Contents3
4
6
18
Overview - Actuators
Product Selection Actuators
Non-Spring return Damper Actuators 5Nm, 10Nm, 20Nm, 34Nm
Spring return Damper Actuators 5Nm, 10Nm, 20Nm
22Fire and Smoke Damper Actuators
Overview - Actuators
Damper actuator advantage
High reliability
Accurate runtime
Same rating torque,actual output torquehigher
Easy wiring
Feature
MCU control, no limitswitchneeded
Motor overheated isprevented;Product servicelife long
The motor speed isreal-time adjusted
Actual output torqueis 1.3 timesthe rating one
Actuator and wiringbox are separate, and terminal blockis incorporatedin wiring box
Function
Accurate positioningcontrol, runtime not varied with load
Smaller-sized actuator is equivalentto the bigger onefrom competitor’s
Saving wiring time No insulation tapeneeded
Benefit
Non Spring Return(CN series)
Fire and Smoke Damper Actuator(MS Series)
Spring Return(CS series)
5NmCN4605CN6105CN7505
10NmCN4610CN6110CN7510
20NmCN4620CN6120CN7220
34NmCN4634CN6134CN7234
5NmCS4105CS7505CS8105
10NmCS4110CS7510CS8110
20NmCS4120CS7520CS8120
510
0
Spring return direct coupled actuators(DCA) for on/off damper control. Theactuator accepts an on/off signalfrom a single-pole, singlethrow(SPST) controller. They are designedto operate reliably in smoke controlsystems requiring UnderwritersLaboratories Inc. UL555S ratings upto 350 F.
3
Product Selection - Actuators
4
NON - SPRING RETURN Power Supply Control Input/Output Price List
Number(without whips)
RunningTime
(50Hz)
24 VAC/DC
220 VAC
On/Off Two
positionFloating 0/2-10 VDC
Modulating
Feedback(0/2-10 VDC)
SPDT Auxiliary Switches
(USD)
CN05 Series (5 Nm, 44 lb-in)CN4605A1001 110 • • 0 148.64
CN4605A1201 110 • • 2 (*)
CN4605A2001 110 • • • 0 (*)
CN4605A2201 110 • • • 2 (*)
CN6105A1011 90 • • • 0 153.91
CN6105A1201 90 • • • 2 (*)
CN6105A2001 90 • • • • 0 (*)
CN6105A2201 90 • • • • 2 (*)
CN7505A1001 110 • • • • 0 (*)
CN7505A1201 110 • • • • 2 (*)
CN7505A2001 110 • • • • • 0 166.37
CN7505A2201 110 • • • • • 2 (*)
CN10 Series (10 Nm, 88 lb-in)CN4610A1001 110 • • 0 158.85
CN4610A1201 110 • • 2 (*)
CN4610A2001 110 • • • 0 (*)
CN4610A2201 110 • • • 2 (*)
CN6110A1003 90 • • • 0 159.41
CN6110A1201 90 • • • 2 239.68
CN6110A2001 90 • • • • 0 (*)
CN6110A2201 90 • • • • 2 (*)
CN7510A1001 110 • • • • 0 (*)
CN7510A1201 110 • • • • 2 (*)
CN7510A2001 110 • • • • • 0 (*)
CN7510A2201 110 • • • • • 2 (*)
CN20 Series (20 Nm, 177 lb-in)CN4620A1007 110 • • 0 (*)
CN4620A1207 110 • • 2 (*)
CN4620A2007 110 • • • 0 (*)
CN4620A2207 110 • • • 2 (*)
CN6120A1006 110 • • • 0 301.98
CN6120A1207 110 • • • 2 (*)
CN6120A2007 110 • • • • 0 (*)
CN6120A2207 110 • • • • 2 (*)
CN7220A1007 110 • • • • 0 (*)
CN7220A1207 110 • • • • 2 (*)
CN7220A2007 110 • • • • • 0 353.74
CN7220A2207 110 • • • • • 2 (*)
CN34 Series (34 Nm, 300 lb-in)CN4634A1003 110 • • 0 401.01
CN4634A1208 110 • • 2 (*)
CN4634A2008 110 • • • 0 (*)
CN4634A2208 110 • • • 2 (*)
CN6134A1003 110 • • • 0 401.01
CN6134A1208 110 • • • 2 (*)
CN6134A2008 110 • • • • 0 (*)
CN6134A2208 110 • • • • 2 (*)
CN7234A1008 110 • • • • 0 (*)
CN7234A1208 110 • • • • 2 (*)
CN7234A2008 110 • • • • • 0 390.71
CN7234A2208 110 • • • • • 2 (*)
CN46
CN46
CN61
CN61
CN61
CN61
CN75
CN75
Product Selection - ActuatorsSPRING RETURN Running Time Power
Supply Control Input/Output Auxiliary Knob Price List
Number (without whips)
Drive(sec)
SpringReturn (sec)
24 VAC/DC
100-250VAC
On/Off Two
position
Modulating and Floating
Feedback(0/2-10VDC)
SPDT Auxiliary Switches
(USD)
CS05 Series (5 Nm, 44 lb-in)CS4105A1002 90 <20 • • 0 305.28
CS4105A1102 90 <20 • • 0 (*)
CS8105A1008 90 <20 • • 0 276.34
CS8105A1102 90 <20 • • 0 (*)
CS7505A2008 90 <20 • • 0 334.09
CS7505A2202 90 <20 • • • 2 (*)
CS10 Series (10 Nm, 88 lb-in)
CS4110A1002 90 <20 • • 0 302.01
CS4110A1200 90 <20 • • 0 396.06
CS8110A1008 90 <20 • • 0 272.56
CS8110A1206 90 <20 • • 0 363.01
CS7510A2008 90 <20 • • 0 357.75
CS7510A2206 90 <20 • • • 2 416.26
CS20 Series (20 Nm, 175 lb-in)
CS4120A1001 90 <20 • • 0 318.63
CS4120A1209 90 <20 • • 0 414.69
CS8120A1007 90 <20 • • 0 286.83
CS8120A1205 90 <20 • • 0 381.19
CS7520A2007 90 <20 • • 0 356.09
CS7520A2205 90 <20 • • • 2 439.81
FIRE AND SMOKE SPRING RETURN
Running Time Power Supply Control Input/Output Auxiliary Knob Price List
Fast acting, two position spring return. Rating up to 350oF
Number(without whips)
Drive(sec)
Spring Return (sec)
24 VAC 120VAC
230VAC
On/ Off Two position
Feedback(0/2-10 VDC)
SPDT Auxiliary Switches
(USD)
MS04 Series (4 Nm, 44 lb-in)MS4104F1010 15 <15 • • 0 (*)
MS4104F1210 15 <15 • • 2 (*)
MS4604F1010 15 <15 • • 0 (*)
MS4604F1210 15 <15 • • 2 (*)
MS8104F1010 15 <15 • • 0 (*)
MS8104F1210 15 <15 • • 2 (*)
MS09 Series (9 Nm, 80 lb-in)
MS4109F1010 15 <15 • • 0 (*)
MS4109F1210 15 <15 • • 2 (*)
MS4609F1010 15 <15 • • 0 523.50
MS4609F1210 15 <15 • • 2 257.50
MS8109F1010 15 <15 • • 0 (*)
MS8109F1210 15 <15 • • 2 (*)
M
M
M
M
M
M
CS7
CS1
CS4
CS4
CS8
CS8
CS7
CS7
CN05, CN10 SERIES NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND TWO-POSITION CONTROL
PRODUCT DATA
GENERAL This non-spring return direct-coupled damper actuator provides floating and two-position control for: • air dampers,• VAV units,• air handlers,• ventilation flaps,• louvers, and• reliable control for air damper applications with up to 10
sq ft / 44 lb-in. (5 Nm) and 20 sq ft / 88 lb-in. (10 Nm)(seal- less damper blades; air friction-dependent).
FEATURES • Declutch for manual adjustment• Adjustable mechanical end limits• Removable access cover for direct wiring• Mountable in any orientation• Rotation direction and service/OFF switch
SPECIFICATIONSSupply voltageCN6105/CN6110 24 Vac/dc -15%/+20%, 50/60 Hz CN4605/CN4610 230 Vac -15%/+20%, 50/60 Hz Nominal voltageCN6105/CN6110 24 Vac/dc, 50/60 HzCN4605/CN4610 230Vac, 50/60 HzAll values stated hereinafter apply to operation under nominal voltage conditions.Power consumptionCN6105/CN6110 5 VA / 2 W CN4605 22 VA / 2 W at 50 Hz CN4610 25 VA / 2 W at 60 Hz Ambient limitsAmbient operating limits -5...+140 °F (20...+60 °C) Ambient storage limits -22...+176 °F (-30...+80 °C) Relative humidity 5...95%, non-condensing SafetyProtection standard IP54 Protection class II as per EN 60730-1 Overvoltage category II LifetimeFull strokes 60000 Repositions 1.5 millionMountingRound damper shaft 3/8 in…5/8 in. Square damper shaft 1/4 in…1/2 in.; 45° steps Shaft length min. 1-5/8 in. End switches (when included)Rating Class IITriggering points 5° / 85° Torque rating 44 lb-in. (5Nm) / 88 lb-in. (10 Nm) Runtime for 90°CN6105 90 sec (dc / 60 Hz ac) CN6110 90 sec (dc / 50 Hz ac) CN4605 65…110 s (60/50 Hz) CN4610 65…140 s (60/50 Hz) Rotation stroke 95° + 3° Dimensions see “Dimensions” on page 11 Weight (without cables) 1 lbs. Noise rating 35 dB(A) max. at 1 m
40 dB(A) for 230 Vac at 65 sec runtime
Certification CN6105/CN6110 CE & UL CN4605/CN4610 CE
C
6
PRODUCT IDENTIFICATION SYSTEM
C-Electrical Motor N-Fail Safe Function (Non-Spring Return)
61-24V Floating Control + ON/OFF 75-24V Modulating Control + Floating + ON/OFF 46-230V ON/OFF
05-44 lb-in. (5 Nm) 10-88 lb-in. (10 Nm)
A-Standard Model 1-No Feedback 2-Voltage Feedback Signal
0-No Internal Auxiliary Switches 2-Two Internal Auxiliary Switches
XX-System Controlled Numbers
C N 75 10 A 2 0 XX
BASIC FEATURES
Fig. 1. Setting units and control elements
Legend for Fig. 1: 1) Universal shaft adapter2) Mechanical end limits (manually adjustable)3) Declutch button4) Function selection switch5) Removable access cover6) Anti-rotation bracket
Contents of Package The delivery package includes the actuator, parts 1 through 6 (see Fig. 1), plus two cable grommets and a spare cable grommet.
RUN MODES The function selection switch (see Fig. 2) can be used to place the actuator into any one of two different modes:
• Service/Off; or• the floating/2-position run mode (“Dir” for CCW-closing
dampers or “Rev” for CW-closing dampers).
Fig. 2. Function selection switch
Power-Off Behavior If power is removed, the shaft adapter remains in position.
Service/Off If the function selection switch is set to the “Service/Off” position, then all rotary movement is cancelled, and all control signals are ignored, thus allowing the actuator to be manually operated safely.
Model Description
CN6105A1011 5Nm, 24Vac/Vdc, floating control, non-spring return, no feedback and without aux. Switch
CN4605A1001 5Nm, 230Vac, floating control, non-spring
return, no feedback and without aux. Switch
CN6110A100310Nm, 24Vac/Vdc, floating control, non-spring return, no feedback and without aux. Switch
CN6110A120110Nm, 24Vac/Vdc, floating control, non-spring
return, no feedback and with aux. Switch
CN4610A100110Nm, 230Vac, floating control, non-spring return, no feedback and without aux. Switch
CN05,CN10 SERIES DAMPER ACTUATORS FOR FLOATING/2-POSITON CONTROL
7
Floating/2-Position Run Mode If the function selection switch has been set to one of the two floating/2-position control settings—and if the actuator is wired correspondingly (see Fig. 7, Fig. 8, and Fig. 9)—then as soon as operating power is applied, the shaft adapter will run according to the control signals applied.
Table 1 describes the behavior (“stops,” rotates “CCW,” or rotates “CW”) of the CN6105/CN6110 in dependence upon the control signals (switch “open” or “24 Vac/dc”) applied to terminals 3 and 4, the function selection switch setting, and the manner in which the actuator is wired (either for floating mode: see Fig. 7; or for 2-position mode: see Fig. 8).
Table 1. Behavior of CN6105/CN6110
wiring control signal at switch setting term 3 term 4 Dir Service/ Off Rev
float. open open stops stops stopsopen 24Vac/dc CCW stops CW
24Vac/dc open CW stops CCW2-pos. 24Vac/dc open CW stops CCW
24Vac/dc 24Vac/dc CCW stops CW
Table 2 describes the behavior (“stops,” rotates “CCW,” or rotates “CW”) of the CN4605/CN4610 in dependence upon the control signals (switch “open” or “230 Vac”) applied to terminals 1 and 3 and the function selection switch setting: only one manner of wiring is permitted (see Fig. 9).
Table 2. Behavior of CN4605/CN4610
control signal at switch setting term 1 term 3 Dir Service/ Off Rev
open open stops stops stops open 230 Vac stops stops stops
230 Vac open CW stops CCW 230 Vac 230 Vac CCW stops CW
MANUAL ADJUSTMENT IMPORTANT
To prevent equipment damage, before manual adjustment, you must remove power or set the func-tion selection switch to the “Service/Off” position.
After removing power or setting the function selection switch to the “Service/Off” position, the gear train can be disengaged using the declutch button, permitting the shaft adapter to be manually rotated to any position.
Limitation of Rotation Stroke Two adjustable mechanical end limits are provided to limit the angle of rotation as desired (see Fig. 3). The mechanical end limits must be securely fastened in place.
Fig.3. Mechanical end limits
To ensure tight closing of the dampers, the shaft adapter has a total rotation stroke of 95°.
INTERNAL END SWITCHES The internal end switches “A” and “B” are changeover switches which are activated when the shaft adapter moves past a position of 5° and 85°, respectively (see also Table 5).
Fig.4. Internal end switch triggering points
CN05,CN10 SERIES DAMPER ACTUATORS FOR FLOATING/2-POSITON CONTROL
8
CN05,CN10 SERIES DAMPER ACTUATORS FOR FLOATING/2-POSITON CONTROL
9
INSTALLATION To avoid personal injury (electrical shock) and to prevent equipment damage, before installation, you must remove power.
These actuators are designed for single-point mounting.
Mounting Instructions All information and steps are included in the Installation Instructions supplied with each actuator.
Mounting Position The actuators can be mounted in any position (IP54 is dependent upon orientation; see Fig. 5). Choose a mounting pKosition permitting easy access to cables and controls.
Fig. 5. Mounting for IP54
NOTE: Further, in order to guarantee IP54, only original Honeywell grommets may be used.
Anti-Rotation Bracket and Screws If the actuator is to be mounted directly on a damper shaft, use the anti-rotation bracket and screws included in the delivery package. The min. distance between the center of the damper shaft and the middle of the anti-rotation bracket is 3.35 in.; a max. of 4.25 in. is allowed (see also Fig 11).
Depending upon the specifics of your mounting site, the actuator may shift in position slightly while tightening the screws at the top of the shaft adapter. The anti-rotation bracket features a T-piece with a 5-mm-long shank to accommodate for this movement. It is important to ensure that this play is not impeded.
Universal Shaft Adapter The universal shaft adapter can be used for shafts of various diameters and shapes (round: 3/8...5/8 in. and square: 1/4...1/2 in.).
WIRING
To avoid personal injury (electrical shock) and to prevent equipment damage, before wiring, you must remove power.
Access Cover IMPORTANT
Once the access cover has been removed, please take care to avoid damaging any of the parts now accessible.
The access cover can be unscrewed and removed in order to gain access to the terminal block(s) and perform wiring.
Fig. 6. Access Cover
Wiring Diagrams
Fig. 7. CN6105/CN6110 (floating mode)
! CAUTION
Fig. 8. CN6105/CN6110 (2-position mode)
CCW
CW
230V~
3
1
2
5
4NL
230V ~
> 3 mm!
Fig. 9. CN4605/CN4610 (2-position mode)
Fig. 10. End switches
NOTE: Both internal end switches must be connected to the same power source.
Tables 3,4 and 5 summarize the information presented in the preceding wiring diagrams.
Table 3. Signals at terminals for CN6105/CN6110 ter-
minal signal in floating signal in 2-pos. mode
2 common ~/- common ~/- 3 24 V ~/+
(control signal) 24 V ~/+
(control/ power signal) 4 24 V ~/+
(control signal) 24 V ~/+
(control signal/power) NOTE: All cables connected to these terminals must be
equipped with spark suppression.
Table 4. Signals at terminals for CN4605/CN4610 terminal signal
1 L (230 V ~) 2 N (230 V ~) 3 control signal
NOTE: All cables connected to these terminals must be equipped with spark suppression.
Table 5. Internal end switches (SSW2) terminal type of switch
S1 common lead for switches A and B
S2 / S3 change-over switch A (S1/S2 opens and S1/S3 closes when shaft adapter moves CW past 5°; reverts to original state when shaft adapter moves CCW past 5°).
S5 / S6 change-over switch B (S1/S5 opens and S1/S6 closes when shaft adapter moves CW past 85°; reverts to original state when shaft adapter moves CCW past 85°).
CN05,CN10 SERIES DAMPER ACTUATORS FOR FLOATING/2-POSITON CONTROL
10
DIMENSIONS
Fig. 11. Dimensions (in in.)
CN05,CN10 SERIES DAMPER ACTUATORS FOR FLOATING/2-POSITON CONTROL
11
CN20, CN34 SERIES NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORSFOR FLOATING / 2-POSITION CONTROL
PRODUCT DATA
GENERALThese direct-coupled damper actuators provide two-position and floating control for:
air dampers,VAV units,air handlers,ventilation flaps,louvers, andreliable control for air damper applications with up to4.6 m2 / 50 sq.ft. (20 Nm / 177 lb-in) or 7.8 m2 / 85 sq. ft.(34 Nm / 300 lb-in) (seal-less dampers; air friction-dependent).
FEATURESSelf-centering shaft adapterAccess cover to facilitate connectivityService/off for safe & easy servicingRotation direction selectable by switchDeclutch for manual adjustmentMechanical end limitsField-installable auxiliary switchesMountable in any orientation (no IP54 if upside down)Mechanical position indicatorCE and UL certified (230V models with CE only)
SPECIFICATIONSSupply voltage CN6120/CN6134 24 Vac/dc 15%, 50/60 Hz CN4620/CN4634 230 Vac 15%, 50/60 Hz Nominal voltage CN6120/CN6134 24 Vac/dc, 50/60 Hz CN4620/CN4634 230 Vac, 50/60 Hz All values stated hereinafter apply to operation under nominal voltage conditions. Power consumption CN6120 6 VA / 3 W CN4620 8 VA / 3 W CN6134 6 VA / 3 W CN4634 10 VA / 4 W Ambient limits Ambient operating limits -20...+60 C (-5...+140 °F) Ambient storage limits -40...+80 C (-40...+175 °F) Relative humidity 5...95%, non-condensing Safety Protection standard IP54 as per EN 60529 Protection class II as per EN 60730-1 Overvoltage category III LifetimeFull strokes 60000 Repositions 1.5 million MountingRound damper shaft 10...27 mm (3/8...1-1/16") Square damper shaft 10...18 mm (3/8...11/16");
spets °54Shaft length min. 22 mm (7/8") End switches (when included) Rating 5 A (resistive) / 3 A (inductive) Triggering points 5 / 85 Torque rating CN6120 / CN4620 20 Nm (177 lb-in) CN6134 / CN4634 34 Nm (300 lb-in) Runtime 95 sec (60 Hz) / 110 sec (50 Hz
or DC supply) Rotation stroke 95 3 Dimensions see "Dimensions" on page 17 Weight (without cables) 1.35 kg (3 lbs.) Noise rating 40 dBA max. at 1 m Certification CE CN6120 / CN6134
CN4620 / CN4634 UL CN6120 / CN6134
12
C
CN20, CN34 SERIES DAMPER ACTUATOR FOR FLOATING AND 2-POS CONTROL
MODELS Description # Model
CN6120A1002 20Nm,24Vac/Vdc, Floating/2-position control, Non-Spring Return, No feedback and without aux. Switch CN4620A1001 20Nm,230V,Floating/2-position control, Non-Spring Return, No feedback and without aux. Switch CN6134A1003 34Nm,24Vac/Vdc, Floating/2-position control, Non-Spring Return, No feedback and without aux. Switch CN4634A1001 34Nm,230Vac, Floating control/2-position, Non-Spring Return, No feedback and without aux. Switch
Product Identification System C – Direct Coupled Actuator
N – Fail Safe Function (Non-Spring Return) 61 – 24V Floating/2-position Control 72 – 24V Modulating and Floating/2-position Control 46 – 230V Floating/2-position Control
20 – 20 Nm (177 lb-in) 34 – 34 Nm (300 lb-in)
A – Standard Model 1 – No Feedback 2 – Voltage Feedback Signal
0 – No Internal Auxiliary Switches 2 – Two Internal Auxiliary Switches
XX – System Controlled Numbers
C N 61 20 A 1 0 XX
Fig. 1. Product Identification System
OPERATION / FUNCTIONS
Fig. 2. Setting units and control elements
Legend for Fig. 2: 1 Self-centering shaft adapter 2 Retainer clip 3 Rotational angle scales (0...90° / 90...0°) 4 Mechanical end limits 5 Declutch button 6 Anti-rotation bracket 7 Function selection switch 8 Access cover
Contents of Package The delivery package includes the actuator itself, parts 1 through 8 (see Fig.2), the anti-rotation bracket screws, and installation instruction.
RUN MODES The function selection switch (see Fig. 3) can be used to place the actuator into any one of three different modes:
Dir, floating/2-position control, cw run.Service/Off, actuator stop running.Rev, floating/2-position control, ccw run.
1
2
3
4
5 6
8 7
13
CN20, CN34 SERIES DAMPER ACTUATOR FOR FLOATING AND 2-POS CONTROL
Fig. 3. Function selection switch
Power-Off Behavior If power is removed, the actuator retains its position.
Service/OffIf the function selection switch is set to the "Service/Off" position, all rotary movement is cancelled, and all control signals are ignored, thus allowing the actuator to be safely manually operated.
Floating/2-Position Run Mode If the function selection switch has been set to one of the two floating/2-position control settings (Dir or Rev) and the actuator is wired correspondingly (see A1 and A2) as soon as the operating power is applied, the actuator will run according to the power applied
Table 1 describes the behavior (stops, rotates CCW, or rotates CW) of the CN6120/CN6134 in relation to the control signals (switch "open" or "24Vac/dc") applied to terminals 3 and 4, the function selection switch setting, and the manner in which the actuator is wired (either for floating mode: see A1, or for 2-position mode: see A2).
Table 1. Behavior of CN6120/CN6134 Control signal at Function selection switchWiring term. 3 term. 4 Dir Service/Off Rev open open stops stops stops open 24Vac/dc CCW stops CW Float.
24Vac/dc open CW stops CCW 24Vac/dc open CW stops CCW 2-pos. 24Vac/dc 24Vac/dc CCW stops CW
Table 2 shows the same actuator behavior as Table 1, but for CN4620/CN4634 (230Vac models).
Table 2. Behavior of CN4620/CN4634 Control signal at Function selection switch Wiring term. 3 term. 4 Dir Service/Off Rev open open stops stops stops open 230Vac CCW stops CW Float.
230Vac open CW stops CCW 230Vac open CW stops CCW 2-pos. 230Vac 230Vac CCW stops CW
Sleep Mode When actuator reaches end stop or any obstacles blocking its running, it will fall into sleep mode automatically. Actuator will
periodically start up and try to resume running, which will save energy significantly through whole service life.
Position Indication The hub adapter indicates the rotation angle position by means of the rotational angle scales (0...90° / 90...0°) provided in the actuator plate (see Fig. 4).
Fig. 4. Position indication
Manual Adjustment
IMPORTANTTo prevent equipment damage, you must remove power or set the rotation direction switch to the "Service/Off" position before manual adjustment.
After removing power or setting the rotation direction switch to the "Service/Off" position, the gear train can be disengaged using the declutch button, permitting the actuator shaft to be manually rotated to any position.
Limitation of Rotation Stroke Two adjustable mechanical end limits (adjustable in 5° increments) are provided to limit the angle of rotation as desired (see Fig. 5).
Fig. 5. Mechanical end limits
The mechanical end limits must be securely fastened in place. It is important that they properly mesh with the rotational angle scales when the screws are tightened.
Internal End Switches NOTE: Applicable to models with internal switches only.
14
!
CN20, CN34 SERIES DAMPER ACTUATOR FOR FLOATING AND 2-POS CONTROL
The internal end switches are set to switch from "common" to "normally open" at angles of 5° and 85°, respectively, from the totally counterclockwise position.
-2.5
85 80 5 590 092.5 51015
CCW internalend switch
CW internalend switch
actuator scale: clockwise
end switch scale
actuator scale: counterclockwise
Fig. 6. Internal end switch triggering points
INSTALLATIONThese actuators are designed for single-point mounting.
In order to prevent equipment damage, you must remove power or set the rotation direction switch to the "Service/Off" position before manual operation.
Mounting Instructions All information and steps are included in the installation instructions supplied with the actuator.
Mounting Position The actuators can be mounted in any position (no IP54 if mounted upside down; see Fig. 7). Choose a mounting posi-tion permitting easy access to the actuator's cables and controls.
IP54 IP54IP54 IP54
Fig. 7. Mounting for IP54
Mounting Bracket and Screws If the actuator is to be mounted directly on a damper shaft, use the mounting bracket and screws included in the delivery package.
Self-Centering Shaft Adapter The self-centering shaft adapter can be used for shafts having various diameters (10...27 mm [3/8...1-1/16"]) and shapes (square or round).
In the case of short shafts, the shaft adapter may be reversed and mounted on the duct side.
Stroke Limitation with Mechanical End Limits The mechanical end limits enable the stroke to be limited from 0...90° in increments of 5°.
WiringConnecting to the Power Supply In order to comply with protection class II, the power source of 24 V actuators must be reliably separated from the network power supply circuits as per DIN VDE 0106, part 101.
Access Cover To facilitate wiring the actuator to the controller, the access cover can be detached from the actuator.
Remove power before detaching the access cover. Once the access cover has been removed, please take care to avoid damaging any of the parts now accessible.
Fig. 8. Access cover (models with internal switches)
Depending upon the model, the access cover may have one or two terminal strips, including a layout with a description for each of the terminals.
Fig. 9. Actuator with access cover removed (models with internal switches)
15
IMPORTANT! IMPORTANT!
CN20, CN34 SERIES DAMPER ACTUATOR FOR FLOATING AND 2-POS CONTROL
Wiring diagrams A1 CN6120,CN4620CN6134,CN4634 FLOATING
A2 CN6120,CN4620CN6134,CN4634 2-POS
A3 END SWITCHS(models with switch only)
NOTE: Internal end switches S1 and S4 must be connected to the same power source. Below 2 tables summarize the information presented in the preceding wiring diagrams.
WiringModels Terminal Floating 2-position
2 common / common / 3 24V ~/+ (clockwise) 24V ~/+
CN6120,CN6134 supply and signal lines
(must be equipped with spark suppressors) 4 24V ~/+ (counterclockwise) 24V ~/+ control signal 2 common / common / 3 230Vac (clockwise) 230Vac
CN4620,CN4634 supply and signal lines
(must be equipped with spark suppressors) 4 230Vac (counterclockwise) 230Vac control signal
Connecting cable Terminal Description S1 common S2 normally closed CCW (left) 5° S3 normally open S4 common S5 normally closed
end switches (models with internal
switches only) CW (right) 85° S6 normally open
OPTIONAL ACCESSORIES The following optional accessories can be ordered separately.
Auxiliary Switch Kit Order no.: SW2
S1S2
S3AB
S4S5
S6 CD45
090
900
A
B
C
D
The auxiliary switches are field-installable parts providing two SPDT freely-adjustable switches.
SPARE PARTS Spare Parts Kit Order no.: A7209.2071 The spare parts kit contains the following items:
Anti-rotation bracket and screwsAccess cover screwPlastic protective cap for protection standard IP54Mechanical end limit screw and retainer
Anti-Rotation Bracket Kit Order no.: A7209.2073 The anti-rotation bracket kit can be ordered separately.
Contains: 10 anti-rotation brackets20 screws
16
CN20, CN34 SERIES DAMPER ACTUATOR FOR FLOATING AND 2-POS CONTROL
DIMENSIONS
17
CS05, CS10, CS20 Series Spring Return Direct Coupled ActuatorsCS4105, CS4110, CS4120, CS7505, CS7510, CS7520, CS8105,CS8110, CS8120
PRODUCT DATA
FEATURES
APPLICATIONCS41XX, CS75XX, CS81XX Spring Return Direct CoupledActuators (DCA) are used within heating, ventilating, and air-conditioning (HVAC) systems. They can drive a variety ofquarter-turn, final control elements requiring spring return fail-safe operation.
Applications include:• Volume control dampers, mounted directly to the drive
shaft or remotely (with the use of accessory hardware).• Quarter-turn rotary valves, such as ball or butterfly valves
mounted directly to the drive shaft.• Linear stroke globe or cage valves mounted with linkages
to provide linear actuation.
• Brushless DC submotor with electronic stall protectionfor floating/modulating models.
• Brush DC submotor with electronic stall protection for2-position models.
• Self-centering shaft adapter (shaft coupling) for widerange of shaft sizes.
• Models available with three torque ratings:44 lb-in. (5 N•m), 88 lb-in. (10 N•m),and 175 lb-in. (20 N•m).
• Models available for use with two-position, single polesingle throw (spst), line-voltage or low-voltagecontrols.
• Models available for use with floating or switchedsingle-pole, double-throw (spdt) controls.
• Models available for use with proportional current orvoltage controls.
• Models available with combined floating/modulatingcontrol in a single device.
• Models available with adjustable zero and span.• Models available with line-voltage internal and
switches.• Access cover to facilitate connectivity.• Metal housing with built-in mechanical end limits.• Spring return direction field-selectable.• Shaft position indicator and scale.• Manual winding capability with locking function.• UL (cUL) listed and CE compliant.• All Models are plenum-rated per UL873.
18
C
M20952
SPECIFICATIONSModels: See Tables 2, 3 and 4.
Dimensions: See Fig. 1.
Device Weight: 7 lb (3.2 kg).
Timing (At Rated Torque and Voltage):Drive Open (typical):
Floating, Modulating Models: 90 seconds.Two-Position Models: 45 seconds ±5 seconds.
Spring Close: 20 seconds typical.
3-15/16 (100)
Temperature Ratings: 1-9/16 1-9/16
Ambient: -40°F to 140°F (-40°C to 60°C).Shipping and Storage: -40°F to 158°F (-40°C to 70°C).
Humidity Ratings: 5% to 95% RH noncondensing.
Electrical Connections:Field wiring 14 to 22 AWG (2.0 to 0.344 mm sq) to screw
terminals, located under the removable access cover.
(40) (40)
1-9/16(40)
2-1/2(64)MIN.
3(76)MIN.FROMSHAFTEND
Electrical Ratings: See Table 1.
End Switches (Two SPDT):Settings (fixed): 7° nominal stroke, 85° nominal stroke.Ratings (maximum load):
Low-Voltage Models: 250 VAC, 5A resistive, 3A inductive.Line-Voltage Models: 250 VAC, 5A resistive.
Mounting: Self-centering shaft adapter (shaft coupling).Round Damper Shafts: 0.375 to 1.06 in. (10 to 27 mm).Square Damper Shafts: 1/2 to 3/4 in. (13 to 19 mm).Actuator can be mounted with shaft in any position.
NOTE: For 175 lb-in. (20 N•m) models: 3/4 in. or greatershaft diameter recommended.
Minimum Damper Shaft Length: 1 in. (25 mm); 3 in.(76 mm) recommended.
1/4 (6)
9-3/4(247)
6-1/8(156)
3 (76)MIN.
2-15/16 (75)
Fig. 1. Dimensional drawing of actuator in in. (mm).
Table 1. Electrical Ratings.Power Input Power Consumption (VA)
44 lb-in. (5 N•m) 88 lb-in. (10 N•m) 175 lb-in. (20 N•m)Model(s) Voltage Frequency Driving Holding Driving Holding Driving Holding
Floating, Modulating 24 VAC±20% (Class 2), 24 VDC 50/60 Hz. 13 5 14 5 16 5Two-Position, Low-voltage 24 VAC±20% (Class 2), 24 VDC 50/60 Hz. 25 8 30 8 40 8Two-Position, Line-voltage 100-250 VAC 50/60 Hz. 45 13 45 13 60 13
ORDERING INFORMATIONIf you have additional questions, need further information, or would like to comment on our products or services, please write orphone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).2. Honeywell ECC Customer Care
35F., Tower A, City Center 100 Zun Yi RoadShanghai 200051 China Tel: (86-21) 5257 4568
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Finland, France, Germany,Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, P.R.C.
19
CS05, CS10,CS20 SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
Model Description
CS4105A1002 100-250 VAC Two-Position Control; Reversible Mount;5N•m; Standard U.S Model; No Feedback; No EndSwitches;
CS4110A1002 100-250 VAC Two-Position Control; Reversible Mount;10N•m; Standard U.S Model; No Feedback; No EndSwitches;
CS4110A1200 100-250 VAC Two-Position Control; Reversible Mount;10N•m; Standard U.S Model; No Feedback; Two EndSwitches;
CS4120A1001 100-250 VAC Two-Position Control; Reversible Mount;20N•m; Standard U.S Model; No Feedback; No EndSwitches;
CS4120A1209 100-250 VAC Two-Position Control; Reversible Mount;20N•m; Standard U.S Model; No Feedback; Two EndSwitches;
CS7505A2008 24 VAC/VDC Modulating and Floating Control ; ReversibleMount; 5N•m; Standard U.S Model; Voltage FeedbackSignal; No End Switches;
CS7510A2008 24 VAC/VDC Modulating and Floating Control ; ReversibleMount; 10N•m; Standard U.S Model; Voltage FeedbackSignal; No End Switches;
CS7510A2206 24 VAC/VDC Modulating and Floating Control ; ReversibleMount; 10N•m; Standard U.S Model; Voltage FeedbackSignal; Two End Switches;
CS7510H2209 24 VAC/VDC Modulating and Floating Control; ReversibleMount; 10N•m; Selectable control signal; Adjustable zeroand span; Includes service and atuo-adapt modes; VoltageFeedback Signal; Two End Switches;
CS7520A2007 24 VAC/VDC Modulating and Floating Control ; ReversibleMount; 20N•m; Standard U.S Model; Voltage FeedbackSignal; No End Switches;
CS7520A2205 24 VAC/VDC Modulating and Floating Control ; ReversibleMount; 20N•m; Standard U.S Model; Voltage FeedbackSignal; Two End Switches;
CS7520H2208 24 VAC/VDC Modulating and Floating Control; ReversibleMount; 20N•m; Selectable control signal; Adjustable zeroand span; Includes service and atuo-adapt modes; VoltageFeedback Signal; Two End Switches;
CS8105A1008 24 VAC/VDC Two-Position Control; Reversible Mount;5N•m; Standard U.S Model; No Feedback; No EndSwitches;
CS8110A1008 24 VAC/VDC Two-Position Control; Reversible Mount;10N•m; Standard U.S Model; No Feedback; No EndSwitches;
CS8110A1206 24 VAC/VDC Two-Position Control; Reversible Mount;10N•m; Standard U.S Model; No Feedback; Two EndSwitches;
CS8120A1007 24 VAC/VDC Two-Position Control; Reversible Mount;20N•m; Standard U.S Model; No Feedback; No EndSwitches;
CS8120A1205 24 VAC/VDC Two-Position Control; Reversible Mount;20N•m; Standard U.S Model; No Feedback; Two EndSwitches;
Table 2. O.S. Number Selection (see Table 3 also).C Motorized Actuator
S Fail Safe Function (Spring Return)41 100-250 VAC Two-Position Control; Reversible Mount75 24 VAC/VDC Modulating and Floating Control ; Reversible Mount81 24 VAC/VDC Two-Position Control; Reversible Mount
05 44 lb-in. (5 N•m)10 88 lb-in. (10 N•m)20 175 lb-in. (20 N•m)
Aa Standard U.S. Model
Bb Standard European Model
Eb
Ha
Selectable control signal; Adjustable zero and span;Includes service and auto-adapt modes
1 No Feedback2 Voltage Feedback Signal
0 No End Switches2 Two End Switches
X X System Controlled Numbers
C S 7a Model manufactured for sale in the United States.b Model manufactured for sale in Europe.
Table 4. Available Model
Table 3. Actuator Catalog Numbering (see Table 2 also).S Spring Return Fail Safe ModeN Non-Spring Return Fail Safe Mode
05 44 lb-in. (5 N•m); Spring Return Only10 88 lb-in. (10 N•m); Spring Return Only
20 175 lb-in. (20 N•m)34 300 lb-in. (34 N•m); Non-Spring Return Only
24 24 VAC/VDC Floating Control24-2POS 24 VAC/VDC Two-Position Control120-2POS 120 VAC Two-Position Control230-2POS 230 VAC Two-Position Control
010 24 VAC/VDC Modulating and Floating ControlFixed Zero/Span, No End Switches
-SW2 Internal End Switches
-SERa Enhanced Modulating; Adjustable Zero/Span
S 10 24-2POS -SW2a Enhanced models include two internal end switches.
20
CS05, CS10,CS20 SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
Stroke: 95° ±3°, mechanically limited.Design Life (at Rated Voltage):Two-position models: 50,000 full stroke cycles;
50,000 full stroke spring returns.Floating and Modulating models: 60,000 full stroke cycles;
1,500,000 repositions; 60,000 full stroke spring returns.
Controller Type:S05, S10, S20: See Table 3.S05, S10, S20: Modulating or Floating; controlled by selector
switch.Input Impedance: 95K ohms minimum.Feedback Signal: 0-10 VDC or 2-10 VDC;
Driving current is 3 mA minimum.
Torque Ratings:Typical Holding, Driving, Spring Return:
S05: 44 lb-in. (5 N•m).S10: 88 lb-in. (10 N•m).S20: 175 lb-in. (20 N•m).
Stall Maximum (fully open at 24°C):S05: 100 lb-in. (11.3 N•m).S10: 200 lb-in. (22.6 N•m).S20: 350 lb-in. (39.6 N•m).
Noise Rating at 1m (Maximum):Holding: 20 dBA (no audible noise).Two-position models:
Driving: 50 dBA.Spring Return: 65 dBA.
Floating and Modulating models:Driving: 40 dBA.Spring Return: 50 dBA.
Environmental Protection Ratings:NEMA2 (US Models) or IP54 (European Models) when
mounted on a horizontal shaft with access cover below theshaft.
Approvals: See Table 5.
Table 5. Approvals.UL/cUL
UL873 Plenum Rating,File No. E4436; Guide No. XAPX.
CEC-TICK
Accessories:32004254-002 Self-Centering Shaft Adapter (supplied with
actuator).50030966-001 Anti-Rotation Bracket (supplied with actuator).6174215 Extension Screw (supplied with actuator).27518 Balljoint (5/16 in.).103598 Balljoint (1/4 in.).205860 Electronic Minimum Position Potentiometer.27520A-E,G,H-L,Q Pushrod (5/16 in. diameter).5450074 Water-tight Cable Gland/Strain-relief Fitting
(supplied with actuator).32003036-001 Weather Enclosure.50001194-001 Foot Mount Kit.50005859-001 NEMA4/4X Enclosure.SW2-US Auxiliary Switch Package.See also Form 63-2620.
SizingRequired TorqueIn lieu of data from a Specification Engineer or Manufacturer,required torque for a given damper load can be determinedusing the following method:
Where:— TR = Required torque for the damper load.— TD = Damper torque rating from the manufacturer,
expressed in either (lb-in.)/(sq ft) or (N•m)/(sq m). thedamper load.
— AD = Damper area expressed in either sq ft or sq m.
Actuators RequiredIn lieu of data from a Specification Engineer or Manufacturer,the number of required actuators for a given damper loadcan be determined using the following method:
Where:N = Number of actuators.
— TR = Required torque for the damper load. (See above.)— TA = Actuator torque rating.— SF = Safety factor.
NOTE: The safety factor accounts for variables such asmis- alignments, aging of the damper, etc. 0.8 is atypical safety factor.
T FS
TN
A
R
DDR ATT
21
CS05, CS10,CS20 SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
PRODUCT DATA
APPLICATIONThe MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 Fast-Acting, Two-Position Actuators are spring return direct coupled actuators (DCA) with an integral junction box for on/o damper control. The actuator accepts an on/o signal from a single-pole, single-throw (spst) controller. Reversible mounting allows actuator to be used for either clockwise (cw) or counterclockwise (ccw) spring return and are designed to operate reliably in smoke control systems requiring
FEATURES• 30 lb-in. (3.4 N•m) or 80 lb-in. (9 N•m) minimum driving
torque at 350 °F (176 °C).
• Reversible mounting facilitates use in either clockwise (cw) or counterclockwise (ccw) spring rotation.
• Integral spring return ensures level of return torque.
• Stainless steel internal spring.
• Fifteen-second spring return timing.
• No special cycling required during long-term holding.
• No audible noise during holding.
• Patent pending design eliminates need for limit switches to reduce power consumption.
• Models available for 24, 120 and 230 Vac.
• N degree angle of rotation.
• Actuator holds rated torque at reduced power level.
• Die-cast aluminum housing.
• Housing design allows ush mounting to damper.
• Designed to operated reliably in smoke control systems requiring Underwriter's Laboratories Inc. UL555S rating up to 350F.
• Models available with SPST position-indicating switches (7°, 85° stroke).
Fire and Smoke Damper ActuatorMS4104, MS4109, MS4604, MS4609, MS8104, MS8109 Fast-Acting, Two-Position Actuators FOR FIRE/SMOKE CONTROL APPLICATIONS
Wiring:
Fig. 1. Typical 24 Vac wiring.
Fig. 2. Typical 120 Vac wiring.
M34624
24 VAC
BLACK
RED
L1 ( )
L2 ( )
YELLOW
YELLOW
BLUE7° AUXILIARY
SWITCH
85° AUXILIARYSWITCH
BLUE
WHITE
BLACK
GREENL1 ( )
L2 ( )
YELLOW
YELLOW
BLUE
BLUE7° AUXILIARY
SWITCH
85° AUXILIARYSWITCH
120 VAC
M34625
Fig. 3. Typical 230 Vac wiring.
Dimensions:
M34626
BLUE
BROWN
GREEN
230 VAC
L1 ( )
L2 ( )
YELLOW
YELLOW
BLUE
BLUE7° AUXILIARY
SWITCH
85° AUXILIARYSWITCH
M34622
2 (51)
1 (25)
90° 0°
11/16(17)
6-3/8(161)
8-15/16(227)
4 (102)2 (51) 1/16
(2)3-1/4 (83)
5-1/8 (130)
9/16 (14)
22N314
MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 FAST-ACTING, TWO-POSITION ACTUATORS
ModelVoltage
(Vac)
Internal Auxiliary Switches
Torquein lb-in.
(N •m)
MS4104F1010
120
120 30 (3.4)None
None
None
None
None
None
MS4104F1210 2 SPST a
2 SPSTa
2 SPSTa
2 SPSTa
2 SPSTa
2 SPSTa
30 (3.4)
120
120
320
320
80 (9)
80 (9)
30 (3.4)
30 (3.4)
320 80 (9)
320 80 (9)
24 30 (3.4)
24 30 (3.4)24 80 (9)
24 80 (9)
MS4109F1010
MS4109F1210
MS4604F1010
MS4604F1210
MS4609F1010
MS4609F1210
MS8104F1010
MS8104F1210MS8109F1010
MS8109F1210
SPECIFICATIONSModels:
a Internal switches are designed to pass UL555S requirements (at 350 °F for 30 minutes) and are intended for use as position indication.
Electrical Ratings:Power Input:
MS4104F, MS4109F: 120 Vac ±10%, 60 Hz.MS4604F, MS4609F: 230 Vac ±10%, 50/60 Hz.MS8104F, MS8109F: 24 Vac +20%, -10%, 50/60 Hz.
Power Consumption:MS4104F: Running: 0.18A, 18W. Holding: 0.11A, 9WMS4109F: Running: 0.25A, 23W. Holding: 0.13A, 7WMS4604F: Running: 0.13A, 18W. Holding: 0.10A, 11WMS4609F: Running: 0.13A, 23W. Holding: 0.09A, 7WMS8104F: Running: 16VA. Holding: 8 VAMS8109F: Running: 23VA. Holding: 7 VA
Electrical Connections:Power Lead Wires:
MS410xF and MS460xF: 32 inches (0.8m), 18 AWGMS810xF: 39 inches (1m), 18 AWG
Switch Lead Wires: 18 inches, 18 AWG, 2 color coded leads.
Controller Type:MS4104, MS4109: Line voltage (120 Vac), two-position, spst
(Series 40).MS4604, MS4609: Line voltage (230 Vac), two-position, spst
(Series 40). MS8104, MS8109: Low voltage (24 Vac), two-position, spst
(Series 80).
Device Weight:5 lb (2.3 kg).
Noise Rating (Maximum):Driving Open: 75 dBA at 1m.Holding: 20 dBA at 1m (no audible noise).
Temperature Ratings:Ambient: 0°F to 130°F (-18°C to 55°C).Shipping and Storage: -40°F to 140°F (-40°C to 60°C).
IMPORTANTThe actuator is designed to meet UL555S standards at 350°F (176°C). The actuator must be tested with the damper to achieve this rating.
Humidity Ratings:5% to 95% RH noncondensing.
Stroke:95° ± 3°, mechanically limited.
Torque Rating (at rated voltage):Spring Return:
MS4104F, MS4604F, MS8104F: 30 lb-in. (3.4 N•m).MS4109F, MS4609F, MS8109: 80 lb-in. (9 N•m).
Stall Maximum:MS4104F, MS4604F, MS8104F: 150 lb-in. (17 N•m).MS4109F, MS4609F, MS8109: 240 lb-in. (27 N•m).
350°F Driving:MS4104F, MS4604F, MS8104F: 30 lb-in. (3.4 N•m).MS4109F, MS4609F, MS8109: 80 lb-in. (9 N•m).
Timing (At Rated Torque and Voltage):Drive Open: 15 seconds typical.Spring Close: 15 seconds typical.
Design Life (at Rated Voltage):30,000 full stroke cycles.
Cycling Requirements:The actuator and the internal spring are designed to require
no special cycling during long-term holding.Honeywell recommends following all local, state and national
codes for periodic testing of the entire smoke control sys-tem. Refer to National Fire Protection Association (NFPA) National Fire Codes®: NFPA90A, NFPA92A and NFPA92B for your application.
NFPA recommends periodic examination of each fire/smoke damper (semi-annually or annually) to ensure proper per-formance.
Minimum Damper Shaft Length:2 in. (51 mm).
Mounting:Round 1/2 inch shaft adapter with 1/4 inch set screws.
Threads: ¼-20 UNC-2AMaterial: Alloy Steel hardened to HRC 45-53Thread Lock: Nylon Patch
IMPORTANTHoneywell does not recommend using linkages with these actuators because si de-loading of the output hub reduces actuator life.
Environmental Protection Ratings:NEMA, IP40.
Accessories:205649 Mounting Bracket (not supplied with actuator).
Approvals:
MS4104F, MS4109F
MS4604F, MS4609F
MS8104F, MS8109F
UL/cUL X X X
UL60730 X X X
CE X X X
C-Tick X X X
23