1sConsumption <0.15vAAuxiliary power supplyHighlevel 80/265vac(50/60Hz)–80/265vdcLowlevel 19/58vdc
ConsumptionHigh level low level
T1:8.5vAmax.T3:20vAmax.
T1:5Wmax.T3:10Wmax.
Analogue outputs
Ratedvalues Current Voltage±1mA,±5mA,±20mA ±1v,±10v
Acceptableresistiveload 15v/Io(1) ≥ 1kΩAcceptablecapacitiveload 0.1μF 0.1μFOverrun 1.2Io(1) 1.2Uo(1)
Peak-peakresidualwave ±0.2%ofIo(1) ±0.2%ofUo(1)
Programmableresponsetime 50ms–100ms–200ms–500ms–1sTransfercurve Linear,2slopesorquadratic(1)Io=outputcurrent,Uo=outputvoltage
TRIAD2Programmablemodel
197
> Electricalspecifications
Optical head Ethernet RS485
Connection USB(PC)Optical(product) RJ45 2wires
Half-duplex
Protocol MODBUSRTUmode
MODBUS/TCPRTUmode
MODBUS/JBUSRTUmode
Speed 38,400baud 10baseT 2,400to115,200baudParity - - Even,oddornoneJBusaddresses - - 1to247Transmissionlength 2m 100m 1.2kmasEIA485
> Communication
Measurements Accuracy classs over measurement range (asperIEC60688)
RT=50ms RT=100ms RT=200ms RT=500ms RT=1s
v,U,I,F,P,Q,S,FP,Tanϕ,Cosϕ,ϕ,ϕU,ϕv ±1% ±0.5% ±0.2% ±0.15% ±0.1%
> Metrologicalspecifications
*RT:ResponsetimeforF=50Hz**Phaseanglebetweenvoltages
EnEr
gy
PErf
orm
ancE
1
nEtw
ork
Qual
ity
2
mEa
surE
mEn
t an
d in
stru
mEn
tati
on
3
I1,F:
v1,F:
v1,I1,P1,Q1,S1,FP1,F,TANϕ,Cosϕ1,ϕ1:
198
2010TRIAD 2 range
> ElectricalconnectionsSingle-phasenetwork
> M
easu
rem
ent
and
inst
rum
enta
tion P
rogr
amm
able
dig
ital t
rans
duce
rs
Balanced3-phase,3-wirenetwork
U12,U23,U31,F:
I1,I2,I3,F:
U12,U23,U31,I1,I2,I3,Pt,St,Qt,FPt,F,TANϕ,Cosϕt,ϕt:
Phaserotationauthorized
199
EnEr
gy
PErf
orm
ancE
1
nEtw
ork
Qual
ity
2
mEa
surE
mEn
t an
d in
stru
mEn
tati
on
3
Phaserotationauthorized
200
2010TRIAD 2 rangeBalanced3-phase,4-wirenetworkv1,v2,v3,U12,U23,U31F:
I1,I2,I3,F:
> M
easu
rem
ent
and
inst
rum
enta
tion P
rogr
amm
able
dig
ital t
rans
duce
rs
Phaserotationauthorized
201
v1,v2,v3,U12,U23,U31,F,Angle(v1/v2,v2/v3,v3/v1),Angle(U12/U23,U23/U31,U31/U12):
Balanced3-phase,4-wirenetwork(continued)
v1,v2,v3,U12,U23,U31,I1,I2,I3,P1,P2,P3,Pt,S1,S2,S3,St,Q1,Q2,Q3,Qt,FP1,FP2,FP3,FPt,F,TANϕ,Cosϕ1,Cosϕ2,Cosϕ3,Cosϕt,ϕ1,ϕ2,ϕ3,ϕt:
Unbalanced3-phase,3-wirenetworkU12,U23,U31,F,Angle(U12/U23,U23/U31,U31/U12):
EnEr
gy
PErf
orm
ancE
1
nEtw
ork
Qual
ity
2
mEa
surE
mEn
t an
d in
stru
mEn
tati
on
3
202
2010TRIAD 2 range
> M
easu
rem
ent
and
inst
rum
enta
tion P
rogr
amm
able
dig
ital t
rans
duce
rs
v1,v2,v3,U12,U23,U31,I1,I2,I3,P1,P2,P3,Pt,S1,S2,S3,St,Q1,Q2,Q3,Qt,FP1,FP2,FP3,FPt,F,TANϕ,Cosϕ1,Cosϕ2,Cosϕ3,Cosϕt,ϕ1,ϕ2,ϕ3,ϕt,Angle(v1/v2,v2/v3,v3/v1),Angle(U12/U23,U23/U31,U31/U12):
I1,I2,I3,F:
Unbalanced3-phase,3-wirenetwork(continued)
U12,U23,U31,I1,I2,I3,Pt,St,Qt,FPt,F,TANϕ,Cosϕt,ϕt,Angle(U12/U23,U23/U31,U31/U12):
Unbalanced 3-phase, 4-wire network
I1, I2, I3, F: V1, V2, V3, U12, U23, U31, F, Angle (V1/V2, V2/V3, V3/V1), Angle (U12/U23, U23/U31, U31/U12):
V1, V2, V3, U12, U23, U31, I1, I2, I3, P1, P2, P3, Pt, S1, S2, S3, St, Q1, Q2, Q3, Qt, FP1, FP2, FP3, FPt, F, TANϕ, Cosϕ1, Cosϕ2, Cosϕ3, Cosϕt, ϕ1, ϕ2, ϕ3, ϕt Angle (V1/V2, V2/V3, V3/V1), Angle (U12/U23, U23/U31, U31/U12):
20
4 chamfers 45 ° x 5 4 holes Ø4.5
R1
R2
40
86±0
.25
7610
2644
±0.2
96
5
86
±0
.2
86
±0
.2
T11, TSPI et TSPU
Panel drilling diagram for plate mounting
Accessory for plate mounting with screw (option)
T12, T13, T21, T22, T23, T31, T32 et T33T11, TSPU et TSPI
T12, T13, T21, T22, T23, T31, T32 et T33
4 holes ø 4.5
70±0.2
60 120
120.5
8181
20
4 chamfers 45 ° x 5 4 holes Ø4.5
R1
R2
40
86±0
.25
7610
2644
±0.2
96
5
86
±0
.2
86
±0
.2
T11, TSPI et TSPU
Panel drilling diagram for plate mounting
Accessory for plate mounting with screw (option)
T12, T13, T21, T22, T23, T31, T32 et T33T11, TSPU et TSPI
T12, T13, T21, T22, T23, T31, T32 et T33
4 holes ø 4.5
70±0.2
60 120
120.5
8181
20
4 chamfers 45 ° x 5 4 holes Ø4.5
R1
R2
40
86±0
.25
7610
2644
±0.2
96
5
86
±0
.2
86
±0
.2
T11, TSPI et TSPU
Panel drilling diagram for plate mounting
Accessory for plate mounting with screw (option)
T12, T13, T21, T22, T23, T31, T32 et T33T11, TSPU et TSPI
T12, T13, T21, T22, T23, T31, T32 et T33
4 holes ø 4.5
70±0.2
60 120
120.5
8181
20
4 chamfers 45 ° x 5 4 holes Ø4.5
R1
R2
40
86±0
.25
7610
2644
±0.2
96
5
86
±0
.2
86
±0
.2
T11, TSPI et TSPU
Panel drilling diagram for plate mounting
Accessory for plate mounting with screw (option)
T12, T13, T21, T22, T23, T31, T32 et T33T11, TSPU et TSPI
T12, T13, T21, T22, T23, T31, T32 et T33
4 holes ø 4.5
70±0.2
60 120
120.5
8181
20
4 chamfers 45 ° x 5 4 holes Ø4.5
R1
R2
40
86±0
.25
7610
2644
±0.2
96
5
86
±0
.2
86
±0
.2
T11, TSPI et TSPU
Panel drilling diagram for plate mounting
Accessory for plate mounting with screw (option)
T12, T13, T21, T22, T23, T31, T32 et T33T11, TSPU et TSPI
T12, T13, T21, T22, T23, T31, T32 et T33
4 holes ø 4.5
70±0.2
60 120
120.5
8181
20
4 chamfers 45 ° x 5 4 holes Ø4.5
R1
R2
40
86±0
.25
7610
2644
±0.2
96
5
86
±0
.2
86
±0
.2
T11, TSPI et TSPU
Panel drilling diagram for plate mounting
Accessory for plate mounting with screw (option)
T12, T13, T21, T22, T23, T31, T32 et T33T11, TSPU et TSPI
T12, T13, T21, T22, T23, T31, T32 et T33
4 holes ø 4.5
70±0.2
60 120
120.5
8181
Weight: 320 g Weight 700 g
> Dimensions (in mm)
All models T1xy T3xy
T1xy T3xy
203
EnEr
gy
PErf
orm
ancE
1
nEtw
ork
Qual
ity
2
mEa
surE
mEn
t an
d in
stru
mEn
tati
on
3
T O O r D E r
Without tropicalization With tropicalization
Numberofinput1
Numberofinput1link Output Supply
Optical±20mA
80-265vAC/DC P01380001 P0138000219-58vDC P01380003 P01380004
±10v80-265vAC/DC P01380005 P01380006
19-58vDC P01380007 P01380008
> T1–SMALLMODEL(60x81x120.5mm)
> T3–LARGEMODEL(120x81x120.5mm)
Without tropicalization With tropicalization
Numberofinput(s) Numberofoutput(s)
link Output Supply 1 2 3 4 1 2 3 4
Optical±20mA
80-265vAC/DC P01380101 P01380103 P01380105 P01380107 P01380102 P01380104 P01380106 P0138010819-58vDC P01380109 P01380111 P01380113 P01380115 P01380110 P01380112 P01380114 P01380116
±10v80-265vAC/DC P01380117 P01380119 P01380121 P01380123 P01380118 P01380120 P01380122 P01380124
19-58vDC P01380125 P01380127 P01380129 P01380131 P01380126 P01380128 P01380130 P01380132
> TRIAD2factory-programmable
1 Model T1:smallmodel–1analogueoutput T3:largemodel–1to4analogueoutput(s)
2 Communication 0:Without 1:RS485 2:Ethernet
3 number of analogue outputs 0:Without(Choiceofaminimumcommunication) 1:1output 2:2outputs(T3modelonly) 3:3outputs(T3modelonly) 4:4outputs(T3modelonly)
4 Frequency 0:50Hz 1:60Hz 5 Supply 0:80-265vAC/DC 1:19-58vDC
6 Tropicalization 0:Without 1:With
7 Analogue output calibres 0:-20mAto+20mA 1:-5mAto+5mA 2:-1mAto+1mA 3:-10vto+10v 4:-1vto+1v
8 network 0:Single-phase 1:Balanced3-phase,3wires 2:Balanced3-phase,4wires 3:Unbalanced3-phase,3wires 4:Unbalanced3-phase,4wires
9 Connection configuration Indicatethediagramnumbe.E.g.TD204
10 Voltage input IndicatedirectvoltagetobemeasuredorthevTratio
11 Current input IndicatedirectcurrenttobemeasuredortheCTratio
12 Analogue output Indicateforeachoutput:
a- Quantitytobemeasured b- Transfercurve c- Inputsignal:Min–Breakingpoint-Max d- Inputunity e- Outputsignal:Min–Breakingpoint-Max
To simplify the procedure when ordering you can send us the form on page xxx.
204
2010TRIAD 2 rangeTrIAD 2 programmable via TrIADJUST 2
> M
easu
rem
ent
and
inst
rum
enta
tion P
rogr
amm
able
dig
ital t
rans
duce
rs
205
Factory-programmed TrIAD 2: order form
(1) Please indicate the unit of the measurement range, e.g. W, kW or MW
Current
WithcurrenttransformerorDirect
5 - Inputs
A A
/
PrimarySecondary
voltage
WithvoltagetransformerorDirect
v v
/
PrimarySecondary
Phase-phase Phase-neutral(√3)
4 - Power supply80to265vac(50/60Hz)/80to265vdcor 19to58vdc
2 - Network
Single-phase
3-wirebalancedthree-phase
4-wirebalancedthree-phase
3-wireunbalancedthree-phase
4-wireunbalancedthree-phase
3 - Options / Connection
Ethernetor
Tropicalization
Connectiondiagram:
RS485
TD
v1 v2 v3 U12 U23 U31 I1 I2 I3 F P1 P2 P3 Pt Q1 Q2 Q3 Qt S1 S2 S3 St
FP1 FP2 FP3 FPt TANϕ COSϕ1 COSϕ2 COSϕ3 COSϕt ϕ1 ϕ2 ϕ3 ϕt
ϕU12/23 ϕU23/31 ϕU31/12 ϕv1/2 ϕv2/3 ϕv3/1
Availablequantities
1 - Model / Hz
T1or
50Hzor
Quantityandmeasurementrange(x)
Min
Transfercurve
Linear
2slopes
Quadratic
Output 1
breakingpoint Max Unit(1)
Indicatequantitytobemeasured
Outputsignal(y)
mAMin Breakingpoint Max
v
Quantityandmeasurementrange(x)
Min
Transfercurve
Linear
2slopes
Quadratic
Output 2
breakingpoint Max Unit(1)
Indicatequantitytobemeasured
Outputsignal(y)
Quantityandmeasurementrange(x)
Min
Transfercurve
Linear
2slopes
Quadratic
Output 3
breakingpoint Max Unit(1)
Indicatequantitytobemeasured
Outputsignal(y)
Quantityandmeasurementrange(x)
Min
Transfercurve
Linear
2slopes
Quadratic
Output 4
breakingpoint Max Unit(1)
Indicatequantitytobemeasured
Outputsignal(y)
T3
60Hz
mAMin Breakingpoint Max
v
mAMin Breakingpoint Max
v
mAMin Breakingpoint Max
v
Accuracyclass
0.1%:1s0.8s
0.15%:0.5s0.4s
0.2%:0.2s0.16s
0.5%:100ms80ms
1%:50ms40ms
50Hz60Hz
Accuracyclass
0.1%:1s0.8s
0.15%:0.5s0.4s
0.2%:0.2s0.16s
0.5%:100ms80ms
1%:50ms40ms
50Hz60Hz
Accuracyclass
0.1%:1s0.8s
0.15%:0.5s0.4s
0.2%:0.2s0.16s
0.5%:100ms80ms
1%:50ms40ms
50Hz60Hz
Accuracyclass
0.1%:1s0.8s
0.15%:0.5s0.4s
0.2%:0.2s0.16s
0.5%:100ms80ms
1%:50ms40ms
50Hz60Hz
EnEr
gy
PErf
orm
ancE
1
nEtw
ork
Qual
ity
2
mEa
surE
mEn
t an
d in
stru
mEn
tati
on
3
Diagnosis-voltageinputs-Currentinputs-Cabling-Phaseorder-Analogueoutputs-Fresnel
Configuration-Inputs/Outputs-Communication-Connectiondiagram-Responsetime
Display-Instantaneousquantities(indigitaloranalogueform)
Recording-Inrealtimeinexportedfile
> DescriptionThe TRIADJUST 2 software allows quick, unlimited programming of all your TRIAD 2’s parameters.
Using a PC and the optical lead supplied in each kit, connect your product’s auxiliary power supply to dialogue with total security. Depending on your TRIAD 2’s configuration, remote communication is possible via RS485 or Ethernet.In the WindowsTM environment, initialize or simply modify the quantities measured, the measurement ranges and the analogue outputs on the transducers installed.TRIADJUST 2 also offers other functions such as DIAGNOSIS of your network, instantaneous DISPLAY of the electrical quantities and REAL-TIME RECORDING of the measurements in an exported file.
You can also print labels indicating the configurations and connections of your products.
Platform: PCOperating system: Windows 2000 or XPProcessor: Pentium-compatibleRAM: 128 MBHard disk: 40 GBDrive: CD-ROMCommunication port:Local: USB 1.1 minimumRemote: RS485 and/or Ethernet
> Minimumconfiguration
206
2010TRIADJUST 2 softwareDesigned for quick configuration and display of all the parameters of your TrIAD 2 transducers
> M
easu
rem
ent
and
inst
rum
enta
tion P
rogr
amm
able
dig
ital t
rans
duce
rs
PRODUCT ADVANTAGES
configuration via oPtical HEad, EtHErnEt or rs485
accEss to all the triad 2 ParamEtErs
diagnosis ofthe installation
laBEl Printing on all tyPEs of lasEr PrintErs
T O O r D E r
Model ReferenceTRIADJUST2kit P01380410TRIADJUST2“PREMIER”workstation P01380420Accessories Setof30sheetsofblanklabels P01380400Optical/USBlead P01330403
This module is a complete tool designed for distribu-tors or any user needing to program a large number of transducersThe TRIADJUST 2 “PREMIER” configuration workstation comprises:■ The TRIADJUST 2 software■ An optical / USB lead■ A benchtop power-supply base■ 210 sheets of blank labels ■ A 500 x 400 x 270 mm carrying case
The TRIADJUST 2 configuration kit comprises:■ The TRIADJUST 2 software■ An optical / USB lead■ 30 sheets of blank labels■ A 230 x 185 x 45 mm carrying case
TRIADJUST2“PREMIER”KITTRIADJUST2
A sheet contains two labels, one for the configuration of the inputs/outputs and the other for the programmed connection diagram. The labels can be printed on all types of laser printers.
Labelscommontobothkits
207
>AssociatedproductTRIAD2programmablewithTRIADJUST2
> page 190
T314 Inputs: 50-60 Hz 10 000 V/√3 100 V/√3 1 000 A 5A
AO 1: V1 0,20 200ms 750Ω
0 V…5 773,5 V4 mA…20 mA
AO 2: I1 0,20 200ms 750Ω
0 A…1 000 A4 mA…20 mA
AO 3: Pt 0,20 200ms 750Ω
0 W…17,32 MW4 mA…20 mA
AO 4: F1 0,20 200ms 750Ω
45 Hz…55 Hz4 mA…20 mA
Made in France
Reference client / Own reference customer
EnEr
gy
PErf
orm
ancE
1
nEtw
ork
Qual
ity
2
mEa
surE
mEn
t an
d in
stru
mEn
tati
on
3